SPC-71463-000.pdf
PDF 248 KB Posted
- Solicitation number
- INL-27-002
- Issued by
-
Department of Energy
About this file
This is a technical specification document for seismic switches required for the Advanced Test Reactor (ATR) Plant Protection System (PPS) operated by Idaho National Laboratory, a U.S. Department of Energy National Laboratory managed by Battelle Energy Alliance.
The specification requires procurement of environmentally and seismically qualified seismic switches to replace obsolete Kinemetrics Model TS-3A units that have exhibited drift issues and reached end-of-life. The switches must detect ground motion in three orthogonal directions and initiate a PPS scram when acceleration exceeds 0.01g threshold. Key performance requirements include: static setpoint trip ≤0.0105g per axis, dynamic response setpoint ≤0.017g at 2.5-6 Hz frequency range, response time ≤150 milliseconds, field-adjustable setpoint range of 0.005-0.05g, one Form C dry contact output rated 10 Watts DC/12VA AC with 10-second hold time, and power consumption ≤5W from 12Vdc source. The seismic switches must be classified as safety-related Class 1E equipment with a qualified life of 20 years, qualified per IEEE 323-2003 and IEEE 344-2004, and listed by a Nationally Recognized Testing Laboratory (NRTL).
The subcontractor must provide complete switches with fabrication, assembly, environmental and seismic qualification testing, all mounting hardware, test equipment, operation and maintenance manuals, and bench testing procedures. Physical constraints limit each unit to 8.5"(L) x 8.5"(D) x 9.5"(H) with all adjustable parameters and test points located on an external vertical panel. Quality assurance must comply with ASME NQA-1-2022, with comprehensive documentation including qualification test reports, setpoint uncertainty analysis per ANSI/ISA-67.04.01-2018, dimensional drawings, external panel layout, connector wiring diagrams, user's manual with in-situ test procedures, and certificates of conformance. Packaging must protect against damage, moisture, vibration, and contamination during shipment, with clear container labeling including purchase order number, item description, serial numbers, and contractor catalog identification.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
The INL is a U.S. Department of Energy National Laboratory operated by Battelle Energy Alliance.
Document ID: SPC-71463 Revision ID: 0
Effective Date: 10/08/2026
Specification
ATR PPS Seismic Switch
Idaho National Laboratory
ATR PPS SEISMIC SWITCH
Identifier:
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 1 of 8
Applicability: ATR Complex Type: Specification DCR Number: 744717 Manual: Stand alone
CONTENTS 2
PART 1 GENERAL .........................................................................................................................2 3
PART 2 WORK INCLUDED ..........................................................................................................2 4
PART 3 WORK NOT INCLUDED ................................................................................................2 5
PART 4 CONTRACTOR-PROVIDED MATERIALS, EQUIPMENT AND SERVICES ............2 6
PART 5 APPLICABLE CODES, PROCEDURES AND REFERENCES .....................................2 7
PART 6 DESIGN REQUIREMENTS .............................................................................................3 8
PART 7 SUBMITTALS ..................................................................................................................5 9
PART 8 QUALITY ASSURANCE .................................................................................................6 10
PART 9 DELIVERY, STORAGE, AND PROTECTION ..............................................................7 11
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 2 of 8
PART 1 GENERAL 1
A. This specification defines the requirements for procuring environmentally and 2 seismically qualified seismic switches for use in the Advanced Test Reactor (ATR) Plant 3 Protection System (PPS). The seismic switches provide a critical safety function by 4 initiating a PPS scram when specified ground motion thresholds are exceeded. 5
B. The existing Kinemetrics Model TS-3A seismic switches are obsolete and have recently 6 exhibited drift issues, resulting in the use of remaining spare inventory. Their 7 obsolescence and degraded performance require replacement with modern, supported 8 units. 9
