IFB_161109_-_DRAWINGS_FOR_CONSTRUCTION_2026-09-28.pdf
PDF 2 MB Posted
- Attached to
- 161109 VDOT Lynchburg Admin Building Chiller Rep
- Solicitation number
- IFB-130628
- Issued by
- Charlottesville City, Virginia
About this file
This file comprises construction drawings and specifications for the Lynchburg District Administration Building Chiller Replacement Project (Project Code 501-B6501-007) issued by the Virginia Department of Transportation (VDOT) as Invitation for Bid (IFB) #161109. The project involves the replacement of a split system air-cooled chiller with a packaged air-cooled chiller at the administration building located at 4219 Campbell Avenue, Lynchburg, Virginia. The owner-furnished chiller is a Carrier 30RC-0205610B-213 packaged air-cooled unit with a nominal capacity of 20 tons, and the contractor is responsible for installation and associated work. The project scope includes demolition of the existing split system chiller and associated refrigerant piping, removal of chilled water supply and return piping, replacement of control systems, installation of heat trace protection for freeze prevention, provision of new concrete pad and screen walls, and coordination with existing mechanical systems. The construction documents consist of a title sheet, demolition plan, structural plan with details for new brick masonry and foundation work, mechanical plan with chiller schematic and specifications, and electrical plans with single-line diagram and panelboard schedules. The project is designed in accordance with the 2021 Virginia Uniform Statewide Building Code, Virginia Mechanical Code, Virginia Energy Conservation Code, and the National Electrical Code (NFPA 70-2020). The construction is scheduled for completion by September 28, 2026, which is the date of these drawings.
The contractor must comply with all applicable Virginia codes and regulations, perform site visits to verify existing conditions prior to bidding, provide pre-demolition photographic documentation, maintain as-built drawings, and coordinate work with all trades and existing building systems. Material submittals are required within thirty days of contract award, and operation and maintenance manuals must be provided at substantial completion. The contractor bears responsibility for site safety, security, utility coordination, environmental protection, and correction of any damage resulting from construction activities. Specific requirements include freeze protection for the chiller system with factory heat-traced components and additional heat trace on outdoor piping connected to dual-circuit controllers with alarms, provision of temporary power and water service, installation of construction fencing, and daily site cleanup. The mechanical systems include dual pump packages with variable frequency drive-compatible motors, air separators, magnetic dirt separators, tangential air separators, and piping insulation requirements. Electrical work requires new circuits from switchboard SWBD-3 to panel BR1 for the chiller, heat trace controllers, and dual-temperature changeover valve actuators, with specific conductor sizing and voltage drop calculations detailed. The project involves coordination with VDOT site representative Mark Burnley (434-363-0818) and requires compliance with all professional services standards outlined in the 2026 Construction and Professional Services Manual.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFB_161109_-_PROJECT_MANUAL_FOR_CONSTRUCTION.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING LIST:
ASBESTOS DISCLOSURE STATEMENT:
LEAD PAINT DISCLOSURE STATEMENT:
DISCLAIMER STATEMENT:
VIRGINIA A&E ASSUMES NO RESPONSIBILITY FOR THE ADEQUACY OR ACCURACY OF THE ASBESTOS AND LEAD INSPECTIONS REPORTS CONTAINED IN THE CONTRACT DOCUMENTS AS THIS INFORMATION WAS PREPARED BY VDOT. THE CONTRACTOR SHALL ADDRESS ANY
RELATED QUESTIONS TO THE VDOT REPRESENTATIVE.
DRAWING NO TITLE
T1 TITLE SHEET
D1 DEMOLITION PLAN
S1 STRUCTURAL PLAN
M1 LEGEND AND SPECIFICATIONS
M2 MECHANICAL PLAN
E1 LEGEND, ABBREVIATIONS, GENERAL NOTES, AND SPECIFICATIONS
E2 SINGLE LINE DIAGRAM
E3 ELECTRICAL PLAN
E4 SCHEDULES, DETAILS, AND CALCULATIONS
(ASBESTOS PRESENT BUT NOT TO BE DISTURBED) AN INSPECTION TO IDENTIFY ABSESTOS-CONTAINING MATERIALS HAS BEEN CONDUCTED AND CAN BE FOUND AS PART OF APPENDIX A TO THE PROJECT SPECIFICATIONS. MATERIALS CONTAINING ASBESTOS BUT ARE NOT TO BE DISTURBED WERE IDENTIFIED BY THE REPORT IN THE BUILDING. SHOULD THE CONTRACTOR ACCESS ANY MATERIAL SUSPECTED OF CONTAINING ASBESTOS NOT IDENTIFIED BY THESE REPORTS, HE SHALL STOP WORK IN THE IMMEDIATE AREA AND NOTIFY THE OWNER (VDOT).
THE REMOVAL OF ASBESTOS MATERIALS IS NOT TO BE CONDUCTED WITHOUT THE OWNERS ASBESTOS PROJECT MONITOR BEING ON-SITE.
AN INSPECTION TO IDENTIFY LEAD COATED BUILDING COMPONENTS HAS BEEN CONDUCTED AND CAN BE FOUND AS PART OF APPENDIX A TO THE ASBESTOS PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE CONTRACTOR'S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY
PERTAIN TO EMPLOYEE EXPOSURES TO LEAD.
LYNCHBURG DISTRICT ADMINISTRATION BUILDING
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
FOR CONSTRUCTION
SEPTEMBER 28, 2026
Drawing No.:
Project No.:
1"
Full Scale Verification
0"
T1
25084
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VA 24551
PHONE: (434) 316-6001
VAE PROJECT NO: 25084
BUILDING LOCATION NORTH
PROJECT LOCATION MAP
SITE
NORTH
VICINITY MAP
GENERAL NOTES:
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED FOR USE AS
FABRICATION DRAWINGS. THESE DRAWINGS INDICATE THE GENERAL AND APPROXIMATE SIZE
AND LOCATION OF MATERIAL. FIELD VERIFY ALL DIMENSIONS AND LOCATIONS PRIOR TO
BEGINNING WORK. ALL UTILITIES NOTED ON PLANS ARE APPROXIMATE AND CONTRACTOR
SHALL FIELD VERIFY LOCATION.
2. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO, THE 2021 VIRGINIA UNIFORM STATEWIDE BUILDING CODE
(JANUARY 18, 2024) AND ASSOCIATED CODES OF REFERENCE. REFER TO APPLICABLE CODES
LIST THIS DRAWING.
3. ALL MATERIAL SHALL BE NEW UNLESS OTHERWISE NOTED. NO ASBESTOS CONTAINING
MATERIALS SHALL BE USED. MATERIALS ARE BASED ON THE INDICATED
MANUFACTURER'S/MODELS AND ARE INTENDED ONLY TO SHOW THE GENERAL SIZE,
CONFIGURATION, LOCATION, CONNECTIONS, AND SUPPORT FOR INDICATED MATERIAL WITH
RELATION TO OTHER BUILDING SYSTEMS. MATERIAL BY ANY MANUFACTURER THAT MEETS THE
SCHEDULED CRITERIA IS ACCEPTABLE. CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATING ACTUAL INSTALLED MATERIAL AND ASSOCIATED CHANGES.
4. CONTRACTOR SHALL COORDINATE THE WORK WITH EXISTING CONDITIONS, INCLUDING BEAMS, COLUMNS, SITE FEATURES, AND OTHER OBSTRUCTIONS, WHETHER OR NOT SUCH IS SHOWN ON
DRAWINGS.
5. CONTACT VIRGINIA 811 AT 1-800-552-7001, OR HTTPS://WWW.VA811.COM NO LESS THAN 72
HOURS PRIOR TO EXCAVATION AND DO NOT DISTURB THE SOIL UNTIL DIG TICKET HAS BEEN
PROCESSED.
6. CONTRACTOR SHALL COORDINATE THE WORK BETWEEN ALL TRADES. MATERIAL LOCATIONS
SHALL BE COORDINATED BETWEEN STRUCTURAL, MECHANICAL, ELECTRICAL, AND DEMOLITION
PLANS TO AVOID CONFLICTS.
7. EXISTING MATERIAL TO BE REMOVED SHALL BE REMOVED CAREFULLY TO AVOID DAMAGING
MATERIAL TO REMAIN. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE THAT OCCURS
TO EXISTING MATERIAL TO REMAIN OR TO BE RELOCATED DURING DEMOLITION AND
CONSTRUCTION.
8. CONTRACTOR SHALL ADVISE THE A/E IMMEDIATELY OF DISCREPANCIES FOUND ON THE
DRAWINGS, IN THE SPECIFICATIONS, OR BETWEEN THE TWO. MINOR DEVIATIONS FROM THE
PLANS MAY BE MADE TO AVOID MINOR CONFLICTS. WHERE MAJOR CONFLICTS ARE
ENCOUNTERED, THE AFFECTED WORK SHALL NOT BE INSTALLED UNTIL THE CONFLICT HAS
BEEN RESOLVED. NEITHER THE A/E NOR THE OWNER SHALL BE RESPONSIBLE FOR
CONSEQUENCES OF PROCEEDING WITH WORK BASED ON CONTRACTOR INTERPRETATION OR
ON DIRECTION FROM OTHER PARTIES, INCLUDING THE OWNER AND INSPECTORS.
9. ALL MATERIAL SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S WRITTEN INSTALLATION
INSTRUCTIONS, MAINTAINING ALL REQUIRED CLEARANCES AND WITH ALL COMPONENTS
ACCESSIBLE AND SERVICEABLE.
10. CONTRACTOR SHALL PROVIDE MATERIAL DATA SUBMITTALS FOR ALL NEW MATERIAL. REFER TO
INDIVIDUAL DRAWINGS FOR ADDITIONAL SUBMITTAL REQUIREMENTS. THE CONTRACTOR SHALL
PROVIDE A SUBMITTAL SCHEDULE WITHIN 30 DAYS OF AWARD OF CONTRACT.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR ASSEMBLING OPERATION AND MAINTENANCE
MANUALS CONTAINING ALL MATERIAL SUBMITTALS, INSTALLATION AND OPERATING
INSTRUCTIONS, AND WARRANTY INFORMATION. ONE (1) ELECTRONIC PDF COPY OF O&M
MANUALS SHALL BE SUBMITTED TO THE A/E FOR REVIEW AT THE TIME OF SUBSTANTIAL
COMPLETION. PROVIDE ONE (1) HARD COPY AND ONE (1) ELECTRONIC PDF COPY OF THE FINAL
O&M MANUALS TO THE OWNER.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A SET OF AS-BUILT DRAWINGS ON
SITE WHICH INDICATE IN RED ALL DEVIATIONS FROM ORIGINAL CONSTRUCTION DOCUMENTS,
INCLUDING APPROVED CONSTRUCTION CHANGE ORDERS. AS-BUILT DRAWINGS SHALL BE
SUBMITTED TO THE A/E AT THE TIME OF SUBSTANTIAL COMPLETION. AS-BUILT DRAWINGS
SHALL BE CLEARLY LEGIBLE AND COMPLETE.
13. CONTRACTOR SHALL KEEP PUBLIC AREAS FREE OF TRASH AND CONSTRUCTION DEBRIS AND
CLEAN ENTIRE WORK AREA ON A DAILY BASIS.
14. TEMPORARY POWER AND WATER SERVICE ARE AVAILABLE ON SITE FOR THE CONTRACTOR'S
USE. CONTRACTOR SHALL COORDINATE ACCESS WITH OWNER AND SHALL PROVIDE ANY
REQUIRED TEMPORARY CONNECTIONS AND EXTENSIONS.
15. CONTRACTOR SHALL PROVIDE A TEMPORARY TOILET FACILITY FOR USE BY CONTRACTOR'S
PERSONNEL FOR THE DURATION OF THE PROJECT.
16. CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE SCOPE OF WORK AND TO
VERIFY EXISTING CONDITIONS PRIOR TO BIDDING THIS PROJECT. ANY DISCREPANCIES OR
AMBIGUOUS ITEMS MUST BE REPORTED TO THE A/E AND THE OWNER FOR CLARIFICATION
PRIOR TO BIDDING.
17. CONTRACTOR SHALL PROTECT THE BUILDING, ADJACENT FEATURES, ROADWAYS, WALKWAYS, SITE IMPROVEMENTS, EXTERIOR PLANTINGS, LANDSCAPING, ETC AS REQUIRED FROM DAMAGE
AND CORRECT DAMAGE RESULTING FROM CONSTRUCTION ACTIVITIES TO THE SATISFACTION
OF THE OWNER.
18. CONTRACTOR SHALL COLLECT DEMOLISHED MATERIALS AND PLACE IN APPROPRIATE
DISPOSAL CONTAINERS. DEMOLISHED MATERIALS SHALL BE PROMPTLY REMOVED FROM THE
OWNER'S PROPERTY AND DISPOSED OF LEGALLY.
19. CONTRACTOR SHALL COORDINATE MATERIAL STORAGE AND DUMPSTER LOCATION WITH
OWNER DURING CONSTRUCTION.
20. CONTRACTOR SHALL BE RESPONSIBLE FOR SITE SAFETY AND SECURITY FOR THE DURATION
OF THE PROJECT. CONTRACTOR SHALL PROVIDE ORANGE CONSTRUCTION FENCING AROUND
PERIMETER OF WORK AREA.
21. CONTRACTOR SHALL PROVIDE PRE-DEMOLITION PHOTOGRAPHIC OR VIDEOGRAPHIC
DOCUMENTATION TO SHOW EXISTING CONDITIONS OF FINISHED SURFACES IN WORK AREA AND
ADJOINING CONSTRUCTION INCLUDING SITE STORAGE AND ACCESS AREAS PRIOR TO
PRE-CONSTRUCTION MEETING AND A MINIMUM OF 10 WORKING DAYS PRIOR TO
COMMENCEMENT OF WORK.
22. CONTRACTOR SHALL NOTIFY OWNER OF ANY INTERRUPTION OF UTILITIES INCLUDING BUT NOT
LIMITED TO POWER, WATER, COMMUNICATIONS, ETC AND COORDINATE OUTAGE WITH OWNER
AND ALL BUILDING TENANTS.
23. ANY ROAD/PARKING LOT CLOSURE SHALL BE DONE IN ACCORDANCE WITH THE LATEST
VERSION OF THE VIRGINIA WORK AREA PROTECTION MANUAL.
24. DEFINITIONS:
FURNISH: SUPPLY AND DELIVER TO PROJECT SITE FOR INSTALLATION BY OTHERS.
INSTALL: INSTALL ITEMS FURNISHED BY OTHERS, INCLUDING UNLOADING, TEMPORARILY
STORING, UNPACKING, AND ASSEMBLY.
PROVIDE: FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.
REMOVE: DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF THEM
OFF-SITE UNLESS INDICATED TO BE REMOVED AND SALVAGED OR REMOVED AND REINSTALLED.
REMOVE AND REINSTALL: DETACH ITEMS FROM EXISTING CONSTRUCTION, PREPARE FOR
REUSE, AND REINSTALL WHERE INDICATED.
REMOVE AND SALVAGE: CAREFULLY DETACH FROM EXISTING CONSTRUCTION, IN A MANNER TO
PREVENT DAMAGE, AND DELIVER TO OWNER.
R O
U
TE
ROUTE 221
ROUTE 501
R O
U
TE
ROUTE 460
GENERAL INFORMATION:
PROJECT INFORMATION:
AGENCY: VIRGINIA DEPARTMENT OF TRANSPORTATION
PROJECT TITLE: LYNCHBURG DISTRICT ADMINISTRATION BUILDING CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
ADDRESS: 4219 CAMPBELL AVE, LYNCHBURG, VA 24501
BUILDING INFORMATION:
BUILDING NAME/NUMBER: ADMINISTRATION BUILDING
WORK PERMITTED: BOILER REPLACEMENT
PURPOSE/OCCUPANCY: BUSINESS
USE GROUP CLASSIFICATION: (B)
TYPE OF CONSTRUCTION: EXISTING CONSTRUCTION TYPE IS MOST SIMILAR TO IIB PER CURRENT VUSBC
BUILDING HEIGHT (FEET): 33'-0"± ABOVE GRADE
NUMBER OF STORIES: THREE (FOUR ALLOWED)
GROSS AREA (GSF): 10,000 GROSS SQUARE FEET (23,000 ALLOWED)
CODE MODIFICATIONS ISSUED: N/A
APPLICABLE CODES & STANDARDS:
BUILDING CODES: 2021 VIRGINIA UNIFORM STATEWIDE BUILDING CODE - VUSBC (EFFECTIVE JANUARY 18, 2024)
VIRGINIA MECHANICAL CODE - VMC (2021)
VIRGINIA EXISTING BUILDING CODE - VEBC (2021)
VIRGINIA FUEL GAS CODE - VFGC (2021)
VIRGINIA ENERGY CONSERVATION CODE - VECC (2021)
NATIONAL ELECTRICAL CODE - NFPA-70 (2020)
OTHER STANDARDS: CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL - CPSM 2026 EDITION, REVISION 0
(JULY 31, 2026)
Lic. No. 035249
STEVEN M. HOVIS SCOTT F. BURGER
Lic. No. 034338Lic. No. 058604
JOSHUA S. KNIGHT
HIGH PERFORMANCE BUILDING STATEMENT:
IN ACCORDANCE WITH THE HIGH PERFORMANCE BUILDING ACT, THE BUILDING IS EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE
RENOVATIONS DOES NOT EXCEED 50% OF THE VALUE OF THE BUILDING.
VECC COMPLIANCE STATEMENT:
IN ACCORDANCE WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING SHALL COMPLY WITH VECC SECTIONS C402
THROUGH C405 AND C408.
09/28/2026 09/28/202609/28/2026
IFB # 161109
SCALE:
NORTH
0 6" 2'1' 3' 4' 5' 3/8"=1'-0"
DEMOLITION PLAN
3"CWS3"CWR
3"DTR3"HWR
CHILLER
3"DTS
3" H
W S
2 3
HEAT PUMP
TO REMAIN
UNDISTURBED
PANEL "BR1"
SWBD-3
PULLBOXES
MECHANICAL
EQUIPMENT
YARD
VIRGINIA DEPARTMENT OF TRANSPORTATION
LYNCHBURG DISTRICT ADMINISTRATION BUILDING
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
GENERAL NOTES:
1. REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR ADDITIONAL
DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING: ANY EXISTING CONSTRUCTION THAT IS TO BE
REMOVED SHALL BE REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY
EXISTING CONSTRUCTION THAT IS TO REMAIN. FLOORS, WALLS, AND CEILINGS
ARE TO BE PATCHED (IN A RECTANGULAR PATTERN) TO MATCH EXISTING
CONDITIONS AND MADE READY TO RECEIVE ANY NEW FINISHES WHERE
APPLICABLE.
DEMOLITION SYMBOLS LEGEND:
DEMOLITION NOTE
LIMIT OF DEMOLITION
DEMOLITION PLAN
D1
X
DEMOLITION NOTES:XX
1. REMOVE SPLIT SYSTEM CHILLER AND ASSOCIATED REFRIGERANT PIPING.
INDOOR AND OUTDOOR EQUIPMENT PADS TO REMAIN.
2. REMOVE CHILLED WATER SUPPLY AND RETURN PIPING TO POINTS INDICATED.
3. SALVAGE CHILLED WATER PUMP. CLEAN AND TURN OVER TO OWNER.
4. REMOVE COMPRESSION TANK.
5. REMOVE MAKEUP WATER LINE TO POINT INDICATED.
6. REMOVE SCREEN WALL AND ASSOCIATED FOUNDATION, IF ANY. REMOVE BRICK
COURSE AT GRADE IN WALL OPENING AND ASSOCIATED FOUNDATION, IF ANY.
7. REMOVE WIRING FROM EXTERIOR CONDENSING UNIT BACK TO SWBD-3 AND
MARK BREAKER AS SPARE. CUT CONDUIT FLUSH WITH CONCRETE PAD AND FILL
WITH GROUT.
8. REMOVE WIRING FROM INTERIOR CHILLER BACK TO SWBD-3 AT CONDUIT. CUT
CONDUIT FLUSH WITH CONCRETE PAD AND FILL WITH GROUT.
9. TRACE RECEPTACLE CIRCUIT. IF RECEPTACLE IS THE ONLY LOAD ON THIS
BREAKER, REMOVE WIRING BACK TO BREAKER AND MARK AS SPARE. ELSE,
REMOVE WIRING BACK TO NEXT UPSTREAM LOAD. REMOVE RECEPTACLE, CUT
CONDUIT FLUSH TO CONCRETE, AND FILL OPENING WITH GROUT.
MATERIAL TO BE DEMOLISHED
Lic. No. 035249
STEVEN M. HOVIS
SCALE:
NORTH
NONE
KEYPLAN
WORK AREA
ADMINISTRATION BUILDING
09/28/2026
0 6" 2'1' 3' 4' 5' 3/8"=1'-0"
STRUCTURAL PLAN
20'-5"±
14'-9 1/2"±5'-0"±7 1/2"
'-1
1/
2"
3' -1
1"
2' -0
1/
2"
EQ
EQ
S1 S1
S1 S1
3' -7
/4
(E)HEAT PUMP
SEE MECHANICAL
(E)SLAB ON GRADE
(E)BRICK WALL
2'-0"
EQ EQ
T/(E) WALL =
(+5'-8") ±
T/WALL =
(+5'-8") ±
1/2" EXPANSION
JOINT BETWEEN
BRICK WALL &
(E)BUILDING
T/WALL = (+5'-8") ±
MECHANICAL EQUIPMENT YARDCH-1 SEE
MECHANICAL
(BOD = 4,000 #,
DIMENSIONS
= 43"x88")
SEE PLAN
3" CLR
FIN GRADE
T/CONC
T/FOOTING
1' -0
1'
-0
3" C
LR
T/WALL
SEE PLAN
SEE PLAN
4"
BRICK WALL
1/2" ISOLATION
JOINT
6" CONCRETE SLAB
DOWEL INTO
(E)PAD W/#4@18"
(3) #4 CONT
#4@12"
SCALE:
3"0 6" 1' 2'
1"=1'-0"
SECTION1
S1 S1
6" COMPACTED
21A STONE
#4@18" OC
ON GRADE
SOLID BRICK HEADER
COURSE TO MATCH
EXISTING
HORIZONTAL LADDER
TIES @ TOP JOINT
& @ 16" OC VERTICALLY,
MAXIMUM
HILTI HIT-HY200
W/4" EMBED
#3@24" OC & AT ENDS
6" M
IN
6"
6"2'-0"(E)FOOTING
CLEAN & ROUGHEN
(E)FOOTING
THICKNESS TO MATCH
NEW WALL FOOTING,
ADJUST ELEVATION &
(E)FOOTING
EQ
EQ
T/FOOTING
FIELD VERIFY
SCALE:
0 3'1'6" 2'
3/4"=1'-0"
NEW TO EXISTING FOOTING DETAIL
(3) #4 DOWELS
DRILL & GROUT
INTO (E)FOOTING
W/HILTI HIT-HY200
VIRGINIA DEPARTMENT OF TRANSPORTATION
LYNCHBURG DISTRICT ADMINISTRATION BUILDING
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
GENERAL NOTES:
1. NEW BRICK AND MORTAR TO MATCH EXISTING IN SIZE, STYLE, AND APPEARANCE.
CONSTRUCTION NOTES:
1. SEE NEW TO EXISTING FOOTING DETAIL THIS DRAWING.
2. TOOTH IN NEW BRICK TO EXISTING BRICK.
3. MATCH BRICK PATTERN OF BRICK WALLS TO REMAIN. REFER TO BRICK PATTERN
PICTURE THIS DRAWING.
XX
STRUCTURAL PLAN
S1Lic. No. 058604
JOSHUA S. KNIGHT
GENERAL STRUCTURAL NOTES:
GENERAL:
1. GOVERNING BUILDING CODE:
2021 VIRGINIA UNIFORM STATEWIDE BUILDING CODE
2. LIVE LOADS:
SLAB ON GRADE LIVE LOAD, UNIFORM: 250 PSF
3. WIND LOAD CRITERIA:
ULTIMATE DESIGN WIND SPEED (3-SEC GUST): 109 MPH
NOMINAL DESIGN WIND SPEED: 85 MPH
BUILDING RISK CATEGORY: II
WIND EXPOSURE CONDITION: B
INTERNAL PRESSURE COEFFICIENT (GCPI): 0.00 +/-
4. CONTRACT DRAWINGS SHALL NOT BE MARKED AND SUBMITTED AS SHOP DRAWINGS.
5. THE CONTRACTOR SHALL VERIFY ALL EXISTING FIELD CONDITIONS, DIMENSIONS, AND ELEVATIONS
BEFORE PROCEEDING WITH CONSTRUCTION.
6. THE CONTRACTOR SHALL LOCATE ALL EXISTING UNDERGROUND UTILITIES AND PROTECT FROM
DAMAGE DURING EXCAVATION AND BACKFILLING OPERATIONS.
7. SUBMIT SHOP DRAWINGS, PRODUCT DATA, AND MATERIAL CERTIFICATIONS FOR REVIEW FOR THE FOLLOWING ITEMS. DO NOT FABRICATE MATERIALS UNTIL SUBMITTALS HAVE BEEN REVIEWED AND ALL
EXCEPTIONS HAVE BEEN RESOLVED.
A. CONCRETE MIX DESIGNS, TESTS, AND CERTIFICATES PER ACI 301
B. REBAR AND WWF PRODUCT DATA
C. ISOLATION JOINT MATERIAL
D. JOINT FILLER
E. MASONRY UNIT TESTS, CERTIFICATES, AND PRODUCT DATA
F. MASONRY UNIT COLOR CHARTS AND PHYSICAL SAMPLES
G. MASONRY MORTAR MIX DESIGNS, TESTS, AND CERTIFICATES
H. MASONRY MORTAR COLOR CHARTS AND PHYSICAL SAMPLES
FOUNDATIONS:
1. DESIGN SOIL BEARING CAPACITY: 2,000 PSF ASSUMED, TO BE VERIFIED A TESTING AND INSPECTION
FIRM.
2. WHERE FOOTING OR SLAB ON GRADE IS TO BE PLACED ON FILL, ALL TOPSOIL, ROOTS, TRASH, AND OTHER EXTRANEOUS MATERIALS SHALL BE REMOVED AND REPLACED WITH SELECT FILL COMPACTED TO A MINIMUM OF 98% OF ITS MAXIMUM DENSITY AT ITS OPTIMUM MOISTURE CONTENT AS MEASURED BY THE STANDARD PROCTOR METHOD (ASTM D698). THE TOP 12" SHALL BE COMPACTED TO A MINIMUM DENSITY OF 98%. EACH LAYER OF FILL SHALL BE NO GREATER THAN 6" THICK AND SHALL BE
COMPACTED AS SPECIFIED PRIOR TO PLACEMENT OF THE FOLLOWING LAYER.
3. OWNER SHALL ENGAGE A TESTING AND INSPECTION FIRM WITH A QUALIFIED GEOTECHNICAL ENGINEER LICENSED IN THE COMMONWEALTH OF VIRGINIA TO INSPECT AND APPROVE THE SUBGRADE INCLUDING FILL AND BACKFILL MATERIALS AND OPERATIONS. ALL FOUNDATION BEARING STRATA SHALL BE INSPECTED AND APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO ANY CONCRETE PLACEMENT. IF UNSUITABLE SOILS ARE ENCOUNTERED, THE GEOTECHNICAL ENGINEER AND THE
STRUCTURAL ENGINEER OF RECORD SHALL DETERMINE THE MEANS OF CORRECTIVE ACTION
INCLUDING, BUT NOT LIMITED TO, ITEMS NOTED BELOW:
A. FOOTING BEARING ELEVATIONS MAY BE LOWERED WHERE REQUIRED TO OBTAIN THE DESIGN SOIL
BEARING CAPACITY SPECIFIED ABOVE.
B. FOOTINGS MAY BE UNDERCUT AND BACKFILLED WITH COMPACTED STONE OR INCREASED IN
THICKNESS AS REQUIRED TO OBTAIN THE DESIGN SOIL BEARING CAPACITY NOTED ABOVE.
4. FOOTING EXCAVATIONS SHALL NOT BE LEFT OPEN OVER NIGHT WHEN RAIN IS FORECAST. OPEN EXCAVATIONS LEFT EXPOSED TO RAIN, SNOW, OR ICE SHALL HAVE A LAYER OF 3" LEAN CONCRETE
PLACED AHEAD OF WEATHER CONDITIONS FOR PROTECTION.
5. TO MINIMIZE WEATHERING, THE LAST 6 INCHES OF EXCAVATION FOR ALL FOOTINGS SHALL BE MADE
IMMEDIATELY PRIOR TO PLACEMENT OF FOOTINGS.
6. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE WELL-BRACED SHORING AT
EXCAVATIONS NEAR EXISTING BUILDINGS AND CONSTRUCTION TO PREVENT SETTLEMENT OR
CAVE-INS.
7. WALLS ACTING AS RETAINING WALLS SHALL NOT BE BACKFILLED WITHOUT BRACING UNTIL ALL
FOUNDATION DRAINS, SUPPORTING SOILS, AND SLABS ARE IN PLACE.
CONCRETE:
1. CONCRETE MIXTURES SHALL COMPLY WITH ACI 301. PREPARE NORMAL-WEIGHT CONCRETE (145 PCF) DESIGN MIXES UNLESS OTHERWISE NOTED, PROPORTIONED ACCORDING TO ACI 301, AS FOLLOWS:
CLASS A: FOOTINGS:
A. EXPOSURE CLASS: ACI 318 F1.
B. MINIMUM COMPRESSIVE STRENGTH: 3500 PSI AT 28 DAYS.
C. MAXIMUM WATER-CEMENTITIOUS MATERIALS RATIO: 0.55
D. SLUMP LIMIT: 4 INCHES +/- 1 INCH WITH A MAXIMUM OF 8
INCHES IF A TYPE I OR II PLASTICIZING
ADMIXTURE CONFORMING TO ASTM
C1017/C1017M OR A TYPE F OR G
HIGH-RANGE WATER-REDUCING ADMIXTURE
CONFORMING TO ASTM C494/C494M IS
PERMITTED.
E. AIR CONTENT: 4.5% (+/- 1.5%)
CLASS B: EXTERIOR:
A. EXPOSURE CLASS: ACI 318 F3.
B. MINIMUM COMPRESSIVE STRENGTH: 5000 PSI AT 28 DAYS.
C. MAXIMUM WATER-CEMENTITIOUS MATERIALS RATIO: 0.40
D. SLUMP LIMIT: 3 INCHES +/- 1 INCH WITH A MAXIMUM OF 8
INCHES IF A TYPE I OR II PLASTICIZING
ADMIXTURE CONFORMING TO ASTM
C1017/C1017M OR A TYPE F OR G
HIGH-RANGE WATER-REDUCING ADMIXTURE
CONFORMING TO ASTM C494/C494M IS
PERMITTED.
