I.B.08. COMBO Attachment 1 - Salient Characteristics - ISO Stand Lighting.pdf
PDF 1 MB Posted
- Attached to
- 143d MXG ISO Stand Lighting
- Solicitation number
- W50S9424Q0014
- Issued by
-
Department of the Army National Guard
About this file
This document appears to be an attachment to a federal contract opportunity for ISO stand lighting. The key details are:
The attachment outlines the minimum requirements for the ISO stand lighting, including the removal and disposal of the existing 20 lighting fixtures, the professional installation of new upgraded light fixtures that match the current specifications, and the required technical specifications for the new light fixtures. The new fixtures must be 140 watt X17 LED flood lights with trunnion mounts, stainless steel hardware, photo cells, color temperature selection, minimum 19,158 lumens, wet location rating, and a 5-year warranty. The fixtures must be able to rotate in 30-degree increments and withstand all weather conditions, with an IP65 rating for dust and water ingress protection. The attachment also requires the installation of wire guards/glass protection, all associated hardware and labor, and testing upon completion.
The related federal contract opportunity is for "143d MXG ISO Stand Lighting" with Solicitation Number W50S9424Q0014, issued by the Department of the Army National Guard. The contract requires the ISO stand lighting to be provided in accordance with the attached Salient Characteristics document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| I.B.08. COMBO - ISO Stand Lighting.pdf | ||
| I.B.08. COMBO - ISO Stand Lighting.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Minimum requirements needed for Iso stand lighting are as follows:
-Removal and disposal of old lighting fixtures (20 each) off of existing ISO Stand which is made up multiple components that link together with 10 lights on the right side, 10 lights on the left side.
- Professionally install and match current workmanship standards with new upgraded light fixtures.
-The current lighting in place are RAB part# X17FA140T, replacements will need the exact specifications listed so that they match current existing setup. Must be 140 WATT X17 LED flood light, trunnion mount with stainless steal hardware, Photo cell, CCT selectable, 19,158 Lumens minimum, 120 -277 volt, Suitable for wet locations, tempered glass lense, polycarbonate reflectors, Mercury and UV free, NEMA beam spread of 7H x 7v, minimum 5 year warranty, cast aluminum housing.
- must be able to rotate in 30 degree increments.
- must be functional in all weather.
-must have Ingress protection rating of IP65 for dust and water
-must include appropriately sized wire guard / glass protection (color bronze) for each fixture (20 each).
-must include any and all associated hardware, wire, misc parts, etc needed to complete installation according to industry standards.
-must include labor in all aspects on removal / installation / cleanup.
-must included testing to satisfaction upon completion of work.
(SEE PICTURES BELOW)
File details come from the government source that posted it. Updated .