C. One seismic switch is currently out of service, placing the PPS in a reduced logic 10 configuration. Restoring the PPS to a normal configuration requires timely procurement 11 of reliable replacement switches. 12
D. The seismic switches detect ground motion in three orthogonal directions and change 13 state when any direction exceeds a threshold of 0.01 g. The resulting dry contact output is 14 monitored by PPS digital input modules to initiate a reactor scram. 15
E. Throughout this document, “Contractor” refers to Battelle Energy Alliance (BEA), and 16 “Subcontractor” refers to the supplier providing the seismic switches. 17
PART 2 WORK INCLUDED 18
A. Subcontractor shall furnish complete seismic switches, including fabrication and 19 assembly. 20
B. Subcontractor shall perform all required environmental and seismic qualification testing 21 and provide associated test reports. 22
C. Subcontractor shall supply all required mounting hardware and any tools, adapters, or 23 equipment needed to verify calibration, response time, and bench testing. 24
D. Subcontractor shall provide operation and maintenance manuals, bench testing 25 procedures, and all documentation identified in the Vendor Data Schedule. 26
E. Subcontractor shall package and ship all items in accordance with manufacturer and 27 industry standards to ensure protection during transport. 28
PART 3 WORK NOT INCLUDED 29
A. The Contractor is responsible for installation of seismic switches at ATR. 30
B. The Contractor is responsible for on-site (ATR) acceptance testing, including setpoint 31 verification and response time testing. 32
C. The Contractor is responsible for removal or disposal of existing equipment. 33
D. Preparation of installation procedures or onsite training is not included. 34
PART 4 CONTRACTOR-PROVIDED MATERIALS, EQUIPMENT AND SERVICES 35
A. Contractor shall provide the Subcontractor with available interface documentation or 36 drawings, as available and desired, to support the Subcontractor’s understanding of the 37 seismic switch electrical and functional interfaces with the ATR Plant Protection System 38
(PPS). 39
PART 5 APPLICABLE CODES, PROCEDURES AND REFERENCES 40
A. ASME NQA-1-2022, Quality Assurance Requirements for Nuclear Facility Applications 42
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 3 of 8
B. IEEE Std 603-2018, Criteria for Safety Systems for Nuclear Power Generating Stations 1 C. IEEE Std 323-2003, IEEE Standard for Qualifying Class 1E Equipment for Nuclear 2
Power Generating Stations 3 D. IEEE Std 344-2004, IEEE Standard for Seismic Qualification of Equipment for Nuclear 4
Power Generating Stations 5 E. ANSI/ISA-67.04.01-2018, Setpoints for Nuclear Safety-Related Instrumentation 6
PART 6 DESIGN REQUIREMENTS 8
A. General: 10
a. The seismic switch shall be safety-related and qualified as Class 1E equipment. 11
b. Qualification documentation shall demonstrate the switch’s ability to perform its 12 safety function for the qualified life under all specified service conditions of section 13 6.C, including normal and abnormal environments per IEEE 323. 14
c. The Subcontractor shall provide all necessary equipment that not standard equipment 15 for the conduct of testing and calibration. 16
B. Performance: 17
a. The switch shall sense ground motion in three orthogonal directions and change the 18
Form C (or equivalent) dry contact output state when any one axis reaches the 19 defined setpoint. 20
b. The switch shall demonstrate by qualification testing that it trips at a static setpoint 21 ≤0.0105g in each axis. This setpoint includes all uncertainties from the test 22 equipment and switch. Uncertainty analysis shall be documented and consistent with 23
ANSI/ISA-67.04.01-2018. 24
c. All switch and test equipment uncertainties, including environmental, reference, and 25 drift effects, shall be provided. 26
d. The switch shall demonstrate by qualification testing that a static setpoint of 0.01g 27 per axis provides a combined dynamic response setpoint of ≤0.017g over a frequency 28 range of 2.5 to 6 Hz. 29
e. The setpoint shall have a 0.005 to 0.05g field adjustable setpoint. 30
f. The response time, defined as the time interval between when the measured variable 31 at the sensor reaches the setpoint and the instant the output contact changes state, 32 shall be ≤150ms. 33
g. The switch shall provide one Form C dry contact, or equivalent, with a rating of 10 34 Watts DC 12VA AC. 35
h. Output contact shall stay closed for 10 seconds after detection of an acceleration over 36 the setpoint value. 37
i. Power consumption of each seismic switch unit shall be ≤5W. 38
j. Each seismic switch shall be powered from 12Vdc source through an external 39 connection on an external panel. 40 C. Site and Operating Environment: 41
a. Normal environment. Temperature: 70 to 105ºF, Relative humidity: 0 to 90%, 42 Gamma Radiation dose rate: 0 to 10 mR/hr. 43
b. Abnormal environment (up to 48 hours). Temperature: 40 to 125ºF, Relative 44 humidity: 0 to 95%, Gamma Radiation dose rate: 0 to 20 mR/hr. 45
c. No chemical spray, submergence, or similar harsh environmental conditions are 46 applicable. 47
D. Reliability and Maintainability: 48
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 4 of 8
a. The switch shall have a qualified life of 20 years. This qualified life shall be 1 established consistent with IEEE 323. Documentation of the qualification shall be 2 provided by Subcontractor. 3
b. The switch shall include means for in-situ testing, to include at a minimum functional 4 actuation of each axis, calibration verification of setpoint per axis, and response time 5 testing which shall include a circuit trigger to be used by Contractor test equipment. 6
c. Subcontractor shall provide all test equipment necessary to perform testing described 7 in 6.D.b. 8
d. Subcontractor shall provide recommended maintenance and surveillance intervals to 9 maintain qualification consistent with IEEE 323. 10
E. Restrictions: 11
a. The mounting of the switch shall be replicated to match the installed configuration. 12
This includes any supporting members and fastener hardware. 13
b. Each switch shall not exceed 8.5in (L) x 8.5in (D) x 9.5in (H). 14
c. Electrical equipment shall be listed/labeled by a NRTL for the intended application. 15
Any use not in accordance with listing requires Contractor Authority Having 16 Jurisdiction (AHJ) approval. 17
d. All user-adjustable parameters, test points, indicators, and terminals shall be on an 18 external vertical panel. Internal adjustments are not permitted. 19
F. Software: 20
a. If embedded software is used, Subcontractor shall implement software quality 21 controls compliant with ASME NQA-1-2022 with evidence provided in the 22 qualification package. 23
b. Subcontractor shall identify all software parameters requiring Contractor adjustment 24 or verification and provide documentation detailing parameter effects, adjustment 25 procedures, default values, and post-adjustment verification. 26
G. Human Factors: 27
a. All connections, adjustments, and indications shall be located on one external vertical 28 panel for ease of maintenance, testing, and visibility. 29
b. The arrangement of controls, indicators, and test connections shall support clear 30 status indication and safe manual actions and be accessible to the 31 operator/maintainer. 32
c. Subcontractor shall provide legible panel labeling and an operation or test guide 33 appropriate for field use. 34
H. Natural Phenomena Hazards: 35
a. Subcontractor shall develop and execute a type-test program demonstrating the 36 seismic switch’s sensing and actuation performance in all three axes. The program 37 shall follow IEEE 344 recommended practices for seismic test planning, mounting, 38 connections, monitoring, and documentation. 39
b. The test program shall demonstrate trip at ≤0.017g dynamic input for 2.5 to 6 hz, 40 consistent with the performance criteria in section 6.B.d. 41
c. The test program shall verify static trip ≤0.0105g per axis, including all equipment 42 uncertainties consistent with section 6.B.b. 43
d. Mount the switch in its expected installation configuration consistent with section 44 6.E.a and connect interfaces representative of field installation per IEEE 344. 45
e. Acquire motion and contact-closure timing with calibrated instrumentation to 46 confirm ≤150ms response time. 47
f. Test monitoring and documentation shall follow IEEE 323 and IEEE 344 guidance. 48
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 5 of 8
PART 7 SUBMITTALS 1
A. General: 2
i. Submittal requirements shall be listed on a Vendor Data Schedule (Form 431.14) 3 provided separately by the Contractor. 4
ii. The Subcontractor shall transmit all submittals using Form 431.13, “Vendor Data 5 Transmittal & Disposition Form.” 6
B. Qualification Documentation 7
i. Environmental and Seismic Qualification documents shall meet the requirements 8 of IEEE 323-2003 and IEEE 344-2004. The qualification documents shall 9 provide the following information at minimum. 10
1. Equipment specification and safety function identification. 11
2. Qualification plan and test procedures. 12
3. Aging/qualified life basis for a 20-year qualified life. 13
4. Test configurations, mounting, and connection details. 14
5. Test performance results including static and dynamic setpoint 15 qualification and response time measurements. 16
a. Static setpoint trip performance ≤0.0105g per axis, including all 17 uncertainties. 18
b. Dynamic response qualification demonstrating combined trip 19
≤0.017g at 2.5 to 6Hz. 20
c. Response time demonstration ≤150ms. 21
d. Test equipment identification, calibration references and 22 standards, data plots. 23
6. Identification of margins, acceptance criteria, and final qualification 24 conclusions. 25
7. Required surveillance, maintenance, or replacement intervals to maintain 26 qualification. 27 C. Setpoint and Calibration Documentation 28
i. Setpoint uncertainty analysis developed in accordance with ANSI/ISA-67.04.01-29 2018. 30
ii. Documentation showing calculation method, uncertainty method, uncertainty 31 terms, test tolerances, and confirmation that as-left and as-found values maintain 32 required safety function. 33
iii. Description of the setpoint configuration and any parameters adjustable by the 34 Contractor. 35
D. Software Quality Documentation (if applicable) 36
i. Evidence of conformance with ASME NQA-1-2022 software requirements. 37
1. Software lifecycle documentation to include requirements, design, 38 verification, and validation. 39
2. Software configuration, revision or version number, and test records. 40
3. Contractor adjustable parameters with documented functional effects. 41
E. Drawings and Interface Documentation 42
i. Dimensional drawings 43
ii. External panel layout showing connector pinout and types, indicators, 44 adjustments, and test points. 45
iii. Connector wiring diagram for cable connection. 46
iv. Recommended mounting orientation and installation details. 47
F. Testing and Maintenance Documentation 48
i. User’s Manual 49
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 6 of 8
1. Installation, adjustment, and configuration instructions. 1
2. In-situ test procedures for each of the axes (functional, calibration, and 2 response time testing). 3
3. Test equipment requirements and any Subcontractor provided tools. 4
4. Safety considerations and precautions. 5
ii. Recommended maintenance and surveillance intervals supporting qualified life 6 basis. 7
G. Certifications and Compliance Documentation 8
i. Certificate of conformance for material, fabrication, testing, and qualification. 9
ii. NRTL listing or certification documentation. 10
iii. Documentation identifying compliance with applicable standards listed in Part 5. 11
PART 8 QUALITY ASSURANCE 13
A. Quality Assurance Program Requirements 15
i. The Subcontractor shall maintain and implement a Quality Assurance Program 16 that meets the applicable requirements of ASME NQA-1-2022. 17
ii. The Subcontractor shall ensure that all activities affecting quality which include 18 design, procurement, fabrication, qualification testing, inspection, handling, 19 storage, calibration, software control, and documentation are performed under 20 controlled conditions in accordance with Subcontractor’s NQA-1 compliant 21 program. 22
B. Subcontractor Quality Assurance Program Evaluation and Audit 23
i. The Contractor will conduct a Subcontractor quality assurance audit prior to 24 acceptance of qualification activities or hardware. 25
ii. The Subcontractor shall permit Contractor access to facilities, personnel, 26 procedures, quality assurance records, and equipment necessary to support the 27 audit. 28
iii. The Subcontractor shall correct any audit findings in accordance with its NQA-1 29 corrective action program and provide documented evidence of resolution. 30
C. Quality Assurance Requirements for Subcontractor Suppliers 31
i. The Subcontractor shall flow down all applicable quality assurance requirements 32 and technical requirements to all suppliers performing work associated with this 33 specification. 34
ii. The Subcontractor shall ensure that suppliers maintain adequate controls for 35 procurement, fabrication, testing, calibration, and software development if 36 applicable. 37
iii. Quality assurance documentation from suppliers shall be retained and included in 38 the final qualification package provided to the Contractor. 39
D. Inspection and Testing Controls 40
i. All qualification testing, calibration, inspection, and acceptance activities shall be 41 performed using procedures controlled under the Subcontractor’s quality 42 assurance program. 43
ii. Measurement and test equipment used in qualification and acceptance shall be 44 calibrated to nationally traceable standards and controlled in accordance with 45 NQA-1 requirements. 46
iii. The Subcontractor shall document test configurations, environmental conditions, 47 mounting details, instrumentation calibration data, acceptance criteria, and results 48 for all qualification tests. 49
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 7 of 8
E. Software Quality Assurance (if applicable) 1
i. If embedded software is used in the seismic switch, the Subcontractor shall 2 implement a software quality assurance program meeting the software 3 requirements contained within ASME NQA-1-2022. 4
ii. All Contractor adjustable software parameters shall be uniquely identified and 5 documented with their functions, constraints, and effects on switch operation. 6
F. Certification, Records, and Traceability 7
i. The Subcontractor shall provide a Certificate of Conformance stating that the 8 seismic switches meet all requirements of this specification and all identified 9 codes and standards. 10
ii. Quality assurance records including material certifications, fabrication and 11 assembly records, maintenance and test equipment calibration certificates, 12 qualification test reports, audit documentation, and software quality assurance 13 records shall be retained and transmitted to the Contractor. 14
iii. All seismic switches shall be traceable to documented manufacturing and 15 qualification records by unique serial number, batch number, or equivalent 16 identifier. 17
G. NRTL Listing 18
i. Electrical components and assemblies shall be listed or recognized by a NRTL. 19
ii. Any use of NRTL listed equipment outside its intended listing shall require 20 formal approval from the Contractor’s AHJ. 21
PART 9 DELIVERY, STORAGE, AND PROTECTION 23
A. Packaging and Shipping 24
a. The seismic switches shall be packaged to prevent damage, moisture intrusion, 25 vibration impact, or contamination during shipment. Packaging shall comply with 26 manufacturer recommendations and industry best practices for sensitive electrical and 27 instrumentation components. 28
b. Each switch shall be shipped in a protective enclosure or crate suitable for forklift or 29 pallet jack handling. The enclosure shall prevent mechanical shock or deformation of 30 the switch’s external panel, connectors, and indicators. 31
c. The Subcontractor shall include all required accessories, mounting hardware, test 32 equipment, manuals, and documentation within the shipment, packaged to prevent 33 loss or damage. 34
B. Marking and Identification 35
a. Shipping containers shall be clearly labeled with: 36
i. Purchase order number 37
ii. Subcontractor name 38
iii. Item description and quantity 39
iv. Total weight 40
v. Serial numbers or unique identifiers for each seismic switch 41
vi. Contractor provide catalog identification number 42
b. Any containers with multiple switches shall include internal identification so each 43 unit can be traced to its qualification and documentation package. 44 C. Storage Conditions 45
a. Subcontractor shall provide any special storage requirements such as orientation, 46 temperature, relative humidity, vibration isolation, and maximum stack height as part 47 of the User’s Manual. 48
Revision:
Effective Date:
SPC-71463
10/08/26 Page: 8 of 8
b. The Subcontractor shall ensure that switches are protected from corrosive 1 environments, excessive dust, and direct precipitation. 2
D. Handling Protection 3
a. The seismic switches shall be handled in a manner that avoids mechanical shock, 4 deformation, or stress on external connectors, test points, and indicators. 5
b. Lifting or handling points shall be identified if required by the design, otherwise the 6
Subcontractor shall specify acceptable handling methods in the User’s Manual. 7 E. Transit Protection 8
a. The Subcontractor shall ensure that the switch is protected from static discharge 9 hazards during shipment using anti-static packaging methods where appropriate. 10
b. The Subcontractor shall ensure the switch is shipped in a manner that prevents 11 inadvertent actuation or mechanical disturbance of internal sensing elements. 12