E. AIR CONTENT: 6% (+/- 1.5%)
2. READY MIXED CONCRETE PRODUCER SHALL CONFORM TO QUALIFICATIONS BY ASTM C94.
3. MEASURE, BATCH, MIX, AND DELIVER CONCRETE ACCORDING TO ASTM C94 AND ASTM C1116. WHEN AIR TEMPERATURE IS ABOVE 90 DEG F, REDUCE MIXING AND DELIVERY TIME TO 60 MINUTES.
4. ALL DETAILING, FABRICATION AND PROCEDURES OF CONCRETE PLACEMENT SHALL CONFORM WITH THE LATEST EDITIONS OF ACI 301 - "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS", ACI 315 - "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT", AND ACI 318 - "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE".
5. REINFORCING BARS SHALL BE ROLLED FROM NEW BILLET STEEL CONFORMING TO ASTM A615 AND BE
GRADE 60 DEFORMED, UNLESS OTHERWISE NOTED.
6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR ALL REINFORCEMENT, UNLESS
OTHERWISE NOTED:
A. CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH 3"
B. CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 THROUGH #18 BARS 2"
#5 BAR AND SMALLER 1 1/2"
C. CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLABS, WALLS, AND JOISTS 3/4"
BEAMS AND COLUMNS 1 1/2"
7. ISOLATION JOINT MATERIAL SHALL BE 1/2" THICK ASPHALT-SATURATED CELLULOSIC FIBER IN
ACCORDANCE WITH ASTM D1751, UNLESS OTHERWISE NOTED.
8. PROVIDE CORNER BARS AT ALL WALL AND FOOTING STEPS AND CORNERS UNLESS OTHERWISE NOTED. CORNER BARS SHALL BE A MINIMUM OF 2'-6"x2'-6" LONG AND SHALL HAVE THE SAME SIZE AND
SPACING AS THE HORIZONTAL REINFORCING.
9. LAP ALL REINFORCING SPLICES AT LEAST 48 BAR DIAMETERS UNLESS OTHERWISE NOTED. SPLICE
LOCATIONS SHALL BE STAGGERED FOR PARALLEL BARS.
10. ALL REINFORCING SHALL BE SECURELY WIRED TOGETHER IN FORMS AS CALLED FOR IN "PLACING
REINFORCING BARS" BY CRSI, LATEST EDITION.
11. NO TORCH CUTTING, HEAT BENDING, OR WELDING OF REINFORCING SHALL BE DONE, UNLESS
OTHERWISE NOTED.
12. CHAMFER EXPOSED EDGES OF CONCRETE 3/4" UNLESS OTHERWISE NOTED.
13. JOINT FILLER SHALL BE TWO COMPONENT, POLYUREA ELASTOMER, FLEXIBLE, 100 PERCENT SOLIDS FOR EXTERIOR APPLICATION. CONTRACTOR SHALL CONFIRM COMPATIBILITY OF JOINT FILLER/SEALANT
WITH FLOORING, SEALING, AND CURING MANUFACTURING.
14. SILOXANE PENETRANT CONCRETE SEALER SHALL BE A CLEAR SOLVENT BASED MATERIAL
PROTECTING FROM EFFECTS OF DE-ICING SALTS, MOISTURE, AND WEATHERING.
15. COMPLY WITH THE LATEST EDITION OF CRSI'S "MANUAL OF STANDARD PRACTICE" FOR FABRICATING, PLACING, AND SUPPORTING REINFORCEMENT.
16. SLAB FINISHES SHALL COMPLY WITH ACI 302.1R RECOMMENDATIONS FOR SCREEDING,
RESTRAIGHTENING, AND FINISHING OPERATIONS FOR CONCRETE SURFACES. APPLY FINISHES TO
FLOORS AND SLABS NOTED BELOW:
A. BROOM FINISH SHALL BE APPLIED TO EXTERIOR CONCRETE PLATFORMS, STEPS, RAMPS, AND AS
INDICATED. IMMEDIATELY AFTER FLOAT FINISHING, SLIGHTLY ROUGHEN TRAFFICKED SURFACE BY BROOMING WITH FIBER-BRISTLE BROOM PERPENDICULAR TO MAIN TRAFFIC ROUTE. COORDINATE
REQUIRED FINAL FINISH WITH OWNER BEFORE APPLICATION.
18. BEGIN CURING CONCRETE SLABS AFTER FINISHING.
BRICK MASONRY:
1. ALL DETAILING, FABRICATION, AND PROCEDURES OF BRICK/CLAY MASONRY SHALL CONFORM TO THE LATEST EDITIONS OF TMS 402-2016 - "BUILDING CODE FOR MASONRY STRUCTURES" AND TMS 602-2016
- "SPECIFICATION FOR MASONRY STRUCTURES".
2. BRICK/CLAY MASONRY UNITS SHALL CONFORM TO ASTM C216 AND C62, UNLESS OTHERWISE NOTED.
COMPRESSIVE STRENGTH ON NET CROSS SECTIONAL AREA OF INDIVIDUAL MASONRY UNIT SHALL BE
3,350 PSI. NET AREA COMPRESSIVE STRENGTH OF MASONRY (F'M) SHALL BE 1,500 PSI.
3. MASONRY SHALL BE LAID IN ASTM C270, TYPE "S" MORTAR, UNLESS NOTED, AND SHALL HAVE FULL
MORTAR COVERAGE OF THE FACE SHELLS IN BOTH HORIZONTAL AND VERTICAL JOINTS.
4. PROVIDE HORIZONTAL REINFORCING AT 16” ON VERTICAL CENTER AND IN JOINTS IMMEDIATELY ABOVE AND BELOW ALL OPENINGS. EXTEND REINFORCEMENT A MINIMUM OF 2'-0" BEYOND THE JAMB ON EACH SIDE OF AN OPENING. HORIZONTAL JOINT REINFORCING SHALL BE LAPPED A MINIMUM OF 8". JOINT REINFORCING SHALL STOP AT CONTROL JOINTS. HORIZONTAL REINFORCING SHALL BE GALVANIZED LADDER TYPE JOINT REINFORCEMENT WITH (2) 9 GAGE (W1.7) RODS AND 9 GAGE CROSS RODS, HOT-DIPPED GALVANIZED AFTER FABRICATION PER ASTM A153 - CLASS B-2.
5. MORTAR JOINTS SHALL BE 3/8" THICK WITH FULL MORTAR COVERAGE ON VERTICAL AND HORIZONTAL
FACE SHELLS.
6. BRICK/CLAY MASONRY SHALL MATCH EXISTING BRICK IN SHAPE, SIZE AND APPEARANCE. MORTAR
SHALL MATCH EXISTING MORTAR IN COLOR AND APPEARANCE.
SCALE:
NORTH
NONE
KEYPLAN
WORK AREA
ADMINISTRATION BUILDING
SCALE: NONE
BRICK PATTERN PICTURE
BRICK PATTERN TO MATCH
(E)PATTERN CENTERED
ON NEW HIGH / LONGER WALL
VIRGINIA DEPARTMENT OF TRANSPORTATION
LYNCHBURG DISTRICT ADMINISTRATION BUILDING
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
LEGEND AND SPECIFICATIONS
M1Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTE A AMPERE
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CA COMPRESSED AIR
CF CHEMICAL FEED, CUBIC FEET
CFM CUBIC FEET PER MINUTE
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
D DRAIN
DIA, Ø DIAMETER
DB DRY BULB
DBA DECIBELS, A WEIGHTED
DEG, ° DEGREE
DTR DUAL TEMPERATURE WATER RETURN
DTS DUAL TEMPERATURE WATER SUPPLY
DX DIRECT EXPANSION
DWG DRAWING
(E) EXISTING
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
EL, ELEV ELEVATION
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
°F DEGREES FAHRENHEIT
FD FIRE DAMPER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FT FOOT, FEET
G GAS
GA GAGE
GAL GALLONS
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H HEIGHT
HD HEAD
HP HORSEPOWER
HR HOUR(S)
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HZ FREQUENCY
ID INSIDE DIAMETER
IN INCHES
INWG INCHES WATER GAUGE
KW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LB POUND(S)
LF LINEAR FEET
LPG LIQUEFIED PETROLEUM GAS (PROPANE)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NC NORMALLY CLOSED
NG NATURAL GAS
NO NORMALLY OPEN, NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
% PERCENT
PD PRESSURE DROP OR DIFFERENTIAL
PH PHASE
PRV PRESSURE REDUCING OR REGULATING
VALVE
PSIG POUNDS PER SQUARE INCH GAGE
PSV PRESSURE SAFETY VALVE
R12, R22 REFRIGERANT (12, 22, ETC.)
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SQUARE FOOT, FEET
SHR SENSIBLE HEAT RATIO
SP STATIC PRESSURE
SPEC SPECIFICATION
SQ SQUARE
TD TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
TOD TOP OF DUCT
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
T'STAT THERMOSTAT
TYP TYPICAL
V VOLTS
VAV VARIABLE AIR VOLUME
VTR VENT THRU ROOF
W WATT, WIDTH
WB WET BULB
MANUAL VOLUME DAMPER
FLEXIBLE DUCTWORK
TRANSITION IN DUCT SIZE
45° BRANCH CONNECTION
FIRE DAMPER IN WALL
FIRE DAMPER IN FLOOR,
CEILING OR ROOF
CONNECT TO EXISTING
INDICATES NUMBER OF
REVISIONS, CORRESPONDS
AIRFLOW
M
M
PIPE CAP
PUMP
THERMOMETER
PRESSURE GAUGE
UNION
PIPE TURNING DOWN
WYE STRAINER
PIPE TURNING UP
TEE DOWN
MOTOR OPERATED DAMPER
REVISION CLOUD
REVISION TRIANGLE
SYMBOLS
LEGEND
ABBREVIATIONS
TAG NO
CFM
DIFFUSER/GRILL TAG
HVAC SPECIFICATIONS
CONCENTRIC REDUCER
PIPE FLANGE
GLOBE VALVE
CHECK VALVE
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
ECCENTRIC REDUCER
MOTORIZED 2-WAY VALVE
PNEUMATIC 2-WAY VALVE
SOLENOID VALVE
MOTORIZED 3-WAY VALVE
PNEUMATIC 3-WAY VALVE
CALIBRATED BALANCING VALVE
BACKFLOW PREVENTER
AIR VENT (AUTO)
PLUG VALVE
SAFETY RELIEF VALVE
PRESSURE REDUCING VALVE
TEMPERATURE SENSOR
FLOW SWITCH
AIR VENT (MANUAL)
EQUIPMENT TAG
PIPE FLOW ARROW
WITH REVISION NOTE
ACCESS DOOR
M
M
S
F
T
A
M
SUPPLY/OA DUCT SECTION OR
DIFFUSER/GRILLE
RETURN/EXHAUST DUCT SECTION
OR DIFFUSER/GRILLE
TRANSITION FROM RECTANGULAR
TO ROUND
45° BRANCH TO ROUND
TAKEOFF CONNECTION
FLEXIBLE CONNECTOR
90° ELBOW UP
90° ELBOW DOWN
45° CONICAL TAP
90° CONICAL TAP
WALL MOUNTED HUMIDISTAT OR
DUCT SMOKE DETECTOR
CONICAL SPIN-IN WITH DAMPER
WALL MOUNTED THERMOSTAT
HUMIDITY SENSOR
OR TEMPERATURE SENSOR
H
T
90° ELBOW WITH TURNING VANES
(RECTANGULAR DUCT)
90° RADIUS ELBOW
(RECTANGULAR DUCT)
45° RADIUS ELBOW
(RECTANGULAR DUCT)
TEE WITH TURNING VANES
(RECTANGULAR DUCT)
RADIUS TEE
(RECTANGULAR DUCT)
Y FITTING
(ROUND DUCT)
AHU-1
X-1
WALL MOUNTED SWITCH
1. DRAWINGS DO NOT INDICATE PIPING SUPPORT LOCATIONS AND DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY PIPE SUPPORTS. SELECTIONS OF PIPE SUPPORT TYPES, SIZES, AND LOCATIONS SHALL CONFORM TO MSS SP-58. SUPPORT SPACING SHALL COMPLY WITH MSS SP-58, INDIVIDUAL SPECIFICATION SECTIONS, OR
TABLE BELOW, WHICHEVER IS MORE STRINGENT.
PIPE SUPPORT (HORIZONTAL HANGER SPACING - VERTICAL SUPPORT SPACING)
STEEL 1" AND SMALLER 6 FT 10 FT
STEEL 1 1/4" - 2" 10 FT 10 FT
STEEL 2 1/2" AND LARGER 12 FT 15 FT
2. THERMOSTATS, HUMIDISTATS, AND SWITCHES SHALL BE MOUNTED WITH TOP LOCATED 48" ABOVE FINISHED FLOOR.
3. PROVIDE FLEXIBLE CONNECTIONS BETWEEN EQUIPMENT AND CONNECTING PIPING.
4. INTERIOR PIPING SHALL BE INSTALLED AS HIGH AS POSSIBLE AND ALL HYDRONIC PIPING SLOPED 1/8" PER FOOT BACK TOWARDS LOW POINT DRAINS. ALL PIPING SHALL BE CLEAN AND FREE OF DIRT AND SCALE AT TIME OF INSTALLATION.
5. PROVIDE AIR VENTS AT HIGH POINTS AND DRAINS AT LOW POINTS IN HYDRONIC PIPING SYSTEMS.
6. PIPING SHALL BE SLEEVED THROUGH WALL AND FLOOR PENETRATIONS WITH PVC SLEEVES.
7. INSTALLATION OF FIELD MOUNTED CONTROL COMPONENTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. CLASS 2 CONTROL CIRCUITS THAT ARE CONCEALED WITHIN INTERIOR PARTITIONS AND ABOVE CEILINGS MAY UTILIZE OPEN
WIRING METHODS WITH PLENUM-RATED POWER LIMITED CABLE.
8. AN ASSOCIATED AIR BALANCE COUNCIL OR NATIONAL ENVIRONMENTAL BALANCING BUREAU CERTIFIED TESTING AND BALANCING CONTRACTOR SHALL BALANCE WATER FLOWS AND SUBMIT REPORTS TO THE ENGINEER AND OWNER FOR APPROVAL. CONTRACTOR SHALL MEASURE FLOW OF EXISTING SYSTEM IN COOLING MODE PRIOR TO DEMOLITION AND
SHALL REPORT RESULTS TO ENGINEER.
9. MAKEUP WATER PIPING SHALL BE TYPE "L" HARD COPPER, ASTM B 88 WITH WROUGHT FITTINGS AND NO LEAD SOLDER
JOINTS.
10. MAKEUP WATER PIPE SHALL BE INSULATED WITH 1/2-INCH-THICK ASTM C 534, TYPE I, CLOSED-CELL FLEXIBLE ELASTOMERIC RUBBER, USING MIL-A-24179A, TYPE II, CLASS I ADHESIVE. ADHESIVE SHALL HAVE VOC CONTENT < 50g/L AND SHALL BE APPLIED PER MANUFACTURER'S INSTRUCTIONS TO MAINTAIN VAPOR BARRIER INTEGRITY ACROSS JOINTS AND
SEAMS. SELF-ADHESIVE STRIPS ARE NOT PERMITTED.
0 6" 2'1' 3' 4' 5' 3/8"=1'-0"
MECHANICAL PLAN
(E)3"CWS
(E)3"CWR
(E)3"DTS
CH-1
(E)HEAT PUMP
(E)PAD
SCALE: NONE
CHILLER SCHEMATIC
2 1/2"CWR
2 1/2"CWS
1" DRAIN VALVE
A CH-1
36" MIN
60" MIN
(E)PAD
NEW PAD
2 1/2"CWS
2 1/2"CWR
2 1/2"CWR
2 1/2"CWS
(E)3"HWR (E)3"DTR
(E )3
"H W
S
(E)BFP (E)PRV
MECHANICAL EQUIPMENT YARD
3/4"MUW
3"CWR
BALL VALVE
IN VERT (NO)
NO NC
MECHANICAL
EQUIPMENT
YARD
VIRGINIA DEPARTMENT OF TRANSPORTATION
LYNCHBURG DISTRICT ADMINISTRATION BUILDING
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
GENERAL NOTES:
1. FREEZE PROTECTION STRATEGY: CHILLER INTERNALS AND HYDRONIC PACKAGE
COMPONENTS ARE FACTORY HEAT TRACED. PROVIDE ADDITIONAL LAYER OF
HEAT TRACE ON CHILLER INTERNALS AND HYDRONIC PACKAGE COMPONENTS
AND CONNECT TO HEAT TRACE CONTROLLER. PROVIDE DOUBLE-WRAP HEAT
TRACE ON ALL OUTDOOR HYDRONIC PIPING. CONNECT PRIMARY HEAT TRACE
STRAND TO HEAT TRACE CONTROLLER. TERMINATE BACKUP STRAND NEAR HEAT
TRACE CONTROLLER FOR OWNER TO SWAP IN EVENT OF PRIMARY STRAND
FAILURE. HEAT TRACE CONTROLLERS SHALL BE EQUIPPED WITH ALARMS.
CHILLER SHALL BE PLACED ON GENERATOR PANEL. PROVIDE WARNING SIGN ON
DISCONNECT SWITCH INDICATING THAT SWITCH IS NOT TO BE CLOSED DURING
THE HEATING SEASON.
CONSTRUCTION NOTES:
1. INSTALL OWNER-FURNISHED CHILLER PER MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS.
2. EXTEND CONCRETE PAD AND PROVIDE SCREEN WALLS. REFER TO STRUCTURAL.
3. PROVIDE 2-1/2" CHILLED WATER SUPPLY AND RETURN PIPING. TRANSITION TO 3"
AT POINTS INDICATED. ROUTE LINES BETWEEN OUTDOORS AND MECHANICAL
ROOM OVER CEILING OF OPEN OFFICE AREA. CAREFULLY REMOVE AND REPLACE
PLASTIC CEILING TILES. CAREFULLY REMOVE AND REPLACE CEILING GRID AS
NECESSARY.
4. PROVIDE 3/4" MAKEUP WATER LINE FROM POINT INDICATED TO INLET SIDE OF AIR
SEPARATOR.
5. PROVIDE 3" TANGENTIAL AIR SEPARATOR WITH AUTOMATIC AIR SEPARATOR BY
BELL & GOSSETT, ARMSTRONG, OR TACO. SUSPEND FROM STRUCTURE ABOVE.
6. PROVIDE 3" MAGNETIC DIRT SEPARATOR IN EXISTING DUAL TEMPERATURE
RETURN LINE BY DIRTMAG, TACO, OR CALEFFI.
7. REMOVE MANUAL VALVE ACTUATORS FROM SEASONAL CHANGEOVER VALVES.
PROVIDE MANUFACTURER'S MOTORIZED ACTUATORS. EXISTING VALVE ARE
VALVETECK BF303R. SUBMITTAL IS AVAILABLE UPON REQUEST. PROVIDE 120V
SPRING RETURN ACTUATOR. PROVIDE TWO-WAY CONTROL SWITCH ON WALL TO
CHANGE BETWEEN HEATING AND COOLING MODES.
8. PROVIDE SINGLE CIRCUIT HEAT TRACE CONTROLLER FOR CHILLER. PROVIDE
DUAL CIRCUIT HEAT TRACE CONTROLLER FOR HYDRONIC PIPING. CONTROLLERS
SHALL BE NEMA 4X FIBERGLASS OR 316 STAINLESS WITH HINGED DOOR AND HIGH
RESOLUTION COLOR TOUCHSCREEN INDICATING LOAD, POWER, AND ALARM
STATUS FOR EACH CIRCUIT.
9. PROVIDE 2-1/2" INLINE AIR SEPARATOR BY BELL & GOSSETT, TACO, OR WATTS AT
OUTLET OF CHILLER. PROVIDE AUTOMATIC AIR VENT AT TOP PORT AND CAP
BOTTOM PORT.
10. PROVIDE PIPE BRIDGE WITH BALL VALVE. KEEP VALVES TO CHILLER CLOSED
UNTIL MAGNETIC DIRT SEPARATOR IS INSTALLED AND PIPE SYSTEM HAS BEEN
THOROUGHLY FLUSHED BY PUTTING SYSTEM IN HEATING MODE AND RUNNING
HEATING WATER PUMP.
11. PROVIDE 2-1/2" CONNECTIONS FOR TEMPORARY CHILLER CONNECTION. PROVIDE
2-1/2" FLANGED BALL VALVES WITH BLIND FLANGES.
XX
MECHANICAL PLAN
M2
PACKAGED CHILLER SCHEDULE - OWNER FURNISHED FOR CONTRACTOR INSTALLATION
TAG TYPE
NOMINAL
CAPACITY
TONS
ACTUAL
CAPACITY
TONS IPLV EER
FLUID REFRIGERANT ELECTRICAL OPERATING
WEIGHT
LBS
SOUND
POWER
dBA
SOUND
PRESSURE
dBA MANUFACTURER AND MODELTYPE
RATE
GPM
DP
FT
EWT
DEG F
LWT
DEG F TYPE COMPRESSORS STAGES
MIN
CAPACITY V / PH MCA MOCP
CH-1 PACKAGED AIR COOLED 20 19.7 17.0 10.4 WATER 47 10.7 54 44 R-32 (2) DIGITAL SCROLL 22 17% 208 / 3 98.5 125 4000 78.5 51.0 CARRIER 30RC-0205610B-213
1. PROVIDE GALVANIZED STEEL CONSTRUCTION WITH BAKED ENAMEL FINISH CAPABLE OF WITHSTANDING 1000-HOUR SALT SPRAY TEST.
2. PROVIDE DUAL 3 HP STANDARD HEAD PUMP PACKAGE WITH VFD-COMPATIBLE MOTORS, EXPANSION TANK, STORAGE TANK, ISOLATION VALVES, CHECK VALVES, BALANCING VALVES, GAUGE TAPS, HEATERS, AND FREEZE PROTECTION TO -20 DEG F.
3. PROVIDE FACTORY INSTALLED FLOW SWITCH AND STRAINER.
4. PROVIDE INTEGRAL CHILLED WATER SUPPLY AND RETURN TEMPERATURE SENSORS.
5. PROVIDE INTEGRAL UNIT MOUNTED MICROPROCESSOR CONTROLS WITH BACNET IP / MSTP.
6. PROVIDE PHASE MONITOR.
7. PROVIDE VARIABLE SPEED LOW-SOUND CONDENSER FANS.
8. PROVIDE COMPRESSOR SOUND BLANKETS.
9. PROVIDE BRAZED PLATE HEAT EXCHANGER AND MICROCHANNEL HEAT EXCHANGER COILS.
10. PROVIDE FILTER DRIER, MOISTURE INDICATING SIGHT GLASS, AND ELECTRONIC EXPANSION DEVICE.
11. PROVIDE PROTECTION AGAINST LOSS OF REFRIGERANT CHARGE, LOSS OF WATER FLOW, REVERSE ROTATION, LOW CHILLED FLUID TEMPERATURE, THERMAL OVERLOAD, HIGH PRESSURE, ELECTRICAL OVERLOAD.
12. PROVIDE SUCTION LINE INSULATION AND SUCTION SERVICE VALVE.
13. PROVIDE VIBRATION ISOLATION KIT.
14. PROVIDE HAIL GUARDS.
15. PROVIDE EVAPORATOR HEATER.
16. PROVIDE 2" VICTAULIC CONNECTIONS.
17. PROVIDE 5-YEAR PARTS WARRANTY.
18. PROVIDE SINGLE POINT POWER CONNECTION WITH FACTORY COMMISSIONED UNIT MOUNTED STARTER AND FACTORY MOUNTED AND WIRED NON-FUSED DISCONNECT SWITCH.
Lic. No. 035249
STEVEN M. HOVIS
SCALE:
NORTH
NONE
KEYPLAN
WORK AREA
ADMINISTRATION BUILDING
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
LEGEND, ABBREVIATIONS,
GENERAL NOTES,
AND SPECIFICATIONS E1
CONSTRUCTION NOTE
DEMOLITION NOTE
SYMBOLS
MDP-1
MDP-1
INDICATES MULTIPLE HOMERUN CIRCUITS FROM SINGLE
PANEL/CIRCUIT.
HOMERUN TO PANEL AND CIRCUIT NUMBER AS INDICATED.
CONDUCTOR AND RACEWAY SIZE AS INDICATED IN
PANELBOARD SCHEDULE, UON.
HOMERUN CIRCUIT TO OTHER CIRCUIT. CONDUCTORS AND
RACEWAY SIZE AS NOTED.
CONDUCTORS AND RACEWAYS
CONDUIT RUN EXPOSED OR ABOVE CEILING
EQUIPMENT CONNECTION
POWER
(3)#12
IN 3/4"C
CONDUIT RUN CONCEALED UNDER FLOOR
JUNCTION BOX
CONDUIT TURNING DOWN
CONDUIT TURNING UP
CIRCUIT BREAKER400AF
300AT
AUTOMATIC TRANSFER SWITCH
PANELBOARD PANELBOARD NUMBER
VOLTAGE
POLES, WIRES
AMP RATING
POINT OF CONNECTION
NEW-TO-EXISTING
LIMIT OF DEMOLITION
A AMPERE
AC ABOVE COUNTER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AFF ABOVE FINISHED FLOOR
APPROX APPROXIMATE
BCSD BARE COPPER SOFT DRAWN
C CONDUIT
CB CIRCUIT BREAKER
DWG DRAWING
(E) EXISTING
ECB ENCLOSED CIRCUIT BREAKER
EGC EQUIPMENT GROUNDING CONDUCTOR
EMT ELECTRICAL METALLIC TUBING
FD FUSED DISCONNECT
FMC FLEXIBLE METALLIC CONDUIT
FTL FEED THROUGH LUGS
FVNR FULL VOLTAGE NON REVERSING
G, GND GROUND
GEC GROUNDING ELECTRODE CONDUCTOR
GFI GROUND FAULT INTERRUPTING
HOA HAND-OFF-AUTO
HP HORSEPOWER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
JB JUNCTION BOX
KVA KILOVOLTAMPS
LFMC LIQUID-TIGHT FLEXIBLE METAL CONDUIT
MAX MAXIMUM
MC METAL CLAD CABLE
MCA MIN CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT BREAKER
MIN MINIMUM
MLO MAIN LUGS ONLY
MOPD MAX OVERCURRENT PROTECTION DEVICE
N NEUTRAL
NF NON FUSED
NIC NOT IN CONTRACT
OCPD OVERCURRENT PROTECTION DEVICE
P PHASES OR POLES
PB PUSHBUTTON
RNC RIGID NONMETALLIC CONDUIT
RSC RIGID STEEL CONDUIT
SE SERVICE ENTRANCE
SPD SURGE PROTECTION DEVICE
STP SHIELDED TWISTED PAIR
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UTP UNSHIELDED TWISTED PAIR
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WIRES
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WR WEATHER RESISTANT
XFMR TRANSFORMER
AMP TRIP
LEGEND
AMP FRAME
EN
LP3
120/208 3P/4W 225A
MCB
STANDARD MOUNTING HEIGHTS
DEVICE MOUNTING HEIGHT (AFF) TO:
PANELBOARD 6'-6" TOP
DISCONNECT SWITCH 6'-6" MAX TOP
RECEPTACLE 1'-6" CENTER
1. ALL MOUNTING HEIGHTS SHALL BE AS LISTED ABOVE UNLESS
OTHERWISE INDICATED ON DRAWINGS.
2. ALL MOUNTING HEIGHTS SHALL BE IN ACCORDANCE WITH THE
AMERICANS WITH DISABILITIES ACT.
PANELBOARD, HATCHED AREA IS
DESIGNATED WORKING SPACE,
PAINTED PER SPECIFICATIONS AND
CPSM MANUAL
GFI DUPLEX RECEPTACLE
WR,WP WP = WEATHERPROOF-WHILE-IN-USE COVER
WR = WEATHER RESISTANT OUTLET
ENCLOSED CIRCUIT BREAKER
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND
INDICATE THE GENERAL AND APPROXIMATE LOCATION OF
EQUIPMENT AND EXISTING CONSTRUCTION. FIELD-VERIFY
ALL DIMENSIONS AND LOCATIONS. INDICATED
UNDERGROUND OBSTRUCTIONS WERE DEVELOPED FROM
EXISTING RECORDS AND ABOVE-GROUND INSPECTION.
ACCURACY OR COMPLETENESS OF LOCATION AND DEPTH
OF UNDERGROUND UTILITIES AND STRUCTURES CANNOT
BE GUARANTEED. VERIFY LOCATION AND DEPTH OF ALL
UNDERGROUND FACILITIES BEFORE STARTING WORK.
2. THESE DRAWINGS MAY NOT INDICATE ALL FITTINGS, PARTS
AND ACCESSORIES THAT ARE REQUIRED FOR A COMPLETE
AND FUNCTIONAL SYSTEM. NO EXCLUSION FROM OR
LIMITATION IN THE SYMBOLISM USED ON THE DRAWINGS
FOR THE WORK, OR THE LANGUAGE USED IN THE
SPECIFICATIONS FOR THE WORK SHALL BE INTERPRETED
AS A REASON FOR OMITTING THE APPURTENANCES OR
ACCESSORIES NECESSARY TO COMPLETE AND REQUIRED
WORK, SYSTEM, OR ITEM OF EQUIPMENT.
3. ALL ELECTRICAL WORK ON THIS PROJECT SHALL BE
INSTALLED IN ACCORDANCE WITH THE 2021 VIRGINIA
UNIFORM STATEWIDE BUILDING CODE, NFPA 70-2020
(NATIONAL ELECTRICAL CODE), CONSTRUCTION AND
PROFESSIONAL SERVICES MANUAL: 2025 CPSM EDITION,
REVISION 0 (MARCH 17, 2025), CHAPTER 2 OF 2010 ADA
STANDARDS FOR ACCESSIBLE DESIGN DATED SEPTEMBER
15, 2010, AND CHAPTERS 1 AND 3 THROUGH 11 OF
STANDARDS FOR ACCESSIBLE AND USABLE BUILDINGS AND
FACILITIES (ICC A117.1-2017) APPROVED MARCH 28, 2017.
4. MATERIALS, EQUIPMENT, AND SYSTEMS SHALL MEET ALL
PERTINENT REQUIREMENTS OF THE AMERICAN SOCIETY
FOR TESTING MATERIALS (ASTM), THE UNDERWRITERS
LABORATORY (UL), THE NATIONAL ELECTRIC
MANUFACTURER'S ASSOCIATION (NEMA), NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA), AMERICAN NATIONAL
STANDARDS INSTITUTE (ANSI), AND OTHER NATIONALLY
RECOGNIZED AGENCIES.
5. COORDINATE ARRANGEMENT, MOUNTING, AND SUPPORT
OF ELECTRICAL EQUIPMENT TO AVOID INTERFERENCES
WITH ELECTRICAL AND OTHER TRADES. COORDINATE
WORK WITH EXISTING CONDITIONS INCLUDING BEAMS,
COLUMNS, SITE FEATURES, AND OTHER CONSTRUCTION
WHETHER OR NOT SUCH IS SHOWN ON THE DRAWINGS.
SET SLEEVES IN CAST-IN-PLACE CONCRETE AND MASONRY
WALLS, AS THEY ARE CONSTRUCTED. COORDINATE
LOCATION OF ACCESS PANELS AND DOORS FOR
ELECTRICAL EQUIPMENT THAT ARE BEHIND FINISHED
SURFACES OR ARE OTHERWISE CONCEALED. COORDINATE
AMPACITY, VOLTAGE, PHASING, OVERCURRENT
PROTECTION, AND LOCAL DISCONNECT REQUIREMENTS
WITH ACTUAL EQUIPMENT PROVIDED.
6. MAINTAIN A SET OF AS-BUILT RED-LINE MARKUPS
INDICATING ACTUAL INSTALLATION. DELIVER TO OWNER AT
CONCLUSION OF PROJECT.
7. PROVIDE PRODUCT DATA SUBMITTALS FOR THE
FOLLOWING EQUIPMENT: PANELBOARDS, ENCLOSED
CIRCUIT BREAKERS, AND DEVICES. MATERIALS INSTALLED
PRIOR TO OBTAINING AN APPROVED SUBMITTAL ARE AT
CONTRACTOR'S RISK.
8. CUT EXISTING CONSTRUCTION AS NEEDED FOR
DEMOLITION AND CONSTRUCTION. USE CUTTING METHODS
THAT MINIMIZE DAMAGE TO FINISHED AND ADJACENT
SURFACES. PATCH EXISTING AND NEW CONSTRUCTION
AND REPAIR ALL DAMAGED SURFACES TO MATCH EXISTING.
PATCH UNUSED AND ABANDONED PENETRATIONS.
9. CONTRACTOR SHALL ADVISE A/E IMMEDIATELY OF
DISCREPANCIES WITHIN DRAWINGS. MINOR DEVIATIONS
FROM THE PLANS MAY BE MADE TO AVOID MINOR
CONFLICTS. WHERE MAJOR CONFLICTS ARE
ENCOUNTERED, THE AFFECTED WORK SHALL NOT BE
INSTALLED UNTIL THE CONFLICT HAS BEEN RESOLVED. THE
A/E IS NOT RESPONSIBLE FOR THE CONSEQUENCES OF
PROCEEDING WITH WORK BASED ON CONTRACTOR
INTERPRETATION OR ON DIRECTION FROM OTHER PARTIES.
10. CONTACT INFORMATION
VDOT SITE REPRESENTATIVE: MARK BURNLEY 434-363-0818
GROUND ROD
GROUND ROD TEST WELL
GENERAL NOTES:
ELECTRICAL SPECIFICATIONS
RACEWAYS AND BOXES
A.MATERIALS:
EMT - ANSI C80.3, COMPRESSION FITTING ONLY, MIN SIZE 3/4-INCH
RSC - ANSI C80.1, THREADED COUPLINGS ONLY, MIN SIZE 3/4-INCH
LFMC - MIN SIZE 3/4-INCH
SET SCREW FITTINGS SHALL NOT BE USED
B.INDOOR RACEWAY APPLICATIONS:
EXPOSED OR CONCEALED: EMT, UON
BOXES AND ENCLOSURES: NEMA 250, TYPE 1, UON
C.OUTDOOR RACEWAY APPLICATIONS:
ABOVEGROUND: RSC.
BOXES AND ENCLOSURES: NEMA 250 TYPE 3R, UON
D.LEAVE 1-INCH MINIMUM CONCRETE COVER FOR EMBEDDED RACEWAY. USE
MANUFACTURED RSC ELBOW TO TURN OUT OF CONCRETE.
E.USE UP TO 72 INCHES OF LFMC FOR CONNECTION TO VIBRATING EQUIPMENT
INCLUDING TRANSFORMERS AND MOTOR-DRIVEN EQUIPMENT.
F. PROVIDE 65-LB TEST PULL STRING TIED OFF AT EACH END IN ALL EMPTY
CONDUITS.
WIRING METHODS
A.SINGLE CONDUCTORS SHALL BE COPPER, #12 MINIMUM CONDUCTOR SIZE,
SOLID FOR #10 AWG AND SMALLER, STRANDED FOR #8 AWG AND LARGER. FOR
ABOVE-GROUND APPLICATIONS USE THHN-THWN, 600VAC INSULATION. FOR
CIRCUITS WHERE ANY PART OF THE CIRCUIT IS BELOW GRADE USE
CONDUCTORS WITH XHHW-2, 600 VAC RATED INSULATION.
B. INSTALL RACEWAYS AND CABLES CONCEALED WITHIN FINISHED WALLS,
CEILINGS, AND FLOORS, UON.
C.RACEWAY APPLICATIONS:
FEEDER CONDUCTORS: SINGLE CONDUCTORS IN RACEWAY, UON
BRANCH CIRCUITS: SINGLE CONDUCTORS IN RACEWAY, UON
CLASS 2 CONTROL CIRCUITS: SINGLE CONDUCTORS IN RACEWAY, UON.
D.CLASS 2 CONTROL CIRCUITS THAT ARE CONCEALED WITHIN INTERIOR
PARTITIONS AND ABOVE CEILINGS MAY UTILIZE OPEN WIRING METHODS WITH
PLENUM-RATED POWER LIMITED CABLE.
E.MINIMIZE SPLICES AND PLACE ONLY IN ACCESSIBLE JUNCTION BOXES AND
ENCLOSURES THAT ARE SIZED AND RATED FOR SUCH.
ELECTRICAL IDENTIFICATION
A.EQUIPMENT IDENTIFICATION: PROVIDE LABELS FOR PANELBOARDS,
DISCONNECT SWITCHES, AND AS ADDITIONALLY INDICATED. LABELS SHALL BE
LAMINATED ACRYLIC, WITH 1/2-INCH ENGRAVED BLACK LETTERING ON
1-1/2-INCH WHITE STOCK ATTACHED WITH SCREWS.
B.PROVIDE A 2” WIDE SAFETY YELLOW PAINTED LINE ON ALL CONCRETE FLOORS
IN FRONT OF NEW AND MODIFIED PANELBOARDS AND OTHER EQUIPMENT AS
IDENTIFIED WITHIN ELECTRICAL AND MECHANICAL ROOMS TO INDICATE THE
ELECTRICAL WORKING SPACE. THE WIDTH OF MARKED SPACE SHALL BE THE
WIDTH OF THE EQUIPMENT OR 30” WHICHEVER IS GREATER. THE DEPTH OF
THE MARKED SPACE SHALL BE 36” FOR 120 AND 208 VOLT SYSTEMS AND 48”
FOR 277 AND 480 VOLT SYSTEMS. CENTERED WITHIN THE OUTLINE OF THE
WORKING SPACE STENCIL “NO STORAGE - ELECTRICAL WORKING SPACE” IN 2”
HIGH SAFETY YELLOW LETTERS.
C.MARK EACH DISCONNECTING MEANS TO INDICATE ITS CIRCUIT SOURCE. MARK
DISCONNECTING MEANS TO INDICATE WHAT LOAD IS SERVED.
D.DEVICE CIRCUIT IDENTIFICATION: PROVIDE SELF-ADHESIVE 1/4-INCH HEIGHT
CLEAR LABELS WITH 1/8-INCH BLACK PRINTED TEXT WITH EACH RECEPTACLE
INDICATING PANELBOARD AND BRANCH CIRCUIT.
E.RACEWAY AND CABLE LABELS: PROVIDE PRE-TENSIONED, PRE-PRINTED,
WRAPAROUND PLASTIC SLEEVES THAT ARE SIZED TO SUIT THE DIAMETER OF
THE ITEM IDENTIFIED.
F. USE VINYL OR VINYL-CLOTH, SELF-ADHESIVE, WRAPAROUND TYPE TAPE
MARKERS FOR WIRE. FOLLOW THESE WIRE COLOR CODING CONVENTIONS.
CONDUCTOR 208/120V
PHASE A BLACK
PHASE B RED
PHASE C BLUE
NEUTRAL WHITE
GROUND GREEN
PENETRATIONS AND SLEEVES
A.FIRE-RATED ASSEMBLIES: APPLY FIRESTOPPING TO ELECTRICAL
PENETRATIONS OF FIRE-RATED FLOOR AND WALL ASSEMBLIES TO RESTORE
ORIGINAL FIRE-RESISTANCE RATING.
B.MASONRY WALLS AND FLOORS: IN CONCRETE SLABS AND WALLS, INSTALL
SLEEVES FOR PENETRATIONS UNLESS CORE-DRILLED HOLES OR FORMED
OPENINGS ARE USED. SELECT SLEEVE SIZE TO ALLOW FOR 1/2-INCH ANNULAR
CLEAR SPACE BETWEEN RACEWAY AND SLEEVES.
C.ABOVE-GRADE EXTERIOR WALL PENETRATIONS: SEAL PENETRATIONS USING
SLEEVES AND CAULK, UON.
SUPPORT AND ANCHORAGE
A.PROVIDE SUPPORT AND ANCHORAGE THAT ARE ADEQUATE IN TENSION,
SHEAR, AND PULLOUT FORCE TO RESIST MAXIMUM LOADS CALCULATED OR
IMPOSED WITH A MINIMUM STRUCTURAL SAFETY FACTOR OF FIVE.
B. STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA-3 FACTORY
FABRICATED COMPONENTS FOR FIELD ASSEMBLY WITH FINISH SUITABLE FOR
THE ENVIRONMENT.
C.FOR ATTACHMENT TO CONCRETE AND SOLID MASONRY, USE WEDGE-TYPE,
ZINC-COATED STEEL EXPANSION ANCHOR FASTENERS. DRILL HOLES AT
LOCATIONS AND DEPTHS THAT AVOID REINFORCING BARS. FOR CONNECTIONS
TO HOLLOW MASONRY USE ALL-STEEL SPRINGHEAD TYPE TOGGLE BOLTS.
D.FOR CLAMPING TO STEEL STRUCTURAL ELEMENTS USE WELDED STEEL STUDS,
BEAM CLAMPS OR SPRING-TENSION CLAMPS.
E.FOR CONNECTIONS TO WOOD USE LAG SCREWS OR THROUGH BOLTS.
F. HANGER RODS TO BE THREADED STEEL.
G.FOR CONNECTIONS TO LIGHT STEEL USE SHEET METAL SCREWS.
H.FOR ITEMS MOUNTED ON HOLLOW WALLS AND NONSTRUCTURAL BUILDING
SURFACES USE SLOTTED-CHANNEL RACKS ATTACHED TO SUBSTRATE.
I. FASTEN HANGERS AND SUPPORTS SECURELY IN PLACE WITH PROVISIONS FOR
STRUCTURAL AND THERMAL MOVEMENT.
J. SEPARATE DISSIMILAR METALS AND METAL PRODUCTS FROM CONTACT WITH
WOOD OR CEMENTITIOUS MATERIALS BY PAINTING EACH METAL SURFACE IN
AREA OF CONTACT WITH A BITUMINOUS COATING OR BY OTHER PERMANENT
SEPARATION.
K.EMT AND RSC MAY BE SUPPORTED BY OPENINGS THROUGH STRUCTURAL
MEMBERS AS PERMITTED IN NFPA-70.
L. RACEWAY SUPPORT INTERVALS
RACEWAY MAX DISTANCE MAX SUPPORT MAX LENGTH
TYPE TO FIRST SUPPORT INTERVAL OF RUN
MC CABLE 12 INCHES 54 INCHES NONE
FMC, LFMC 12 INCHES 54 INCHES 72 INCHES
RSC/RAC <1” DIA 36 INCHES 120 INCHES NONE
RSC/RAC >1” DIA 36 INCHES PER NEC NONE
EMT 36 INCHES 120 INCHES NONE
DEVICES
A.GFCI RECEPTACLES: STRAIGHT BLADE, FEED-THROUGH TYPE. COMPLY WITH
NEMA WD 1, NEMA WD 6, UL 498, AND UL 943, CLASS A, 125 V, 20 A, AND INCLUDE
INDICATOR LIGHT THAT IS LIGHTED WHEN DEVICE IS TRIPPED.
B. WALL COVER PLATES: PROVIDE SINGLE TYPES TO MATCH CORRESPONDING
WIRING DEVICES. FOR WET OR DAMP LOCATIONS PROVIDE METALLIC, HEAVY
DUTY, "WEATHERPROOF WHILE IN USE" LOCKABLE COVER.
C.DEVICE COLORS: DEVICES GREY, COVERPLATES GREY.
PANELBOARDS
A.MODIFIED PANELBOARDS: PROVIDE OR RELOCATE BREAKERS AS INDICATED.
NEW BREAKERS SHALL BE FROM SAME MANUFACTURER AS PANELBOARD AND
SHALL HAVE SUITABLE FAULT CURRENT RATINGS.
B.PROVIDE TYPED PANELBOARD INDEXES FOR ALL NEW AND MODIFIED
PANELBOARDS.
GROUNDING
A.PROVIDE GROUNDING IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE
AND ADDITIONALLY AS INDICATED.
CONNECTORS AND SPLICES
A. DESCRIPTION: FACTORY-FABRICATED CONNECTORS AND SPLICES OF SIZE,
AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND
SERVICE INDICATED; LISTED AND LABELED AS DEFINED IN NFPA 70, BY A
QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND
APPLICATION. USE SINGLE OR MULTI-TAP INSULATED CONNECTORS TO FIT THE
APPLICATION.
B. MAKE SPLICES, TERMINATIONS, AND TAPS THAT ARE COMPATIBLE WITH
CONDUCTOR MATERIAL AND THAT POSSESS EQUIVALENT OR BETTER
MECHANICAL STRENGTH AND INSULATION RATINGS THAN UNSPLICED
CONDUCTORS. USE OXIDE INHIBITOR IN EACH SPLICE, TERMINATION, AND TAP
FOR ANY CONNECTIONS TO EXISTING ALUMINUM CONDUCTORS.
C. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO
MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF
MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE
SPECIFIED IN UL 486A-486B.
ABBREVIATIONS
SCOTT F. BURGER
Lic. No. 034338
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
SINGLE LINE DIAGRAM
E2
CONSTRUCTION NOTES:XX
1. ADJUST CIRCUITS PER PANEL SCHEDULE
(E)MDP3
(#12)
208/120V
3PH, 4W
600A MLO
(E)MDP4
208/120V
3PH, 4W
400A MLO
BR1
120/208V
1PH, 3W
100A MLO
(E)PC (#6)
208/120V
3PH, 4W
225A MCB
(E)LB
120/208V
1PH, 3W
225A MLO
(E)PB (#5)
208/120V
3PH, 4W
225A MCB
(E)PA (#4)
208/120V
3PH, 4W
225A MCB
(E)EMERGENCY
GENERATOR
PANEL #3
120/208V
1PH, 3W
MLO
(E)FIRE
ALARM
CONTROL
PANEL
120/208V
(E)EMERGENCY
GENERATOR
PANEL #4
(#16)
120/208V
1PH, 3W
225A MLO
(E)(#15)
120/208V
1PH, 3W
100A MLO
(E)(#26)
120/208V
1PH, 3W
___A XXX
(E)LPC
120/208V
1PH, 3W
225 MLO
(E)LPD (#9)
120/208V
1PH, 3W
225 MLO
(E)PD (#8)
208/120V
3PH, 4W
225A MLO
(E)PE
208/120V
3PH, 4W
225A MLO
(E)PB1
(FORMERLY
#10)
120/208V
1PH, 3W
___A MCB
(E)ELEVATOR
CONTROL PANEL
120/208V
1PH, 3W
(E)LP2
(FORMERLY
#19)
120/208V
1PH, 3W
100A MLO
(E)LP3
120/208V
1PH, 3W
100A MLO
(E)L1
120/208V
1PH, 3W
225A MLO
(E)L2
120/208V
1PH, 3W
225A MLO
(E)BR2
(PRESENTLY
BR IN FIELD)
120/208V
1PH, 3W
MLO
(E)#23
208/120V
3PH, 4W
100A MCB
(E)(#24)
120/208V
1PH, 3W
150A MCB
(E)(#25)
120/208V
1PH, 3W
125A MCB
(E)#26
120/208V
1PH, 3W
125A MCB
SCALE: NONE
BUILDING 3 - SINGLE LINE DIAGRAM - CONSTRUCTION
TO (E)ATS
ELEVATOR
MOTOR
3-SWBD
208/120V 3P, 4W 1200A
MCB
ADMIN BLDG
SCOTT F. BURGER
Lic. No. 034338
0 6" 2'1' 3' 4' 5' 3/8"=1'-0"
ELECTRICAL PLAN
CH-1
BR1-28
BR1-30
SWBD3-15
WP/GFI
BR1-29
BR1-27
(E)PANEL "BR1" (E)PULLBOXES
(E)SWBD-3
ROUTE ALONG
BUILDING WALL
AND SCREEN WALL.
ROUTE ABOVE CEILING. PENETRATE
EXTERIOR WALL ABOVE INTERIOR
CEILING AND TURN DOWN AT
EXTERIOR WALL.
BR1-12
VIRGINIA DEPARTMENT OF TRANSPORTATION
LYNCHBURG DISTRICT ADMINISTRATION BUILDING
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
CONSTRUCTION NOTES:
1. DUAL-TEMP CHANGEOVER SUPPLY VALVE. PROVIDE CIRCUIT PER PANEL
SCHEDULE BR1.
2. DUAL-TEMP CHANGEOVER RETURN VALVE. PROVIDE CIRCUIT PER PANEL
SCHEDULE BR1.
3. HEAT TRACE CONTROLLER. PROVIDE CIRCUIT PER PANEL SCHEDULE BR1.
4. REUSE EXISTING CONDUIT BETWEEN SWBD-3 AND PULL BOXES. PROVIDE NEW
RACEWAY BETWEEN PULL BOXES AND CH-1.
5. PROVIDE TAG ON DISCONNECT SWITCH STATING "DO NOT TURN OFF DURING
HEATING SEASON. CHILLER MUST REMAIN ENERGIZED FOR FREEZE
PROTECTION".
XX
ELECTRICAL PLAN
E3
SCALE:
NORTH
NONE
KEYPLAN
WORK AREA
ADMINISTRATION BUILDING
SCOTT F. BURGER
Lic. No. 034338
CHILLER REPLACEMENT
PROJECT CODE: 501-B6501-007
LYNCHBURG, VIRGINIA
25084 2026-09-28
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
SCHEDULES, DETAILS, AND CALCULATIONS
E4
SWITCHBOARD-3 SCHEDULE
PANEL BUS RATING 1200A ENCLOSURE NEMA 3R
PANEL MAIN OVERCURRENT 1200A MCB MOUNTING SURFACE
PANEL VOLTAGE RATING 208Y/120 LINESIDE TOP
PHASES / WIRES 3P/4W OTHER FEED-THROUGH LUGS, 200% NEUTRAL
MIN SHORT CIRCUIT RATING 65 KAIC
CKT CONNECTED LOAD (A) OVERCURRENT PROTECTION CONDUCTOR AND CONDUIT
NO. DESCRIPTION A B C PHASE TYPE FRAME TRIP COMMENTS PHASE NEUT EGC COND
1 SPACE 3 250
2 AC-ROOF 3 30
3 C-WATER-PUMP 3 250
4 RTU-UNIT 3
5 PANEL-LB 2
6 PANEL-L1 2
7 PANEL-L2 2
8 PANEL-L2P 2 100
9 SPARE 2 100
10 PANEL-BR 2 100
11 MDP-3 3
12 MDP-4 3
13 PANEL-PA 3
14 PANEL-PC 3
15 CHILLER CH-1 3 250 NOTE: 1, 2 #1 #1 #6 2"
TOTAL CONNECTED LOAD 0.0 0.0 0.0
AVERAGE AMPS/PHASE 0.0
NOTES:
1 REMOVE EXISTING CIRCUIT FEEDING CHILLER. RETAIN CONDUIT BETWEEN SPLICE BOX AND SWBD-3 FOR RE-USE. PROVIDE NEW CONDUIT FROM SPLICEBOX TO
CHILLER AND NEW CONDUCTORS FROM SWBD-3 TO THE CHILLER. ROUTE PER PLANS.
2…