Drawings_HSCGG1-15-B-PFA030_Replace_Circuit_Wiring_Michel_Hall_Project__6005224.pdf
PDF 3 MB Posted
- Attached to
- REPLACE ELECTRICAL WIRING FOR BRANCH CIRCUITS IN MICHEL HALL USCG ACADEMY NEW LONDON CT PROJECT #6005225
- Solicitation number
- HSCGG1-15-B-PFA030
About this file
DRAWINGS HSCGG1-15-B-PFA030 WIRING FOR BRANCH CIRCUITS IN MICHEL HALL USCG ACADEMY PROJECT 6005224
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUFFALO
PITTSBURGH
BANGOR
PORTLAND
BURLINGTON
HARTFORD
PROVIDENCE
ALBANY
NEW YORK CITY
PHILADELPHIA
SCRANTON
CONCORD
BOSTON
ME
NHVT
MA
NY
PA
NJ
CT RI
SYRACUSE
ATLANTIC OCEAN
NEW LONDON
U.S. COAST GUARD ACADEMY
R.R. STA.
FRONTAGE
W
ILLIAMS ST.
BR
IG
GS
COLMAN
NORTH
SOUTH
FRONTAGE
Perry Pd.
ST.
AVENUE
MOHEGAN
GOLD STAR MEMORIAL BRIDGE
PIER
STATE
RAILROAD
RAILROAD
WINTHROP COVE
HUNTINGTON ST.
W
ILLIAMS ST.
THAMES RIVER
THAMES RIVER
U.S. COAST GUARD ACADEMY
15 MOHEGAN AVENUE
NEW LONDON, CT
C.G. MEMORIAL
CHAPEL
ROLAND HALL
ATHLETIC FIELD
ATHLETIC FIELD
CULLOCH ST
FARNSW
ORTH AVE
MOHEGAN AVE
CHASE HALL-D
CHASE HALL
PLAZA
DESHON ST
MOHEGAN AVE
WAESCHE
HALL
DIMICK
HALL
SMITH HALL
ONECO AVE
HUNTER LIGGETT DR
C
JOHNSON HALL
TA
MPA
ST
BEAR DR
OFFICERS
QUARTERS
MAIN
GATE SE
NE
CA
D R
WASHINGTON PARADE GROUND
HAMILTON HALL
CHASE HALL-A
A
CHASE HALL-B
A YEATON HALL
SATTERLEE HALL
CAMPBELL DR
O-CLUB
PARCEL 3
THAMES SHIPYARD
ACADEMY
NEW ENGLAND CENTRAL RAILROAD
DESHON ST
GATE
MUNRO HALL
RUNNING TRACK
CREW ROWING
CENTER
SOCCER PRACTICE FIELD
EAGLE DR
HARRIET LN
MCALLISTER HALL
CADET MEMORIAL FIELD
LEAMY HALL
MICHEL HALL
BILLARD
HALL
MAINT.
SHOP
BASEBALL FIELD
PICKERING RD
SA
IL
LO
FT
BOILER
HOUSE BI
BB
S
T
TENNIS
COURTS
PINE HALL
THAMES RIVER
EAGLE
PIER
TENNIS
COURT
TENNIS
COURT
RIVERSIDE PARK
TENNIS
COURTS
VISITOR
CENTER
AMMO
BUNKER
CIEPLIK HALL
SOCCER FIELD
SEAMANSHIP CENTER
JACOB'S ROCK
T-BOAT
PIER
ALUMNI
CENTER
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
WORK AREA
MICHEL HALL
DRAWING INDEX
SHEET
NUMBER
DISCIPLINE
SHEET TITLE
1 OF 28 G001 COVER SHEET
2 OF 28 A100 ARCHITECTURAL BASEMENT PLANS
3 OF 28 A101 ARCHITECTURAL 1ST FLOOR PLAN
4 OF 28 A102 ARCHITECTURAL 2ND FLOOR PLAN
5 OF 28 A103 ARCHITECTURAL 3RD FLOOR PLAN
6 OF 28 A104 ARCHITECTURAL 4TH FLOOR PLAN
7 OF 28 E001 ELECTRICAL NOTES
8 OF 28 E002 ELECTRICAL ABBREVIATIONS AND SYMBOLS
9 OF 28 E100 ELECTRICAL BASEMENT PLANS
10 OF 28 E101 ELECTRICAL 1ST FLOOR PLAN
11 OF 28 E102 ELECTRICAL 2ND FLOOR PLAN
12 OF 28 E103 ELECTRICAL 3RD FLOOR PLAN
13 OF 28 E104 ELECTRICAL 4TH FLOOR PLAN
14 OF 28 E105 ELECTRICAL PANEL SCHEDULES SUB-BASEMENT
15 OF 28 E106 ELECTRICAL PANEL SCHEDULES BASEMENT
16 OF 28 E107 ELECTRICAL PANEL SCHEDULES FIRST FLOOR
17 OF 28 E108 ELECTRICAL PANEL SCHEDULES SECOND FLOOR
18 OF 28 E109 ELECTRICAL PANEL SCHEDULES THIRD FLOOR
19 OF 28 E110 ELECTRICAL PANEL SCHEDULES FOURTH FLOOR
20 OF 28 E111 ELECTRICAL RACEWAY MOUNTING DETAILS
21 OF 28 T001 NOTES, ABBREVIATIONS & SYMBOLS
22 OF 28 T100 TELECOMMUNICATIONS BASEMENT PLANS
23 OF 28 T101 TELECOMMUNICATIONS 1ST FLOOR PLAN
24 OF 28 T102 TELECOMMUNICATIONS 2ND FLOOR PLAN
25 OF 28 T103 TELECOMMUNICATIONS 3RD FLOOR PLAN
26 OF 28 T104 TELECOMMUNICATIONS 4TH FLOOR PLAN
27 OF 28 T105 TELECOMMUNICATIONS DATA/TELE RISER DIAGRAM
28 OF 28 T106 TELECOMMUNICATIONS DATA/TELE SITE PLAN
LOCATION MAP
SCALE: NONE SCALE: NONE
VICINITY MAP
U.S. COAST GUARD ACADEMY
NEW LONDON, CONNECTICUT
REPLACE ELECTRICAL WIRING FOR BRANCH
AT
DETAIL SITE MAP
CIRCUITS IN MICHEL HALL
OFFICE
B24
OFFICE
B25
OFFICE
B21
STRG
B15
WOMENS
LOCKER
RM
B11
OFFICE
B23
RECEP
B22
ELEV
RM
MECH RM
MECH RM
STORAGE
B18
SUPPLY
B17
STRG
B16
LAUNDRY
B09
PIPE RUN
ACCESS TUNNEL
UP
UP
UP
JAN RM
B12
1st FLOOR OUTLINE 1st FLOOR OUTLINE
CORRIDOR
B08
CORRIDOR
B08
WOMEN
B14
ELEC RM
TEL/ELEC/
FIRE PANEL
RM
UP
BACKUP
GENERATOR
RM
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
1 2
2 22
2 2
TYP
C
TYP
TYP
TYP
1 TYP
B B 1
TYP
B
A A
C
TYP TYP
TYP
A
A
A
A
SUB-BASEMENT FLOOR PLAN
SCALE: 1/8" = 1'-0"2
BASEMENT FLOOR PLAN
SCALE: 1/8" = 1'-0"1
KEYNOTES:
1 CMU/CONCRETE WALL
2 GYPSUM DRYWALL WALL
3 PLASTER WALL
4 CERAMIC TILE: HALF WALL HEIGHT
5 CERAMIC TILE: FULL WALL HEIGHT
A 2'x2' ACOUSTICAL LAY IN CEILING TILE
B 2'x4' ACOUSTICAL LAY IN CEILING TILE
C SOLID GYPSUM DRYWALL CEILING
D EXPOSED CEILING
GENERAL NOTES:
1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO
SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL
SURFACES AND THE VARIOUS CEILING MATERIALS IN
EACH SPACE.
2. CONTRACTOR TO REPLACE EXISTING CEILING PANELS
WITH GOVERNMENT FURNISHED CEILING PANELS AS
INDICATED AND EXPRESSED BY THE CONTRACTING
OFFICER REPRESENTATIVE. CONTRACTOR TO PAINT THE
CEILING GRID PRIOR TO INSTALLATION OF NEW PANELS.
COORDINATE WITH CONTRACTING OFFICER
REPRESENTATIVE FOR EXTENT OF CEILING PANEL
INSTALLATION.
