This is an installation specifications document for Baconton Charter School's outdoor walk-in freezer procurement. The project requires a pre-fabricated, modular walk-in freezer manufactured by Bally, with prior approval required for any alternative manufacturers. The freezer shall be supplied with complete installation instructions and erection drawings with panel identification to facilitate field assembly. The refrigeration system and associated equipment must comply with NSF Standard 7 and carry NSF Seal of Approval certification. All prime electrical components must feature UL labels or recognized markings where available, with specific UL approval required for the door electrical circuit assembly.
The walk-in freezer panels must meet ASTM E-84 (UL723) fire hazard classification standards with a maximum flame spread rating of 25, featuring Factory Mutual Approved non-CFC polyurethane foam insulation that shall not flame, glow, smolder, or smoke at minimum test temperatures of 250°F. Panels and doors must achieve minimum R-Value ratings of R-25 for cooler applications and R-32 for freezer applications per Federal Regulation 431.304. The manufacturer shall provide a ten-year warranty on panels against poor workmanship and defective materials, with one year of parts and labor coverage on the refrigeration system and an additional four-year compressor warranty. The refrigeration system must comply with the January 1, 2026 commercial refrigeration requirements regarding refrigerant specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Freezer shelving.pdf | ||
| Equipment Specification.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BACONTON CHARTER SCHOOL
WALK-IN FREEZER SPECIFICATIONS
OUTDOOR INSTALLATION
GENERAL:
A. Walk-in freezer shall be constructed of pre-fabricated, precision-formed, modular panels designed for rapid field assembly. Walk-in freezer shall be manufactured and furnished by Bally. 10 day prior approval for any other manufacturers.
CONSTRUCTION PLANS AND INSTRUCTIONS:
A. Walk-in freezer shall be supplied with a complete set of installation instructions and erection drawings. All panels shall have panel identification corresponding with erection drawings to facilitate rapid and accurate field erection.
GUARANTEES:
A. Walk-in freezer panels shall be guaranteed for a period of ten (10) years after final approval against poor workmanship and defective materials. Any defect within this period shall be corrected at no charge to Owner. Refrigeration system shall be guaranteed for parts and labor for a period of one year (1) year with an additional four (4) year compressor warranty.
CODES AND STANDARDS:
A. NSF Standards: Comply with applicable National Sanitation Foundation (NSF) Standard 7 construction and recommended criteria. Provide equipment with a NSF “Seal of Approval."
B. UL Labels: Where available, provide UL labels on prime electrical components.
Provide UL "recognized marking" on other items with electrical components, signifying listing by UL where available. Provide UL approval of door electrical circuit assembly.
C. ASTME-84 (UL723): Comply with fire hazard classification ASTME-84 (UL723).
Panels shall be supplied with a fire hazard classification in accordance with ASTME-84 (UL723). Panels shall be classified according to ASTME-84 (UL723) shall be flame spread rating of 25 or less with a certifying Underwriters Label Factory Mutual Approved Toxicity Rated Non-CFC polyurethane foam required.
Insulation tested according to E-84 “shall not flame, glow, smolder or smoke” at a minimum test temperature of 250°F. (Flame Spread 25 indicates lower surface burning of materials. This standard is used solely to measure and describe properties of products in response to heat and flame under controlled laboratory conditions. This rating provides the walk-in panels with additional thermal resistance and may reduce the need for sprinkler systems.)
D. ASTM D-C518: Panels & doors must meet or exceed minimum R-Values for cooler (R25) and freezer R-32) per Federal Regulation 431.304.
E. Refrigeration systems must meet the January 1, 2026 requirement that all new commercial refrigeration products use a refrigerant <300 GWP (R-454A) for systems under 200 Lbs. and <150 GWP (R-454C & R-455A) for systems above 200 Lbs.
PRODUCTS:
A. Furnish one (1) outdoor walk-in freezer to be actual 11’-7“x 14’-5 ½” x 8’ 6“.
B. Walk-in freezer is to comply with the US Energy Independence & Security Act.
C. Interior wall finish: 190 Series embossed white galvanized. Exterior finish: 190 Series embossed white galvanized. Interior ceiling finish: 190 Series embossed white galvanized. Exterior ceiling finish: 190 Series embossed white galvanized.
Single-span reinforced ceiling. 4” thick floor panels with 3/8” inside coved radius built in around the perimeter of skins and NSF certified. Interior floor finish:
0.125” textured aluminum with integral kickplates.
D. Panels shall be equipped with Bally Speed-Loc diaphragmatic joining devices. The distance between locks shall not exceed 46”. Each device shall consist of a cam action, hooked locking arm placed in one panel, and a steel rod positioned in the adjoining panel, so that when the arm is rotated, the hood engages the rod and draws the panels tightly together with cam action. Arms and rods shall be housed in individual steel pockets. Pockets on one side of the panel shall be connected to pockets on the other side in width, by use of 2” wide metal straps set into and completely surrounded by insulation. When panels are joined these straps shall form lock-to-lock connections for superior strength. Locking device shall be accessible from the inside to facilitate installations in confined areas and shall be provided with flush press-fit caps. Surface mounted plastic plugs will not be accepted.
E. Panels shall consist of interior and exterior metal skins precisely foamed with steel dies and roll-form equipment and thoroughly checked with gauges for accuracy.
Metal skins shall be treated on the inside surface with a bonding agent to ensure a stable adhesion with the chemical bonding agents of the urethane. Urethane shall be Enovate 3000 or Solstice foamed in place (poured, not frothed) and, when completely cured, shall bind tenaciously to metal skins to form an insulated panel.
Panels shall contain 100% urethane insulation and have no internal wood or structural members between skins unless required as structural support for external accessories. To ensure tight joints, panel edges must have foamed-in place tongue and groove with flexible vinyl gasket foamed-in place on the interior and exterior of all tongue edges. Gaskets shall be resistant to damage from oil, fats, water and detergents and must be NSF-approved. Gaskets shall not be stapled or glued to metal skins. All panels (except corner panels) shall be made in 23” and 46” widths, fully interchangeable for fast, easy assembly. 11-1/2", 17- 1/4", 34-1/2" wide are to be furnished only if required to fit allocated space. To ensure perfect alignment and maximum strength, corner panels shall employ a right-angle configuration with exterior horizontal dimensions of 12” on each side.
a. Unit shall be fitted with cooler door with 36" x 78" swing out type hinged entrance door. Doors shall be flush mounted, in-fitting type will have a 14-gauge unitized structural “U” channel steel door frame with 1/8” steel plates where all hardware is mounted. The steel frame with an internal thermal breaker will prevent twisting, sagging, and eliminates the need for structural members. Door shall be equipped with a magnetic steel core gasket across the top and both sides of the door. Bottom of the door shall be fitted with adjustable, double vinyl wiper gasket. NSF approved removable gasket.
b. Each door frame shall be provided with an LED vapor proof light fixture and an inside safety release.
c. Doors and door handles shall be Kason 27C satin aluminum finish and listed by U.L.
d. A positive action Kason 1094 hydraulic door closer shall be included to ensure gentle closing action of door and ensure a positive seal.
e. Provide each door with (3) heavy-duty adjustable/spring assisted Kason 1346 satin aluminum hinges. Hinges shall be cam-lift, self-closing type, ”hold-open” feature allowing door to remain open unaided, when opened to 180 degrees position.
f. Door frames shall be provided with a 2" diameter flush-face dial thermometer.
g. Doors provided with thermostatically controlled warmer cable around entire perimeter of opening.
h. Freezer door to have pressure relief port.
i. 14”x14” view window provided in door.
j. 2-piece locking bar with interior release.
k. Provide doors and frames with 1/8”, 0.125”, textured aluminum treadplate
36” high on interior/exterior door and frame.
l. Kason strip curtain provided for door.
F. Freezer compartment to have Two (2) 48” long LED light fixtures. Lights are to be designed to operate properly in their respective moisture and temperature environments.
G. Supply and install trim made from material with same finish as exposed exterior where walk-in cooler/freezer is adjacent to walls; seal to walls and boxes for rodent, dirt and moisture protection.
H. Freezer provided with (1) Bally BLP314LE-S1D SV+, SmartVap+ Electric Defrost evaporators 208-230/1/60, with EEV Installed and (1) 3 ½ HP air-cooled BEZA035- L9-HT3EN, scroll condensing units with A2L complaint refrigerant R454A (208- 230/1/60), designed for outdoor operation.
I. Manufacturer shall furnish a single-ply reinforced thermoplastic membrane roof cap in one complete roll, sized to fully cover the ceiling panels with sufficient material for turn-down on all sides (minimum 6 inches on free-standing sides; 8-12 inches if adjacent to building wall). The membrane shall be fire-resistant, chemical-resistant, and suitable for outdoor exposure. No field welding of seams shall be required.
J. To prevent ponding and ensure proper water runoff, manufacturer shall furnish pre-cut sloped foam blocks (tapered insulation inserts) designed to provide a minimum slope of 1/8 inch per foot (or as required by local codes/snow load).