Inspection Results.pdf
PDF 2 MB Posted
- Attached to
- Z1DA--NRM| 460-26-007 Electrical Distribution Inspection Repairs | NCO 4 Construction East (VA-26-00057558)
- Solicitation number
- 36C24427B0002
About this file
This is a Low Voltage Power Circuit Breaker Test and Inspection report for Job #861903 at Wilmington, VA (1601 Kirkwood Highway, Wilmington, DE 19805), dated 5/17/2025 and 5/18/2025. The report documents testing results for three separate circuit breakers and includes a deficiency summary identifying maintenance and replacement needs.
Main Breaker (Building 143 - Emergency Gear): An Eaton NGS 50K breaker with 1200A frame size was tested on 5/18/2025. All inspected components including cubicle/racking devices, arc chutes, and mechanism were found in acceptable condition. Contact resistance measurements were 37, 36, and 36 micro-ohms for phases A, B, and C respectively. Primary injection testing was not performed (N/T). The critical deficiency noted is that the breaker would not reset while operating, with immediate replacement recommended. Megger testing was not completed (N/T).
Sub B Main Breaker (Room 244): A Westinghouse DS 416H breaker with 1600A frame size and Digitrip RMS 610 trip unit was tested on 5/17/2025. All mechanical components and contacts were in acceptable condition with no contact resistance testing performed (N/T). Primary injection testing confirmed instantaneous, short time, and long time function performance met specifications across all three phases. Megger testing showed 1,000 meg-ohms across all phase-to-ground and phase-to-phase measurements. The significant deficiency is a broken racking mechanism preventing the breaker from being racked out of its cell; a spare unit should be ordered for repairs. Additional deficiencies identified in the broader job summary relate to medium voltage disconnect switches (29000 series) with insulator terminal boot covers showing signs of tracking/treeing requiring replacement across multiple outdoor switch locations (S4 and S5).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24427B0002.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOW VOLTAGE POWER CIRCUIT BREAKER
TEST AND
15 PAGE
JOB # 861903
Cat #NGS312033E, Style: 149r3D04G Lin b ker to perform insulation resistance testing. All test results acceptable to NETA test standa a e
While operating- breaker, the breaker would not reset. Recommend repla s possible ng as oon
TESTED BY: BS Form Number:15118, Designed By FM 4/16/2020
CUSTOMER Wilmington VA
ADDRESS 1601 Kirkwood Highway ; Wilmington DE 19805
USER Wilmington VA
N/A
SENSOR TAPS: N/A
FUSE CAT. NO:
OPS AS FOUND /AS LEFT: On On
OWNER REPRESENTATIVE
DATE 5/18/2025 TEMPERATURE 30 °C HUMIDITY 28 % EQPT. LOCATION
SUBSTATION Building 143 ( Emergency Gear) POSITION
TELEPHONE
1601 Kirkwood Highway
Main Breaker
MANUFACTURER:
BREAKER TYPE:
TRIP UNIT TYPE:
FRAME SIZE:
SN /SO NO: N/A MOUNTING: B.I. D.O.
MANUAL/ELECTRIC: E
CONTROL VOLTAGE CLOSE: N/A
CONTROL VOLTAGE TRIP: N/A
Eaton
NGS 50K
Description INSPECTED CONDITION CLEAN/LUBE
CUBICLE AND RACKING DEVICES 17 7 Acceptable C
CONTACT FINGERS n N/A N/A
LOADING AND ARCING CONTACTS I- N/A N/A
OVERCURRENT DEV. BATTERY r N/A N/A
Description INSPECTED CONDITION CLEAN/LUBE
ARC CHUTES J7 Acceptable C
AUXILIARY DEVICES I - N/A N/A
GROUND CONNECTION r N/A N/A
MECHANISM 17 Acceptable C
_J
SETTINGS AS FOUND
LONG TIME PU
X 1200 A = 1200 A DELAY 2
RATING PLUG(R) 1200 SHORT TIME PU 2
1200 A ( ON 0 OFF DELAY N/A PT 0 IN r , OUT aiN N/A
SENSOR TAP N/A INST. PU N/A
N/A A (") ON OFF
GRD. FLT. PU N/A
N/A A O ON (4.` OFF DELAY N/A PT 0 IN 0 OUT (.4‘ N/A
SETTINGS AS LEFT
LONG TIME PU 1200 X 1200 A = 1200 A DELAY 2
RATING PLUG(R) 1200 SHORT TIME PU 2 = 1200 A 0 ON r OFF DELAY N/A PT O IN C' OUT (4-1P N/A
SENSOR TAP Nli, INST. PU
GRD. FLT. PU
N/A =
N/A A
A
C' ON r OFF
C' ON O OFF DELAY N/A PT O IN ("N OUT AP N/A
N/A N/A
PRIMARY INJECTION TEST
FUNCTION
TEST
CURRENT
TIME BAND / CURRENT
MINIMUM MAXIMUM
PICK UP
INSTANTANEOUS N/A N/A N/A
SHORT TIME N/T N/T NfT
LONG TIME N/T N/T N/T
GROUND FAULT N/A N/A N/A
PHASE A PHASE B PHASE C
AS
FOUND
AS
LEFT
AS
FOUND
AS
LEFT
AS
FOUND
AS
LEFT
N/A N/A N/A N/A N/A N/A
N/T N/T N/T N/T N/T N/T
N/T N/T N/T N/T N/T N/T
N/A N/A N/A N/A N/A N/A
CONTACT RESISTANCE - IN MICRO-OHMS Test Current @ 10 Amps
A B C
BREAKER 37 36 36
FUSE N/A N/A N/A
BREAKER & FUSE N/A N/A N/A
MEGGER TEST RESULTS - MEGGER VOLTAGE @ 1,000 VDC
BREAKER
CLOSED
Phase A - Ground
Phase B - Ground
Phase C - Ground
NIT
Meg-Ohms N/T
Meg-Ohms
Phase A - Phase B
Phase B - Phase C
Phase C - Phase A
NIT
BREAKER
OPEN
Phase A Line - Load
Phase B Line - Load
Phase C Line - Load
N/T
Meg-Ohms NIT
Meg-Ohms NTT
COMMENTS:
DEFICIENCIES:
Megger Cal #185627. AEMC Cal # 100343.
SENSOR TAPS:
FUSE CAT. NO: N/A
SETTINGS AS FOUND
RATING PLUG(R) 1600
SENSOR TAP
SETTINGS AS LEFT
RATING PLUG(R) 1600
SENSOR TAP
GRD. FLT. PU N/A = N/A A C' ON @ OFF DELAY 0.3 PT r IN C' OUT @ N/A
MANUFACTURER:
BREAKER TYPE:
TRIP UNIT TYPE:
FRAME SIZE:
SN /SO NO: Can not see due to issue
OPS AS FOUND / AS LEFT: N/A /
MOUNTING: C' B.I. D.O.
MANUAL/ELECTRIC: M C' E
CONTROL VOLTAGE CLOSE: N/A
CONTROL VOLTAGE TRIP:
Description INSPECTED CONDITION CLEAN/LUBE
CUBICLE AND RACKING DEVICES r.7 Acceptable C/L
CONTACT FINGERS J7 Acceptable C
LOADING AND ARCING CONTACTS sl7 Acceptable C
OVERCURRENT DEV. BATTERY 17 Acceptable C
Description INSPECTED CONDITION CLEAN/LUBE
ARC CHUTES 7 Acceptable C
AUXILIARY DEVICES F N/A N/A
GROUND CONNECTION 17 Acceptable C
MECHANISM 7 Acceptable C/L
GRD. FLT. PU N/A = N/A A C' ON 6. OFF DELAY 0.3 PT r, IN r, OUT (3 N/A
PRIMARY INJECTION TEST
FUNCTION
TEST
CURRENT
TIME BAND / CURRENT
MINIMUM MAXIMUM
PICK UP N/A N/A N/A
INSTANTANEOUS NIT -20% +20%
SHORT TIME 14400 .240 .335
LONG TIME 9600 16.08 24.00
GROUND FAULT N/A N/A N/A
PHASE A PHASE B PHASE C
AS
FOUND
AS
LEFT
AS
FOUND
AS
LEFT
AS
FOUND
AS
LEFT
N/A N/A N/A N/A N/A N/A
NO DELAY NO DELAY NO DELAY NO DELAY NO DELAY NO DELAY
.24 .24 .24 .24 .24 .24
21.2 21.2 21.2 21.2 21.2 21.2 N/A N/A N/A N/A N/A N/A
Westinghouse
DS 416H
Digitrip RMS 610
1600 N/A
N/A
1.0 X 1600 A = 1600 A DELAY 24
S2 = 19200 A @ ON r, OFF DELAY 0.3 PT r IN r, OUT @ N/A
6 = 9600 A @ ON C' OFF
LONG TIME PU
SHORT TIME PU
INST. PU
1.0 X 1600 A = 1600 A DELAY 24
S2 = 19200 A @ ON r, OFF DELAY 0.3 PT C' IN C' OUT @ N/A 6 = 9600 A ON r, OFF
LONG TIME PU
SHORT TIME PU
INST. PU
LOW VOLTAGE POWER CIRCUIT BREAKER
TEST AND INSPECTION
CUSTOMER Wilmington VA
ADDRESS 1601 Kirkwood Highway ; Wilmington DE 19805 USER Wilmington VA
OWNER REPRESENTATIVE
DATE 5/17/2025 TEMPERATURE 20 °C HUMIDITY 82 % EQPT. LOCATION
SUBSTATION
PAGE
JOB # 861903
TELEPHONE
1601 Kirkwood Highway
Sub B Main Breaker
Room 244 POSITION
CONTACT RESISTANCE - IN MICRO-OHMS Test Current @ 10 Amps
A B C
BREAKER N/T N/T
MEGGER TEST RESULTS - MEGGER VOLTAGE @ 1,000 VDC
N/T
FUSE N/A N/A N/A
BREAKER & FUSE N/A N/A N/A
r BREAKER
CLOSED
Phase A - Ground Phase B - Ground Phase C - Ground 1,000 Meg-Ohms 1,000 Meg-Ohms 1,000 Meg-Ohms
Phase A - Phase B Phase B - Phase C Phase C - Phase A 1,000 Meg-Ohms 1,000 Meg-Ohms 1,000 Meg-Ohms
BREAKER
OPEN
Phase A Line - Load Phase B Line - Load Phase C Line - Load 1,000 Meg-Ohms 1,000 Meg-Ohms 1,000 Meg-Ohms
COMMENTS: All test results meet NETA recommended specs.
DEFICIENCIES: Breaker racking mechanism is broken. Can not rack out of cell. Spare should be ordered to take out of service for repair.
V1/4)041-1 vt :34"-e.y4.4.-y_As—. c;,v‘e— 0 (.;7 44-0 tp e--
4,Xec... Ne' ckt.v0;% ok-v-c9—ses, 1644_,\L
TESTED BY: FV / EB /AG
dt 501keC
Form Number:15118, De3d,ned 3y FL1 4/16/2020
Red in tor terminal ot covers need show signs of tracking/treeing. Recommend replacing all 3 DEFICIENCIES:
Deficiency Summary Job #861903
Plant: Wilmington
Page: 92
Date: 5/17/2025 Substation: Outdoor Switches S4 Circuit_ID: Switch Loop Interconnect SW 4 to SW 3
Equipment: 29000 - MEDIUM VOLTAGE DISCONNECT (TXT)
DEFICIENCIES: Red insulator terminal boot covers need show signs of tracking/treeing. Recommend replacing all 3.
Plant: Wilmington
Substation: Outdoor Switches S4 Page: 93
Date: 5/17/2025 Circuit_ID: Switch Loop Interconnect SW 4 to SW 5
Equipment: 29000 - MEDIUM VOLTAGE DISCONNECT (TXT)
DEFICIENCIES: Red insulator show signs of tracking/treeing. Recommend replacing all 3.
Plant: Wilmington Substation: Outdoor Switches S5
Page: 96
Date: 5/17/2025 Circuit_ID: Switch Loop Interconnect SW 5 to SW 4
Equipment: 29000 - MEDIUM VOLTAGE DISCONNECT (TXT)
DEFICIENCIES: Red insulator terminal boot covers need show signs r king/treeing. Recommend replacing all 3.
Plant: Wilmington Substation: Outdoor Switches S5
Page: 97
Date: 5/17/2025 Circuit_ID: Switch Loop Interconnect SW 5 to SW 6
Equipment: 29000 - MEDIUM VOLTAGE DISCONNECT (TXT)
Plant: Wilmington Substation: Room 244
Page: 116
Date: 5/17/2025 Circuit_ID: Sub B Main Breaker
Equipment: 15118 - LV-CKT BKR TEST
DEFICIENCIES:
t-C.v> $c_ u s— )14; Vt 16V NiVtLA:i ) 3 .<-4 t -C 'O4-ti Z sO p$4,re
Plant: Wilmington
Substation: Room 244 (ATS) Circuit ID: ATS 3
Page: 128
Date: 5/18/2025
TEST EQUIPMENT USED: TESTED BY: