Drawings_HSCGG1-15-B-PFA030_Replace_Circuit_Wiring_Michel_Hall_Project__6005224.pdf

PDF 3 MB Posted

Attached to
REPLACE ELECTRICAL WIRING FOR BRANCH CIRCUITS IN MICHEL HALL USCG ACADEMY NEW LONDON CT PROJECT #6005225
Solicitation number
HSCGG1-15-B-PFA030
Issued by

About this file

DRAWINGS HSCGG1-15-B-PFA030 WIRING FOR BRANCH CIRCUITS IN MICHEL HALL USCG ACADEMY PROJECT 6005224

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BUFFALO

PITTSBURGH

BANGOR

PORTLAND

BURLINGTON

HARTFORD

PROVIDENCE

ALBANY

NEW YORK CITY

PHILADELPHIA

SCRANTON

CONCORD

BOSTON

ME

NHVT

MA

NY

PA

NJ

CT RI

SYRACUSE

ATLANTIC OCEAN

NEW LONDON

U.S. COAST GUARD ACADEMY

R.R. STA.

FRONTAGE

W

ILLIAMS ST.

BR

IG

GS

COLMAN

NORTH

SOUTH

FRONTAGE

Perry Pd.

ST.

AVENUE

MOHEGAN

GOLD STAR MEMORIAL BRIDGE

PIER

STATE

RAILROAD

RAILROAD

WINTHROP COVE

HUNTINGTON ST.

W

ILLIAMS ST.

THAMES RIVER

THAMES RIVER

U.S. COAST GUARD ACADEMY

15 MOHEGAN AVENUE

NEW LONDON, CT

C.G. MEMORIAL

CHAPEL

ROLAND HALL

ATHLETIC FIELD

ATHLETIC FIELD

CULLOCH ST

FARNSW

ORTH AVE

MOHEGAN AVE

CHASE HALL-D

CHASE HALL

PLAZA

DESHON ST

MOHEGAN AVE

WAESCHE

HALL

DIMICK

HALL

SMITH HALL

ONECO AVE

HUNTER LIGGETT DR

C

JOHNSON HALL

TA

MPA

ST

BEAR DR

OFFICERS

QUARTERS

MAIN

GATE SE

NE

CA

D R

WASHINGTON PARADE GROUND

HAMILTON HALL

CHASE HALL-A

A

CHASE HALL-B

A YEATON HALL

SATTERLEE HALL

CAMPBELL DR

O-CLUB

PARCEL 3

THAMES SHIPYARD

ACADEMY

NEW ENGLAND CENTRAL RAILROAD

DESHON ST

GATE

MUNRO HALL

RUNNING TRACK

CREW ROWING

CENTER

SOCCER PRACTICE FIELD

EAGLE DR

HARRIET LN

MCALLISTER HALL

CADET MEMORIAL FIELD

LEAMY HALL

MICHEL HALL

BILLARD

HALL

MAINT.

SHOP

BASEBALL FIELD

PICKERING RD

SA

IL

LO

FT

BOILER

HOUSE BI

BB

S

T

TENNIS

COURTS

PINE HALL

THAMES RIVER

EAGLE

PIER

TENNIS

COURT

TENNIS

COURT

RIVERSIDE PARK

TENNIS

COURTS

VISITOR

CENTER

AMMO

BUNKER

CIEPLIK HALL

SOCCER FIELD

SEAMANSHIP CENTER

JACOB'S ROCK

T-BOAT

PIER

ALUMNI

CENTER

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

WORK AREA

MICHEL HALL

DRAWING INDEX

SHEET

NUMBER

DISCIPLINE

SHEET TITLE

1 OF 28 G001 COVER SHEET

2 OF 28 A100 ARCHITECTURAL BASEMENT PLANS

3 OF 28 A101 ARCHITECTURAL 1ST FLOOR PLAN

4 OF 28 A102 ARCHITECTURAL 2ND FLOOR PLAN

5 OF 28 A103 ARCHITECTURAL 3RD FLOOR PLAN

6 OF 28 A104 ARCHITECTURAL 4TH FLOOR PLAN

7 OF 28 E001 ELECTRICAL NOTES

8 OF 28 E002 ELECTRICAL ABBREVIATIONS AND SYMBOLS

9 OF 28 E100 ELECTRICAL BASEMENT PLANS

10 OF 28 E101 ELECTRICAL 1ST FLOOR PLAN

11 OF 28 E102 ELECTRICAL 2ND FLOOR PLAN

12 OF 28 E103 ELECTRICAL 3RD FLOOR PLAN

13 OF 28 E104 ELECTRICAL 4TH FLOOR PLAN

14 OF 28 E105 ELECTRICAL PANEL SCHEDULES SUB-BASEMENT

15 OF 28 E106 ELECTRICAL PANEL SCHEDULES BASEMENT

16 OF 28 E107 ELECTRICAL PANEL SCHEDULES FIRST FLOOR

17 OF 28 E108 ELECTRICAL PANEL SCHEDULES SECOND FLOOR

18 OF 28 E109 ELECTRICAL PANEL SCHEDULES THIRD FLOOR

19 OF 28 E110 ELECTRICAL PANEL SCHEDULES FOURTH FLOOR

20 OF 28 E111 ELECTRICAL RACEWAY MOUNTING DETAILS

21 OF 28 T001 NOTES, ABBREVIATIONS & SYMBOLS

22 OF 28 T100 TELECOMMUNICATIONS BASEMENT PLANS

23 OF 28 T101 TELECOMMUNICATIONS 1ST FLOOR PLAN

24 OF 28 T102 TELECOMMUNICATIONS 2ND FLOOR PLAN

25 OF 28 T103 TELECOMMUNICATIONS 3RD FLOOR PLAN

26 OF 28 T104 TELECOMMUNICATIONS 4TH FLOOR PLAN

27 OF 28 T105 TELECOMMUNICATIONS DATA/TELE RISER DIAGRAM

28 OF 28 T106 TELECOMMUNICATIONS DATA/TELE SITE PLAN

LOCATION MAP

SCALE: NONE SCALE: NONE

VICINITY MAP

U.S. COAST GUARD ACADEMY

NEW LONDON, CONNECTICUT

REPLACE ELECTRICAL WIRING FOR BRANCH

AT

DETAIL SITE MAP

CIRCUITS IN MICHEL HALL

OFFICE

B24

OFFICE

B25

OFFICE

B21

STRG

B15

WOMENS

LOCKER

RM

B11

OFFICE

B23

RECEP

B22

ELEV

RM

MECH RM

MECH RM

STORAGE

B18

SUPPLY

B17

STRG

B16

LAUNDRY

B09

PIPE RUN

ACCESS TUNNEL

UP

UP

UP

JAN RM

B12

1st FLOOR OUTLINE 1st FLOOR OUTLINE

CORRIDOR

B08

CORRIDOR

B08

WOMEN

B14

ELEC RM

TEL/ELEC/

FIRE PANEL

RM

UP

BACKUP

GENERATOR

RM

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

1 2

2 22

2 2

TYP

C

TYP

TYP

TYP

1 TYP

B B 1

TYP

B

A A

C

TYP TYP

TYP

A

A

A

A

SUB-BASEMENT FLOOR PLAN

SCALE: 1/8" = 1'-0"2

BASEMENT FLOOR PLAN

SCALE: 1/8" = 1'-0"1

KEYNOTES:

1 CMU/CONCRETE WALL

2 GYPSUM DRYWALL WALL

3 PLASTER WALL

4 CERAMIC TILE: HALF WALL HEIGHT

5 CERAMIC TILE: FULL WALL HEIGHT

A 2'x2' ACOUSTICAL LAY IN CEILING TILE

B 2'x4' ACOUSTICAL LAY IN CEILING TILE

C SOLID GYPSUM DRYWALL CEILING

D EXPOSED CEILING

GENERAL NOTES:

1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO

SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL

SURFACES AND THE VARIOUS CEILING MATERIALS IN

EACH SPACE.

2. CONTRACTOR TO REPLACE EXISTING CEILING PANELS

WITH GOVERNMENT FURNISHED CEILING PANELS AS

INDICATED AND EXPRESSED BY THE CONTRACTING

OFFICER REPRESENTATIVE. CONTRACTOR TO PAINT THE

CEILING GRID PRIOR TO INSTALLATION OF NEW PANELS.

COORDINATE WITH CONTRACTING OFFICER

REPRESENTATIVE FOR EXTENT OF CEILING PANEL

INSTALLATION.

D

D

D

UP

DN

UP

DN

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

PHARMACY

URGENT CARE

X-RAY

FILE RM

OFFICE

FILM RM

WOMEN

MEN

OFFICE

OFFICE

OFFICE

EXAM RM

**122**

BREAK RM

WAITING

**126**

STRG

FILE RM

OFFICE

EXAM

110B

OFFICE

110A

BREAK

STRG

STRG

LAB

OXYGEN

STRG

MINOR

SURGERY

EMT

SUPPLY

BIO

STRG

STRG

ROOM

STRG

BATH

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

ROOM

ROOM

RECEPTION

CORRIDOR

CORRIDOR

CORRIDOR

COMMS

COMMS

ROOM

WOMEN

MEN

ROOM

EXAM

WAITING

CORRIDOR

ELEV

ELEV

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

5 TYP 5 TYP

5 TYPA

A A

A

A

A

A A

A

A

A

A

A

A

A

A

A

A

A

C

C

C

TYP

2 TYP

A

2 TYP

A

2 TYP

A

2 TYP

A

2 TYP

A

2 TYP

A

2 TYP

A

1 1 1

1 1 1 1 1 1 2

2 2

2 2 22 22 222

2 2

A

A

A

A

AA

A

AAA

A

A

A A

5 TYP

TYP

3 TYPA

5 TYP

1 1 1 1

3 TYP

TYP

3 TYP

3 TYP

3 TYP

3 TYP

3 TYP

3 TYP

3 TYP 3 TYP

3 TYP

3 TYP

3 TYP

3 TYP

1 1 1 1 1 1

1ST FLOOR PLAN

SCALE: 1/8" = 1'-0"1

KEYNOTES:

1 CMU/CONCRETE WALL

2 GYPSUM DRYWALL WALL

3 PLASTER WALL

4 CERAMIC TILE: HALF WALL HEIGHT

5 CERAMIC TILE: FULL WALL HEIGHT

A 2'x2' ACOUSTICAL LAY IN CEILING TILE

B 2'x4' ACOUSTICAL LAY IN CEILING TILE

C SOLID GYPSUM DRYWALL CEILING

D EXPOSED CEILING

GENERAL NOTES:

1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO

SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL

SURFACES AND THE VARIOUS CEILING MATERIALS IN

EACH SPACE.

2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING

PANELS WITH GOVERNMENT FURNISHED CEILING PANELS

AS INDICATED AND EXPRESSED BY THE CONTRACTING

OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO

PAINT THE CEILING GRID PRIOR TO INSTALLATION OF

NEW PANELS. COORDINATE WITH CONTRACTING OFFICER

REPRESENTATIVE FOR EXTENT OF CEILING PANEL

INSTALLATION.

OFFICE

OFFICE

OFFICE

CONF RM

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM RM

OFFICE

OFFICE

BREAK

OFFICE

STRG

STRG

DENTAL

LAB

EXAM RM

BREAK RM

RECEP

X-RAY RM

DARK RM

DENTAL

LAB

UP

DN

UP

DN

UP

DN

STRG

JAN

ROOM

BATH

BATH

BATH

ELEV

ELEV

STAIR

CLO

248A

EXAM RM

CORRIDOR

CORRIDOR

BATH

DENTAL

STAIR STAIR

CORRIDOR

CORRIDOR

CLOSET

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

3 TYP

5 TYP

3 TYP 3 TYP

TYP

TYP

3 TYP

2 TYP

2 2 TYP

1 TYP

2 TYP 2

3 TYP

12122

A A

A

A

A A A

A

A A A A

A

A A

AAA

A

A

A A

A

A A

A

A

A

A A A

A

A

A

A

A A

A

A

A

A A

A A

22 TYP2 TYP2 TYP2 TYP

2 TYP

5 TYP

2 TYP

2 TYP

4 TYP

2ND FLOOR PLAN

SCALE: 1/8" = 1'-0"1

2 2

3 TYP

3 TYP

3 TYP

KEYNOTES:

1 CMU/CONCRETE WALL

2 GYPSUM DRYWALL WALL

3 PLASTER WALL

4 CERAMIC TILE: HALF WALL HEIGHT

5 CERAMIC TILE: FULL WALL HEIGHT

A 2'x2' ACOUSTICAL LAY IN CEILING TILE

B 2'x4' ACOUSTICAL LAY IN CEILING TILE

C SOLID GYPSUM DRYWALL CEILING

D EXPOSED CEILING

GENERAL NOTES:

1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO

SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL

SURFACES AND THE VARIOUS CEILING MATERIALS IN

EACH SPACE.

2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING

PANELS WITH GOVERNMENT FURNISHED CEILING PANELS

AS INDICATED AND EXPRESSED BY THE CONTRACTING

OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO

PAINT THE CEILING GRID PRIOR TO INSTALLATION OF

NEW PANELS. COORDINATE WITH CONTRACTING OFFICER

DN

DN

UP

DN

TRAINING RM

PATIENT RM

PATIENT RM

STATIONERY

BICYCLES

MALE

DUTY RM

OFFICE

FEMALE

DUTY RM

PATIENT RM

JAN

STRG

LINEN

PHYSICAL THERAPY

STRG

ICE RM

OFFICE

STRG

STORAGE

RECEPTION

PHYSICAL

THERAPY

STRG

MEN'S

LOCKER

WOMEN'S

LOCKER

NURSES

STATION

UTILITY RM

UTILITY

RM

STRG

STRG

WOMEN'S

LOCKER RM

MEN'S

LOCKER RM

ROOM

PATIENT RM

STAIR

STAIR

STAIR

ELEV

ELEV

ROOM

STRG

ROOM

310A

ROOM

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

C

ABB

A

3RD FLOOR PLAN

SCALE: 1/8" = 1'-0"1

TYP

4 TYP

5 TYP

1 TYP

A A

A

C

1 TYP

4 TYP

4 TYP

B

C

5 TYP

5 TYP

5 TYP

3 3

3 TYP

A A

B B

B B

B

B

B

B

5 TYP

A

3 TYP

5 TYP

C

5 TYP

C

3 TYP

A

3 TYP

5 TYP

3 TYP

C

3 TYP

1A

TYP

C

5 TYP 5 TYP

CC

C

3 TYP

4 TYP

C

3 TYP

1 TYP

5 TYP

5 TYP

A A

A

12 2

C

KEYNOTES:

1 CMU/CONCRETE WALL

2 GYPSUM DRYWALL WALL

3 PLASTER WALL

4 CERAMIC TILE: HALF WALL HEIGHT

5 CERAMIC TILE: FULL WALL HEIGHT

A 2'x2' ACOUSTICAL LAY IN CEILING TILE

B 2'x4' ACOUSTICAL LAY IN CEILING TILE

C SOLID GYPSUM DRYWALL CEILING

D EXPOSED CEILING

GENERAL NOTES:

1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO

SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL

SURFACES AND THE VARIOUS CEILING MATERIALS IN

EACH SPACE.

2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING

PANELS WITH GOVERNMENT FURNISHED CEILING PANELS

AS INDICATED AND EXPRESSED BY THE CONTRACTING

OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO

PAINT THE CEILING GRID PRIOR TO INSTALLATION OF

NEW PANELS. COORDINATE WITH CONTRACTING OFFICER

STORAGE

MECH RM

MECH RM

WORKOUT RM

WORKOUT RM

STORAGE

STORAGE

STORAGE

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

2 TYP

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

C

2 TYPC

2 TYPC

4TH FLOOR PLAN

SCALE: 1/8" = 1'-0"1

KEYNOTES:

1 CMU/CONCRETE WALL

2 GYPSUM DRYWALL WALL

3 PLASTER WALL

4 CERAMIC TILE: HALF WALL HEIGHT

5 CERAMIC TILE: FULL WALL HEIGHT

A 2'x2' ACOUSTICAL LAY IN CEILING TILE

B 2'x4' ACOUSTICAL LAY IN CEILING TILE

C SOLID GYPSUM DRYWALL CEILING

D EXPOSED CEILING

D

D

GENERAL NOTES:

1. THE INTENT OF THESE ARCHITECTURAL DRAWINGS IS TO

SHOW THE VARIOUS MATERIALS OF THE INTERIOR WALL

SURFACES AND THE VARIOUS CEILING MATERIALS IN

EACH SPACE.

2. GENERAL CONTRACTOR TO REPLACE EXISTING CEILING

PANELS WITH GOVERNMENT FURNISHED CEILING PANELS

AS INDICATED AND EXPRESSED BY THE CONTRACTING

OFFICER REPRESENTATIVE. GENERAL CONTRACTOR TO

PAINT THE CEILING GRID PRIOR TO INSTALLATION OF

NEW PANELS. COORDINATE WITH CONTRACTING OFFICER

GENERAL NOTES AND CONDITIONS: (CONT.)

3. THIS INSTALLATION WILL CONFORM TO ALL CODES AND THE REQUIREMENTS OF

FEDERAL, STATE, AND LOCAL REGULATORY AGENCIES HAVING JURISDICTION. IN

PARTICULAR, THE WORK WILL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE

INTERNATIONAL BUILDING CODE, INCLUDING ALL OF ITS APPLICABLE SUBCODES AND

AMENDMENTS, INCLUDING, BUT NOT LIMITED TO THE FOLLOWING:

BUILDING: INTERNATIONAL BUILDING CODE - 2009

INTERNATIONAL EXISTING BUILDING CODE - 2009

LIFE SAFETY: NFPA 101 - 2009

ELECTRICAL: NATIONAL ELECTRIC CODE - NFPA 70 - 2011

4. ALL WORK WILL BE LAWFULLY EXECUTED IN A NEAT AND WORKMANLIKE MANNER AND

WILL BE COMPLETED IN ACCORDANCE WITH THE GOVERNING CODES (ABOVE), INDUSTRY

STANDARDS, AND IN CONFORMANCE WITH THE MANUFACTURERS RECOMMENDATIONS

AND REQUIREMENTS.

5. WORK UNDER THIS CONTRACT SHALL CONSIST OF THE CONTRACTOR PROVIDING ALL

LABOR, MATERIALS, AND SERVICES, INCLUDING WORK NOT SPECIFICALLY SHOWN BUT

REASONABLY IMPLIED. THIS SHALL INCLUDE CUTTING, PATCHING AND RESTORATION OF

EXISTING SURFACES DAMAGED DURING THE CONSTRUCTION. CONTRACTOR SHALL

ALSO PROVIDE ALL EQUIPMENT SHOWN OR SPECIFIED OR AN APPROVED EQUIVALENT.

SUBSTITUTED EQUIPMENT OR MATERIALS SHALL NOT BE INSTALLED UNTIL GIVEN

WRITTEN APPROVAL BY THE CGA/AGENT.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR COSTS INCURRED FOR NONCOMPLIANCE

WITH THESE CONTRACT DOCUMENTS. CONTRACTOR WILL NOT BE ALLOWED CHANGE

ORDERS FOR PROBLEMS ARISING FROM NEGLECT OF PROVISIONS INCLUDED IN THESE

CONDITIONS.

7. MAINTAIN ORDERLY HOUSEKEEPING DURING CONSTRUCTION, AND UPON SUBSTANTIAL

COMPLETION PERFORM FINAL CLEANUP. REMOVE CONSTRUCTION RUBBISH,

SCAFFOLDING, EQUIPMENT, TEMPORARY PROTECTION, TEMPORARY FIELD

STRUCTURES, AND OTHER MATERIALS OR EQUIPMENT THAT WAS REQUIRED IN

CONNECTION WITH THE CONSTRUCTION, BUT NOT A PERMANENT PART THEREOF.

8. THOSE PERFORMING WORK AS A CONTRACTOR MUST EXAMINE SUBSTRATES AND

CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED AND NOTIFY THE

CONTRACTOR IN WRITING, OF CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY

COMPLETION OF THE WORK. COMMENCEMENT OF WORK BY A TRADE ON A SURFACE OR

CONSTRUCTION SHALL IMPLY ACCEPTANCE OF SUCH SURFACE OR CONSTRUCTION. DO

NOT PROCEED WITH INSTALLATION UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN

CORRECTED.

9. THE CONTRACTOR SHALL SECURE ALL PERMITS AND APPLICATIONS AND PAY ANY AND

ALL FEES AS REQUIRED. THE CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES AND

CERTIFICATES OF INSPECTION REQUIRED BY THE AUTHORITIES HAVING JURISDICTION.

DELIVER ALL PERMITS, CERTIFICATES AND APPROVALS TO THE CGA/AGENT PRIOR TO

FINAL ACCEPTANCE OF THE WORK. THE CONTRACTOR MUST FILE NECESSARY

DRAWINGS, PREPARE DOCUMENTS AND MAKE APPLICATIONS FOR EACH REQUIRE

PERMIT AND INSPECTION, PRIOR TO COMMENCING WORK TO AVOID DELAYS DURING

CONSTRUCTION.

10. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND MANUFACTURERS DATA SHEETS ON

ALL EQUIPMENT AND MATERIALS SPECIFIED ON DRAWINGS FOR APPROVAL BY

CGA/AGENT. THESE DRAWINGS OR SHEETS SHALL CONTAIN ALL NECESSARY DATA, I.E.,

MANUFACTURER, CATALOG NUMBER, SIZE, DIMENSIONS, CAPACITY, WIRING DETAILS

AND ALL OTHER ENGINEERING DATA AND DETAILS NECESSARY FOR COMPLETE CLARITY

AND INSTALLATION.

11. THE CONTRACTOR SHALL KEEP ONE SET OF THE LATEST ISSUE OF DRAWINGS WHICH

SHALL REFLECT THE ACTUAL INSTALLED CONDITIONS AND CONNECTIONS OF ALL

EQUIPMENT AND DEVICES. THE CONTRACTOR SHALL PROVIDE COPIES OF ALL

MAINTENANCE INFORMATION AND INSTRUCTIONS RECEIVED WITH EQUIPMENT AND

SYSTEMS. ALL "AS-BUILT" DRAWINGS SHALL BE MARKED-UP "LEGIBLY" WITHOUT

INTERPRETATION REQUIRED. CONTRACTOR IS TO PROVIDE ELECTRONIC COPIES (CAD

2009) OF AS-BUILT DRAWINGS AS WELL AS HARD COPIES. MISCELLANEOUS INFORMATION

SHALL BE GIVEN TO THE CGA/AGENT AND ENGINEER AT COMPLETION OF WORK. THE

CONTRACTOR SHALL GUARANTEE ALL MATERIAL AND LABOR TO BE FREE FROM

DEFECTS FOR A ONE YEAR PERIOD FROM THE TIME OF CGA/AGENT ACCEPTANCE. ANY

DEFECTS OCCURRING DURING THIS PERIOD SHALL BE CORRECTED BY THE

CONTRACTOR AT NO ADDITIONAL COST TO THE CGA/AGENT.

12. ALL POWER OUTAGES AND DISRUPTIONS TO POWER AT THE CGA WILL BE LIMITED TO

WEEKENDS, AFTER HOURS AND SCHEDULED HOLIDAYS. REFER TO SPECIFICATIONS FOR

ACCEPTABLE DATES FOR POWER DISRUPTIONS. DO NOT PROCEED WITH POWER

OUTAGES AND DISRUPTIONS WITHOUT APPROVAL FROM THE CGA/AGENT.

13. THE CONTRACTOR, AS PART OF MAINTAINING "AS BUILT" DRAWINGS, SHALL UPDATE ALL

PANELBOARD DIRECTORIES TO REFLECT ALL THE CIRCUITING AT THE CONCLUSION OF

THE PROJECT. CONTRACTOR TO DETERMINE AND LABEL USES OF ALL CIRCUITS.

CIRCUITS LABELED "EXISTING CIRCUIT" AND REMAINING ACTIVE WILL NOT BE

ACCEPTABLE.

GENERAL ELECTRICAL NOTES (CONT.):

17. PANEL COMPARTMENT DESIGNATIONS ARE AS INDICATED BELOW:

17.1 BLANK- NOT INTENDED FOR USE, COVERPLATE ONLY.

17.2 SPACE- CONTAINS NECESSARY BUS AND HARDWARE FOR FUTURE

ADDITION OF BREAKERS OR STARTERS WITHIN RANGE SHOWN.

17.3. SPARE- CONTAINS A COMPLETE BREAKER OR STARTER INSTALLED, SIZE

AS INDICATED, AVAILABLE FOR FUTURE USE.

18. ALL TEMPORARY WIRING, LIGHTING AND POWER CIRCUITS AND DEVICES SHALL BE

INSTALLED TO MEET THE LATEST REQUIREMENTS OF THE NATIONAL ELECTRICAL

CODE, LOCAL, STATE AND FEDERAL REQUIREMENTS FOR SUCH TEMPORARY

INSTALLATION.

19. THE CONTRACTOR SHALL ENSURE THAT RECEPTACLES USED FOR HAND TOOLS AND

OTHER MISCELLANEOUS EQUIPMENT SHALL BE INSTALLED WITH GROUND FAULT

INTERRUPTER OR OTHER APPROVED AND RECOGNIZED INTERRUPTING SENSORS.

20. THE COMPLETE INSTALLATION SHALL BE TESTED AT COMPLETION OF WORK, TO BE

FREE OF GROUNDS AND SHORT CIRCUITS CONDITIONS.

21. CONTRACTOR SHALL COORDINATE AND SCHEDULE ALL WORK AND SHUTDOWNS OF

EQUIPMENT WITH FACILITY.

22. EXCAVATION FOR UNDERSLAB OR UNDERGROUND INSTALLATION OF CONDUITS

SHALL BE APPROACHED WITH EXTREME CAUTION SO AS NOT TO DAMAGE EXISTING

UNDERGROUND PIPING, WIRING AND CONDUITS.

GENERAL NOTES AND CONDITIONS:

1. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE

AVAILABLE BUILDING DRAWINGS, ARCHITECTURAL BACKGROUNDS PROVIDED BY THE

CGA AND FIELD SURVEY INFORMATION COMPILED BY THE ENGINEERING DESIGN

TEAM FOR THE PURPOSE OF ENGINEERING DESIGN. EXISTING CONDITIONS ARE

SHOWN AS ACCURATELY AS POSSIBLE. THERE IS THE POSSIBILITY THAT CONDITIONS

SHOWN DO NOT DEPICT ALL DEVICES OR CIRCUITS FEEDING THE DEVICES OR ARE

NOT EXACTLY AS EXISTING. CONTRACTOR SHALL VERIFY ALL DIMENSIONS,

ELEVATIONS, LOCATIONS, SIZES AND CONDITIONS AT THE SITE AND REPORT ANY

DISCREPANCIES TO THE CGA/AGENT PRIOR TO BEGINNING INSTALLATION OR

FABRICATION WORK.

1.1. DO NOT SCALE DRAWINGS.

1.2. SHOULD IT APPEAR THAT THE WORK INTENDED TO BE DESCRIBED OR

RELATED WORK ARE NOT SUFFICIENTLY DETAILED OR EXPLAINED ON THE

DRAWINGS, OR IN THE SPECIFICATIONS, CONSULT THE ENGINEER FOR

NECESSARY CLARIFICATIONS, AND CONFORM TO THOSE CLARIFICATIONS

INSOFAR AS THEY ARE CONSISTENT WITH THE ORIGINAL DRAWINGS AND

SPECIFICATIONS. IN NO CASE SHALL WORK PROCEED IN UNCERTAINTY.

1.3. EQUIPMENT ARRANGEMENTS ARE DESIGNED TO SHOW PREFERRED

CONFIGURATIONS TO SUIT KNOWN CONDITIONS. ACTUAL INSTALLATION BY

CONTRACTOR MAY BE ALTERED AS REQUIRED TO SUIT FIELD CONDITIONS

ENCOUNTERED DURING CONSTRUCTION WITHOUT COMPROMISING THE

INTENT OF THE ORIGINAL DESIGN.

1.4. THE CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND

CONDITIONS AT SITE PRIOR TO STARTING WORK.

1.5. AT PROJECT COMPLETION ALL DEVICES, I.E., RECEPTACLES, LIGHTING AND

EQUIPMENT NOW POWERED SHALL BE FUNCTIONING AS IT WAS PRIOR TO THE

START OF THE PROJECT. ANY DEVICES NOT FUNCTIONING PRIOR TO THE

START OF THE PROJECT SHALL BE INVESTIGATED BY THE CONTRACTOR AND

BROUGHT TO THE ATTENTION OF THE CGA/AGENT FOR DISPOSITION. ANY

ITEMS NOT ADDRESSED PRIOR TO STARTING THE PROJECT WILL NOT BE

HONORED AFTER THE PROJECT STARTS AND MUST BE MADE TO FUNCTION AS

DESIGNED AT THE CONTRACTOR'S EXPENSE.

ELECTRICAL DEMOLITION NOTES:

1. THE CONTRACTOR (EC) SHALL INCLUDE IN HIS BID ALL COSTS ASSOCIATED WITH

RELOCATION AND REMOVAL OF ELECTRICAL WORK AS DESCRIBED IN THE DRAWINGS

AND SPECIFICATIONS.

2. NOTE THAT THE FACILITY WILL BE FULLY OPERATIONAL DURING THE COURSE OF

THIS PROJECT.

2.1. THE CONTRACTOR IS TO COORDINATE ALL OF THE DEMOLITION WORK WITH

THE FACILITY PERSONNEL TO MINIMIZE DISTURBING THE OPERATING

EQUIPMENT, WIRING AND SYSTEMS.

2.2. THE CONTRACTOR SHALL PERFORM REMOVAL AND DEMOLITION WORK WITH

MINIMAL INTERFERENCE WITH EXISTING SYSTEMS.

3. DEMOLITION AND REMOVAL OF WORK SHALL BE PERFORMED IN A NEAT AND

PROFESSIONAL MANNER. THE CONTRACTOR SHALL RESTORE, PATCH, PAINT, ETC.,

ANY INTERIOR/EXTERIOR BUILDING SURFACE TO ITS ORIGINAL CONDITION.

4. REFER TO ELECTRICAL PLANS FOR NEW EQUIPMENT LAYOUT AND EXTENT OF

EQUIPMENT BEING REPLACED, RELOCATED, OR REMOVED. PATCH AND PAINT (TO

MATCH SURROUNDING CONDITIONS) ALL OPENINGS CREATED BY THIS DEMOLITION.

5. EXISTING CONDITIONS, EQUIPMENT, MATERIALS & SIZES ARE SHOWN FOR

REFERENCE ONLY. VERIFY EXISTING CONDITIONS AND BRING ANY DISCREPANCIES

TO THE CONTRACTING OFFICER'S ATTENTION IN WRITING PRIOR TO BID SUBMISSION.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELECTRICAL DEMOLITION WORK FOR

THIS PROJECT WHETHER OR NOT SPECIFICALLY INDICATED ON THIS OR OTHER

DEMOLITION PLANS. THIS WORK SHALL INCLUDE BUT IS NOT LIMITED TO THE

DISCONNECTION, REMOVAL AND DISPOSAL OF; PANELBOARDS, DISCONNECT

SWITCHES, RECEPTACLES, JUNCTION BOXES, WIRE, CABLE, CONDUIT, MOUNTING

HARDWARE STRAPS OR CABLES, ELECTRICAL SERVICES ETC. PER THE SCOPE OF

WORK FOR THIS PROJECT.

7. THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL OUTLETS, SWITCHES, ETC.,

INCLUDING ASSOCIATED WIRING, CONDUITS, COVERS, BOXES, ETC.. WHERE THE

REMOVAL OF THESE ITEMS DISRUPTS EXISTING WIRING THAT IS TO REMAIN, THE

CONTRACTOR SHALL INSTALL IN THE CEILING SPACE; JUNCTION BOXES AND OTHER

DEVICES AND PROVIDE BYPASS CONNECTIONS NECESSARY TO MAKE CIRCUITS

AFFECTED CONTINUOUS AND READY FOR OPERATION. OTHERWISE, WIRING SHALL

BE REMOVED BACK TO THE NEAREST ELECTRICAL JUNCTION BOX THAT IS TO REMAIN

OR TO THE SOURCE PANELBOARD.

8. ALL WORK MUST BE SCHEDULED AND PERFORMED AS NOT TO INTERRUPT NORMAL

OPERATIONS. REMOVAL OF ITEMS THAT WILL CAUSE ANY TYPE OF TEMPORARY

SHUTDOWN SHALL BE PERFORMED DURING OFF-PEAK HOURS.

9. CONTRACTOR SHALL THEN DEVELOP PHASING SCHEDULING AND SEQUENCING WITH

FINAL REVIEW AND APPROVAL BY THE CONTRACTING OFFICER. CONTRACTOR SHALL

CLOSELY FOLLOW THE DEMOLITION AND PHASING SCHEDULE AND PROCEED IN THE

SPECIFIED SEQUENCE. REFER TO SPECIFICATIONS FOR GENERAL PHASING

SEQUENCE AND REQUIREMENTS.

10. THE SHUTDOWN OF EXISTING BUILDING ELECTRICAL SERVICES SHALL BE

COORDINATED WITH THE CONTRACTING OFFICER REPRESENTATIVE (COR). MAKE

APPROPRIATE ARRANGEMENTS AT LEAST 5 BUSINESS DAYS PRIOR TO A SHUTDOWN.

11. THE CONTRACTOR SHALL REMOVE AND/OR RELOCATE ALL EXISTING ELECTRICAL

WORK WHICH INTERFERES WITH THE NEW ELECTRICAL LAYOUTS. ALL SYSTEMS

WHICH ARE NO LONGER REQUIRED TO FUNCTION SHALL BE DE-ENERGIZED AND

DISCONNECTED AT THE POWER SUPPLY SOURCE.

12. CONTRACTOR SHALL PROVIDE AND MAINTAIN ANY CONNECTIONS / DISCONNECTIONS

AS NEEDED TO ENSURE ADEQUATE SAFETY AND PROTECTION OF ALL PERSONNEL

AND EQUIPMENT.

13. ALL ELECTRICAL PANELS SHALL BE MAINTAINED AS WORKING PANELS THROUGHOUT

CONSTRUCTION AND WILL CONTINUE TO MAINTAIN CIRCUITS FOR EXISTING LIGHTING

OR EQUIPMENT TO REMAIN. PROVIDE AS NECESSARY TEMPORARY LIGHTING AND

ELECTRICAL FEEDS TO ANY DEVICES THAT MAY BE REQUIRED FOR UNINTERRUPTED

USE. PROVIDE TEMPORARY CONNECTIONS FOR RELOCATED EQUIPMENT DURING

CONSTRUCTION.

14. CONTRACTOR SHALL ENSURE THAT ANY DEVICES AND/OR FIXTURES LOCATED

OUTSIDE OF DEMOLITION WORK AREA ARE NOT AFFECTED BY REMOVAL OF WIRING

AND/OR CIRCUITING. WIRING/CONDUIT SHALL BE LEFT IN A SAFE CONDITION,

IDENTIFIED ON THE PANEL SCHEDULE, AND EXTENDED AS REQUIRED TO MAINTAIN

CIRCUIT CONTINUITY, INCLUDING ALL APPLICABLE CONTROLS.

15. PORTIONS OF FEEDER RUNS THAT SHALL BE REMOVED OR ABANDONED AS A

RESULT OF DEMOLITION WORK, BUT WHICH ARE REQUIRED TO REMAIN ENERGIZED,

SHALL BE CUT AT CONVENIENT LOCATIONS, REROUTED AND RECONNECTED.

16. EXISTING RACEWAYS THAT ARE NOT BEING REUSED SHALL BE REMOVED BACK TO

THE NEAREST JUNCTION OR PULLBOX, AND THE OPENINGS BLANKED. ANY CONDUITS

PENETRATING MASONRY SURFACES SHALL BE CUT INTO SURFACE, PATCHED, AND

PAINTED TO MATCH SURROUNDINGS.

17. DISCONNECT, RELOCATE OR REMOVE ELECTRICAL INSTALLATIONS AND EQUIPMENT

AS INDICATED BY PLANS AND AS REQUIRED BY CHANGES IN CONSTRUCTION. WHERE

EXISTING ELECTRICAL INSTALLATIONS INTERFERE WITH NEW WORK AND WHERE

SUCH INSTALLATIONS ARE TO REMAIN IN USE, THE NEW INSTALLATIONS SHALL BE

RELOCATED AND/OR RECONNECTED TO COORDINATE WITH THE WORK INDICATED

ON THE CONTRACT DRAWINGS. DETERMINE AND COORDINATE ALL EQUIPMENT

LOCATIONS PRIOR TO INITIAL ROUGH-IN.

ELECTRICAL DEMOLITION NOTES (CONT.):

18. DISCONNECT AND RELOCATE/RECONNECT ANY ELECTRICAL LINES, BRANCH CIRCUITS,

DEVICES, ETC. AND REPAIR PULL BOXES THAT MAY BE DISTURBED DURING THIS

RENOVATION. UNLESS NOTED OTHERWISE, ALL EXISTING ELECTRICAL WORK WHICH WILL

NOT BE RENDERED OBSOLETE AND WHICH MAY BE DISTURBED DUE TO ANY CHANGES

REQUIRED UNDER THE CONTRACT, SHALL BE RESTORED TO ITS ORIGINAL OPERATING

CONDITION AT NO COST TO THE GOVERNMENT. IF ANY EQUIPMENT TO REMAIN IS

DAMAGED DURING CONSTRUCTION, IT SHALL BE REPLACED WITH NEW (WITH NO COST

APPLIED TO THE GOVERNMENT).

19. FOR EXISTING PANELS MODIFIED AS PART OF THIS PROJECT, E.C. SHALL TEST AND KEEP

ALL EXISTING WORKING CIRCUIT BREAKERS AND SHALL USE THEM FOR NEW EQUIPMENT,

DEVICES, LIGHTING, AND/OR SPARES. E.C. SHALL REPLACE NON-WORKING BREAKERS

WITH NEW "IN KIND" BREAKERS. PROVIDE BLANK COVERS/COVERPLATES FOR ALL

EXPOSED CIRCUIT BREAKER SPACES (THOSE WITHOUT INSTALLED CIRCUIT BREAKERS;

EXPOSED BUS BARS) FOR PERSONNEL PROTECTION.

20. AS DIRECTED BY THE CGA/AGENT, ALL EXISTING EQUIPMENT AND MATERIAL IN USABLE

CONDITION THAT IS REMOVED SHALL REMAIN THE PROPERTY OF THE CGA/AGENT, OR

HANDLED AS INSTRUCTED BY THE CGA/AGENT, BE DISPOSED OF BY THE CONTRACTOR.

ALL MATERIALS DEEMED FOR REMOVAL SHALL BE RECYCLED WHENEVER POSSIBLE.

21. EXISTING PANELBOARD DIRECTORIES SHALL BE REPLACED WITH NEW "TYPED"

DIRECTORIES, TO ACCURATELY REFLECT EXISTING CONDITIONS. SPARE CIRCUIT

BREAKERS SHALL BE IDENTIFIED, LABELED AS SUCH. LEAVE "SPARE" CIRCUIT BREAKERS

IN THE 'OPEN' POSITION.

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL BE COORDINATED WITH THE CGA/AGENT AND ALL

OTHER DISCIPLINES INVOLVED IN THIS PROJECT.

2. THE CONDUITS, CABLE TRAY AND SURFACE MOUNTED RACEWAYS SHOWN ON THESE

DRAWINGS ARE DIAGRAMMATIC IN NATURE, THEY SHOW THE GENERAL

ROUTING/ARRANGEMENT AND SIZE OF THE CONDUITS. THEY ARE NOT INTENDED TO

SHOW EVERY OFFSET OR INTERFERENCE THAT MAY BE ENCOUNTERED.

CONTRACTOR IS RESPONSIBLE FOR ROUTING ALL CONDUIT AND TRAY IN THE MOST

EFFICIENT MANNER IN ACCORDANCE WITH PROJECT SPECIFICATIONS.

3. ALL CONTRACTOR SUPPLIED MATERIALS SHALL BE NEW AND UL APPROVED (OR

APPROVED BY ANOTHER NATIONALLY RECOGNIZED ORGANIZATION).

4. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER,

RECTILINEAR TO BUILDING STRUCTURE. HORIZONTAL OR CROSS RUNS IN

PARTITIONS AND WALLS NOT PERMITTED.

5. ALL WIRING SHALL BE RUN CONCEALED IN CONDUIT UNLESS SPECIFIED OTHERWISE.

6. SECURE ALL SUPPORTS TO BUILDING STRUCTURE BY STEEL FOR VERTICAL

SUPPORT AND BY MEANS OF TOGGLE BOLTS ON HOLLOW MASONRY UNITS,

EXPANSION SHIELDS IN CONCRETE OR BRICK. MACHINE SCREWS ON METAL

SURFACE, AND WOOD SCREWS ON WOOD CONSTRUCTION. NAILS, RAWL OR WOOD

PLUGS NOT PERMITTED. SUPPORT HORIZONTAL RUNS OF METALLIC CONDUITS NOT

MORE THAN 10 FT. APART. SUPPORT RACEWAY RISERS AT EACH FLOOR LEVEL. RUN

EXPOSED RACEWAYS PARALLEL WITH OR AT RIGHT ANGLES TO WALLS.

7. ALL UNDERGROUND CONDUITS SHALL BE SEALED TO PREVENT THE ENTRY OF

WATER OR GASES.

8. CUT STEEL CONDUIT ENDS SQUARE, REAM SMOOTH, PAINT MALE THREADS OF FIELD

THREADED CONDUIT WITH GRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH

CONDUIT COUPLINGS.

9. ALL WIRING SHALL BE SOLID COPPER CONDUCTOR UNLESS OTHERWISE NOTED.

REFERENCE SPECIFICATIONS FOR MORE INFORMATION.

10. GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL

CODE REGARDING ELECTRODE, GROUNDING AND BONDING REQUIREMENTS FOR

SERVICE, EQUIPMENT AND ENCLOSURES. ALL EQUIPMENT SHALL BE PROVIDED WITH

A SEPARATE GROUNDING CONDUCTOR.

11. LEAVE WIRE SUFFICIENTLY LONG TO PERMIT MAKING FINAL CONNECTIONS AT

DEVICES.

12. WIRE COLOR CODING: PER CODE. WHERE COLOR-CODED CABLE IS NOT AVAILABLE,

CERTIFY IN WRITING AND REQUEST PERMISSION FOR OVERLAP COLOR TAPING OF

CONDUCTORS (MINIMUM LENGTH 6") IN ACCESSIBLE LOCATIONS. COLOR CODING,

ONCE SELECTED, MUST BE USED CONSISTENTLY FOR THE ENTIRE PROJECT.

13. PULL NO THERMOPLASTIC WIRES AT TEMPERATURES LOWER THAN 32°F. PROVIDE

CABLE SUPPORTS FOR WIRE IN RISER CONDUITS AS REQUIRED BY CODE.

14. PROVIDE PULL BOXES AS INDICATED AND WHEREVER NECESSARY TO FACILITATE

PULLING OF WIRE AND COORDINATE LOCATIONS WITH OTHER TRADES.

15. JUNCTION AND PULL BOXES: LOCATE GENERALLY NOT EXPOSED IN FINISHED

SPACES. WHERE NECESSARY, REROUTE CONDUITS OR MAKE OTHER

ARRANGEMENTS FOR CONCEALMENT. COVERS OF JUNCTION AND PULL BOXES

SHALL BE ACCESSIBLE.

16. SUPPORT JUNCTION AND PULL BOXES INDEPENDENTLY TO BUILDING STRUCTURE

WITH NO WEIGHT BEARING ON CONDUITS.

2. THE CONTRACTOR WILL BE RESPONSIBLE FOR ENSURING THAT ALL RULES AND

REGULATIONS, INCLUDING THOSE WHICH MAY BE ISSUED BY THE CGA/AGENT, ARE

BEING OBSERVED, PARTICULARLY WORKPLACE SAFETY AND THE CONDUCT OF ALL

THOSE EMPLOYED DIRECTLY AND INDIRECTLY BY HIM ON THE PREMISES, AND THE

CGA/AGENT'S EMPLOYEES WHO MAY BE IMPACTED OR AFFECTED BY CONSTRUCTION

ACTIVITIES. THE CONTRACTOR WILL INSTALL SIGNAGE, BARRIERS, AND OTHER

MEANS TO PROVIDE WARNING AND PERSONNEL SAFETY. PLACEMENT OF THESE

ITEMS WILL BE COORDINATED WITH THE CGA AND HIS ONGOING OPERATIONS AND

WILL PROMPTLY BE REVISED WHEN WORK IN A PARTICULAR AREA HAS BEEN

COMPLETED.

2.1. DURING PERFORMANCE OF WORK, THE CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVISION AND MAINTENANCE OF WARNING SIGNS, LIGHT

SIGNAL DEVICES, GUARD LIGHTS, BARRICADES, GUARD RAILS, FENCES AND

OTHER DEVICES, APPROPRIATELY LOCATED ON AND AROUND THE JOB SITE

WHICH GIVE PROPER AND UNDERSTANDABLE WARNING TO PERSONS WITH

REGARD TO HAZARDOUS CONDITIONS, EQUIPMENT AND OPERATIONS BEING

PERFORMED IN CONJUNCTION WITH THE WORK

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

ELECTRICAL SYMBOLS

SYMBOL LIST SHOWN IS FOR GENERAL REFERENCE ONLY. THE

PRESENCE OF A SYMBOL DOES NOT IMPLY ITS USE ON THIS

PROJECT. REFER TO THE DRAWINGS FOR SPECIFIC SYMBOLS USED.

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT

INTERRUPTER & "IN-USE" RATED WEATHERPROOF COVER.

1PH SINGLE-PHASE

1P SINGLE POLE

3PH THREE-PHASE

4W FOUR-WIRE

AC ALTERNATING CURRENT OR

ARMORED CABLE

AF AMPERE FRAME OR AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMP AMPERE

AT AMPERE TRIP

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CD CONSTRUCTION DOCUMENTS

CGA COAST GUARD ACADEMY

CKT CIRCUIT

CLG CEILING

CL&P CONNECTICUT LIGHT & POWER

COR CONTRACTING OFFICER

REPRESENTATIVE

DEMARC DEMARCATION POINT

DEMO DEMOLITION

DISC DISCONNECT

DS DISCONNECT SWITCH

DWG DRAWING

DWM DIGITAL WATT METER

ELEC ELECTRIC OR ELECTRICAL

EMT ELECTRICAL METALLIC TUBING

EX EXISTING

G GROUND

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

I.E. THAT IS

IMC INTERMEDIATE METAL CONDUIT

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATT

LV LOW VOLTAGE

MC METAL-CLAD

MLO MAIN LUGS ONLY

MTD MOUNTED

MTG MOUNTING

MTRG METERING

(N) NEW EQUIPMENT

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

N NEUTRAL

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

PH PHASE

PVC POLYVINYL CHLORIDE

(PLASTIC)

RGS RIGID GALVANIZED STEEL

SMR SURFACE MOUNTED RACEWAY

TTB TELEPHONE TERMINAL BOARD

TYP TYPICAL

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

V VOLT

VA VOLT AMPERE

WP WEATHERPROOF

W/ WITH

XFMR TRANSFORMER

ELECTRICAL ABBREVIATIONS

RECEPTACLE, QUAD

SURFACE METAL RACEWAY, MOUNTED HORIZONTALLY.

SURFACE METAL RACEWAY, VERTICAL RISER.

S SWITCH, SINGLE POLE, THREE WAY OR FOUR WAY.

LP11-22

HOMERUN TO PANEL. 2 #12 & 1#12 GROUND IN 3/4"

CONDUIT, UON. PANEL AND CIRCUIT NUMBER INDICATED.

EXISTING PANELBOARD.

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

J JUNCTION BOX

COMMENTSTYPESYMBOL DESCRIPTION MTG. METHOD MTG. HEIGHT VOLTSLAMPING WATTS

1X4 SURFACE

WRAP

120-

EX

1. SHADED FIXTURE ON PLAN DRAWING INDICATES THE FIXTURE CONTAINS A BATTERY

PACK TO POWER THE FIXTURE AND PROVIDE EMERGENCY EGRESS LIGHTING.

2. THE LIGHTING DESIGN IS BASED ON THE ABOVE FIXTURES.

WALL / CEILINGA LED 50W

RH

COMPLETE WITH EMERGENCY BATTERY PACK AND

OCCUPANCY SENSOR.

EXIT SIGN WITH

HEADS

- WALL/CEILING 120 UNIVERSAL MOUNT. E.C. SHALL VERIFY SINGLE/DOUBLE

FACE AND DIRECTION AS REQUIRED.

REMOTE HEADS 0.78W WALL 3.6VDC LISTED FOR WET LOCATIONS. POWERED FROM EXIT

SIGN.

LED

EX1 WALL/CEILING 120 UNIVERSAL MOUNT. E.C. SHALL VERIFY SINGLE/DOUBLE

FACE AND DIRECTION AS REQUIRED. REMOTE CAPACITY.

EXIT SIGN WITH

HEADS

BAT BATTERY PACK

WITH HEADS

LED

LED

SEE PLAN

DRAWING

1.55W

2.8W -

WALLLED 0.33W SEE PLAN

DRAWING

RECEPTACLE, SPECIAL PURPOSE.

B24

OFFICE

B25

OFFICE

B21

STRG

B15

WOMENS

LOCKER

RM

B11

OFFICE

B23

RECEP

B22

ELEV

RM

MECH RM

MECH RM

STORAGE

B18

SUPPLY

B17

STRG

B16

LAUNDRY

B09

PIPE RUN

ACCESS TUNNEL

UP

UP

UP

JAN RM

B12

1st FLOOR OUTLINE 1st FLOOR OUTLINE

LPB2-41

CORRIDOR

B08

CORRIDOR

B08

WOMEN

B14

PP

A

ELP-1

LPB-1

PUMP P1

MAIN XRAY

PPD

LDP-1

4" X 12" CABLE TRAY (TYPICAL)

PPB-LSPPB-RS

1 S 2

LPB2-22

1 1

SSS

SSS

SS 2

S2

S2

S2S 2 S2

SSSSS S

SS 2

2 2

+80"

SS

GFI

SS2

2 22

SS

S 2

S2

S2

S2 2

1 1

PPBRS-21,23

LPB2-21

LPB2-23

LPB2-5

S2

LPB2-42

LPB2-24

LPB2-40

LPB2-14

PPA-6

PPA-6

PPBLS-4

PPA-8

PPA-8

PPA-8

PPBLS-4 PPBLS-6 PPBLS-3

PPBLS-27

PPBLS-3

PPBLS-27

LPB2-3

LPB2-1

2 LPB2-5

PPBLS-11

PPBLS-10

GFILPB2

+80"

+46"

+46" +46" 2

A

A

J

LV

4 4

J 5

LV

EX1

RHEX

EX

EX1

RH

FIRESEAL

PPA-42 2

ELEC RM

TEL/ELEC/

FIRE PANEL

RM

UP

BACKUP

GENERATOR

RM

PP

E

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

SUB-BASEMENT PLAN

SCALE: 1/8" = 1'-0"2

BASEMENT PLAN

SCALE: 1/8" = 1'-0"1

MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:

MOUNT SMR AT 32" AFF

MOUNTING HEIGHTS:

REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING

DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT

AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.

MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT

MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER

FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.

INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO

SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"

AFF FOR RECEPTACLE, UON, MEASURED FROM CENTER OF BOX. INSTALL

WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN

ROOM.

REMOVE EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW

FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS

REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK COVERPLATE.

INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO

TO BE REPLACED WITH NEW FIXTURES.

REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.

INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE

FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST

ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.

FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL

INTERIOR MOUNTED EXIT SIGN.

WALL MOUNTED TELEDATA CABINET BY CONTRACTOR. SEE TELECOM

DRAWINGS.

KEYED NOTES:GENERAL NOTES:

1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.

2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE WAY,

FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.

3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING

HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.

4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE

AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL FOR

ALL LOCATIONS).

5. CABLE TRAY SHALL BE CENTER SUPPORTED.

6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING

TILE PRIOR TO INSTALLATION OF CABLE TRAY.

7. INSTALLATION OF CABLE TRAY WILL REQUIRE CONTRACTOR TO CHANGE ELEVATION

FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED SUCH AS

DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT FIXTURES

MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.

8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR

LIGHTING CABLES.

9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT

HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR IS

10 COVERS.)

10. SEE T001 FOR ADDITIONAL NOTES REGARDING CABLE TRAY.

DN

UP

DN

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

PHARMACY

URGENT CARE

X-RAY

FILE RM

OFFICE

FILM RM

WOMEN

MEN

OFFICE

OFFICE

OFFICE

EXAM RM

BREAK RM

WAITING

STRG

FILE RM

OFFICE

EXAM

110B

OFFICE

110A

BREAK

STRG

STRG

LAB

OXYGEN

STRG

MINOR

SURGERY

EMT

SUPPLY

BIO

STRG

STRG

ROOM

STRG

BATH

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

ROOM

ROOM

RECEPTION

CORRIDOR

CORRIDOR

CORRIDOR

COMMS

COMMS

ROOM

WOMEN

MEN

ROOM

EXAM

WAITING

116LP-12 LP-13 LP-14

LP11-4

4" X 16" CABLE TRAY

4" X 16" CABLE TRAY

CORRIDOR

DNTL XRAY

ELEV

ELEV

LP11-13

S 2

GFI

S

S

1 1 1

S

S

GFI

LP11-2

S 2 S 2 S 2 S 2

LP11-15

LP11-43 LP11-17

LP11-19

GFI

S

GFI

1 1

GFI

S

1 1

GFI

S

1 1

LP11-23

LP11-8

GFI

GFI

GFI

LP11-47

1 1

11 1 1 1 1 1

2 2

1 6

S 2S

S S S

S

22222222 3 3

LP11-16,18,20

SSS

S

S 2S

S2

2 2

MOUNTED ABOVE DESKTOP

MOUNTED BELOW DESKTOP

+46"

FAN GFI

2 2 2 2

2 2 2

2 2

MOUNTED ABOVE DESKTOP

3 3

S2

S2

22222

S2 S2

S

SS S

S

S

S

2S

S

SS

SS

SS2

S2

2 SS S2 S

S2

S2

S2

S2

S2

S2S

S 2S 2

GFI GFI

GFI

S2

1 1

GFI

LP11-21

LP11-45

LP11-22

LP11-6

LP12-26

LP12-9

LP12-22

LP12-4

LP12-12

LP12-12

LP12-12 LP12-16

LP12-17

LP14-36

LP14-38

LP13-15

LP13-15

LP13-19

LP13-23

LP13-21

LP13-5

LP13-15

LP13-7

LP14-16

LP14-4

LP14-4

LP13-34,36

LP13-40

LP13-38

LP13-42

LP12-15

LP12-23 LP12-19LP12-24

LP12-21

LP13-15

LP11-44

LP11

EWC

+80"+46"

+46" +46"

+46"

+46" +46"

+46" +46"

LP11-46LP11-46

LP11-46

LP11-46

S 2

2LP13-15

+46"

+46"

LP13-15

2+46"

LP11-46

A

A

4" X 4"

CABLE

TRAY

4" X 4"

CABLE

TRAY

4" X 16" CABLE TRAY

4" X 16" CABLE TRAY 4" X 16" CABLE TRAY

GFI GFI

4" X 16" CABLE TRAY

+18" +18"

+42"

+42"

ELP1-28

ELP1-32

ELP1-34

4" X 16" CABLE TRAY

(MOUNT BOTTOM OF TRAY AT 79" AFF)

(TOP OF RACK IS 78.39")

(CURRENT CEILING HEIGHT IS 86")

FIRESEAL FIRESEAL

FIRESEAL

FIRESEAL

FIRESEAL

FIRESEAL

FIRESEAL

ELP1-36

J

RH

LV

BATEX1

+80"

55 EX

EX

5 EX1

J

6 RH

+80"LV

+80"

EX

ELP1-30

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

1ST FLOOR PLAN

SCALE: 1/8" = 1'-0"1

MOUNTING HEIGHTS:

KEYED NOTES:GENERAL NOTES:

MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:

MOUNT SMR AT 32" AFF

MOUNT SMR AT 34" AFF

MOUNT SMR AT 40" AFF

MOUNT SMR AT 42" AFF

MOUNT SMR AT 45 1/2" AFF

MOUNT SMR ABOVE COUNTER/BACKSPLASH

REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING

DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT

AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.

MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT

MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER

FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.

INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO

SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"

AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL

WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN

ROOM.

EXISTING SMR AND RECEPTACLES TO REMAIN. REFEED TO PANEL & CIRCUT

SHOWN.

REMOVE EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW

FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS

REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK

COVERPLATE. INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT

SHOWN) ARE ALSO TO BE REPLACED WITH NEW FIXTURES. ENSURE ALL

FIXTURES ARE CONNECTED AHEAD OF ANY SWITCHING DEVICE.

REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.

INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE

FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST

ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.

FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL

INTERIOR MOUNTED EXIT SIGN.

1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.

2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE WAY,

FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.

3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING

HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.

4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE

AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL FOR

ALL LOCATIONS).

5. CABLE TRAY SHALL BE CENTER SUPPORTED.

6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING

TILE PRIOR TO INSTALLATION OF CABLE TRAY.

7. INSTALLATION OF CABLE TRAY WILL REQUIRE THE CONTRACTOR TO CHANGE ELEVATION

FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED SUCH AS

DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT FIXTURES

MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.

8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR LIGHTING

CABLES.

9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT

HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR IS

20 COVERS.)

10. SEE T001 FOR ADDITIONAL CABLE TRAY NOTES.

KEYED NOTES (CONTINUED):

REMOVE HARD CEILING IN THIS ROOM TO GAIN MORE ACCESS TO CABLE TRAY

FOR INSTALLATION OF CABLES. RELOCATE/REMOVE ITEMS AFTER CEILING IS

REMOVED THAT ARE IN THE PATH OF THE TRAY. FIREPROOF DECK IF REQUIRED.

INSTALL 3/4" FIRE RETARDANT PLYWOOD ON WALL FOR TELEPHONE DEMARK.

REMOVE EXISTING SLEEVES CONTAINING CAT 5 CABLES AND ENLARGE

OPENING FOR CABLE TRAY.

REMOVE WALL EXHAUST FAN, APPROXIMATE SIZE 16"X16", FOR INSTALLATION

OF CABLE TRAY.

REMOVE ROOM EXHAUST FAN AND RELATED CONDUIT AND WIRE FOR

INSTALLATION OF A/C UNIT (BY OTHERS).

OFFICE

OFFICE

OFFICE

CONF RM

OFFICE

OFFICE

OFFICE

OFFICE

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM RM

OFFICE

OFFICE

BREAK

OFFICE

STRG

STRG

DENTAL

LAB

EXAM RM

BREAK RM

RECEP

DARK RM

DENTAL

LAB

UP

DN

UP

DN

UP

DN

STRG

JAN

ROOM

BATH

BATH

BATH

ELEV

ELEV

STAIR

CLO

248A

EXAM RM

CORRIDOR

LP22 LP22A

4" X 12" CABLE TRAY

CORRIDOR

BATH

DENTAL

STAIR

STAIR

LP

LP

CORRIDOR

CORRIDOR

CLOSET

S2

LP21-11

1 S

S

SS 2 2

S

S

S

S

S

S

S

S

S2

SS 2

S

S 2

S21

1 1

1 1 1

S2

S 2

S2

1 1 1

1 1 1

1111 1

1 1

S

S

S

S 2

S2

S

LP21-7

LP21-7

2 LP23-21

LP23-23 LP23-27LP23-25

LP23-29

LP23-26 LP23-28

2SS

SS2

LP23-30

LP21-42

2 LP21-422 LP21-42

LP21-42

S

2 LP22-29GFI

GFI

LP22A-41

S

LP21-13

LP21-19

LP23-14

LP23-16

S

S

S

LP21-9

LP23-18

LP21-272

LP21-2

GFI LP21-22

LP21-5

LP22A-5

2 LP22-17

LP21-7

LP21-7

S

LP23-20

+80" +80"

+46" +46"

+46"+46"

+46"+46"

SS

GFI

LP21-8

+42"

GFI

A A

A

A

A A

104" X 12" CABLE TRAY

FIRESEAL

J

RH

+80"5

EX1

LV

EX

EX1

J

RH

LV

101010

ELP1-1

ELP1-2

SS

S 2

1 111

S 2

S

S S

SS

S S

S LP22-16S 2

LP22-29

LP22-29

S

SS

S

2 LP22-29LP22-24 2 LP22-17

+46"+46"

LP23-17 LP23-19

LP22A-42 +80"

LP22A-6

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

2ND FLOOR PLAN

SCALE: 1/8" = 1'-0"1

MOUNTING HEIGHTS:GENERAL NOTES:

MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:

MOUNT SMR AT 27' AFF

MOUNT SMR AT 45" AFF

MOUNT SMR AT 44" AFF

MOUNT SMR ABOVE COUNTER/BACKSPLASH

KEYED NOTES:

REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING

DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT

AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.

MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT

MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER

FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.

INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO

SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"

AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL

WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN

ROOM.

EXISTING SMR AND RECEPTACLES TO REMAIN. REFEED TO PANEL & CIRCUT

SHOWN.

REMOVE ALL EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW

FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS

REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK

COVERPLATE. INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT

SHOWN) ARE ALSO TO BE REPLACED WITH NEW FIXTURES. ENSURE ALL

FIXTURES ARE CONNECTED AHEAD OF ANY SWITCHING DEVICE.

REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.

INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE

FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST

ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.

FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL

INTERIOR MOUNTED EXIT SIGN.

1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.

2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE WAY,

FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.

3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING

HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.

4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE

AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL FOR

ALL LOCATIONS).

5. CABLE TRAY SHALL BE CENTER SUPPORTED.

6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING

TILE PRIOR TO INSTALLATION OF CABLE TRAY.

7. INSTALLATION OF CABLE TRAY WILL REQUIRE THE CONTRACTOR TO CHANGE

ELEVATION FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED

SUCH AS DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT

FIXTURES MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.

8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR

LIGHTING CABLES.

9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT

HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR

IS 15 COVERS.)

10. SEE T001 FOR ADDITIONAL CABLE TRAY NOTES.

KEYED NOTES (CONTINUED):

INSTALL NEW LIGHTING FIXTURE ON UNDERSIDE OF DECK. CONNECT TO PANEL

AND CIRCUIT SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL

LIGHT SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY

LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH

NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY

SWITCHING DEVICE.

INSTALL NEW LIGHTING FIXTURE ON CEILING. CONNECT TO PANEL AND CIRCUIT

SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL LIGHT

SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY

LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH

NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY

SWITCHING DEVICE.

CONTINUE LIGHTING CIRCUIT UP TO 3RD FLOOR STAIRWAY LIGHTING.

REMOVE ALL EXISTING "JELLY JAR" LIGHTING FIXTURES, WIRING AND

BACKBOXES. PATCH AND PAINT TO MATCH SURROUNDING SURFACES.

WALL MOUNTED TELEDATA CABINET BY IT CONTRACTOR. SEE TELECOM

DRAWINGS.

DN

UP

DN

TRAINING RM

PATIENT RM

PATIENT RM

STATIONERY

BICYCLES

MALE

DUTY RM

OFFICE

FEMALE

DUTY RM

PATIENT RM

JAN

STRG

LINEN

PHYSICAL THERAPY

STRG

ICE RM

OFFICE

STRG

STORAGE

RECEPTION

PHYSICAL

THERAPY

STRG

MEN'S

LOCKER

WOMEN'S

LOCKER

NURSES

STATION

UTILITY RM

UTILITY

RM

STRG

STRG

WOMEN'S

LOCKER RM

MEN'S

LOCKER RM

4" X 12" CABLE TRAYUG1

PD

P1

LP31

ROOM

PATIENT RM

LP32

STAIR

STAIR

STAIR

ELEV

ELEV

ROOM

STRG

ROOM

310A

ROOM

S

LP31-15

1 1 1

1 1

2 41

S 2

S 2

S2 S2

S2S2

1 1 1

1 1

S 2 S 2

S

S

S

S

2S2S

S

S

S

2S

S

S

S 2

S2

S 2

S2 S2

SS 2

S

SS2

SS2

SS2

S2

S2

S2

S2

S

2S

S2 S2

S2

S2

S

2 11

S2

S2S2

S2

S

S

SS SS2 2

SS 2

SS

SS

S

SS2

SS

S

2 2

LP31-24

LP31-27

LP31-29 GFI

LP31-31

GFI

LP31-33

LP31-6

2 LP31-12

LP31-12

LP31-12

2 LP31-12

LP31-12

LP31-16

UG1-20,22

GFI

LP31-20 LP32-42

LP32-23,25

LP31-18 LP32-33

2LP32-38 2LP32-37

LP32-37

LP32-35

LP32-38

LP32-36

LP32-34

LP32-32

LP32-41

LP32-38

LP32-38

GFI

GFI

GFI

GFI

GFI

LP31-21LP31-19LP31-17

LP31-24

GFI

GFI

LP32-40

LP32-31

GFI

GFI

+80" +80" +46"

+46"

GFI

+46" +46"

+46"

LP31-28,42

UG1-24,26

GFI

+40"

GFI

+40"

GFI+40"

GFI

+40"

LP32-2

LP32-2

LP31-7

LP31-7

A A

A

A

A A

FIRESEAL7

8 8

EX5

EX 5EX

1010 1010

GFI

LP32-39

+80"UG1-19

PDP1-30,32

PDP1-30,32

(A/C)

PDP1-34,36

(A/C)

PDP1-38,40 (A/C)

PDP1-38,40

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

3RD FLOOR PLAN

SCALE: 1/8" = 1'-0"1

MOUNTING HEIGHTS:KEYED NOTES:GENERAL NOTES:

MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:

MOUNT SMR AT 24" AFF

MOUNT SMR ABOVE COUNTER/BACKSPLASH

MOUNT SMR AT 32" AFF

MOUNT SMR AT 36" AFF

REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING

DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT

AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.

MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT

MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER

FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.

INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO

SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"

AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL

WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE FOR SWITCHING IN

ROOM.

EXISTING SMR AND RECEPTACLES TO REMAIN. REFEED TO PANEL & CIRCUT

SHOWN.

REMOVE ALL EXISTING STAIRWAY LIGHTING FIXTURES AND REPLACE WITH NEW

FIXTURES IN SAME LOCATION AS REMOVED FIXTURES. EXTEND WIRING AS

REQUIRED. REMOVE WALL LIGHT SWITCH(ES) AND INSTALL BLANK

COVERPLATE. INTERMEDIATE STAIRWAY LANDING LIGHTING FIXTURES (NOT

SHOWN) ARE ALSO TO BE REPLACED WITH NEW FIXTURES. ENSURE ALL

FIXTURES ARE CONNECTED AHEAD OF ANY SWITCHING DEVICE.

REMOVE EXISTING EXIT SIGN AND REPLACE WITH NEW IN SAME LOCATION.

INSTALL LOW VOLTAGE WEATHERPROOF REMOTE HEADS AT 80" ABOVE

FINISHED GRADE. INSTALL SURFACE MOUNTED WEATHERPROOF CAST

ALUMINUM (BLACK COLOR) JUNCTION BOX FOR MOUNTING OF REMOTE HEADS.

FEED HEADS WITH #12 LOW VOLTAGE WIRING IN PVC CONDUIT FROM NEW WALL

INTERIOR MOUNTED EXIT SIGN.

1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.

2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE, THREE

WAY, FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.

3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF MOUNTING

HARDWARE TO ATTACH SMR PER MANUFACTURER'S RECOMMENDATIONS.

4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW RECEPTACLE

AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE A/C UNIT. (TYPICAL

FOR ALL LOCATIONS).

5. CABLE TRAY SHALL BE CENTER SUPPORTED.

6. CONTRACTOR SHALL REMOVE ALL ABANDONED CONDUIT AND WIRING ABOVE CEILING

TILE PRIOR TO INSTALLATION OF CABLE TRAY.

7. INSTALLATION OF CABLE TRAY WILL REQUIRE THE CONTRACTOR TO CHANGE

ELEVATION FOR ROUTING ABOVE/BELOW OBJECTS THAT CAN NOT BE RELOCATED

SUCH AS DUCTWORK AND/OR PIPING OR MISC. CONDUITS. RE-SUPPORTING OF LIGHT

FIXTURES MAY BE REQUIRED IN SOME LOCATIONS FOR INSTALLATION OF TRAY.

8. CABLE TRAY IS FOR INSTALLATION OF TELEDATA CABLES ONLY. NO POWER OR

LIGHTING CABLES.

9. INSTALL COVERPLATES ON ALL ABOVE CEILING ELECTRICAL BOXES DISCOVERED NOT

HAVING COVERS DURING THIS RENOVATION. (MAXIMUM ALLOWANCE FOR THIS FLOOR

IS 15 COVERS.)

10. SEE T001 FOR ADDITIONAL CABLE TRAY NOTES.

KEYED NOTES (CONTINUED):

INSTALL NEW LIGHTING FIXTURE ON UNDERSIDE OF DECK. CONNECT TO PANEL

AND CIRCUIT SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL

LIGHT SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY

LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH

NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY

SWITCHING DEVICE.

INSTALL NEW LIGHTING FIXTURE ON WALL AT 96" AFF. CONNECT TO PANEL AND

CIRCUIT SHOWN USING SMR. REMOVE EXISTING LIGHT FIXTURES, WALL LIGHT

SWITCH(ES) AND INSTALL BLANK COVERPLATE. INTERMEDIATE STAIRWAY

LANDING LIGHTING FIXTURES (NOT SHOWN) ARE ALSO TO BE REPLACED WITH

NEW FIXTURES. ENSURE ALL FIXTURES ARE CONNECTED AHEAD OF ANY

SWITCHING DEVICE.

CONTINUE LIGHTING CIRCUIT UP/DOWN TO STAIRWAY LIGHTING.

REMOVE ALL EXISTING "JELLY JAR" LIGHTING FIXTURES, WIRING AND

BACKBOXES. PATCH AND PAINT TO MATCH SURROUNDING SURFACES.

WALL MOUNTED TELEDATA CABINET BY IT CONTRACTOR. SEE TELECOM

DRAWINGS.

STORAGE

MECH RM

MECH RM

WORKOUT RM

WORKOUT RM

STORAGE

STORAGE

STORAGE

PPL-LS LPA1

PPL-RS

PPF

S

S

SSS

S

S

S 2

1 1

LPA1-21

LPA1-19

LPA1-9

LPA1-9

LPA1-9

LPA1-9

LPA1-9

SS

LPA1-9

LPA1-21

2A A A A

EX

4EX6 5 69

LPA1-21

MICHAEL BAKER JR, INC

MOON TOWNSHIP, PA 15108

(412) 269-6300

100 AIRSIDE DRIVE

SCALE: 1/8" = 1'-0"

0 4'-0" 8'-0" 16'-0"

PLAN

NORTH

N

4TH FLOOR PLAN

SCALE: 1/8" = 1'-0"1

MOUNTING HEIGHTS:KEYED NOTES:GENERAL NOTES:

MOUNTING HEIGHTS MEASURED FROM BOTTOM OF RACEWAY:

MOUNT SMR AT 24" AFF

1. ALL RECEPTACLES SHALL BE LISTED AS HOSPITAL GRADE IN ALL AREAS.

2. CONTRACTOR SHALL VERIFY SWITCH AND DEVICE TYPE, I.E. SINGLE POLE,

THREE WAY, FOUR WAY, DUPLEX AND REPLACE WITH SAME IN SMR BOX.

3. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPES FOR SELECTION OF

MOUNTING HARDWARE TO ATTACH SMR PER MANUFACTURER'S

RECOMMENDATIONS.

4. EXISTING RECEPTACLES FOR A/C UNITS SHALL BE REPLACED WITH NEW

RECEPTACLE AND WIRING/RACEWAY REPLACED TO THE PANEL SERVING THE

A/C UNIT. (TYPICAL FOR ALL LOCATIONS).

REMOVE ALL EXISTING RECEPTACLES, BOXES AND WIRING FROM EXISTING

DEVICES IN THIS ROOM BACK TO THEIR SOURCE OF SUPPLY. PATCH AND PAINT

AREA WHERE DEVICES WERE REMOVED TO MATCH SURROUNDING SURFACES.

MOUNT SURFACE METAL RACEWAY (SMR) HORIZONTALLY AT INDICATED HEIGHT

MEASURED FROM BOTTOM OF RACEWAY. INSTALL VERTICAL SMR FOR POWER

FEED TO RACEWAY FROM PANEL AND CIRCUIT INDICATED.

INSTALL SMR FOR POWER FEED VERTICALLY FROM 6" ABOVE DROP CEILING TO

SMR BOX MOUNTED AT 46" ABOVE FINISHED FLOOR (AFF) FOR SWITCH AND 18"

AFF FOR RECEPTACLE, UNO, MEASURED FROM CENTER OF BOX. INSTALL

WIRING FROM SWITCH TO NEAREST LIGHTING FIXTURE…