D
D
D
UP
DN
UP
DN
OFFICE
OFFICE
OFFICE
OFFICE
EXAM
PHARMACY
URGENT CARE
X-RAY
FILE RM
OFFICE
FILM RM
WOMEN
MEN
OFFICE
OFFICE
OFFICE
EXAM RM
**122**
BREAK RM
WAITING
**126**
STRG
FILE RM
OFFICE
EXAM
110B
OFFICE
110A
BREAK
STRG
STRG
LAB
OXYGEN
STRG
MINOR
SURGERY
EMT
SUPPLY
BIO
STRG
STRG
ROOM
STRG
BATH
OFFICE
OFFICE
OFFICE
OFFICE
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
ROOM
ROOM
RECEPTION
CORRIDOR
CORRIDOR
CORRIDOR
COMMS
COMMS
ROOM
WOMEN
MEN
ROOM
EXAM
WAITING
CORRIDOR
ELEV
ELEV
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
5 TYP 5 TYP
5 TYPA
A A
A
A
A
A A
A
A
A
A
A
A
A
A
A
A
A
C
C
C
TYP
2 TYP
A
2 TYP
A
2 TYP
A
2 TYP
A
2 TYP
A
2 TYP
A
2 TYP
A
1 1 1
1 1 1 1 1 1 2
2 2
2 2 22 22 222
2 2
A
A
A
A
AA
A
AAA
A
A
A A
5 TYP
TYP
3 TYPA
5 TYP
1 1 1 1
3 TYP
TYP
3 TYP
3 TYP
3 TYP
3 TYP
3 TYP
3 TYP
3 TYP 3 TYP
3 TYP
3 TYP
3 TYP
3 TYP
1 1 1 1 1 1
1ST FLOOR PLAN
SCALE: 1/8" = 1'-0"1
KEYNOTES:
1 CMU/CONCRETE WALL
2 GYPSUM DRYWALL WALL
3 PLASTER WALL
4 CERAMIC TILE: HALF WALL HEIGHT
5 CERAMIC TILE: FULL WALL HEIGHT
A 2'x2' ACOUSTICAL LAY IN CEILING TILE
B 2'x4' ACOUSTICAL LAY IN CEILING TILE
C SOLID GYPSUM DRYWALL CEILING
D EXPOSED CEILING
GENERAL NOTES:
1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO
SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL
SURFACES AND THE VARIOUS CEILING MATERIALS IN
EACH SPACE.
2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING
PANELS WITH GOVERNMENT FURNISHED CEILING PANELS
AS INDICATED AND EXPRESSED BY THE CONTRACTING
OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO
PAINT THE CEILING GRID PRIOR TO INSTALLATION OF
NEW PANELS. COORDINATE WITH CONTRACTING OFFICER
REPRESENTATIVE FOR EXTENT OF CEILING PANEL
INSTALLATION.
OFFICE
OFFICE
OFFICE
CONF RM
OFFICE
OFFICE
OFFICE
OFFICE
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM RM
OFFICE
OFFICE
BREAK
OFFICE
STRG
STRG
DENTAL
LAB
EXAM RM
BREAK RM
RECEP
X-RAY RM
DARK RM
DENTAL
LAB
UP
DN
UP
DN
UP
DN
STRG
JAN
ROOM
BATH
BATH
BATH
ELEV
ELEV
STAIR
CLO
248A
EXAM RM
CORRIDOR
CORRIDOR
BATH
DENTAL
STAIR STAIR
CORRIDOR
CORRIDOR
CLOSET
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
3 TYP
5 TYP
3 TYP 3 TYP
TYP
TYP
3 TYP
2 TYP
2 2 TYP
1 TYP
2 TYP 2
3 TYP
12122
A A
A
A
A A A
A
A A A A
A
A A
AAA
A
A
A A
A
A A
A
A
A
A A A
A
A
A
A
A A
A
A
A
A A
A A
22 TYP2 TYP2 TYP2 TYP
2 TYP
5 TYP
2 TYP
2 TYP
4 TYP
2ND FLOOR PLAN
SCALE: 1/8" = 1'-0"1
2 2
3 TYP
3 TYP
3 TYP
KEYNOTES:
1 CMU/CONCRETE WALL
2 GYPSUM DRYWALL WALL
3 PLASTER WALL
4 CERAMIC TILE: HALF WALL HEIGHT
5 CERAMIC TILE: FULL WALL HEIGHT
A 2'x2' ACOUSTICAL LAY IN CEILING TILE
B 2'x4' ACOUSTICAL LAY IN CEILING TILE
C SOLID GYPSUM DRYWALL CEILING
D EXPOSED CEILING
GENERAL NOTES:
1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO
SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL
SURFACES AND THE VARIOUS CEILING MATERIALS IN
EACH SPACE.
2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING
PANELS WITH GOVERNMENT FURNISHED CEILING PANELS
AS INDICATED AND EXPRESSED BY THE CONTRACTING
OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO
PAINT THE CEILING GRID PRIOR TO INSTALLATION OF
NEW PANELS. COORDINATE WITH CONTRACTING OFFICER
DN
DN
UP
DN
TRAINING RM
PATIENT RM
PATIENT RM
STATIONERY
BICYCLES
MALE
DUTY RM
OFFICE
FEMALE
DUTY RM
PATIENT RM
JAN
STRG
LINEN
PHYSICAL THERAPY
STRG
ICE RM
OFFICE
STRG
STORAGE
RECEPTION
PHYSICAL
THERAPY
STRG
MEN'S
LOCKER
WOMEN'S
LOCKER
NURSES
STATION
UTILITY RM
UTILITY
RM
STRG
STRG
WOMEN'S
LOCKER RM
MEN'S
LOCKER RM
ROOM
PATIENT RM
STAIR
STAIR
STAIR
ELEV
ELEV
ROOM
STRG
ROOM
310A
ROOM
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
C
ABB
A
3RD FLOOR PLAN
SCALE: 1/8" = 1'-0"1
TYP
4 TYP
5 TYP
1 TYP
A A
A
C
1 TYP
4 TYP
4 TYP
B
C
5 TYP
5 TYP
5 TYP
3 3
3 TYP
A A
B B
B B
B
B
B
B
5 TYP
A
3 TYP
5 TYP
C
5 TYP
C
3 TYP
A
3 TYP
5 TYP
3 TYP
C
3 TYP
1A
TYP
C
5 TYP 5 TYP
CC
C
3 TYP
4 TYP
C
3 TYP
1 TYP
5 TYP
5 TYP
A A
A
12 2
C
KEYNOTES:
1 CMU/CONCRETE WALL
2 GYPSUM DRYWALL WALL
3 PLASTER WALL
4 CERAMIC TILE: HALF WALL HEIGHT
5 CERAMIC TILE: FULL WALL HEIGHT
A 2'x2' ACOUSTICAL LAY IN CEILING TILE
B 2'x4' ACOUSTICAL LAY IN CEILING TILE
C SOLID GYPSUM DRYWALL CEILING
D EXPOSED CEILING
GENERAL NOTES:
1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO
SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL
SURFACES AND THE VARIOUS CEILING MATERIALS IN
EACH SPACE.
2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING
PANELS WITH GOVERNMENT FURNISHED CEILING PANELS
AS INDICATED AND EXPRESSED BY THE CONTRACTING
OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO
PAINT THE CEILING GRID PRIOR TO INSTALLATION OF
NEW PANELS. COORDINATE WITH CONTRACTING OFFICER
STORAGE
MECH RM
MECH RM
WORKOUT RM
WORKOUT RM
STORAGE
STORAGE
STORAGE
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
2 TYP
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
C
2 TYPC
2 TYPC
4TH FLOOR PLAN
SCALE: 1/8" = 1'-0"1
KEYNOTES:
1 CMU/CONCRETE WALL
2 GYPSUM DRYWALL WALL
3 PLASTER WALL
4 CERAMIC TILE: HALF WALL HEIGHT
5 CERAMIC TILE: FULL WALL HEIGHT
A 2'x2' ACOUSTICAL LAY IN CEILING TILE
B 2'x4' ACOUSTICAL LAY IN CEILING TILE
C SOLID GYPSUM DRYWALL CEILING
D EXPOSED CEILING
D
D
GENERAL NOTES:
1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO
SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL
SURFACES AND THE VARIOUS CEILING MATERIALS IN
EACH SPACE.
2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING
PANELS WITH GOVERNMENT FURNISHED CEILING PANELS
AS INDICATED AND EXPRESSED BY THE CONTRACTING
OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO
PAINT THE CEILING GRID PRIOR TO INSTALLATION OF
NEW PANELS. COORDINATE WITH CONTRACTING OFFICER
GENERAL NOTES AND CONDITIONS: (CONT.)
3. THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF
FEDERAL, STATE, AND LOCAL REGULATORY AGENCIES HAVING JURISDICTION. IN
PARTICULAR, THE WORK WILL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
INTERNATIONAL BUILDING CODE, INCLUDING ALL OF ITS APPLICABLE SUBCODES AND
AMENDMENTS, INCLUDING, BUT NOT LIMITED TO THE FOLLOWING:
BUILDING: INTERNATIONAL BUILDING CODE - 2009
INTERNATIONAL EXISTING BUILDING CODE - 2009
LIFE SAFETY: NFPA 101 - 2009
ELECTRICAL: NATIONAL ELECTRIC CODE - NFPA 70 - 2011
4. ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND
WILL BE COMPLETED IN ACCORDANCE WITH THE GOVERNING CODES (ABOVE), INDUSTRY
STANDARDS, AND IN CONFORMANCE WITH THE MANUFACTURERS RECOMMENDATIONS
AND REQUIREMENTS.
5. WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL
LABOR, MATERIALS, AND SERVICES, INCLUDING WORK NOT SPECIFICALLY SHOWN BUT
REASONABLY IMPLIED. THIS SHALL INCLUDE CUTTING, PATCHING AND RESTORATION OF
EXISTING SURFACES DAMAGED DURING THE CONSTRUCTION. CONTRACTOR SHALL
ALSO PROVIDE ALL EQUIPMENT SHOWN OR SPECIFIED OR AN APPROVED EQUIVALENT.
SUBSTITUTED EQUIPMENT OR MATERIALS SHALL NOT BE INSTALLED UNTIL GIVEN
WRITTEN APPROVAL BY THE CGA/AGENT.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE
WITH THESE CONTRACT DOCUMENTS. CONTRACTOR WILL NOT BE ALLOWED CHANGE
ORDERS FOR PROBLEMS ARISING FROM NEGLECT OF PROVISIONS INCLUDED IN THESE
CONDITIONS.
7. MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTION, AND UPON SUBSTANTIAL
COMPLETION PERFORM FINAL CLEANUP. REMOVE CONSTRUCTION RUBBISH,
SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD
STRUCTURES, AND OTHER MATERIALS OR EQUIPMENT THAT WAS REQUIRED IN
CONNECTION WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF.
8. THOSE PERFORMING WORK AS A CONTRACTOR MUST EXAMINE SUBSTRATES AND
CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED AND NOTIFY THE
CONTRACTOR IN WRITING, OF CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY
COMPLETION OF THE WORK. COMMENCEMENT OF WORK BY A TRADE ON A SURFACE OR
CONSTRUCTION SHALL IMPLY ACCEPTANCE OF SUCH SURFACE OR CONSTRUCTION. DO
NOT PROCEED WITH INSTALLATION UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN
CORRECTED.
9. THE CONTRACTOR SHALL SECURE ALL PERMITS AND APPLICATIONS AND PAY ANY AND
ALL FEES AS REQUIRED. THE CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES AND
CERTIFICATES OF INSPECTION REQUIRED BY THE AUTHORITIES HAVING JURISDICTION.
DELIVER ALL PERMITS, CERTIFICATES AND APPROVALS TO THE CGA/AGENT PRIOR TO
FINAL ACCEPTANCE OF THE WORK. THE CONTRACTOR MUST FILE NECESSARY
DRAWINGS, PREPARE DOCUMENTS AND MAKE APPLICATIONS FOR EACH REQUIRE
PERMIT AND INSPECTION, PRIOR TO COMMENCING WORK TO AVOID DELAYS DURING
CONSTRUCTION.
10. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND MANUFACTURERS DATA SHEETS ON
ALL EQUIPMENT AND MATERIALS SPECIFIED ON DRAWINGS FOR APPROVAL BY
CGA/AGENT. THESE DRAWINGS OR SHEETS SHALL CONTAIN ALL NECESSARY DATA, I.E.,
MANUFACTURER, CATALOG NUMBER, SIZE, DIMENSIONS, CAPACITY, WIRING DETAILS
AND ALL OTHER ENGINEERING DATA AND DETAILS NECESSARY FOR COMPLETE CLARITY
AND INSTALLATION.
11. THE CONTRACTOR SHALL KEEP ONE SET OF THE LATEST ISSUE OF DRAWINGS WHICH
SHALL REFLECT THE ACTUAL INSTALLED CONDITIONS AND CONNECTIONS OF ALL
EQUIPMENT AND DEVICES. THE CONTRACTOR SHALL PROVIDE COPIES OF ALL
MAINTENANCE INFORMATION AND INSTRUCTIONS RECEIVED WITH EQUIPMENT AND
SYSTEMS. ALL "AS-BUILT" DRAWINGS SHALL BE MARKED-UP "LEGIBLY" WITHOUT
INTERPRETATION REQUIRED. CONTRACTOR IS TO PROVIDE ELECTRONIC COPIES (CAD
2009) OF AS-BUILT DRAWINGS AS WELL AS HARD COPIES. MISCELLANEOUS INFORMATION
SHALL BE GIVEN TO THE CGA/AGENT AND ENGINEER AT COMPLETION OF WORK. THE
CONTRACTOR SHALL GUARANTEE ALL MATERIAL AND LABOR TO BE FREE FROM
DEFECTS FOR A ONE YEAR PERIOD FROM THE TIME OF CGA/AGENT ACCEPTANCE. ANY
DEFECTS OCCURRING DURING THIS PERIOD SHALL BE CORRECTED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE CGA/AGENT.
12. ALL POWER OUTAGES AND DISRUPTIONS TO POWER AT THE CGA WILL BE LIMITED TO
WEEKENDS, AFTER HOURS AND SCHEDULED HOLIDAYS. REFER TO SPECIFICATIONS FOR
ACCEPTABLE DATES FOR POWER DISRUPTIONS. DO NOT PROCEED WITH POWER
OUTAGES AND DISRUPTIONS WITHOUT APPROVAL FROM THE CGA/AGENT.
13. THE CONTRACTOR, AS PART OF MAINTAINING "AS BUILT" DRAWINGS, SHALL UPDATE ALL
PANELBOARD DIRECTORIES TO REFLECT ALL THE CIRCUITING AT THE CONCLUSION OF
THE PROJECT. CONTRACTOR TO DETERMINE AND LABEL USES OF ALL CIRCUITS.
CIRCUITS LABELED "EXISTING CIRCUIT" AND REMAINING ACTIVE WILL NOT BE
ACCEPTABLE.
GENERAL ELECTRICAL NOTES (CONT.):
17. PANEL COMPARTMENT DESIGNATIONS ARE AS INDICATED BELOW:
17.1 BLANK- NOT INTENDED FOR USE, COVERPLATE ONLY.
17.2 SPACE- CONTAINS NECESSARY BUS AND HARDWARE FOR FUTURE
ADDITION OF BREAKERS OR STARTERS WITHIN RANGE SHOWN.
17.3. SPARE- CONTAINS A COMPLETE BREAKER OR STARTER INSTALLED, SIZE
AS INDICATED, AVAILABLE FOR FUTURE USE.
18. ALL TEMPORARY WIRING, LIGHTING AND POWER CIRCUITS AND DEVICES SHALL BE
INSTALLED TO MEET THE LATEST REQUIREMENTS OF THE NATIONAL ELECTRICAL
CODE, LOCAL, STATE AND FEDERAL REQUIREMENTS FOR SUCH TEMPORARY
INSTALLATION.
19. THE CONTRACTOR SHALL ENSURE THAT RECEPTACLES USED FOR HAND TOOLS AND
OTHER MISCELLANEOUS EQUIPMENT SHALL BE INSTALLED WITH GROUND FAULT
INTERRUPTER OR OTHER APPROVED AND RECOGNIZED INTERRUPTING SENSORS.
20. THE COMPLETE INSTALLATION SHALL BE TESTED AT COMPLETION OF WORK, TO BE
FREE OF GROUNDS AND SHORT CIRCUITS CONDITIONS.
21. CONTRACTOR SHALL COORDINATE AND SCHEDULE ALL WORK AND SHUTDOWNS OF
EQUIPMENT WITH FACILITY.
22. EXCAVATION FOR UNDERSLAB OR UNDERGROUND INSTALLATION OF CONDUITS
SHALL BE APPROACHED WITH EXTREME CAUTION SO AS NOT TO DAMAGE EXISTING
UNDERGROUND PIPING, WIRING AND CONDUITS.
GENERAL NOTES AND CONDITIONS:
1. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE
AVAILABLE BUILDING DRAWINGS, ARCHITECTURAL BACKGROUNDS PROVIDED BY THE
CGA AND FIELD SURVEY INFORMATION COMPILED BY THE ENGINEERING DESIGN
TEAM FOR THE PURPOSE OF ENGINEERING DESIGN. EXISTING CONDITIONS ARE
SHOWN AS ACCURATELY AS POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS
SHOWN DO NOT DEPICT ALL DEVICES OR CIRCUITS FEEDING THE DEVICES OR ARE
NOT EXACTLY AS EXISTING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS,
ELEVATIONS, LOCATIONS, SIZES AND CONDITIONS AT THE SITE AND REPORT ANY
DISCREPANCIES TO THE CGA/AGENT PRIOR TO BEGINNING INSTALLATION OR
FABRICATION WORK.
1.1. DO NOT SCALE DRAWINGS.
1.2. SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR
RELATED WORK ARE NOT SUFFICIENTLY DETAILED OR EXPLAINED ON THE
DRAWINGS, OR IN THE SPECIFICATIONS, CONSULT THE ENGINEER FOR
NECESSARY CLARIFICATIONS, AND CONFORM TO THOSE CLARIFICATIONS
INSOFAR AS THEY ARE CONSISTENT WITH THE ORIGINAL DRAWINGS AND
SPECIFICATIONS. IN NO CASE SHALL WORK PROCEED IN UNCERTAINTY.
1.3. EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED
CONFIGURATIONS TO SUIT KNOWN CONDITIONS. ACTUAL INSTALLATION BY
CONTRACTOR MAY BE ALTERED AS REQUIRED TO SUIT FIELD CONDITIONS
ENCOUNTERED DURING CONSTRUCTION WITHOUT COMPROMISING THE
INTENT OF THE ORIGINAL DESIGN.
1.4. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND
CONDITIONS AT SITE PRIOR TO STARTING WORK.
1.5. AT PROJECT COMPLETION ALL DEVICES, I.E., RECEPTACLES, LIGHTING AND
EQUIPMENT NOW POWERED SHALL BE FUNCTIONING AS IT WAS PRIOR TO THE
START OF THE PROJECT. ANY DEVICES NOT FUNCTIONING PRIOR TO THE
START OF THE PROJECT SHALL BE INVESTIGATED BY THE CONTRACTOR AND
BROUGHT TO THE ATTENTION OF THE CGA/AGENT FOR DISPOSITION. ANY
ITEMS NOT ADDRESSED PRIOR TO STARTING THE PROJECT WILL NOT BE
HONORED AFTER THE PROJECT STARTS AND MUST BE MADE TO FUNCTION AS
DESIGNED AT THE CONTRACTOR'S EXPENSE.
ELECTRICAL DEMOLITION NOTES:
1. THE CONTRACTOR (EC) SHALL INCLUDE IN HIS BID ALL COSTS ASSOCIATED WITH
RELOCATION AND REMOVAL OF ELECTRICAL WORK AS DESCRIBED IN THE DRAWINGS
AND SPECIFICATIONS.
2. NOTE THAT THE FACILITY WILL BE FULLY OPERATIONAL DURING THE COURSE OF
THIS PROJECT.
2.1. THE CONTRACTOR IS TO COORDINATE ALL OF THE DEMOLITION WORK WITH
THE FACILITY PERSONNEL TO MINIMIZE DISTURBING THE OPERATING
EQUIPMENT, WIRING AND SYSTEMS.
2.2. THE CONTRACTOR SHALL PERFORM REMOVAL AND DEMOLITION WORK WITH
MINIMAL INTERFERENCE WITH EXISTING SYSTEMS.
3. DEMOLITION AND REMOVAL OF WORK SHALL BE PERFORMED IN A NEAT AND
PROFESSIONAL MANNER. THE CONTRACTOR SHALL RESTORE, PATCH, PAINT, ETC.,
ANY INTERIOR/EXTERIOR BUILDING SURFACE TO ITS ORIGINAL CONDITION.
4. REFER TO ELECTRICAL PLANS FOR NEW EQUIPMENT LAYOUT AND EXTENT OF
EQUIPMENT BEING REPLACED, RELOCATED, OR REMOVED. PATCH AND PAINT (TO
MATCH SURROUNDING CONDITIONS) ALL OPENINGS CREATED BY THIS DEMOLITION.
5. EXISTING CONDITIONS, EQUIPMENT, MATERIALS & SIZES ARE SHOWN FOR
REFERENCE ONLY. VERIFY EXISTING CONDITIONS AND BRING ANY DISCREPANCIES
TO THE CONTRACTING OFFICER'S ATTENTION IN WRITING PRIOR TO BID SUBMISSION.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELECTRICAL DEMOLITION WORK FOR
THIS PROJECT WHETHER OR NOT SPECIFICALLY INDICATED ON THIS OR OTHER
DEMOLITION PLANS. THIS WORK SHALL INCLUDE BUT IS NOT LIMITED TO THE
DISCONNECTION, REMOVAL AND DISPOSAL OF; PANELBOARDS, DISCONNECT
SWITCHES, RECEPTACLES, JUNCTION BOXES, WIRE, CABLE, CONDUIT, MOUNTING
HARDWARE STRAPS OR CABLES, ELECTRICAL SERVICES ETC. PER THE SCOPE OF
WORK FOR THIS PROJECT.
7. THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL OUTLETS, SWITCHES, ETC.,
INCLUDING ASSOCIATED WIRING, CONDUITS, COVERS, BOXES, ETC.. WHERE THE
REMOVAL OF THESE ITEMS DISRUPTS EXISTING WIRING THAT IS TO REMAIN, THE
CONTRACTOR SHALL INSTALL IN THE CEILING SPACE; JUNCTION BOXES AND OTHER
DEVICES AND PROVIDE BYPASS CONNECTIONS NECESSARY TO MAKE CIRCUITS
AFFECTED CONTINUOUS AND READY FOR OPERATION. OTHERWISE, WIRING SHALL
BE REMOVED BACK TO THE NEAREST ELECTRICAL JUNCTION BOX THAT IS TO REMAIN
OR TO THE SOURCE PANELBOARD.
8. ALL WORK MUST BE SCHEDULED AND PERFORMED AS NOT TO INTERRUPT NORMAL
OPERATIONS. REMOVAL OF ITEMS THAT WILL CAUSE ANY TYPE OF TEMPORARY
SHUTDOWN SHALL BE PERFORMED DURING OFF-PEAK HOURS.
9. CONTRACTOR SHALL THEN DEVELOP PHASING SCHEDULING AND SEQUENCING WITH
FINAL REVIEW AND APPROVAL BY THE CONTRACTING OFFICER. CONTRACTOR SHALL
CLOSELY FOLLOW THE DEMOLITION AND PHASING SCHEDULE AND PROCEED IN THE
SPECIFIED SEQUENCE. REFER TO SPECIFICATIONS FOR GENERAL PHASING
SEQUENCE AND REQUIREMENTS.
10. THE SHUTDOWN OF EXISTING BUILDING ELECTRICAL SERVICES SHALL BE
COORDINATED WITH THE CONTRACTING OFFICER REPRESENTATIVE (COR). MAKE
APPROPRIATE ARRANGEMENTS AT LEAST 5 BUSINESS DAYS PRIOR TO A SHUTDOWN.
11. THE CONTRACTOR SHALL REMOVE AND/OR RELOCATE ALL EXISTING ELECTRICAL
WORK WHICH INTERFERES WITH THE NEW ELECTRICAL LAYOUTS. ALL SYSTEMS
WHICH ARE NO LONGER REQUIRED TO FUNCTION SHALL BE DE-ENERGIZED AND
DISCONNECTED AT THE POWER SUPPLY SOURCE.
12. CONTRACTOR SHALL PROVIDE AND MAINTAIN ANY CONNECTIONS / DISCONNECTIONS
AS NEEDED TO ENSURE ADEQUATE SAFETY AND PROTECTION OF ALL PERSONNEL
AND EQUIPMENT.
13. ALL ELECTRICAL PANELS SHALL BE MAINTAINED AS WORKING PANELS THROUGHOUT
CONSTRUCTION AND WILL CONTINUE TO MAINTAIN CIRCUITS FOR EXISTING LIGHTING
OR EQUIPMENT TO REMAIN. PROVIDE AS NECESSARY TEMPORARY LIGHTING AND
ELECTRICAL FEEDS TO ANY DEVICES THAT MAY BE REQUIRED FOR UNINTERRUPTED
USE. PROVIDE TEMPORARY CONNECTIONS FOR RELOCATED EQUIPMENT DURING
CONSTRUCTION.
14. CONTRACTOR SHALL ENSURE THAT ANY DEVICES AND/OR FIXTURES LOCATED
OUTSIDE OF DEMOLITION WORK AREA ARE NOT AFFECTED BY REMOVAL OF WIRING
AND/OR CIRCUITING. WIRING/CONDUIT SHALL BE LEFT IN A SAFE CONDITION,
IDENTIFIED ON THE PANEL SCHEDULE, AND EXTENDED AS REQUIRED TO MAINTAIN
CIRCUIT CONTINUITY, INCLUDING ALL APPLICABLE CONTROLS.
15. PORTIONS OF FEEDER RUNS THAT SHALL BE REMOVED OR ABANDONED AS A
RESULT OF DEMOLITION WORK, BUT WHICH ARE REQUIRED TO REMAIN ENERGIZED,
SHALL BE CUT AT CONVENIENT LOCATIONS, REROUTED AND RECONNECTED.
16. EXISTING RACEWAYS THAT ARE NOT BEING REUSED SHALL BE REMOVED BACK TO
THE NEAREST JUNCTION OR PULLBOX, AND THE OPENINGS BLANKED. ANY CONDUITS
PENETRATING MASONRY SURFACES SHALL BE CUT INTO SURFACE, PATCHED, AND
PAINTED TO MATCH SURROUNDINGS.
17. DISCONNECT, RELOCATE OR REMOVE ELECTRICAL INSTALLATIONS AND EQUIPMENT
AS INDICATED BY PLANS AND AS REQUIRED BY CHANGES IN CONSTRUCTION. WHERE
EXISTING ELECTRICAL INSTALLATIONS INTERFERE WITH NEW WORK AND WHERE
SUCH INSTALLATIONS ARE TO REMAIN IN USE, THE NEW INSTALLATIONS SHALL BE
RELOCATED AND/OR RECONNECTED TO COORDINATE WITH THE WORK INDICATED
ON THE CONTRACT DRAWINGS. DETERMINE AND COORDINATE ALL EQUIPMENT
LOCATIONS PRIOR TO INITIAL ROUGH-IN.
ELECTRICAL DEMOLITION NOTES (CONT.):
18. DISCONNECT AND RELOCATE/RECONNECT ANY ELECTRICAL LINES, BRANCH CIRCUITS,
DEVICES, ETC. AND REPAIR PULL BOXES THAT MAY BE DISTURBED DURING THIS
RENOVATION. UNLESS NOTED OTHERWISE, ALL EXISTING ELECTRICAL WORK WHICH WILL
NOT BE RENDERED OBSOLETE AND WHICH MAY BE DISTURBED DUE TO ANY CHANGES
REQUIRED UNDER THE CONTRACT, SHALL BE RESTORED TO ITS ORIGINAL OPERATING
CONDITION AT NO COST TO THE GOVERNMENT. IF ANY EQUIPMENT TO REMAIN IS
DAMAGED DURING CONSTRUCTION, IT SHALL BE REPLACED WITH NEW (WITH NO COST
APPLIED TO THE GOVERNMENT).
19. FOR EXISTING PANELS MODIFIED AS PART OF THIS PROJECT, E.C. SHALL TEST AND KEEP
ALL EXISTING WORKING CIRCUIT BREAKERS AND SHALL USE THEM FOR NEW EQUIPMENT,
DEVICES, LIGHTING, AND/OR SPARES. E.C. SHALL REPLACE NON-WORKING BREAKERS
WITH NEW "IN KIND" BREAKERS. PROVIDE BLANK COVERS/COVERPLATES FOR ALL
EXPOSED CIRCUIT BREAKER SPACES (THOSE WITHOUT INSTALLED CIRCUIT BREAKERS;
EXPOSED BUS BARS) FOR PERSONNEL PROTECTION.
20. AS DIRECTED BY THE CGA/AGENT, ALL EXISTING EQUIPMENT AND MATERIAL IN USABLE
CONDITION THAT IS REMOVED SHALL REMAIN THE PROPERTY OF THE CGA/AGENT, OR
HANDLED AS INSTRUCTED BY THE CGA/AGENT, BE DISPOSED OF BY THE CONTRACTOR.
ALL MATERIALS DEEMED FOR REMOVAL SHALL BE RECYCLED WHENEVER POSSIBLE.
21. EXISTING PANELBOARD DIRECTORIES SHALL BE REPLACED WITH NEW "TYPED"
DIRECTORIES, TO ACCURATELY REFLECT EXISTING CONDITIONS. SPARE CIRCUIT
BREAKERS SHALL BE IDENTIFIED, LABELED AS SUCH. LEAVE "SPARE" CIRCUIT BREAKERS
IN THE 'OPEN' POSITION.
GENERAL ELECTRICAL NOTES:
1. ALL ELECTRICAL WORK SHALL BE COORDINATED WITH THE CGA/AGENT AND ALL
OTHER DISCIPLINES INVOLVED IN THIS PROJECT.
2. THE CONDUITS, CABLE TRAY AND SURFACE MOUNTED RACEWAYS SHOWN ON THESE
DRAWINGS ARE DIAGRAMMATIC IN NATURE, THEY SHOW THE GENERAL
ROUTING/ARRANGEMENT AND SIZE OF THE CONDUITS. THEY ARE NOT INTENDED TO
SHOW EVERY OFFSET OR INTERFERENCE THAT MAY BE ENCOUNTERED.
CONTRACTOR IS RESPONSIBLE FOR ROUTING ALL CONDUIT AND TRAY IN THE MOST
EFFICIENT MANNER IN ACCORDANCE WITH PROJECT SPECIFICATIONS.
3. ALL CONTRACTOR SUPPLIED MATERIALS SHALL BE NEW AND UL APPROVED (OR
APPROVED BY ANOTHER NATIONALLY RECOGNIZED ORGANIZATION).
4. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER,
RECTILINEAR TO BUILDING STRUCTURE. HORIZONTAL OR CROSS RUNS IN
PARTITIONS AND WALLS NOT PERMITTED.
5. ALL WIRING SHALL BE RUN CONCEALED IN CONDUIT UNLESS SPECIFIED OTHERWISE.
6. SECURE ALL SUPPORTS TO BUILDING STRUCTURE BY STEEL FOR VERTICAL
SUPPORT AND BY MEANS OF TOGGLE BOLTS ON HOLLOW MASONRY UNITS,
EXPANSION SHIELDS IN CONCRETE OR BRICK. MACHINE SCREWS ON METAL
SURFACE, AND WOOD SCREWS ON WOOD CONSTRUCTION. NAILS, RAWL OR WOOD
PLUGS NOT PERMITTED. SUPPORT HORIZONTAL RUNS OF METALLIC CONDUITS NOT
MORE THAN 10 FT. APART. SUPPORT RACEWAY RISERS AT EACH FLOOR LEVEL. RUN
EXPOSED RACEWAYS PARALLEL WITH OR AT RIGHT ANGLES TO WALLS.
7. ALL UNDERGROUND CONDUITS SHALL BE SEALED TO PREVENT THE ENTRY OF
WATER OR GASES.
8. CUT STEEL CONDUIT ENDS SQUARE, REAM SMOOTH, PAINT MALE THREADS OF FIELD
THREADED CONDUIT WITH GRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH
CONDUIT COUPLINGS.
9. ALL WIRING SHALL BE SOLID COPPER CONDUCTOR UNLESS OTHERWISE NOTED.
REFERENCE SPECIFICATIONS FOR MORE INFORMATION.
10. GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CODE REGARDING ELECTRODE, GROUNDING AND BONDING REQUIREMENTS FOR
SERVICE, EQUIPMENT AND ENCLOSURES. ALL EQUIPMENT SHALL BE PROVIDED WITH
A SEPARATE GROUNDING CONDUCTOR.
11. LEAVE WIRE SUFFICIENTLY LONG TO PERMIT MAKING FINAL CONNECTIONS AT
DEVICES.
12. WIRE COLOR CODING: PER CODE. WHERE COLOR-CODED CABLE IS NOT AVAILABLE,
CERTIFY IN WRITING AND REQUEST PERMISSION FOR OVERLAP COLOR TAPING OF
CONDUCTORS (MINIMUM LENGTH 6") IN ACCESSIBLE LOCATIONS. COLOR CODING,
ONCE SELECTED, MUST BE USED CONSISTENTLY FOR THE ENTIRE PROJECT.
13. PULL NO THERMOPLASTIC WIRES AT TEMPERATURES LOWER THAN 32°F. PROVIDE
CABLE SUPPORTS FOR WIRE IN RISER CONDUITS AS REQUIRED BY CODE.
14. PROVIDE PULL BOXES AS INDICATED AND WHEREVER NECESSARY TO FACILITATE
PULLING OF WIRE AND COORDINATE LOCATIONS WITH OTHER TRADES.
15. JUNCTION AND PULL BOXES: LOCATE GENERALLY NOT EXPOSED IN FINISHED
SPACES. WHERE NECESSARY, REROUTE CONDUITS OR MAKE OTHER
ARRANGEMENTS FOR CONCEALMENT. COVERS OF JUNCTION AND PULL BOXES
SHALL BE ACCESSIBLE.
16. SUPPORT JUNCTION AND PULL BOXES INDEPENDENTLY TO BUILDING STRUCTURE
WITH NO WEIGHT BEARING ON CONDUITS.
2. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND
REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE CGA/AGENT, ARE
BEING OBSERVED, PARTICULARLY WORKPLACE SAFETY AND THE CONDUCT OF ALL
THOSE EMPLOYED DIRECTLY AND INDIRECTLY BY HIM ON THE PREMISES, AND THE
CGA/AGENT'S EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY CONSTRUCTION
ACTIVITIES. THE CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER
MEANS TO PROVIDE WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE
ITEMS WILL BE COORDINATED WITH THE CGA AND HIS ONGOING OPERATIONS AND
WILL PROMPTLY BE REVISED WHEN WORK IN A PARTICULAR AREA HAS BEEN
COMPLETED.
2.1. DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT
SIGNAL DEVICES, GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND
OTHER DEVICES, APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE
WHICH GIVE PROPER AND UNDERSTANDABLE WARNING TO PERSONS WITH
REGARD TO HAZARDOUS CONDITIONS, EQUIPMENT AND OPERATIONS BEING
PERFORMED IN CONJUNCTION WITH THE WORK
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
ELECTRICAL SYMBOLS
SYMBOL LIST SHOWN IS FOR GENERAL REFERENCE ONLY. THE
PRESENCE OF A SYMBOL DOES NOT IMPLY ITS USE ON THIS
PROJECT. REFER TO THE DRAWINGS FOR SPECIFIC SYMBOLS USED.
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER & "IN-USE" RATED WEATHERPROOF COVER.
1PH SINGLE-PHASE
1P SINGLE POLE
3PH THREE-PHASE
4W FOUR-WIRE
AC ALTERNATING CURRENT OR
ARMORED CABLE
AF AMPERE FRAME OR AMP FUSE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMP AMPERE
AT AMPERE TRIP
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CD CONSTRUCTION DOCUMENTS
CGA COAST GUARD ACADEMY
CKT CIRCUIT
CLG CEILING
CL&P CONNECTICUT LIGHT & POWER
COR CONTRACTING OFFICER
REPRESENTATIVE
DEMARC DEMARCATION POINT
DEMO DEMOLITION
DISC DISCONNECT
DS DISCONNECT SWITCH
DWG DRAWING
DWM DIGITAL WATT METER
ELEC ELECTRIC OR ELECTRICAL
EMT ELECTRICAL METALLIC TUBING
EX EXISTING
G GROUND
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
I.E. THAT IS
IMC INTERMEDIATE METAL CONDUIT
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
LV LOW VOLTAGE
MC METAL-CLAD
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTRG METERING
(N) NEW EQUIPMENT
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
N NEUTRAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
PH PHASE
PVC POLYVINYL CHLORIDE
(PLASTIC)
RGS RIGID GALVANIZED STEEL
SMR SURFACE MOUNTED RACEWAY
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT AMPERE
WP WEATHERPROOF
W/ WITH
XFMR TRANSFORMER
ELECTRICAL ABBREVIATIONS
RECEPTACLE, QUAD
SURFACE METAL RACEWAY, MOUNTED HORIZONTALLY.
SURFACE METAL RACEWAY, VERTICAL RISER.
S SWITCH, SINGLE POLE, THREE WAY OR FOUR WAY.
LP11-22
HOMERUN TO PANEL. 2 #12 & 1#12 GROUND IN 3/4"
CONDUIT, UON. PANEL AND CIRCUIT NUMBER INDICATED.
EXISTING PANELBOARD.
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
J JUNCTION BOX
COMMENTSTYPESYMBOL DESCRIPTION MTG. METHOD MTG. HEIGHT VOLTSLAMPING WATTS
1X4 SURFACE
WRAP
120-
EX
1. SHADED FIXTURE ON PLAN DRAWING INDICATES THE FIXTURE CONTAINS A BATTERY
PACK TO POWER THE FIXTURE AND PROVIDE EMERGENCY EGRESS LIGHTING.
2. THE LIGHTING DESIGN IS BASED ON THE ABOVE FIXTURES.
WALL / CEILINGA LED 50W
RH
COMPLETE WITH EMERGENCY BATTERY PACK AND
OCCUPANCY SENSOR.
EXIT SIGN WITH
HEADS
- WALL/CEILING 120 UNIVERSAL MOUNT. E.C. SHALL VERIFY SINGLE/DOUBLE
FACE AND DIRECTION AS REQUIRED.
REMOTE HEADS 0.78W WALL 3.6VDC LISTED FOR WET LOCATIONS. POWERED FROM EXIT
SIGN.
LED
EX1 WALL/CEILING 120 UNIVERSAL MOUNT. E.C. SHALL VERIFY SINGLE/DOUBLE
FACE AND DIRECTION AS REQUIRED. REMOTE CAPACITY.
EXIT SIGN WITH
HEADS
BAT BATTERY PACK
WITH HEADS
LED
LED
SEE PLAN
DRAWING
1.55W
2.8W -
WALLLED 0.33W SEE PLAN
DRAWING
RECEPTACLE, SPECIAL PURPOSE.
B24
OFFICE
B25
OFFICE
B21
STRG
B15
WOMENS
LOCKER
RM
B11
OFFICE
B23
RECEP
B22
ELEV
RM
MECH RM
MECH RM
STORAGE
B18
SUPPLY
B17
STRG
B16
LAUNDRY
B09
PIPE RUN
ACCESS TUNNEL
UP
UP
UP
JAN RM
B12
1st FLOOR OUTLINE 1st FLOOR OUTLINE
LPB2-41
CORRIDOR
B08
CORRIDOR
B08
WOMEN
B14
PP
A
ELP-1
LPB-1
PUMP P1
MAIN XRAY
PPD
LDP-1
4" X 12" CABLE TRAY (TYPICAL)
PPB-LSPPB-RS
1 S 2
LPB2-22
1 1
SSS
SSS
SS 2
S2
S2
S2S 2 S2
SSSSS S
SS 2
2 2
+80"
SS
GFI
SS2
2 22
SS
S 2
S2
S2
S2 2
1 1
PPBRS-21,23
LPB2-21
LPB2-23
LPB2-5
S2
LPB2-42
LPB2-24
LPB2-40
LPB2-14
PPA-6
PPA-6
PPBLS-4
PPA-8
PPA-8
PPA-8
PPBLS-4 PPBLS-6 PPBLS-3
PPBLS-27
PPBLS-3
PPBLS-27
LPB2-3
LPB2-1
2 LPB2-5
PPBLS-11
PPBLS-10
GFILPB2
+80"
+46"
+46" +46" 2
A
A
J
LV
4 4
J 5
LV
EX1
RHEX
EX
EX1
RH
FIRESEAL
PPA-42 2
ELEC RM
TEL/ELEC/
FIRE PANEL
RM
UP
BACKUP
GENERATOR
RM
PP
E
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
SUB-BASEMENT PLAN
SCALE: 1/8" = 1'-0"2
BASEMENT PLAN
SCALE: 1/8" = 1'-0"1
MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:
MOUNT SMR AT 32" AFF
MOUNTING HEIGHTS:
REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING
DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT
AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.
MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT
MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER
FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.
INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO
SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"
AFF FOR RECEPTACLE, UON, MEASURED FROM CENTER OF BOX. INSTALL
WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN
ROOM.
REMOVE EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW
FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS
REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK COVERPLATE.
INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO
TO BE REPLACED WITH NEW FIXTURES.
REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.
INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE
FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST
ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.
FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL
INTERIOR MOUNTED EXIT SIGN.
WALL MOUNTED TELEDATA CABINET BY CONTRACTOR. SEE TELECOM
DRAWINGS.
KEYED NOTES:GENERAL NOTES:
1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.
2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE WAY,
FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.
3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING
HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.
4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE
AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL FOR
ALL LOCATIONS).
5. CABLE TRAY SHALL BE CENTER SUPPORTED.
6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING
TILE PRIOR TO INSTALLATION OF CABLE TRAY.
7. INSTALLATION OF CABLE TRAY WILL REQUIRE CONTRACTOR TO CHANGE ELEVATION
FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED SUCH AS
DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT FIXTURES
MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.
8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR
LIGHTING CABLES.
9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT
HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR IS
10 COVERS.)
10. SEE T001 FOR ADDITIONAL NOTES REGARDING CABLE TRAY.
DN
UP
DN
OFFICE
OFFICE
OFFICE
OFFICE
EXAM
PHARMACY
URGENT CARE
X-RAY
FILE RM
OFFICE
FILM RM
WOMEN
MEN
OFFICE
OFFICE
OFFICE
EXAM RM
BREAK RM
WAITING
STRG
FILE RM
OFFICE
EXAM
110B
OFFICE
110A
BREAK
STRG
STRG
LAB
OXYGEN
STRG
MINOR
SURGERY
EMT
SUPPLY
BIO
STRG
STRG
ROOM
STRG
BATH
OFFICE
OFFICE
OFFICE
OFFICE
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
ROOM
ROOM
RECEPTION
CORRIDOR
CORRIDOR
CORRIDOR
COMMS
COMMS
ROOM
WOMEN
MEN
ROOM
EXAM
WAITING
116LP-12 LP-13 LP-14
LP11-4
4" X 16" CABLE TRAY
4" X 16" CABLE TRAY
CORRIDOR
DNTL XRAY
ELEV
ELEV
LP11-13
S 2
GFI
S
S
1 1 1
S
S
GFI
LP11-2
S 2 S 2 S 2 S 2
LP11-15
LP11-43 LP11-17
LP11-19
GFI
S
GFI
1 1
GFI
S
1 1
GFI
S
1 1
LP11-23
LP11-8
GFI
GFI
GFI
LP11-47
1 1
11 1 1 1 1 1
2 2
1 6
S 2S
S S S
S
22222222 3 3
LP11-16,18,20
SSS
S
S 2S
S2
2 2
MOUNTED ABOVE DESKTOP
MOUNTED BELOW DESKTOP
+46"
FAN GFI
2 2 2 2
2 2 2
2 2
MOUNTED ABOVE DESKTOP
3 3
S2
S2
22222
S2 S2
S
SS S
S
S
S
2S
S
SS
SS
SS2
S2
2 SS S2 S
S2
S2
S2
S2
S2
S2S
S 2S 2
GFI GFI
GFI
S2
1 1
GFI
LP11-21
LP11-45
LP11-22
LP11-6
LP12-26
LP12-9
LP12-22
LP12-4
LP12-12
LP12-12
LP12-12 LP12-16
LP12-17
LP14-36
LP14-38
LP13-15
LP13-15
LP13-19
LP13-23
LP13-21
LP13-5
LP13-15
LP13-7
LP14-16
LP14-4
LP14-4
LP13-34,36
LP13-40
LP13-38
LP13-42
LP12-15
LP12-23 LP12-19LP12-24
LP12-21
LP13-15
LP11-44
LP11
EWC
+80"+46"
+46" +46"
+46"
+46" +46"
+46" +46"
LP11-46LP11-46
LP11-46
LP11-46
S 2
2LP13-15
+46"
+46"
LP13-15
2+46"
LP11-46
A
A
4" X 4"
CABLE
TRAY
4" X 4"
CABLE
TRAY
4" X 16" CABLE TRAY
4" X 16" CABLE TRAY 4" X 16" CABLE TRAY
GFI GFI
4" X 16" CABLE TRAY
+18" +18"
+42"
+42"
ELP1-28
ELP1-32
ELP1-34
4" X 16" CABLE TRAY
(MOUNT BOTTOM OF TRAY AT 79" AFF)
(TOP OF RACK IS 78.39")
(CURRENT CEILING HEIGHT IS 86")
FIRESEAL FIRESEAL
FIRESEAL
FIRESEAL
FIRESEAL
FIRESEAL
FIRESEAL
ELP1-36
J
RH
LV
BATEX1
+80"
55 EX
EX
5 EX1
J
6 RH
+80"LV
+80"
EX
ELP1-30
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
1ST FLOOR PLAN
SCALE: 1/8" = 1'-0"1
MOUNTING HEIGHTS:
KEYED NOTES:GENERAL NOTES:
MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:
MOUNT SMR AT 32" AFF
MOUNT SMR AT 34" AFF
MOUNT SMR AT 40" AFF
MOUNT SMR AT 42" AFF
MOUNT SMR AT 45 1/2" AFF
MOUNT SMR ABOVE COUNTER/BACKSPLASH
REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING
DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT
AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.
MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT
MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER
FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.
INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO
SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"
AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL
WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN
ROOM.
EXISTING SMR AND RECEPTACLES TO REMAIN. REFEED TO PANEL & CIRCUT
SHOWN.
REMOVE EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW
FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS
REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK
COVERPLATE. INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT
SHOWN) ARE ALSO TO BE REPLACED WITH NEW FIXTURES. ENSURE ALL
FIXTURES ARE CONNECTED AHEAD OF ANY SWITCHING DEVICE.
REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.
INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE
FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST
ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.
FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL
INTERIOR MOUNTED EXIT SIGN.
1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.
2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE WAY,
FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.
3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING
HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.
4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE
AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL FOR
ALL LOCATIONS).
5. CABLE TRAY SHALL BE CENTER SUPPORTED.
6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING
TILE PRIOR TO INSTALLATION OF CABLE TRAY.
7. INSTALLATION OF CABLE TRAY WILL REQUIRE THE CONTRACTOR TO CHANGE ELEVATION
FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED SUCH AS
DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT FIXTURES
MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.
8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR LIGHTING
CABLES.
9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT
HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR IS
20 COVERS.)
10. SEE T001 FOR ADDITIONAL CABLE TRAY NOTES.
KEYED NOTES (CONTINUED):
REMOVE HARD CEILING IN THIS ROOM TO GAIN MORE ACCESS TO CABLE TRAY
FOR INSTALLATION OF CABLES. RELOCATE/REMOVE ITEMS AFTER CEILING IS
REMOVED THAT ARE IN THE PATH OF THE TRAY. FIREPROOF DECK IF REQUIRED.
INSTALL 3/4" FIRE RETARDANT PLYWOOD ON WALL FOR TELEPHONE DEMARK.
REMOVE EXISTING SLEEVES CONTAINING CAT 5 CABLES AND ENLARGE
OPENING FOR CABLE TRAY.
REMOVE WALL EXHAUST FAN, APPROXIMATE SIZE 16"X16", FOR INSTALLATION
OF CABLE TRAY.
REMOVE ROOM EXHAUST FAN AND RELATED CONDUIT AND WIRE FOR
INSTALLATION OF A/C UNIT (BY OTHERS).
OFFICE
OFFICE
OFFICE
CONF RM
OFFICE
OFFICE
OFFICE
OFFICE
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM RM
OFFICE
OFFICE
BREAK
OFFICE
STRG
STRG
DENTAL
LAB
EXAM RM
BREAK RM
RECEP
DARK RM
DENTAL
LAB
UP
DN
UP
DN
UP
DN
STRG
JAN
ROOM
BATH
BATH
BATH
ELEV
ELEV
STAIR
CLO
248A
EXAM RM
CORRIDOR
LP22 LP22A
4" X 12" CABLE TRAY
CORRIDOR
BATH
DENTAL
STAIR
STAIR
LP
LP
CORRIDOR
CORRIDOR
CLOSET
S2
LP21-11
1 S
S
SS 2 2
S
S
S
S
S
S
S
S
S2
SS 2
S
S 2
S21
1 1
1 1 1
S2
S 2
S2
1 1 1
1 1 1
1111 1
1 1
S
S
S
S 2
S2
S
LP21-7
LP21-7
2 LP23-21
LP23-23 LP23-27LP23-25
LP23-29
LP23-26 LP23-28
2SS
SS2
LP23-30
LP21-42
2 LP21-422 LP21-42
LP21-42
S
2 LP22-29GFI
GFI
LP22A-41
S
LP21-13
LP21-19
LP23-14
LP23-16
S
S
S
LP21-9
LP23-18
LP21-272
LP21-2
GFI LP21-22
LP21-5
LP22A-5
2 LP22-17
LP21-7
LP21-7
S
LP23-20
+80" +80"
+46" +46"
+46"+46"
+46"+46"
SS
GFI
LP21-8
+42"
GFI
A A
A
A
A A
104" X 12" CABLE TRAY
FIRESEAL
J
RH
+80"5
EX1
LV
EX
EX1
J
RH
LV
101010
ELP1-1
ELP1-2
SS
S 2
1 111
S 2
S
S S
SS
S S
S LP22-16S 2
LP22-29
LP22-29
S
SS
S
2 LP22-29LP22-24 2 LP22-17
+46"+46"
LP23-17 LP23-19
LP22A-42 +80"
LP22A-6
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
2ND FLOOR PLAN
SCALE: 1/8" = 1'-0"1
MOUNTING HEIGHTS:GENERAL NOTES:
MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:
MOUNT SMR AT 27' AFF
MOUNT SMR AT 45" AFF
MOUNT SMR AT 44" AFF
MOUNT SMR ABOVE COUNTER/BACKSPLASH
KEYED NOTES:
REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING
DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT
AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.
MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT
MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER
FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.
INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO
SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"
AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL
WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN
ROOM.
EXISTING SMR AND RECEPTACLES TO REMAIN. REFEED TO PANEL & CIRCUT
SHOWN.
REMOVE ALL EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW
FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS
REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK
COVERPLATE. INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT
SHOWN) ARE ALSO TO BE REPLACED WITH NEW FIXTURES. ENSURE ALL
FIXTURES ARE CONNECTED AHEAD OF ANY SWITCHING DEVICE.
REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.
INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE
FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST
ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.
FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL
INTERIOR MOUNTED EXIT SIGN.
1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.
2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE WAY,
FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.
3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING
HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.
4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE
AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL FOR
ALL LOCATIONS).
5. CABLE TRAY SHALL BE CENTER SUPPORTED.
6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING
TILE PRIOR TO INSTALLATION OF CABLE TRAY.
7. INSTALLATION OF CABLE TRAY WILL REQUIRE THE CONTRACTOR TO CHANGE
ELEVATION FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED
SUCH AS DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT
FIXTURES MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.
8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR
LIGHTING CABLES.
9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT
HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR
IS 15 COVERS.)
10. SEE T001 FOR ADDITIONAL CABLE TRAY NOTES.
KEYED NOTES (CONTINUED):
INSTALL NEW LIGHTING FIXTURE ON UNDERSIDE OF DECK. CONNECT TO PANEL
AND CIRCUIT SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL
LIGHT SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY
LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH
NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY
SWITCHING DEVICE.
INSTALL NEW LIGHTING FIXTURE ON CEILING. CONNECT TO PANEL AND CIRCUIT
SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL LIGHT
SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY
LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH
NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY
SWITCHING DEVICE.
CONTINUE LIGHTING CIRCUIT UP TO 3RD FLOOR STAIRWAY LIGHTING.
REMOVE ALL EXISTING "JELLY JAR" LIGHTING FIXTURES, WIRING AND
BACKBOXES. PATCH AND PAINT TO MATCH SURROUNDING SURFACES.
WALL MOUNTED TELEDATA CABINET BY IT CONTRACTOR. SEE TELECOM
DRAWINGS.
DN
UP
DN
TRAINING RM
PATIENT RM
PATIENT RM
STATIONERY
BICYCLES
MALE
DUTY RM
OFFICE
FEMALE
DUTY RM
PATIENT RM
JAN
STRG
LINEN
PHYSICAL THERAPY
STRG
ICE RM
OFFICE
STRG
STORAGE
RECEPTION
PHYSICAL
THERAPY
STRG
MEN'S
LOCKER
WOMEN'S
LOCKER
NURSES
STATION
UTILITY RM
UTILITY
RM
STRG
STRG
WOMEN'S
LOCKER RM
MEN'S
LOCKER RM
4" X 12" CABLE TRAYUG1
PD
P1
LP31
ROOM
PATIENT RM
LP32
STAIR
STAIR
STAIR
ELEV
ELEV
ROOM
STRG
ROOM
310A
ROOM
S
LP31-15
1 1 1
1 1
2 41
S 2
S 2
S2 S2
S2S2
1 1 1
1 1
S 2 S 2
S
S
S
S
2S2S
S
S
S
2S
S
S
S 2
S2
S 2
S2 S2
SS 2
S
SS2
SS2
SS2
S2
S2
S2
S2
S
2S
S2 S2
S2
S2
S
2 11
S2
S2S2
S2
S
S
SS SS2 2
SS 2
SS
SS
S
SS2
SS
S
2 2
LP31-24
LP31-27
LP31-29 GFI
LP31-31
GFI
LP31-33
LP31-6
2 LP31-12
LP31-12
LP31-12
2 LP31-12
LP31-12
LP31-16
UG1-20,22
GFI
LP31-20 LP32-42
LP32-23,25
LP31-18 LP32-33
2LP32-38 2LP32-37
LP32-37
LP32-35
LP32-38
LP32-36
LP32-34
LP32-32
LP32-41
LP32-38
LP32-38
GFI
GFI
GFI
GFI
GFI
LP31-21LP31-19LP31-17
LP31-24
GFI
GFI
LP32-40
LP32-31
GFI
GFI
+80" +80" +46"
+46"
GFI
+46" +46"
+46"
LP31-28,42
UG1-24,26
GFI
+40"
GFI
+40"
GFI+40"
GFI
+40"
LP32-2
LP32-2
LP31-7
LP31-7
A A
A
A
A A
FIRESEAL7
8 8
EX5
EX 5EX
1010 1010
GFI
LP32-39
+80"UG1-19
PDP1-30,32
PDP1-30,32
(A/C)
PDP1-34,36
(A/C)
PDP1-38,40 (A/C)
PDP1-38,40
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
3RD FLOOR PLAN
SCALE: 1/8" = 1'-0"1
MOUNTING HEIGHTS:KEYED NOTES:GENERAL NOTES:
MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:
MOUNT SMR AT 24" AFF
MOUNT SMR ABOVE COUNTER/BACKSPLASH
MOUNT SMR AT 32" AFF
MOUNT SMR AT 36" AFF
REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING
DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT
AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.
MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT
MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER
FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.
INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO
SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"
AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL
WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN
ROOM.
EXISTING SMR AND RECEPTACLES TO REMAIN. REFEED TO PANEL & CIRCUT
SHOWN.
REMOVE ALL EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW
FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS
REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK
COVERPLATE. INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT
SHOWN) ARE ALSO TO BE REPLACED WITH NEW FIXTURES. ENSURE ALL
FIXTURES ARE CONNECTED AHEAD OF ANY SWITCHING DEVICE.
REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.
INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE
FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST
ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.
FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL
INTERIOR MOUNTED EXIT SIGN.
1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.
2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE
WAY, FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.
3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING
HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.
4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE
AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL
FOR ALL LOCATIONS).
5. CABLE TRAY SHALL BE CENTER SUPPORTED.
6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING
TILE PRIOR TO INSTALLATION OF CABLE TRAY.
7. INSTALLATION OF CABLE TRAY WILL REQUIRE THE CONTRACTOR TO CHANGE
ELEVATION FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED
SUCH AS DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT
FIXTURES MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.
8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR
LIGHTING CABLES.
9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT
HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR
IS 15 COVERS.)
10. SEE T001 FOR ADDITIONAL CABLE TRAY NOTES.
KEYED NOTES (CONTINUED):
INSTALL NEW LIGHTING FIXTURE ON UNDERSIDE OF DECK. CONNECT TO PANEL
AND CIRCUIT SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL
LIGHT SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY
LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH
NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY
SWITCHING DEVICE.
INSTALL NEW LIGHTING FIXTURE ON WALL AT 96" AFF. CONNECT TO PANEL AND
CIRCUIT SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL LIGHT
SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY
LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH
NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY
SWITCHING DEVICE.
CONTINUE LIGHTING CIRCUIT UP/DOWN TO STAIRWAY LIGHTING.
REMOVE ALL EXISTING "JELLY JAR" LIGHTING FIXTURES, WIRING AND
BACKBOXES. PATCH AND PAINT TO MATCH SURROUNDING SURFACES.
WALL MOUNTED TELEDATA CABINET BY IT CONTRACTOR. SEE TELECOM
DRAWINGS.
STORAGE
MECH RM
MECH RM
WORKOUT RM
WORKOUT RM
STORAGE
STORAGE
STORAGE
PPL-LS LPA1
PPL-RS
PPF
S
S
SSS
S
S
S 2
1 1
LPA1-21
LPA1-19
LPA1-9
LPA1-9
LPA1-9
LPA1-9
LPA1-9
SS
LPA1-9
LPA1-21
2A A A A
EX
4EX6 5 69
LPA1-21
MICHAEL BAKER JR, INC
MOON TOWNSHIP, PA 15108
(412) 269-6300
100 AIRSIDE DRIVE
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
PLAN
NORTH
N
4TH FLOOR PLAN
SCALE: 1/8" = 1'-0"1
MOUNTING HEIGHTS:KEYED NOTES:GENERAL NOTES:
MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:
MOUNT SMR AT 24" AFF
1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.
2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE,
THREE WAY, FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.
3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF
MOUNTING HARDWARE TO ATTACH SMR PER MANUFACTURER'S
RECOMMENDATIONS.
4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW
RECEPTACLE AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE
A/C UNIT. (TYPICAL FOR ALL LOCATIONS).
REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING
DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT
AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.
MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT
MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER
FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.
INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO
SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"
AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL
WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE…