This document is a Request for Information (RFI) from the Department of the Air Force Air Education and Training Command regarding industrial fans for Buildings 10263 and 5423. The RFI is seeking information from potential contractors on their ability to provide the required industrial ceiling and beam-mounted directional fans, including details on their manufacturing/production capabilities, past military experience, and pricing. The key product specifications are provided, such as fan size, motor power, sound levels, and electrical requirements. Contractors are asked to respond by November 25, 2024 with their pricing, whether it is GSA or open market, and other company information. This RFI is for market research purposes only and is not a solicitation for a future contract award.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
502D AIR BASE WING
JOINT BASE SAN ANTONIO
18 November 2024
| TO: | 502D Contracting Squadron |
| 1655 Selfridge Ave. | |
| JBSA – Lackland AFB, TX 78236 |
| FROM: | Company Name _________________________________ |
| Address _______________________________________ | |
| Phone No. _____________________________________ | |
| Email Address __________________________________ | |
| Cage Code ____________________________________ |
SUBJECT: Industrial Fans Bldg. 10263 and 5423
1. The Government is only conducting market research and attaining information to identify contractors that can provide all items listed below and the cost associated to acquire these specific items/services. All information provided is STRICTLY VOLUNTARY.
2. Is your company a small business? ______________ (Yes/ No)
3. If Small Business, please identify company’s socio-economic concern(s): ______________________ (HUBZone, service-disable veteran-owned small bus., women-owned small bus., etc.…)
4. Have you previously supplied the item to military customers? ________(Yes/No)
5. Do you manufacture/produce the items listed below? ______________ (Yes/ No)
6. If you do not manufacture/produce the items, do you obtain them from a small business in the USA? ______________ (Yes/ No)
7. Please take the opportunity to provide cost input for the products listed below (voluntarily). Please note there are no estimated quantities. Refer to Attachment 1 and Attachment 2 (listed on page 2) Industrial Fans Bldg. 10263 AND 5423 (brand name or equal)
IMPORTANT NOTE: This requirement is brand name or equal
| Products |
| Unit |
| QTY. |
| Unit Price |
| Extended Amount |
| Industrial Ceiling Mounted Fans |
| 4 |
| 4 |
| Industrial Beam Mounted Directional Fans |
| 2 |
| 2 |
SPECIFIC REQUIREMENTS:
Building 10263
The industrial ceiling fans shall be mounted to structural steel beams and shall have stainless steel safety cables that are approximately 3/32” in diameter
The contractor shall hang industrial ceiling fans with mount from the manufacturer and installed in accordance with manufacturer specifications
The contractors shall make electrical connections from the industrial ceiling fans to the electrical panel
Contractor shall run applicable, fire code compliant cable from the fans to the fire relay panel
Contractor shall wire fans to power off if the fire suppression system is activated
All required electrical cable, and wires shall be placed in electric metal tubing (EMT) conduit, there shall not be any exposed cable or wires routed through the ceiling or walls
Contractor shall ensure automatic shutoff of all fans anytime the fire suppression system is activated. All required cabling that is routed to the fire relay panel shall be placed in steel conduit that is coated with red paint to easily identify cables running to fire relay panel
Contractor shall install fans to give the Government the option to operate independently or together
The contractor shall ensure all possible deflection, vibration, torque, and other such detrimental forces are taken into account, controlled, and eliminated as necessary
Operation of all four fans shall be controlled by one control panel mounted at a height of 4’ 6” to the steel support beam located closes to the south end of the modular office
The contractor shall provide and install all conduit, fittings, boxes, wire, and switches necessary to establish full and necessary electrical circuits and ensure a fully functional and code compliant ceiling fan system
Contractor shall install fans to have a minimum clearance of 10’ 6” from the ground
Contractor shall install fans to give 18” clearance from fire suppression system
Contractor shall install Fan 1 on main structural ceiling beam 63’ from the north wall and 15’ from the east wall. Fan shall be centered between vertical beams
Contractor shall install Fan 2 on main structural ceiling beam 32’ from south wall and 15’ from east wall. Fan shall be centered between vertical beams
Contractor shall install Fan 3 on main structural ceiling beam 22’ from the south wall of the modular office and 15’ from the west wall. Fan shall be centered between vertical beams
Contractor shall install Fan 4 on main structural ceiling beam 26’ from south wall and 15’ from west wall. Fan shall be centered between vertical beams
Building 5423
Industrial directional fans shall be mounted to structural beams
Contractor shall mount industrial directional fans with mounting equipment from the manufacturer and install in accordance with manufacturer specifications
Contractor shall make necessary electrical connections from fans to electrical panel
Contractor shall route all cable/wire through conduit, there shall not be any exposed cable routed through the ceiling or walls
Contractor shall provide and install all conduit, fittings, boxes, wire, and switches necessary to establish full and necessary electrical circuits and ensure a fully functional and code compliant ceiling fan system
Contractor shall install power controls to support beams located closest to the fan at height of 4 ½’ (see layout for further information)
Contractor shall mount fans in a direction that provides the most cooling and air circulation to work area
Contractor shall ensure all possible deflection, vibration, torque, and other such detrimental forces are taken into account, controlled, and eliminated as necessary
Contractor shall install Fan 1 from the ceiling support beam south of the modular office on the east side of building approximately 9’ from the east wall.
Contractor shall install Fan 2 from the southernmost support beam 6’ from the west wall (See attached project layout for more information)
PRODUCT SPECIFICATIONS:
Image of ceiling structural beams
(4) INDUSTRIAL CEILING MOUNTED FAN
Diameter: Approximately 8 ft
Number of Blades: 8
Sound at max speed: Approximately 55 decibels (dBA)
Overall, Weight without the mount: Approximately135 lbs. (61 kgs)
Motor size: Approximately 1.0 hp
Variable Speed: Approximately 0 – 191 revolutions per minute (RPM)
Input power and required breaker: 100-125 VAC, 50/60Hz, 15A
Operation: Keypad & LCD Screen
Fan Controls: Speed Up/Slow Down, Forward/Reverse, On/Off
Mounting Safety Cables: Approximately 3/32” Stainless Steel Cable
Fire relay to shut off fans in case of fire suppression system activation
Image of ceiling structural beams
(2) INDUSTRIAL BEAM MOUNTED DIRECTIONAL FAN
Diameter: Approximately 30”
Input power: 100-120 VAC, 50/60 Hz
Weight: Approximately 67 lbs. (30.4 kg)
Max Amp: 9.46 A
Max Power: 702 W
Max Speed: Approximately 950 RPM
Sound at max speed: Approximately 72 dBA
Approximately 18’ power supply cord
Variable speed: Approximately 0-100
8. Is the pricing offered GSA or Open Market pricing?
9. This request for information (RFI) is strictly voluntary and is not to be interpreted as a quote in anticipation of a future contract award.
10. Please respond via e-mail by 25 Nov 2024, 12 pm CST. Email: Caroline Holmon caroline.holmon.1@us.af.mil and Mr. Lance Watters lance.watters.1@us.af.mil . If you have any questions, please contact Caroline Holmon caroline.holmon.1@us.af.mil.
Attachments:
Attach 1 – Salient Characteristics Attach 2- Statement of Work