IFQ_1100_CPG1095_IFQ_ATT_1_v1.pdf
PDF 160 KB Posted
- Attached to
- Spare Main Generator Breaker
- Solicitation number
- IFQ 1100 CPG1095
- Issued by
- Texas
About this file
This Scope of Work document, issued by the City of Austin, Austin Energy for the Decker Creek Power Station, requests the procurement of one complete spare medium-voltage generator breaker assembly suitable for power generation applications. The breaker must be new or refurbished, factory-tested, and compliant with applicable ANSI/IEEE standards for 15 kV class switchgear equipment, specifically meeting or exceeding the specifications of the original ITE Imperial Corporation Model 11 breaker (Serial 95757-A1-3-8A). Deliverables include breaker specifications and drawings with dimensional and weight information, quality assurance documentation, warranty terms, datasheets, certified drawings, installation and operation manuals, Factory Acceptance Test reports, and a recommended spare parts list for two-year and five-year periods. Services required encompass Factory Acceptance Testing, commissioning and startup support, and maintenance scheduling. All submittals must be directed to Rogelio Zavala, James Cox, and Maria Bernal Mora at designated City of Austin email addresses, with technical questions routed through the City of Austin procurement department.
The document establishes a quote item sheet format requiring bidders to submit pricing for the main generator breaker, shipping costs, and total project cost with a "not to exceed" price stated in words. The original breaker specifications include a rated voltage of 13.8 kV (maximum 15 kV), rated continuous current of 3,000 amperes, and rated symmetric MVA capacity of 11.5 to 15.0 kV at 1,000 MVA with a symmetric short-circuit current of 8,500 amperes. No specific response deadline, award date, contract term, renewal options, set-asides, incumbent information, or funding source amounts are identified in this document. Bidders must comply with IEEE standards C37.04, C37.06, C37.09, C37.20.1, C37.013, IEEE 80, and IEC 62271-37-013 for breaker selection, capabilities, testing procedures, and generator-specific performance and safety requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFQ_1100_CPG1095_IFQ_ADD_1_v1.xlsx | XLSX spreadsheet | |
| IFQ_1100_CPG1095_IFQ_PAC_1_v1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Scope of Work for Main Generator Breaker October 22, 2026 Decker Creek Power Station
Main Generator Breaker 1
SOW Main Generator Breaker
Main Generator Breaker 2
1. General
The supplier shall furnish one (1) complete spare medium-voltage generator breaker assembly suitable for use in a power generation application. The breaker shall be new, or refurbished, factory-tested, and compliant with applicable ANSI/IEEE standards for 15 kV class switchgear equipment.
1.1 Defined Terms
As used in this specification, each of the following terms shall have the meaning as set forth below.
1.2 Document Submittal Requirements
All Documents required in this specification shall be digitally submitted to the following:
Rogelio Zavala ............................................................. rogelio.zavala@austinenergy.com James Cox ......................................................................... james.cox@austinenergy.com Maria Bernal Mora .................................................. maria.bernalmora@austinenergy.com
1.2.1 Documents required with submittals
1.2.1.1 Breaker specifications demonstrating specifications requested in section 2.
1.2.1.2 Breaker drawings to include dimensions of enclosure, and approximate package weight, at minimum.
1.2.1.3 Quality assurance and Warranty terms
1.3 Communication
All digital correspondence pertaining to this specification shall include the personnel listed in section 1.2
All questions regarding the Contract Requirements/Terms and Conditions shall be directed to City of Austin procurement department.
Engineer The Engineer who developed this specification on behalf of Owner
OEM The Entity that designed, manufactured, and furnished Owner’s existing equipment
Owner City of Austin, Austin Energy, Decker Creek Power Station Staff, Purchaser, Buyer
SOW Scope of Work
NEC National Electric Code mailto:rogelio.zavala@austinenergy.com mailto:james.cox@austinenergy.com mailto:maria.bernalmora@austinenergy.com
Main Generator Breaker 3
1.4 Standards
• IEEE C37.04 – Rating structure for AC high-voltage circuit breakers (relevant for breaker selection and coordination) IEEE Standards Association.
• IEEE C37.06 – Preferred ratings and related capabilities for high-voltage AC circuit breakers IEEE Standards Association.
• IEEE C37.09 – Test procedures for AC high-voltage circuit breakers IEEE Standards Association.
• IEEE C37.20.1 – ANSI Standard for Metal-Clad Switchgear (older version, superseded by C37.20.2) search.abb.com.
• IEEE 80 – Guide for safety in AC substation grounding (important for grounding design in substations) IEEE Standards Association.
• IEEE C37.013 (AC High-Voltage Generator Circuit Breakers) and the newer IEC/ANSI dual-logo standard
• IEC 62271-37-013, which define performance, testing, and safety requirements for generator-specific circuit breakers
2. Specifications for Compressor
2.1 Original Main Generator Breaker – ITE Imperial Corporation, Model 11, Serial
95757-A1-3-8A. Name plate data:
• Rated KV 13.8, Maximum KV 15
• Impulse KV 95
• Frequency 60
• Rated continuous current 3000
• Rated SYM MVA 11.5 to 15.0 KV 1000
• Rated SYM Short-Circuit current 3 8500
• Asymmetrical rating factor 1.15
• Control voltage {Charge close trip 1 25DC
2.2 Documentation Deliverables
• Datasheets and certified drawings
• Installation, operation, and maintenance manuals
• FAT test reports
• Recommended spare parts list (2-year and 5-year)
2.3 Services
• Factory Acceptance Test (FAT)
• Commissioning and startup support
• Maintenance schedule https://www.bing.com/ck/a?!&&p=70e8888cfa25b87f530d679449afba0757571c39bb82d90814a034db49a6e017JmltdHM9MTc5MjYyNzIwMA&ptn=3&ver=2&hsh=4&fclid=05447265-4573-63cc-048f-6592442062fa&psq=ANSI%2fIEEE+standards+for+15+kV+class+switchgear+equipment&u=a1aHR0cHM6Ly9zdGFuZGFyZHMuaWVlZS5vcmcvd3AtY29udGVudC91cGxvYWRzL2ltcG9ydC9kb2N1bWVudHMvdG9jcy9zd2l0Y2hnZWFyX3N0YW5kYXJkc19jb2xsZWN0aW9uLnBkZg&ntb=1 https://www.bing.com/ck/a?!&&p=70e8888cfa25b87f530d679449afba0757571c39bb82d90814a034db49a6e017JmltdHM9MTc5MjYyNzIwMA&ptn=3&ver=2&hsh=4&fclid=05447265-4573-63cc-048f-6592442062fa&psq=ANSI%2fIEEE+standards+for+15+kV+class+switchgear+equipment&u=a1aHR0cHM6Ly9zdGFuZGFyZHMuaWVlZS5vcmcvd3AtY29udGVudC91cGxvYWRzL2ltcG9ydC9kb2N1bWVudHMvdG9jcy9zd2l0Y2hnZWFyX3N0YW5kYXJkc19jb2xsZWN0aW9uLnBkZg&ntb=1 https://www.bing.com/ck/a?!&&p=70e8888cfa25b87f530d679449afba0757571c39bb82d90814a034db49a6e017JmltdHM9MTc5MjYyNzIwMA&ptn=3&ver=2&hsh=4&fclid=05447265-4573-63cc-048f-6592442062fa&psq=ANSI%2fIEEE+standards+for+15+kV+class+switchgear+equipment&u=a1aHR0cHM6Ly9zdGFuZGFyZHMuaWVlZS5vcmcvd3AtY29udGVudC91cGxvYWRzL2ltcG9ydC9kb2N1bWVudHMvdG9jcy9zd2l0Y2hnZWFyX3N0YW5kYXJkc19jb2xsZWN0aW9uLnBkZg&ntb=1 https://www.bing.com/ck/a?!&&p=70e8888cfa25b87f530d679449afba0757571c39bb82d90814a034db49a6e017JmltdHM9MTc5MjYyNzIwMA&ptn=3&ver=2&hsh=4&fclid=05447265-4573-63cc-048f-6592442062fa&psq=ANSI%2fIEEE+standards+for+15+kV+class+switchgear+equipment&u=a1aHR0cHM6Ly9zdGFuZGFyZHMuaWVlZS5vcmcvd3AtY29udGVudC91cGxvYWRzL2ltcG9ydC9kb2N1bWVudHMvdG9jcy9zd2l0Y2hnZWFyX3N0YW5kYXJkc19jb2xsZWN0aW9uLnBkZg&ntb=1 https://www.bing.com/ck/a?!&&p=da3d4304009112ed04d261c82a7425cdd94fa3eacc43a31727c97b725445c363JmltdHM9MTc5MjYyNzIwMA&ptn=3&ver=2&hsh=4&fclid=05447265-4573-63cc-048f-6592442062fa&psq=ANSI%2fIEEE+standards+for+15+kV+class+switchgear+equipment&u=a1aHR0cHM6Ly9zZWFyY2guYWJiLmNvbS9saWJyYXJ5L0Rvd25sb2FkLmFzcHg_RG9jdW1lbnRJRD0xVkFMMTA3MDAzLVRHJkRvY3VtZW50UGFydElk&ntb=1 https://www.bing.com/ck/a?!&&p=ca9c0a7c6ad9a268902c26af26e30ab34d01f616ecf80dbed6a8408856e9b78cJmltdHM9MTc5MjYyNzIwMA&ptn=3&ver=2&hsh=4&fclid=05447265-4573-63cc-048f-6592442062fa&psq=ANSI%2fIEEE+standards+for+15+kV+class+switchgear+equipment&u=a1aHR0cHM6Ly9zdGFuZGFyZHMuaWVlZS5vcmcvd3AtY29udGVudC91cGxvYWRzL2ltcG9ydC9kb2N1bWVudHMvdG9jcy9wb3dlcl9jb2xsLnBkZg&ntb=1
Main Generator Breaker 4
2.4 Quality and Standards
• Compliance with applicable standards refer to section 1.4
• Vendor quality assurance and warranty terms
Main Generator Breaker 5
3. Quote Item Sheet
Quote Item Description Quote Item Cost
1. Main Generator Breaker
2. Shipping cost
3.
Total Cost for all Work Items
Total NOT TO EXCEED Quote Price (In Words) For All Work in Above Table:
Company Name:
Company Contact Phone Number:
Company Contact Fax Number:
Authorized Representative’s Name (Print)
Authorized Representative’s Signature:
Date: