P3578953Dwgs.pdf
PDF 14 MB Posted
- Attached to
- USCG SECTOR FIELD OFFICE SOUTHWEST HARBOR, ME CONSTRUCT BMF AND REPAIR CONCRETE PAVEMENT
- Solicitation number
- HSCGG1-14-B-PRV264
About this file
Drawings
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Abstract_HSCGG1-14-B-PRV264.pdf | ||
| P3578953d06_DETAILS_9-5-14.pdf | ||
| Amendment0005_14-B-PRV264.pdf | ||
| Amendment0004_14-B-PRV264.pdf | ||
| Amendment0003_14-B-PRV264.pdf | ||
| Amendment0002_14-B-PRV264.pdf | ||
| P3578953Spcs.pdf | ||
| IFB_HSCGG1-13-B-PRV264.pdf | ||
| SF_24.pdf | ||
| Amendment0001_14-B-PRV264.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
CHRISTOPHER
A.
WILSON
#9269
S
TA T E O F M A I N
E
R
N
P
I
GNE
F O
LANOISS
N DE
L IC S E
G
ID
R T H
TULOS
LI
V
C
TS
AEHTRO
(208V) 4#2 AWG & #8 GND, 1-1/4"C
(480V) 2#8 AWG & #10 GND, 1-1/4"C
(SPARE), 1-1/4"C
RISE ABOVE GROUND & PENETRATE BUILDING
EXTERIOR IN RIGID STEEL CONDUIT TO MINIMUM
24" AFG. STUB SPARE INSIDE BUILDING.
ROUTE IN SURFACE
EMT TO PANELS.
SEE SHEET E-101
FOR CONTINUATION
BOAT
MAINTENANCE
BUILDING
EXISTING
COAST GUARD
STATION
VEHICLE
ENTRANCE
(TUNNEL)
COAST GUARD
HAZMAT
BOUY STORAGE
RAMP
FU
EL
T
AN
K
SHED
EXIST
SHED
HAZ-MAT SUPPLY BOXES
JOHAN N BUI SMAN
JI M FI SHER
Northeast Civil Solutions
. S.
U OC
A
ENGINEERING UNIT
EX
L
E
I N
PROVIDENCE
CIVIL
NG
NEER
U
D
GNI
511 Congress St., Suite 200, Portland ME 04101 P: (207) 775-5401 F: (207) 772-4762 www.amec.com
CONSULTANTS
U. S. COAST GUARD
CIVIL ENGINEERING UNIT
USCG. CEU PROVIDENCE
475 KILVERT STREET
WARWICK, RI 02886
ER I NGENIGNE
NI
CE
L L E N
U CO
A S
U A
ISSUE
MARK DATE DESCRIPTION
A/E PROJECT NO:
CAD FILE NAME:
DESIGNED BY:
DRAWN BY:
EDITED BY:
CHECKED BY:
SCALE:
SHEET TITLE
PLOT SCALE:
PROJECT NUMBER DRAWING NUMBER
DISCIPLINE/SHT NO
SHEET OF
REVIEWED BY: REVIEWED BY: REVIEWED BY:
PROJECT ENG. BRANCH CHIEF TECH. DIRECTOR
APPROVING OFFICER DATE
3 421
B
1" = 20'-0"
ISSUED FOR CONSTRUCTION06-23-14
ELECTRICAL SITE PLAN
ES-101 19
LAM
ELECTRICAL
MESOUTHWEST HARBOR
CG SFO SOUTHWEST HARBOR
CONSTRUCT BMF AND RPR CONC PAVT
D. CASS D. GLASS A. JACOBS
A. A. JACOBS, BY
P35789533578953
TR
P3578953d19
3618138332
CAW
NOTE:
1. SEE SHEET E-001 FOR LEGEND, ABBREVIATIONS
AND GENERAL NOTES.
2. FOR WORK PREFORMED AT EXISTING BUILDINGS:
SCALE: 1" = 20'-0"A1 SITE PLAN
10' 20' 40'0
KEYED NOTES:
LOCATION OF EXISTING PANELBOARDS
PP1 - 480Y/277V & PP2 - 208Y/120V
LOCATION OF EXISTING COMMUNICATIONS ROOM AND
INFRASTRUCTURE ON THE 2ND FLOOR OF THE
STATION BUILDING. INSTALL TERMINATION EQUIPMENT
AND EXTEND NEW COMMUNICATION CABLING THROUGH
THE STATION BUILDING AND UNDERGROUND TO NEW
BMF PER USCG REQUIREMENTS.
ROUTE NEW COMMUNICATIONS CABLING CONCEALED
ABOVE ACCESSIBLE CEILINGS IN FINISHED AREAS
AND IN EMT WHERE EXPOSED INSIDE MAINTENANCE
SHOP.
COMMUNICATION SERVICE CONDUIT: 1-4� SCHEDULE
80 PVC WITH (1) 1-1/4� INNERDUCT FOR
INSTALLATION OF COMMUNICATIONS CABLING PER
USCG ELECTRONIC SYSTEM REQUIREMENTS INCLUDING
IN THE SPECIFICATIONS. NEW 25-PAIR CAT 5E
OUTSIDE PLANT CABLE SHALL BE INSTALLED LOOSE
AND NEW 6 STRAND SINGLE MODE FIBER OPTIC
OUTSIDE PLANT CALBE INSTALLED IN THE
INNDERDUCT.
1. USE CARE TO PROTECT ALL EXISITNG FINISHES.
2. REMOVE AND SALVAGE EXISTING CELING TIEL AND
GRID AS REQUIRED TO INSTALL CONDUITS AND
CABLES.
3. INSTALL SALVAGE CEILING TILES AND GRID AT
COMPLETION OF WORK. REPLACE ALL TIEL AND
GRID DAMAGED DURING THE WORK AT NO COST
THE GOVEREMENT.
2014-06-25T08:49:23-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
1 2 3 4 5
A.9
A.1
A.8
A.2
PANEL BP1
208Y/120V
100A MCB
BP1-4
BP1-1,3,5
PB
WP
BP1-14
BP1-2
RH
EF
BP1-4
BP1-4 WPBP1-4WP
BP1-11
BP1-9
BP1-
BP1-7BP1-13,
15,17
2 1
BP1-19,21,23
30AS
20AF
BP1-12
BP1-6
S S3a
BP1-8
Cb Cb Cb Cb
Cb
Cb Cb Cb Cb
S S3a 3b
BP1-10
WP A
Ba
CHAIN HUNG
26'-0" A.F.F. (TYP. 12)
MOUNT APPROX.
9'-4"+/- A.F.F. (TYP. 9)
MOUNT 20'-0" A.F.F. (TYP. 4)
REFERENCE ARCH BLDG
ELEVS FOR HORIZONTAL
LOCATIONS
3b
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING NOTES
LED ARCHITECTURAL WALL MOUNT EXTERIOR FIXTURE WITH FULL
CUTOFF TYPE 3 DISTRIBUTION, INTEGRAL PHOTOCELL CONTROL,
AND DARK BRONZE FINISH
73W LED
3500K SURFACE WALL
SINGLE FACE LED EXIT SIGN WITH INTEGRAL
MAINTENANCE FREE BATTERY BACKUP.
UL LISTED FOR WET LOCATION
LED
INCLUDED SURFACE WALL
DUAL HEAD EMERGENCY LIGHTING UNIT WITH INTEGRAL
MAINTENANCE FREE BATTERY BACKUP.
UL LISTED FOR WET LOCATION
2-7.2W
HALOGEN SURFACE WALL
LAMP
QUANTITY
& TYPE
8' SEALED AND GASKETED LED INDUSTRIAL FIXTURE WITH
POLYCARBONATE LENS. MEDIUM LUMEN OUTPUT (9800 MIN.)
105W LED
4000K
STAINLESS
STEEL CHAIN
HUNG
SURFACE WALL
NOTES
CONTRACTOR SHALL CAPTURE ALL AVAILABLE EFFICIENCY MAINE INCENTIVES FOR LIGHTING FIXTURES AS SPECIFIED AND SUBMIT
APPLICATIONS AND PRODUCT DATA ON BEHALF OF THE OWNER DURING CONSTRUCTION.
120V
8' SEALED AND GASKETED LED INDUSTRIAL FIXTURE WITH
POLYCARBONATE LENS. MEDIUM LUMEN OUTPUT (9800 MIN.)
105W LED
4000K
PROVIDE WITH ADDITIONAL CAPACITY
FOR REMOTE HEAD(S) AS INDICATED.
AM
AM
kVA LOAD
A B C C
T N
. A B C kVA LOAD
T N
A B C
DIRECTORY
0.6
20 2
RECEPTACLES
DIRECTORY
0.9
0.9
VOLTAGE:
MOUNTING:
MAIN BREAKER
NOTES:
SC RATING:
GROUND BUS
NEUTRAL BUS
6.35.8 6.3 2.1 1.2 1.2
22.7
7.9
7.5
7.5
10,000 AIC
120V/208Y
SURFACE
SUB-TOTAL
AMP TRIP
WIRE4PHASE3 AMP BUS
LOCATION:
PANEL NO.:
SUB-TOTAL
BMF BUILDING
BP1TOTAL kVA
TOTAL kVA A
TOTAL kVA C
TOTAL kVA
HEATERS
OVERHEAD DOOR (3/4HP)
0.7
1.2
1.2
EF-1 (1/2HP)
EF-2 (1/2HP)
WELDING RECEPTACLE
CRANE 30
RECEPTACLES
OVERHEAD INTERIOR LIGHTS
PERIMETER INTERIOR LIGHTS
1.0
EMERGENCY LIGHTS
TELCOM RACK
SPARE
SPARE
SURGE PROTECTION DEVICE
EXTERIOR LIGHTS0.3
0.2
SPACE
0.2
400A
100/315/3
"PP1"
480V,3PH,3
W
400A MCB
150kVA
DRY-TYPE
480V-
208Y/120V
3PH,4W
"PP2"
208Y/120
400A
MCB
EXISTING FEEDER 8320V,3PH,3W
WELDING
RECEPTACLE
480V,1PH,
20A/3P
"BP1"
208Y/120V, 100A MCB
NEMA 4X
300kVA
PAD-MOUNT
TRANSFORMER
8320/4800V-
480V,3PH,3W
FROM EXISTING
SUBSTATION
30AS
NEMA
4X
SPD
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
As indicated
POWER & LIGHTING PLANS
E-101 20
P3578953d20
PLAN
NORTH
4' 8' 16'0SCALE: 1/8" = 1'-0"A1 FIRST FLOOR POWER PLAN
SCALE: 1/8" = 1'-0"A3 FIRST FLOOR LIGHTING PLAN
4' 8' 16'0
1. SEE SHEET E-001 FOR LEGEND, ABBREVIATIONS AND GENERAL NOTES
PROVIDE 480V, 1PH, 20A/3 POLE WEATHERPROOF DISCONNECT SWTICH WITH WELDING
RECEPTACLE, W/ NEW PLUG TO MATCH EXISTING USCG 480V SHOP WELDER. SURFACE
MOUNT TO EXTERIOR CONCRETE WALL AT 24" AFG TO BOTTOM.
2#8 AWG & #10 GND, 1-1/4"C BRANCH CIRCUIT TO 480V WELDING RECEPTACLE.
4#2 AWG & #8 GND, 1-1/4"C FEEDER TO NEW 208Y/120V PANELBOARD BP1 FROM
PP1.
PROVIDE 208V, 1PH, 50A/3 POLE WEATHERPROOF WELDING RECEPTACLE W/NEW PLUG TO
MATCH EXISTING USCG 208V SHOP WELDER. SURFACE MOUNT TO INTERIOR CONCRETE
WALL AT 24" AFG. CONDUCTORS SHALL BE 2#8AWG & #10GND, 3/4"C.
PROVIDE NEW BREAKER IN EXISTING 480V PANEL (WESTINGHOUSE TYPE PRL4) TO MATCH
EXISTING STYLE AND RATINGS.
PROVIDE NEW BREAKER IN EXISTING 208V PANEL (WESTINGHOUSE TYPE PRL1) TO MATCH
EXISTING STYLE AND RATING.
PROVIDE SINGLE POINT POWER POINT CONNECTION TO BRIDGE CRANE CONTROLLER -
FURNISHED WITH CRANE SYSTEM. CONDUCTORS SHALL BE 3#10AWG & #10 GND, 3/4"C.
SEE BID OPTION #1 ON SHEET G-001.
TELCOMMUNICATIONS EQUIPMENT LOCATION. REFER TO USCG ELECTRONICS SYSTEM
REQUIREMENTS CONTAINED IN THE SPECIFICATIONS. FURNISH AND INSTALL NEMA 4X
ENCLOSURE WITH HINGED COVER LARGE ENOUGH TO HOUSE THE FOLLOWING: MIN. 18U
TALL, 19� WIDE, 24� DEEP COMMUNICATIONS RACK, TERMINATIONS OF 25 PAIR CAT 5E
COPPER AND 6 STRAND SINGLE MODE FIBER OPTIC OUTSIDE PLANT CABLES, A 20A QUAD
RECEPTACLE, TELECOMMUNICATIONS GROUDING BUS-BAR (TGB), AND A 60WATT, 70V TALK
BACK PUBLIC ADDRESS SYSTEM AMPLIFIER TO BE COMPATABLE WITH THE EXISTING
SYSTEM. ENCLOSURE SHALL BE WALL MOUNTED USING STAINLESS STEEL STRUT. OUTSIDE
PLANT CABLE SHALL BE ROUTED FROM STATION BUILDING AS INDICATED ON ES-101.
PROVIDE (1) 5/8� X 10� COPPER CLAD GROUND ROD BONDED TO BP1 EQUIPMENT
GROUND BUS, BUILDING STEEL, AND TELECOMMUNICATIONS RACK GROUND BUS.
PROVIDE PANELBOARD STYLE NIPPLE MOUNTED SURGE SUPPRESSION DEVICE WITH MIN.
100KA WITHSTAND RATING. CONNECT TO BP1-20,22,24 PER MANUFACTURER�S
RECOMMENDATIONS
SCALE: NOT TO SCALEB3 ONE LINE DIAGRAM
2014-06-25T08:50:03-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
P R O X .E
R I NGENIGNE
C E L L E N
U A
1t
SCALE:A2 DRAWING BLOCK TITLE
1/4" = 1'-0"
ROOM NAME
GRAPHIC SCALE
AE-606
INDICATES ELEVATION LETTER AND NUMBER
INDICATES SHEET WHERE ELEVATION IS SHOWN
EXTERIOR ELEVATION
A1
AE-101
SIM
INDICATES SECTION LETTER AND NUMBER
INDICATES SHEET WHERE SECTION IS SHOWN
SECTION
AE-222
A1 SIM
INDICATES DETAIL LETTER AND NUMBER
INDICATES SHEET WHERE DETAIL IS SHOWNDETAIL
AREA OF DETAIL
AE-222
INDICATES ELEVATION LETTER AND NUMBER
INDICATES SHEET WHERE ELEVATION IS SHOWN
INTERIOR ELEVATION
ROOM/AREA NAME
ROOM NO.
ROOM/AREA
IDENTIFIER
WINDOW TAG INDICATOR
DOOR TAG INDICATOR
KEYED NOTE
DEMOLITION KEYED NOTE
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
COVER SHEET
G-001 1
TJK
GENERAL
DIRECTION
ALM
P3578953d01
MSD
NO. SHEET SEQUENCE DRAWING NAME
G-001 1 OF 20 COVER SHEET
C-101 2 OF 20 EXISTING CONDITIONS PLAN
C-102 3 OF 20 GRADING AND DRAINAGE PLAN
C-102A 4 OF 20 EROSION CONTROL PLAN
C-103 5 OF 20 SITE AND UTILITY PLAN
C-104 6 OF 20 CONSTRUCTION DETAILS
C-105 7 OF 20 DECK REPAIR PLAN
S-001 8 OF 20 STRUCTURAL NOTES
S-101 9 OF 20 FOUNDATION PLAN
S-102 10 OF 20 CRANE RAIL FRAMING
S-501 11 OF 20 FOUNDATION DETAILS
S-502 12 OF 20 SECTIONS AND DETAILS
A-101 13 OF 20 FLOOR & RCP PLANS
A-201 14 OF 20 EXTERIOR ELEVATIONS
A-301 15 OF 20 SECTIONS & DETAILS
A-601 16 OF 20 WINDOW & DOOR ELEVS
M-101 17 OF 20 FLOOR PLAN
E-001 18 OF 20 LEGEND, ABBRS & NOTES
ES-101 19 OF 20 ELECTRICAL SITE PLAN
E-101 20 OF 20 POWER & LIGHTING PLANS
USCG SECTOR FIELD OFFICE SOUTHWEST HARBOR
SOUTHWEST HARBOR, MAINE
HANCOCK COUNTYPROJECT DESCRIPTION
BUILDING CODE INFORMATION
LEGEND
ABBREVIATIONS
DRAWING LIST
CONSTRUCT BOAT MAINTENANCE FACILITY
& REPAIR CONCRETE PAVEMENT
CIVIL ENGINEERING UNIT PROVIDENCE
UNITED STATES COAST GUARD
SINGLE STORY PRE-ENGINEERED METAL BUILDING
CODE ANALYSIS
USE GROUP: S-1; MODERATE HAZARD STORAGE
CONSTRUCTION TYPE: IIB
AREA: 2554 SF
HEIGHT: 35'-11"
NON-SPRINKLERED REQUIRED PROVIDED
EXIST ACCESS TRAVEL DISTANCE: 200' MAX
NUMBER EXITS: 1 2
COMMON PATH OF TRAVEL: 100' MAX
OCCUPANT LOAD: 1 PERSON/500SF 5
FIRE RATING REQUIREMENTS
STRUCTURAL FRAME: 0 HR 0 HR
NON-BEARING WALLS 0 HR 0 HR
(BASED ON SEPERATION DISTANCE > 30'-0")
ROOF CONSTRUCTION 0 HR 0 HR
INTERNATIONAL BUILDING CODE (IBC) 2012
MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES (ASCE/SEI 7-10)
BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318-11)
STEEL CONSTRUCTION MANUAL AISC 14TH EDITION
INTERNATIONAL MECHANICAL CODE (IMC)
NFPA 54, NATIONAL FUEL GAS CODE
NFPA 58, LIQUEFIED PETROLEUM GAS CODE
ASHRAE 90.1-2010, ENERGY STANDARD FOR BUILDINGS
UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES (MARCH 2013)
INTERNATIONAL FIRE CODE (IFC) (2012 ED)
NFPA 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE (2012 ED)
NFPA 30A, CODE FOR MOTOR FUEL DISPENSING FACILITIES AND REPAIR GARAGES
STANDARD (2012 ED)
NFPA 101, LIFE SAFETY CODE (2012 ED)
& AND
@ AT
± PLUS OR MINUS
ACT ACOUSTICAL CEILING TILE
BLDG BUILDING
BOS BOTTOM OF STEEL
BOT BOTTOM
CPT CARPET
CONC CONCRETE
CT CERAMIC TILE
CW CLEAR WIDTH
DEMO DEMOLITION
DIA DIAMETER
DR DOOR
DET DETAIL
DWG DRAWING
EA EACH
ELEC ELECTRICAL
ELEV ELEVATION
EXIS EXISTING
FD FLOOR DRAIN
FF FINISH FLOOR
FIN FINISH
FLR FLOOR
F.0. FACE OF
FT FOOT, FEET
GA GAUGE
GALV GALVANIZED
GFI GROUND FAULT INTERCEPT
GWB GYPSUM WALL BOARD
HGT HEIGHT
HVAC HEATING, VENTILATION AND AIR CONDITIONING
LF LINEAR FOOT
LOC LOCATION
LTG LIGHTING
LVL LAMINATED VENEER LUMBER (ENGINEERED LUMBER)
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MTL METAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OH OVERHEAD
PLYWD PLYWOOD
P.T. PRESSURE TREATED
PWR POWER
RTG RATING
RM ROOM
SECT SECTION
SHT SHEET
SIM SIMILAR
SQ FT. SQUARE FOOT, SQUARE FEET
THK THICKNESS
THRU THROUGH
TOS TOP OF STEEL
TPO THERMOPLASTIC POLYOLEFIN
TS TUBE STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VCB VINYL COVE BASE
VIF VERIFY IN FIELD
W/ WITH
WD WOOD
LOCATION MAP
SCALE: NONE
VICINITY MAP
SCALE: NONE
3578953
BID OPTION LIST
BID OPTION 1: OVERHEAD TRAVELLING CRANE.
PROVIDE AND INSTALL A 2-TON SINGLE HOIST
UNDERHUNG BRIDGE CRANE. PROVIDE ALL MATERIALS
FOR THE CRANE ITSELF, INCLUDING HOIST, CABLE,
MOTOR, WIRING AND CONTROLS, TROLLEYS, AND
RAILS. INSTALL PER THE DRAWING DETAILS AND
SPECIFICATION SECTION 41 22 31.15. PROVISIONS
FOR STRUCTURALLY SUPPORTING THE CRANE AND
PROVIDING SUFFICIENT POWER CAPACITY TO THE
BUILDING PANEL SHALL BE INCLUDED IN THE BASE
BID.
BID OPTION 2: UNDERSLAB CONTAINMENT TANK.
FORM AND INSTALL A CONCRETE ENCLOSURE BELOW
THE LOW POINT OF THE FLOOR SLAB AS SHOWN ON
S-101, IN DETAIL A3 ON S-502 AND KEYED NOTES
2 AND 3 ON A-101. BASE BID PROVIDES A SLOPED
FLOOR ONLY, WITH NO GRATE, AND NO CONTAINMENT
STRUCTURE (WALLS, SUMP), AND GRADE BEAMS AT
TANK LOCATION USING STANDARD GB-2 DIMENSIONS
AND REINFORCEMENT.
BID OPTION 3: DECK REPAIR #1:
CUT AND REMOVE 1,520 SF OF CONCRETE DECK AS
SHOWN ON SHEET C-103. EXCAVATE 18� OF
SUBGRADE AND REPLACE WITH 12� BANK RUN
GRAVEL, 6� CRUSHED GRAVEL AND 8� CAST IN
PLACE CONCRETE DECK.
BID OPTION 4: DECK REPAIR #2:
CUT AND REMOVE 22,550 SF OF CONCRETE DECK AS
SHOWN ON SHEET C-105. EXCAVATE 18� OF
SUBGRADE AND REPLACE WITH 12� BANK RUN
GRAVEL, 6� CRUSHED GRAVEL AND 8� CAST IN
PLACE CONCRETE DECK.
2014-06-25T08:29:00-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
2014-06-25T08:28:24-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
2014-06-25T08:27:38-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
2014-06-25T08:29:56-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
2014-06-25T08:31:51-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
2014-06-25T08:33:09-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
2014-06-25T08:34:08-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
STRUCTURAL NOTES
S-001 8
EJG
STRUCTURAL
A. A. JACOBS BY
JJD
P4991006d08.dwg
DESIGN LOADS
1. THE DRAWINGS COMPLY WITH THE APPLICABLE REQUIREMENTS OF THE FOLLOWING STANDARDS:
a. INTERNATIONAL BUILDING CODE (IBC) 2012
b. ASCE/SEI 7-10 �MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES�
2. BUILDING OCCUPANCY CATEGORY II
3. DEAD LOADS:
a. ROOF 20 PSF
4. LIVE LOADS:
a. ROOF 20 PSF
b. FLOORS 250 PSF
c. WEIGHT OF BOAT 40,000 LBS
d. TRAVEL LIFT WHEEL LOAD
(MARINE TRAVEL LIFT MODEL NO. 35 BFM) 18,000 LBS
e. OVERHEAD BRIDGE CRANE 2 TONS
5. SNOW LOADS:
a. GROUND SNOW LOAD (PG) 50 PSF
b. IMPORTANCE FACTOR (IS) 1.0
6. WIND LOADS:
a. BASIC WIND SPEED, 3-SECOND GUST (V) 115 MPH
b. EXPOSURE D
7. SEISMIC LOADS:
a. SPECTRAL RESPONSE ACCELERATIONS: SS 0.200
S1 0.080
b. IMPORTANCE FACTOR (IE) 1.0
c. SITE CLASSIFICATION D
d. SEISMIC DESIGN CATEGORY B
GENERAL NOTES
1. NOTES ON THESE DRAWINGS ARE NOT INTENDED TO REPLACE SPECIFICATIONS. SEE
SPECIFICATIONS FOR REQUIREMENTS IN ADDITION TO GENERAL NOTES. INCONSISTENCIES
BETWEEN THESE DRAWINGS AND THE SPECIFICATIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE CONTRACTING OFFICERS TECHNICAL REPRESENTATIVE (COTR) PRIOR TO
PROCEEDING WITH THE AFFECTED PORTION OF THE WORK.
2. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH JOB SPECIFICATIONS AND
ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND SITE DRAWINGS. CONSULT THESE
DRAWINGS FOR LOCATIONS AND DIMENSIONS OF OPENINGS, CHASES, INSERTS, REGLETS,
SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.
3. THE TERM LICENSED ENGINEER IN THIS DOCUMENT REFERS TO AN ENGINEER LICENSED IN
THE STATE OR JURISDICTION CONTAINING THIS PROJECT.
4. MAKE NO DEVIATIONS FROM THE DOCUMENTS WITHOUT WRITTEN DIRECTION FROM THE COTR.
5. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD. NOTIFY THE COTR OF DISCREPANCIES
BETWEEN THE NOTES, DRAWINGS, SPECIFICATIONS, AND EXISTING CONDITIONS BEFORE
PROCEEDING WITH THE AFFECTED PORTIONS OF THE WORK.
6. COORDINATE ALL WORK WITH THE OWNER TO MINIMIZE DISRUPTION TO OPERATIONS, AND
PROTECT EXISTING FACILITIES, STRUCTURES, AND UTILITIES FROM DAMAGE.
7. THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE ONLY AFTER THE
STRUCTURAL WORK CONTAINED IN THE DRAWINGS IS COMPLETED. IT IS THE CONTRACTOR'S
SOLE RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE THE
SAFETY OF THE BUILDING AND ITS COMPONENTS DURING CONSTRUCTION. THIS INCLUDES
THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS OR
TIEDOWNS. SUCH MATERIAL SHALL REMAIN THE PROPERTY OF THE CONTRACTOR AFTER
COMPLETION OF THE PROJECT.
8. CONSIDER SECTIONS AND DETAILS SHOWN ON ANY STRUCTURAL DRAWINGS TO BE TYPICAL
FOR SIMILAR CONDITIONS AS DETERMINED BY THE ENGINEER.
9. SUBMIT COMPLETE SHOP DRAWINGS FOR ALL PARTS OF THE WORK, INCLUDING DESCRIPTION
OF SHORING, AND CONSTRUCTION METHODS AND SEQUENCING WHERE APPLICABLE. NO
PERFORMANCE OF THE WORK SHALL COMMENCE WITHOUT REVIEW OF THE SHOP DRAWINGS BY
THE COTR.
10. ADHERE TO ALL APPLICABLE FEDERAL, STATE, AND MUNICIPAL LAWS, RULES, REGULATIONS, AND ORDINANCES, INCLUDING THE FEDERAL DEPARTMENT OF LABOR OCCUPATIONAL SAFETY
AND HEALTH ACT (OSHA).
FOUNDATION NOTES
1. FOUNDATION DESIGN IS BASED ON DRIVEN, CONCRETE FILLED STEEL END BEARING PILES.
2. EXTEND BOTTOM OF EXTERIOR GRADE BEAMS AT LEAST 5'-0"�BELOW THE FINAL EXTERIOR
GRADE
3. HORIZONTAL JOINTS ARE NOT PERMITTED IN THE WALLS OR SLABS UNLESS OTHERWISE NOTED.
4. PROTECT SOILS EXPOSED AT THE BASE OF ALL SATISFACTORY FOUNDATION EXCAVATIONS
AGAINST ANY DETRIMENTAL CHANGE IN CONDITION, SUCH AS DISTURBANCE FROM RAIN OR
FROST. DRAIN SURFACE RUNOFF AWAY FROM THE EXCAVATIONS. ANTICIPATE GROUNDWATER IN
EXCAVATIONS AND EMPLOY APPROPRIATE DEWATERING MEASURES.
5. SLOPE EXCAVATIONS AS REQUIRED FOR STABILITY AND SAFETY OR PROVIDE SHEETING OR
SHORING IN ACCORDANCE WITH OSHA REQUIREMENTS. BRACED EXCAVATIONS SHALL BE
DESIGNED BY A LICENSED PROFESSIONAL ENGINEER.
CONCRETE NOTES
1. CONCRETE WORK SHALL CONFORM TO "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318)," AND "SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301)." THE CONTRACTOR SHALL HAVE AVAILABLE ON SITE AT ALL TIMES A COPY OF ACI "FIELD REFERENCE MANUAL SP-15".
2. REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 60 DEFORMED BARS AND SHALL BE DETAILED, FABRICATED AND PLACED IN ACCORDANCE WITH ACI 315, LATEST EDITION. WELDING OF
REINFORCEMENT SHALL NOT BE PERMITTED.
3. PORTLAND CEMENT SHALL CONFORM TO ASTM C150 TYPE I OR II. AGGREGATES SHALL CONFORM TO
ASTM C33 CLASS 3M.
4. CONCRETE MIX DESIGN:
a. READY-MIX CONCRETE MUST COMPLY WITH THE REQUIREMENTS OF ASTM C94, AND AS SPECIFIED
HEREIN. PROVIDE BATCH TICKET FOR EACH BATCH DISCHARGED AND USED IN WORK, INDICATING PROJECT NAME, MIX TYPE, MIX TIME, BATCH QUANTITY, AND PROPORTIONS OF INGREDIENTS.
JOB-SITE MIXING WILL NOT BE PERMITTED.
b. SUBMIT CONCRETE MIX DESIGNS TO THE COTR FOR REVIEW. NO CONCRETE SHALL BE PLACED
WITHOUT THE DESIGN MIX BEING REVIEWED BY THE COTR.
c. CONCRETE STRENGTH (f�c) SHALL BE 4,500 PSI AT 28 DAYS FOR PILE CAPS, GRADE BEAMS, FOUNDATION WALLS, PIERS, AND SLABS.
d. AGGREGATE: 3/4" NOMINAL MAXIMUM.
e. CONCRETE EXPOSED TO WEATHER SHALL HAVE 4% TO 6% ENTRAPPED AIR.
f. SLUMP: 4"(±1") BEFORE ADDITION OF HIGH RANGE WATER REDUCER OR PLASTICIZER. MAXIMUM
SLUMP AFTER ADDITIONOF ADMIXTURE SHALL BE 8 INCHES.
g. ADJUSTMENT TO CONCRETE MIXES: MIX ADJUSTMENTS MAY BE REQUESTED BY THE CONTRACTOR, WHEN CHARACTERISTICS OF THE MATERIALS, JOB CONDITIONS, WEATHER OR OTHER
CIRCUMSTANCES WARRANT, AT NO ADDITIONAL COST TO THE OWNER AND AS ACCEPTED BY THE
COTR. LABORATORY TEST DATA FOR THE REVISED MIX DESIGN AND STRENGTH DATA MUST BE
SUBMITTED AND ACCEPTED BY THE COTR BEFORE USING IN WORK.
h. WATER MAY BE ADDED AT THE PROJECT SITE ONLY IF THE MAXIMUM SPECIFIED WATER-CEMENT
RATIO AND SLUMP ARE NOT EXCEEDED. CONTRACTOR SHALL HAVE BATCH TICKET INDICATING
WATER AND CEMENT MIXED IN THE PLANT, AND SHALL RECORD THE WATER ADDED AS EVIDENCE
THAT THE WATER-CEMENT RATIO HAS NOT BEEN EXCEEDED.
5. COMPLETE SHOP DRAWINGS AND SCHEDULES OF ALL REINFORCING STEEL SHALL BE PREPARED BY THE CONTRACTOR AND SUBMITTED TO THE COTR FOR REVIEW. PROVIDE NECESSARY ACCESSORIES TO HOLD
REINFORCEMENT SECURELY IN POSITION.
6. MINIMUM CONCRETE PROTECTIVE COVERING FOR REINFORCEMENT SHALL BE AS FOLLOWS UNLESS NOTED
OTHERWISE
a. SURFACES CAST AGAINST AND PERMANENTLY IN CONTACT WITH EARTH: 3"
b. FORMED SURFACES IN CONTACT WITH EARTH OR EXPOSED TO WEATHER: 2"
c. SURFACES NOT IN CONTACT WITH EARTH OR EXPOSED TO WEATHER: 1 1/2"
7. REINFORCEMENT SHALL BE CONTINUOUS AROUND CORNERS AND AT INTERSECTIONS. PROVIDE LAPPED BARS AT SPLICES OR HOOKED BARS AT DISCONTINUOUS ENDS. PROVIDE CLASS B TENSION LAP
SPLICES FOR ALL REINFORCING UNLESS OTHERWISE SHOWN ON PLAN.
8. PROVIDE PVC SLEEVES WHERE PIPES PASS THROUGH EXTERIOR CONCRETE OR SLABS UNLESS NOTED
OTHERWISE.
9. COMPLETE INSTALLATION OF REINFORCEMENT AT LEAST 24 HOURS PRIOR TO THE SCHEDULED
CONCRETE PLACEMENT. NOTIFY THE COTR OF COMPLETION AT LEAST 24 HOURS PRIOR TO THE
SCHEDULED COMPLETION OF THE INSTALLATION OF REINFORCEMENT.
10. PLACE CONCRETE IN THE PRESENCE OF A REPRESENTATIVE OF AN APPROVED TESTING AGENCY.
11. DO NOT PLACE CONCRETE IN WATER OR ON FROZEN GROUND. PLACE CONCRETE WITHOUT HORIZONTAL CONSTRUCTION JOINTS EXCEPT WHERE SHOWN OR NOTED. PROVIDE VERTICAL CONSTRUCTION JOINTS
AND STOPS IN CONCRETE WORK AT MIDSPAN OR AT POINTS OF MINIMUM SHEAR.
12. PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX.
13. HOT WEATHER CONCRETING SHALL CONFORM TO ACI 305. COLD WEATHER CONCRETING SHALL
CONFORM TO ACI 306.
14. DELAY FLOATING AND TROWELING UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN. FINISHING
OF SLAB SURFACES SHALL COMPLY WITH THE RECOMMENDATIONS OF ACI 302 AND 304.
15. TROWEL FINISH AND SMOOTH TOP OF FOUNDATION WALL. TYPE B SURFACE IS REQUIRED FOR ALL CAST
IN PLACE CONCRETE WORK UNLESS NOTED OTHERWISE.
16. PROVIDE 7 DAY CURING IMMEDIATELY AFTER FINISHING USING APPROVED CURING METHOD.
17. REPAIR CONCRETE EXHIBITING VOIDS, SPALLS OR OTHERWISE DAMAGED SURFACE WITH DRY PACK OR CEMENT GROUT AND FINISH FLUSH. AT THE DISCRETION OF THE COTR OR AS QUALIFIED BY TESTING, REMOVE AND REPLACE EXCESSIVE "HONEYCOMBS" AT THE EXPENSE OF THE CONTRACTOR.
METAL BUILDING NOTES
1. THESE NOTES ARE TO AUGMENT PROJECT SPECIFICATIONS. SEE PROJECT SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
2. DESIGN BUILDING TO SUPPORT HANGING MECHANICAL LOADS. SEE MECHANICAL DRAWINGS FOR MORE
INFORMATION.
3. SEE ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ROOF AND WALL PENETRATIONS.
4. SUBMIT COMPLETE SHOP DRAWINGS AND CALCULATIONS SEALED BY A LICENSED ENGINEER REGISTERED
IN THE STATE CONTAINING THIS PROJECT.
5. FOUNDATION DESIGN IS BASED ON ASSUMED BUILDING LOADS & FRAME SIZES. CONTRACTOR SHALL PROVIDE A REDESIGN OF THE FOUNDATIONS, SIGNED AND SEALED BY AN ENGINEER LICENSED IN THE STATE OF MAINE IF ACTUAL BUILDING LOADS AND FRAME SIZES EXCEED ASSUMED SIZES. SEE
BUILDING REACTION SCHEDULE ON SHEET S-101.
2014-06-25T08:35:00-0400
JACOBS.ALFRED.A.JR.1271168337
BUILDING FRAME REACTION SCHEDULE
LOCATION
Ry
Rx
MAX COLUMN
DEPTH AT BASE
PLATE
GRAVITY UPLIFT
A1/B1 15 KIPS -11 KIPS 5 KIPS 12 INCHES
A2/B2 26 KIPS -19 KIPS 6 KIPS 12 INCHES
A3/B3 26 KIPS -19 KIPS 7 KIPS 12 INCHES
A4/B4 26 KIPS -19 KIPS 6 KIPS 12 INCHES
A5/B5 15 KIPS -11 KIPS 5 KIPS 12 INCHES
A.1/1 17 KIPS -12 KIPS 3 KIPS 10 INCHES
A.9/1 17 KIPS -12 KIPS 3 KIPS 10 INCHES
A.2/5 14 KIPS -10 KIPS 4 KIPS 12 INCHES
A.8/5 14 KIPS -10 KIPS 4 KIPS 12 INCHES
1' - 5" 14' - 7" 16' - 0" 16' - 0" 14' - 7"
1' - 5"
64' - 0"
1'
PC-1
PC-1PC-1PC-1
PC-1 PC-1
P18P18 P18 P18
P18P18P18P18P18
P18
T.O.W. 99'-0" T.O.W. 99'-0"
7'
1' - 2"
SEE SLAB SCHEDULE ON SHEET S-501 FOR REINFORCING
TOP OF SLAB ELEVATION 100'-0" AT H.P., 99'-10" AT L.P.
"PC-1
GB-1
GB-1
H.P.
L.P.
SLOPE
SL
A2
S-502
CONTAINMENT TANK
SEE BID OPTION #2 ON SHEET G-001.
EQ
6'
8' - 0" 6' - 0" 9' - 2"
S2
B3
S3
S2
8'
DO
PE
N
IN
GB-3
GB-3
P14
(2) #5 HOOKED END
HAIR PINS (TYP)
COORDINATE WIND
COLUMNS WITH OH
DOOR MANUFACTURER
(VERIFY CLEARANCES)
S-501
B2
NOTE: DO NOT SAWCUT SLAB.
SLAB IS STRUCTURAL "ELEVATED" SLAB
S2S2
A4
T.O.W.
99'-0"
A3
S1
BOLLARD (SEE ARCH)
1. SEE SHEET S-001 FOR STRUCTURAL NOTES.
2. SEE SHEET G-001 FOR BID OPTIONS.
3. SEE SHEETS S-501 & S-502 FOR FOUNDATION DETAILS AND SECTIONS.
4. ALL ELEVATIONS NOTED ON STRUCTURAL DRAWINGS ARE BASED ON 100'-0" REFERENCED TO
LOCAL SURVEY DATUM OF 97.40'. SEE CIVIL DRAWINGS FOR MORE INFORMATION.
5. CONTRACTOR SHALL COORDINATE WITH BUILDING MANUFACTURER FOR REQUIRED COLUMN
SETTING REQUIREMENTS (e.g. GROUT, LEVELING, PLATES, THREADED PROJECTION & NUTS, BOLT
SIZES & LOCATIONS ETC).
6. GRID LINES AND GRID DIMENSIONS ARE TO CENTERS OF PILE CAPS AND PIERS- SEE METAL
BUILDING MANUFACTURER'S DRAWINGS FOR COLUMN LOCATIONS.
7. SEE METAL BUILDING NOTE 5 ON SHEET S-001 FOR POTENTIAL RE-DESIGN REQUIREMENTS.
B.O. INDICATES BOTTOM OF
CL INDICATES CENTER LINE
OH INDICATES OVER HEAD
T.O.P. INDICATES TOP OF PIER ELEVATION, T.O.P = 100'-6" (U.N.O.).
T.O.F. INDICATES TOP OF FOOTING/PILE CAP ELEVATION, T.O.F. = 97'-0" (U.N.O.).
T.O.W. INDICATES TOP OF WALL ELEVATION, T.O.W. = 104'-0" (U.N.O.).
H.P. INDICATES HIGH POINT ON FLOOR SLAB (SEE PLAN)
L.P. INDICATES LOW POINT ON FLOOR SLAB (SEE PLAN).
PXX INDICATES PIER TYPE, SEE SCHEDULE ON S-501.
PC-X INDICATES PILE CAP TYPE, SEE S-501.
GB-X INDICATES GRADE BEAM TYPE, SEE S-501.
INDICATES SLAB TYPE, SEE S-501.
INDICATES VERTICAL ROD BRACING PER BUILDING MANUFACTURER.
INDICATES CONCRETE FILLED STEEL PILES. SEE STEEL PILE NOTES FOR SIZE.
SX
LEGEND:
PILE (TYP)
6' - 7" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 6' - 7"
61' - 2"
EA
M
YP
GR
AD
BEAM TYP
CL GRADE
9'
1/
2" 9'
3'
N
TA
IN
M
EN
TA
S-
SE
DE
IL
PILE (SEE PLAN)
SLAB SLOPED TO CENTER
SEE SLAB SCHEDULE ON SHEET
S-501 FOR REINFORCING TOP OF
SLAB ELEVATION 94'-6" AT H.P.,
92'-6" AT L.P.
CONCRETE TANK
WALL (SEE PLAN
AND SECTIONS)
L.P.H.P.
7' - 4" 4"
G R
AD
E B
M
CL WALL & PILES
CL WALL & PILES
G R
AD
E B
SEE BID OPTION #2
ON SHEET G-001.
N
TA
IN
M
EN
LE
GT
PI
LE
V
AR
IE
STEEL PIPE PILE (SEE NOTE 1)
CONCRETE (SEE NOTE 3)
O.D. 8-5/8"A A
SECTION A-A
I.D. 8-3/16"
CONICAL POINT: VERSA-STEEL, INC
VS 900 OR EQUAL
60.00° 5/16
STEEL PILE NOTES:
1. STEEL PIPE PILES SHALL BE ASTM A252 GRADE 2 WITH AN OUTSIDE DIAMETER OF 8-5/8 INCHES
AND A WALL THICKNESS OF 7/32 INCHES.
2. PRIOR TO PLACEMENT OF CONCRETE, THE PILES SHALL BE INSPECTED TO CONFIRM FULL DEPTH
AND DRY CONDITIONS.
3. CONCRETE SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3,000 PSI.
4. CONTRACTOR SHALL SUBMIT A DESCRIPTION OF THE PILE DRIVING EQUIPMENT PRIOR TO DRIVING
PILES. THE SUBMITTAL SHALL INCLUDE A DESCRIPTION OF THE HAMMER, HAMMER CUSHION,
HELMET AND PILE CUSHON.
5. PILES SHALL ACHIEVE A CAPACITY OF 18 TONS.
6. PILES ARE END BEARING PILES AND SHALL BE DRIVEN TO BEDROCK TO ACHIEVE THE REQUIRED
CAPACITY. THE LENGTH OF PILES WILL VARY AS THE DEPTH OF BEDROCK VARIES UNDER
FOOTPRINT OF THE BUILDING. THE ESTIMATED AVERAGE LENGTHS OF PILES IS 15 FEET.
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
FOUNDATION PLAN
S-101 9
P4991006d09.dwg
1/8" = 1'-0"A3 FOUNDATION PLAN
NORTH4' 8' 16'0
1/8" = 1'-0"A1 PILE PLAN
1/4" = 1'-0"B3 PART PLAN - B.O. CONTAINMENT TANK 1/2" = 1'-0"B1 PILE DETAIL
2' 4' 8'0
1' 2' 4'0
2014-06-25T08:35:51-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
*W14x34 STEEL FRAMING PER
BUILDING MANUFACTURER
WALL GIRTS PER BUILDING
MANUFACTURER
C1
2-TON SINGLE HOIST
UNDERHUNG BRIDGE CRANE
SEE BID OPTION #1 ON
SHEET G-001.
14' - 7" 16' - 0" 16' - 0" 14' - 7"
*W14x34
61' - 2"
B1
S-102
*CRANE RUNWAY BEAMS
SHALL BE OF SIZE NOTED
OR APPROVED EQUIVALENT
1. SEE SHEET S-001 FOR STRUCTURAL NOTES.
2. SEEE SHEET G-001 FOR BID OPTIONS.
3. SEE SHEET S-502 FOR FRAMING DETAILS.
4. ALL ELEVATIONS NOTED ON STRUCTURAL DRAWINGS ARE BASED ON 100'-0" REFERENCED TO
LOCAL SURVEY DATUM OF 97.40'. SEE CIVIL DRAWINGS FOR MORE INFORMATION.
5. TOP OF RUNWAY BEAM ELEVATION = 126'-6" (U.N.O.). COORDINATE WITH CRANE MANUFACTURER AND
CRANE PICK REQUIREMENTS. SEE BID OPTION #1 ON SHEET G-001.
6. REFER TO CRANE MANUFACTURER FOR MORE INFORMATION. SEE BID OPTION #1 ON SHEET G-001.
7. GRID LINES AND GRID DIMENSIONS ARE TO CENTERS OF PILE CAPS AND PIERS- SEE METAL
BUILDING MANUFACTURER'S DRAWINGS FOR COLUMN LOCATIONS.
INDICATES VERTICAL ROD BRACING PER BUILDING MANUFACTURER.
OH INDICATES OVER HEAD
64' - 0"
3' - 10"
EXTENTS OF PICK AREA
56' - 4" 3' - 10"
5'
TE
N
C K A
RE
S-102
APPROX
4' - 2"
AP
PR
AP
PR
" APPROX
4' - 1"
COORDINATE OH DOOR
CLEARANCES WITH CRANE
PICK REQUIREMNTS
C2
B A
TE
N
C K A
5' - 4"
EXTENTS OF PICK AREA
29' - 4" 5' - 4"
H
EI
GH
TO
AR
AT
SEE BID OPTION #1
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
1/8" = 1'-0"
CRANE RAIL FRAMING
S-102 10
P4991006d10.dwg
1/8" = 1'-0"A3 CRANE RAIL FRAMING
4' 8' 16'0 1/8" = 1'-0"A1 CRANE PICK PLAN
1/8" = 1'-0"B1 CRANE PICK SECTION
2014-06-25T08:42:56-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
(2) #4 REINFORCING
BARS (4'-0" LONG) AT
ALL SLAB CORNERS (TYP.)
TOP OF BAR (-) 1 1/2"
FROM TOP OF SLAB
EDGE OF CONCRETE FLOOR
SLAB ON GRADE
FLOOR SLAB, SEE PLAN
3"
SLAB SCHEDULE
TYPE DEPTH TOP REINFORCING BOTTOM REINFORCING TEMPERATURE NOTES
S1 8" #5 @ 9" O.C. #5 @ 9" O.C. (1) LAYER OF REINFORCING
S2 8" #5 @ 6" O.C. #5 @ 6" O.C. (1) LAYER OF REINFORCING
S3 10" #5 @ 6" O.C. #5 @ 6" O.C. #5 @ 6" O.C. (2) LAYERS OF REINFORCING
GRADE BEAM SCHEDULE
TYPE SIZE WxD TOP REINFORCING BOTTOM REINFORCING STIRRUPS NOTES
GB-1 24"x24" (4) #5 (4) #5 #3 @ 10" O.C.
GB-2 24"x18" (4) #5 (4) #5 #3 @ 7" O.C.
GB-3 16" x 24" (4) #5 (4) #5 #3 @ 10" O.C.
PIER SCHEDULE
TYPE SIZE WxD VERTICAL REINFORCING STIRRUPS NOTES
P14 14"x14" (4) #5 (3) #3 @ TOP 5", BALANCE @ 8" O.C. PROVIDE #5 "U" BARS (SEE DETAILS)
P18 18"x18" (8) #5 (3) #3 @ TOP 5", BALANCE @ 8" O.C. PROVIDE #5 "U" BARS (SEE DETAILS)
COL
COL CONCRETE PILE CAP
PILE
(2) PILES SEE PLAN
#5 BARS W/ STD HOOK & 36"
EMBED. INTO PILE
#5 @ 8" O.C., T&B
CONTINUE GRADE BEAM
REINF THROUGH PILE CAP
(NOT SHOWN FOR CLARITY)
5'-6"
2'
6"
2'
8"
1'-9" 1'-9"
EQEQ
VAPOR BARRIER
SEE ARCH
REINF SEE PLAN
12" MIN. COMPACTED
STRUCTURAL FILL
SEE PLAN
T.O. SLAB
TH
TH
SLAB REINF SEE PLAN
T.O. SLAB
GRADE BEAM REINF SEE
SCHEDULE
PILE SEE PLAN
CL PIER & GRADE BEAM
SEE PC-1 FOR TOP OF
PILE REQUIREMENTS
SEE
SC
ED
TYP WALL
REINF
ADDT'L #5 EA FACE
T.O. WALL
PL
STD 90° HOOK
ALTERNATE
CORNER BARS TO MATCH
HORIZ WALL REINF
FN
AL
1 2
1' - 6"
1' - 6"
P18 P18
9"
9" 9"
(REF)
7"
PIER REINFORCING
SEE SCHEDULE
PIER REINFORCING
U
FA
C
TU
VE
RI
FY
#5 @ 12" O.C. W/
STD HOOKS (TYP)
9" 9"
ADJUST PIER LOCATION
W/ DOOR MFG
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
FOUNDATION DETAILS
S-501 11
P4991006d11.dwg
1/2" = 1'-0"A1 RE-ENTRANT BAR DETAIL
1/2" = 1'-0"B1 PILE CAP (PC-1) DETAIL
1/2" = 1'-0"A2 SLAB DETAIL
1/2" = 1'-0"C1 GRADE BEAM DETAIL
1/2" = 1'-0"A4 WALL DETAIL AT DOOR OPENING
1/2" = 1'-0"A4' CONCRETE WALL DETAILS
1/2" = 1'-0"B2 PIER DETAILS
2014-06-25T08:43:58-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
CONCRETE SLAB (SEE PLAN)
GRADE BEAM (SEE PLAN)
#5 BARS @
12" O.C. EW
FINISH GRADE
(SEE CIVIL)
T.O. SLAB (H.P.)
REVEAL
(SEE ARCH)
ED
(4) #5 TOP AND BOTTOM
#3 TIES @ 10" O.C.
T.O. GRADE BEAM
STRUCTURAL SLAB, NO GAP/EXP
JOINT MATERIAL BETWEEN SLAB &
WALL
INSULATION, SEE ARCH
SLAB GRADE BEAM (SEE PLAN)
INSULATION WRAPS AROUND GRADE BEAM.
SEE ARCH FOR MORE INFORMATION
STEEL COLUMN (BY BUILDING MANUF)
PILE CAP (SEE PLAN)
T.O. PIER
T.O. PILE CAP
GRID LINES AND GRID DIMENSIONS ARE
TO CENTERS OF PILE CAPS AND PIERS
VERIFY W/ BLDG MANUF
CONTINUOUS GRADE BEAM
REINF. THROUGH PILE CAP
(NOT SHOWN FOR CLARITY)
PIER (SEE PLAN)
T.O. RUNWAY BEAM
RUNWAY BEAM
STIFFENER PLATE
B/S TYP IF REQ'D
STEEL FRAMING
AND PANELS PER
BUILDING MANUF
HANGING BRACKET AS REQ'D
LATERAL & LONGITUDINAL BRACING
NOT SHOWN. COORDINATE &
PROVIDE PER CRANE/BUILDING
MANUFACTURER'S REQUIREMENTS
EAVE
SEE ARCH
3" CLEAR
OBSTRUCTION ABOVE
AR
BRIDGE CRANE
8" SEE PLAN 8"
CONCRETE SLABS (SEE PLAN)
WATERSTOP (TYP)
#5 BARS @ 12" O.C. EW
T.O. SLAB (L.P.)
EQ1' - 6"EQ
SEE SCHEDULE SEE SCHEDULE
ED
CONCRETE SLAB
(SLOPED TO CENTER
SEE PLAN)
LAP WALL REINF. W/ HOOKED
DOWELS INTO GRADE BEAM
PROVIDE HOT DIP GALVANIZED GHB 1-1/4"x1/4" BAR GRATING & L2x1-1/2x1/4 (LLH) H.D. GALV CONT. PERIMETER FRAME, W/ 1/2"øx3" HEADED
STUDS @ 16" O.C.
NOTE: SUMP AND BAR GRATING ARE DESIGNED FOR
UNIFORM FLOOR LOAD ONLY - NOT FOR BOAT LOADING.
SEE BID OPTION #2 ON SHEET G-001.
ED
CONCRETE SLAB (SEE PLAN)APRON
SEE WALL SECTION
FOR REINF.
AX CONSTRUCTION PAPER BOND BREAK
SEE WALL SECTION
FOR REINF.
ED
CONCRETE SLABS (SEE PLAN)
T.O. SLAB (L.P.)
SEE SCHEDULE SEE PLAN SEE SCHEDULE
CONCRETE SLAB
(SEE PLAN)
REINFORCING SHALL BE
CONTINUOUS BETWEEN
BOLLARD AND FACE OF
PILE CAP
APRON
BOLLARD (SEE ARCH)
PILE CAP (SEE PLAN)
4 1/2" MIN
PIPE SLEEVE
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
SECTIONS AND DETAILS
S-502 12
P4991006d12.dwg
1/2" = 1'-0"A2 SECTION AT CONC WALL
1/2" = 1'-0"A1 SECTION AT COL PIER
3/4" = 1'-0"C1 SECTION AT CRANE BEAM
1' 2' 3'0
1' 2' 4'0 1' 2' 4'0
1' 2' 4'0 1/2" = 1'-0"B3 SECTION AT CONTAINMENT TANK
1/2" = 1'-0"A4 SECTION AT OH DOOR
1' 2' 4'0 1/2" = 1'-0"A3 SECTION AT MAN DOOR
1/2" = 1'-0"C3 SECTION AT SLAB S3- BASE BID
1/2" = 1'-0"C2 SECTION AT BOLLARD
2014-06-25T08:44:36-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
A-201
C3
5"
0"
5"
1'-5" 2'-7" 3'-4"
8'-8" 16'-0" 16'-0" 8'-8" 3'-4"
2'-7" 1'-5"
64'-0"
A-301
A-101
EXTERIOR WALL MOUNTED
LIGHT FIXTURE
EXIT LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE
CEILING AND WALL
MOUNTED LIGHT FIXTURES
FIRE EXTINGUISHER.
20lb ABC WITH WALL HOOK
INTERIOR LINER PANEL
D O
EN
OVERHEAD COILING
DOOR TRACK
STRUCTURAL STEEL
DOOR SUPPORT
CONCRETE
8" 2'-0"
6" DIA
BOLLARD
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
FLOOR & RCP PLANS
A-101 13
ARCHITECTURAL
P3578953d13
4' 8' 16'0SCALE: 1/8" = 1'-0"A2 FLOOR PLAN
4' 8' 16'0SCALE: 1/8" = 1'-0"B2 REFLECTED CEILING PLAN
1. SEE SHEET G-001 FOR LEGEND, ABBREVIATIONS AND GENERAL NOTES.
2. SEE SHEET A-601 FOR DOOR AND WINDOW TYPES AND DOOR SCHEDULE.
3. ALL ELEVATIONS NOTED ON ARCHITECTURAL DRAWINGS ARE BASED ON 100'-0"
REFERENCED TO LOCAL SURVEY DATUM OF 97.40'. SEE CIVIL DRAWINGS FOR
MORE INFORMATION.
TYP
INTERIOR LINER PANELS FROM FINISHED FLOOR TO UNDERSIDE OF ROOF SECONDARY FRAMING.
DASHED LINE INDICATES EXTENTS OF UNDER SLAB WASH CONTAINMENT TANK, SEE BID OPTION
#2 ON SHEET G-001.
SQUARE STEEL DRAINAGE GRATE, SEE BID OPTION #2 ON SHEET G-001.
GAS FIRED RADIANT HEATER, SEE MECHANICAL.
PLAN DIMENSIONS SHOWN ARE TO EXTERIOR FACE OF CONCRETE WALLS.
6" DIA BOLLARDS, CONCRETE FILLED AND PAINTED SAFETY YELLOW. FOR EXTERIOR BOLLARDS, REFERENCE CIVIL DRAWINGS. FOR EXTERIOR BOLLARDS, REFERENCE STRUCTURAL DRAWINGS.
FUEL GAS PIPING, SEE MECHANICAL.
BOAT AND CRADLE PROFILE; (N.I.C.)
OVERHEAD CRANE BRIDGE AND RUNWAY FRAMING, SEE BID OPTION #1 ON SHEET G-001.
EMERGENCY EYE/FACE WASH; PORTABLE SELF-CONTAINED DUAL 32oz BOTTLES WITH HIGH
VISIBILITY WALL MOUNT STATION. EQUAL TO FENDALL MODEL WB116270.
SCALE: 1" = 1'-0"A4 BOLLARD DETAIL @ OH DOOR
2014-06-25T08:45:24-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
129'-8"
T.O. CONC WALL
104'-0"
FINISHED FLOOR
100'-0"
A A A AA A AA
2'-7"
8'-0" 4'-0" 4'-0" 8'-0" 4'-0" 4'-0" 8'-0" 4'-0" 4'-0" 8'-0"
2'-7"
TY
12345
10'-4" 10'-4"
A.1A.9
3'-10"3'-10"
BA
A.8A.2
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
EXTERIOR ELEVATIONS
A-201 14
P3578953d14
SCALE: 1/8" = 1'-0"C1 SOUTH ELEVATION
SCALE: 1/8" = 1'-0"A1 NORTH ELEVATION
SCALE: 1/8" = 1'-0"C3 WEST ELEVATION
SCALE: 1/8" = 1'-0"A3 EAST ELEVATION
4' 8' 16'0 4' 8' 16'0
4' 8' 16'04' 8' 16'0
METAL WALL SYSTEM
INSULATED OVERHEAD COILING DOOR
ALUMINUM FIXED WINDOW
INSULATED METAL DOOR AND FRAME
CONCRETE STEM WALLWITH PAINT FINISH, SEE STRUCTURAL.
NOT USED
STANDING SEAM METAL ROOFING
SNOW RETENTION FENCE
DUCT, SEE MECHANICAL.
LIGHT FIXTURE, SEE ELECTRICAL.
ELECTRICAL OUTLET, SEE ELECTRICAL.
FUEL GAS PIPING, SEE MECHANICAL.
LOUVER, SEE MECHANICAL.
EXHAUST FAN, SEE MECHANICAL.
WALL CORNER CLOSURE TRIM, TYPICAL.
BOLLARDS
RIDGE CAP
3. SNOW RETENTION FENCE(S) (KEYED NOTE 8) SHALL BE CALCULATED AND
LAID OUT BY METAL BUILDING MANUFACTURER.
16 16
14 14
2014-06-25T08:46:00-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
T.O. CRANE BEAM
126'-6"
T.O. CRANE BEAM
126'-6"
B4
B3
104'-0"2"
1"+/-
METAL PANEL
CLOSURE TRIM
RIGID INSULATION
CONCRETE WALL
CONTINUOUS
SEALANT
PRE-ENGINEERED
BUILDING STRUCTURE
CONCRETE PIER BEYOND,
SEE STRUCTURAL
SPRAY FOAM INSULATION
1/2" CONTINUOUS
SEALANT JOINT MIN.
SEE DETAIL A4
THIS SHEET FOR
MATERIAL NOTES.
METAL TRACK.
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
SECTIONS & DETAILS
A-301 15
P3578953d15
SCALE: 1/8" = 1'-0"C1 LONGITUDINAL SECTION
SCALE: 1/8" = 1'-0"C3 TRANSVERSE SECTION
4' 8' 16'0 4' 8' 16'0
SCALE: 1 1/2" = 1'-0"A4 DETAIL @ BOTTOM OF WALL
SCALE: 1 1/2" = 1'-0"B4 DETAIL @ EAVE
STANDING SEAM METAL ROOFING SYSTEM
PURLIN
SCALE: 1 1/2" = 1'-0"B3 DETAIL @ RIDGE
STANDING SEAM METAL
ROOFING SYSTEM
PURLIN
GIRT
RIGID WALL
INSULATION, MIN
R-13.3
CONCRETE STEM WALL WITH
PAINT FINISH, SEE STRUCTURAL
R-19 INSULATION WITH 5-PLY
R-19 INSULATION WITH
RIDGE COVER
1/2' 1' 1 1/2'0
1/2' 1' 1 1/2'0SCALE: 1 1/2" = 1'-0"A3 DETAIL @ RAKE
3. SNOW RETENTION FENCE(S) (KEYED NOTE 8) SHALL BE CALCULATED AND
LAID OUT BY METAL BUILDING MANUFACTURER.
INSULATED OVERHEAD COILING DOOR
INSULATED METAL DOOR AND FRAME
CONCRETE STEM WALL
OVERHEAD CRANE, SEE BID OPTION #1 ON SHEET G-001.
STANDING SEAM METAL ROOFING
GAS FIRED RADIANT HEATER, SEE MECHANICAL.
LIGHT FIXTURE, SEE ELECTRICAL.
SNOW RETENTION FENCE
WASTE CONTAINMENT TANK, SEE BID OPTION #2 ON SHEET G-001.
SQUARE STEEL DRAINAGE GRATE, SEE BID OPTION #2 ON SHEET G-001.
LOUVER, SEE MECHANICAL.
PRE-ENGINEERED METAL BUILDING STRUCTURE
METAL RIDGE CAP.
CONTINUOUS HORIZONTAL UNDER-SLAB PERIMETER INSULATION, R-10 & 24" WIDE,
MINIMUM; WRAP CONTINUOUSLY AROUND GRADE BEAMS. CONTINUOUS VERTICAL
INSULATION FROM TOP OF GRADE BEAM TO BOTTOM OF SLAB, R-10 MINIMUM.
BOLLARDS.
BOAT AND CRADLE PROFILE; (N.I.C.)
CLOSURE
BASE FLASHING
STANDING SEAM METAL
ROOFING SYSTEM
R-13 INSULATION WITH
5-PLY VAPOR BARRIER
+ R-19 UNFACED
INSULATION
RIGID WALL INSULATION,
MIN R-5.6.
METAL BUILDING
STRUCTURE
INTERIOR LINER
PANEL
SCALE: 3" = 1'-0"A1 DETAIL @ CONCRETE REVEAL
FASCIA TRIM
RAKE TRIM
COORDINATE WITH PRE-ENGINEERED
METAL BUILDING MANUFACTURER
INSULATION,
INSULATION,
METAL BUILDING
STRUCTURE
R-19 INSULATION WITH
SCALE: 1 1/2" = 1'-0"A2 DETAIL @ COLUMN
SCALE: 3" = 1'-0"B1 DETAIL @ BASE OF WALL
3" 6" 9"0
3" 6" 9"0
PURLINS BEYOND
R-13 INSULATION
R-19
5-PLY
VAPOR
BARRIER
5-PLY
VAPOR
R-19
R-13
R-19 INSULATION
5-PLY VAPOR
R-13 INSULATION
THERMAL STAND-OFF
THERMAL STAND-OFF
Z-FURRING CHANNEL
@ 24" O.C.
REFERENCE
DETAIL C1/S502
2014-06-25T08:46:50-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
FLUSH
WITH
NARROW
VISION
LITE
6"x24"
TEMPERED
GLAZING
WELDED
HOLLOW METAL
FRAME
SEE 2"
OHD
OVERHEAD
COILING
DOOR
D O
EN
DOOR HOOD
EXTERIOR METAL
WALL SYSTEM
MOUNTING PLATE
HEAD CLOSURE TRIM WRAP
PANEL AND RIGID
WALL INSULATION
HEAD TRIM FLASHING
JAMB CLOSURE
TRIM WRAP
D O
EN
RIGID INSULATION
CONCRETE
CONTINOUS
D O
EN
CONTINOUS
STRUCTURAL STEEL GIRT
HOLLOW METAL FRAME
HEAD CLOSURE
SEALANT, EACH SIDE
HEAD TRIM FLASHING
HOLLOW METAL FRAME
GIRT FRAME
GROUT FILL FRAME TO TOP OF
CONCRETE STEM WALL
WINDOW
J1
A-601
4'-0"
4'
TO BOT OF SILL
REFERENCE
BLDG ELEVATIONS
H1
SILL CLOSURE
WINDOW
SILL TRIM FLASHING
STRUCTURAL STEEL GIRT
HEAD CLOSURE
TRIM WRAPHEAD TRIM FLASHING
WINDOWCONTINUOUS
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
WINDOW & DOOR ELEVS
A-601 16
P3578953d16
DOOR SCHEDULE
NO. TYPE
DOOR
RATING
HRDWR
SET NO.
COMMENTSWIDTH HEIGHT THK MAT'L TYPE MAT'L HEAD JAMB
101 OHD 24'-0" 26'-10" INSUL STL 1 OHD STL H2 J2 & J3 MINIMUM CLEAR HEIGHT INDICATED
102 A 3'-0" 7'-0" 1 3/4" INSUL HM 2 1 HM H3 J4
103 A 3'-0" 7'-0" 1 3/4" INSUL HM 2 1 HM H3 J4
SCALE: 1/4" = 1'-0"B3 DOOR & FRAME TYPES
2' 4' 8'0
2' 4' 6'0
SCALE: 1 1/2" = 1'-0"H2 OH DOOR HEAD DETAIL
SCALE: 1 1/2" = 1'-0"J3 OH DOOR JAMB DETAIL @ CONCRETE
SCALE: 1 1/2" = 1'-0"J2 OH DOOR JAMB DETAIL @ WALL PANEL
SCALE: 1 1/2" = 1'-0"H3 HM DOOR HEAD DETAIL
SCALE: 1 1/2" = 1'-0"J4 HM DOOR JAMB DETAIL @ WALL PANEL
SCALE: 1 1/2" = 1'-0"J1 WINDOW JAMB DETAIL
SCALE: 3/8" = 1'-0"A4 WINDOW TYPE
SCALE: 1 1/2" = 1'-0"S1 WINDOW SILL DETAIL
SCALE: 1 1/2" = 1'-0"H1 WINDOW HEAD DETAIL
25'-0
1.
2.
FINISH NOTES:
ROOF, WALL, AND LINER PANELS ARE PREFINISHED FROM MANUFACTGURER.
OWNER TO SELECT COLORS FROM ALL STANDARD OPTIONS.
FIELD PAINTED ITEMS TO MATCH BUILDING FINISHES, EXCEPT SAFETY
MARKINGS, SIGNAGE, ETC.
2014-06-25T08:47:30-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
OA LOUVER L-1
40"x24", MOUNT ABOVE DOOR
MOUNT BOT @ 10'-0" AFF
M-101
6" COMBUSTION AIR INTAKE
W/ WALL CAP & INSECT SCREEN
6" COMBUSTION AIR INTAKE
W/ WALL CAP & INSECT SCREEN
4" EXHAUST FLUE W/ WALL CAP
4" EXHAUST FLUE
W/ WALL CAP
1" LP
1/2" LP FROM SITE STORAGE
TANK
REFER TO SITE UTILITY PLAN
LP PRESSURE REGULATOR
ASSEMBLY
1 1/4"
LP
OA LOUVER L-2
40"x24" - MOUNT BOT @ 10'-0" AFF
A.8 A.2
M-101
C2
1" LP 1" LP
30.00°
E
CE
L L E N
U A
DESIGNED BY:
DRAWN BY:
FLOOR PLAN
M-101 17
PWZ
MECHANICAL
JRS
P3578953d17
PWZ
SCALE: 1/8" = 1'-0"A1 FIRST FLOOR PLAN
AND MODEL NUMBER NOTES
UNIT
NO.
L-1
1. EXTRUDED ALUMINUM LOUVER WITH EXTENDED SILL, BIRD SCREEN, & MOTORIZED DAMPER. INTERLOCK DAMPER OPERATION WITH EXHAUST FANS EF-1 & EF-2.
LOUVER SCHEDULE
FREE AREA
(SQ. FT.)
SP LOSS
(IN. WG)
FREE AREA
VELOCITY
(FPM)
SIZE
WxH
(IN.)
AIRFLOW
(CFM)
BLADE ORIENTATION
& FRAME DEPTH
EF-1
SERVES TYPE
INTAKE 1000 0.025 40x24 3.5 HORIZONTAL / 5" RUSKIN ELF375DX
FAN SCHEDULE
EF-1
1. PROVIDE WITH WALL MOUNTING SLEEVE, WALL MOUNTING SLEEVE GUARD, WALL SHUTTER, WEATHERSHIELD HOOD & WEATHERSHIELD GUARD.
MOUNT FAN APPROXIMATELY 25'-0" AFF.
2. PROVIDE WITH WALL SWITCH. INTERLOCK FAN MOTOR WITH OA LOUVER L-1 & L-2 MOTORIZED DAMPER.
3. PROVIDE FAN AND ALL ACCESSORIES WITH EPOXY POWDER COATING SUITABLE FOR A MARINE ENVIRONMENT.
4. PROVIDE WITH PREMIUM EFFICIENCY MOTOR.
DRIVE
TYPE
DIRECT
CFM
VOLTS
ELECTRICA
DATA
HZPH
AND MODEL
NUMBER
NOTESFAN TYPE
SP
WG
HP
FAN
RPM
MOTOR
RPM
PROPELLER
SERVES
BUILDING EXHAUST 1000 0.375 1/2 860 860 208 1 60 PENN BARRY BC24 1-4
280 1
HEATING AND VENTILATION SYSTEM SEQUENCE OF OPERATION:
HEATING SYSTEM
PROPANE GAS FIRED INFRA-RED HEATERS, RH-1 & 2, WILL BE CONTROLLED MANUALLY BY AN ON/OFF WALL SWITCH. WHEN HEATERS ARE BEING OPERATED, WALL MOUNTED THERMOSTATS (SET AT 50F) CYCLE THE HEATERS TO MAINTAIN SPACE
TEMPERATURE.
VENTILATION SYSTEM
THE VENTILATION SYSTEM CONSISTS OF WALL MOUNTED EXHAUST FANS, EF-1 & 2, AND OUTSIDE AIR INTAKE LOUVERS WITH
MOTOR OPERATED DAMPERS, L-1 & 2.
EF-1 & 2 WILL BE OPERATED MANUALLY UTILIZING A WALL MOUNTED SWITCH. EF-1 & 2 ARE INTERLOCKED WITH L-1&2.
WHEN EF-1 & 2 ARE ON, THE OUTSIDE AIR DAMPERS ARE OPEN. WHEN EF-1 & 2 ARE OFF, THE OUTSIDE AIR DAMPERS ARE
CLOSED.
REFER TO SECTION FOR MOUNTING HEIGHT AND ANGLE OF RADIANT HEATER.
MANUFACTURERS NAME AND MODEL NUMBER ARE USED FOR DESCRIPTIVE
PURPOSES ONLY AND ARE INTENDED TO INDICATE THE STANDARD OF
MATERIAL OR ARTICLES REQUIRED. DESIGN IS PREDICATED AROUND LISTED
MANUFACTURERS AS NOTED ON SCHEDULES AND IS NOT INTENDED TO LIMIT
THE CONTRACTOR TO ONE MANUFACTURER.
SCALE: 1/8" = 1'-0"C1 BUILDING SECTION
GAS FIRED RADIANT HEATER SCHEDULE
RH-1
1. LP GAS TWO STAGE DIRECT VENT RADIANT HEATER.
2. PROVIDE WITH WALL SWITCH.
3. PROVIDE WITH WALL MOUNTED THERMOSTAT. MOUNT THERMOSTAT 60" AFF ON THERMALLY ISOLATED BASE.
GAS
TYPE
LP
INPUT
MBH
VOLTS
DATA
AMPSPH
AND MODEL
NUMBER
NOTES
MIN.
SUPPLY
PRESS
W.C.
SERVES
BUILDING HEATING 125 11" 14" 120 1 2.6 SPACE RAY LTS125-40 1-3
MAX.
SUPPLY
PRESS
W.C.
GENERAL NOTES:
1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO
DRAWINGS MARKED M#.
2. DRAWINGS ARE DIAGRAMMATIC. DETERMINE LOCATIONS OF SYSTEMS
AND COMPONENTS IN FIELD.
3. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.
4. REMOVALS SHALL BE COORDINATED BY THE CONTRACTOR TO MAINTAIN
THE INTEGRITY OF THE BUILDING.
5. VERIFY EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED
DRAWINGS.
6. CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC AND
SPECIFICATIONS.
7. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES
AS NECESSARY TO PREVENT STRESS ON PIPING.
@ AT
A AMP
ABV ABOVE
AFF ABOVE FINISHED FLOOR
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOT BOTTOM
BTUH BTU PER HOUR
CFM CUBIC FEET PER MINUTE
CONC CONCRETE
CONN CONNECTION
DIA DIAMETER
DN DOWN
DWG DRAWING
DWGS DRAWINGS
EA EXHAUST AIR
EF EXHAUST FAN
ELEC ELECTRIC, ELECTRICAL
EXH EXHAUST
F FAN, DEGREES FAHRENHEIT
FLR FLOOR
G GAS
HP HORSEPOWER
HZ HERTZ
IN INCHES
KW KILOWATT
LP LIQUEFIED PROPANE
MBH 1000 BTU PER HOUR
MCA MAXIMUM CIRCUIT AMPS
MD MOTORIZED DAMPER
MFG MANUFACTURER
MIN MINIMUM, MINUTES
N/A NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NFPA NATIONAL FIRE
PROTECTION ASSOCIATION
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
PD PRESSURE DROP
PRESS PRESSURE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE
INCH GAUGE
RA RETURN AIR
RPM REVOLUTIONS PER MINUTE
SF SQUARE FOOT
SP STATIC PRESSURE
SS STAINLESS STEEL
STL STEEL
T THERMOSTAT
TEMP TEMPERATURE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VEL VELOCITY
W WIDTH, WATT
W/ WITH
WC WATER COLUMN
RH-2 LPBUILDING HEATING 125 11" 14" 120 1 2.6 SPACE RAY LTS125-40 1-3
L-2 EF-2 INTAKE 1000 0.025 40x24 3.5 HORIZONTAL / 5" RUSKIN ELF375DX280 1
EF-2 DIRECTPROPELLERBUILDING EXHAUST 1000 0.375 1/2 860 860 208 1 60 PENN BARRY BC24 1-4
SCALE: 1/2" = 1'-0"C2 RADIANT HEATER MOUNTING
2014-06-25T08:48:17-0400
JACOBS.ALFRED.A.JR.1271168337
I am approving this document
LIGHTING
609.6 mm [2'] x 1219.2mm [4'] FLUORESCENT FIXTURE
304.8mm [1'] x 1219.2mm [4'] FLUORESCENT FIXTURE
304.8mm [1'] x 2438.4mm [8'] FLUORESCENT FIXTURE
609.6mm [2'] x609.6mmm [2'] FLUORESCENT FIXTURE
UNDERCABINET FLUORESCENT FIXTURE
FIXTURE WIRED TO EMERGENCY BALLAST
DOWNLIGHT
FLUORESCENT STRIP
WALL MOUNTED FIXTURES
POLE MOUNTED SITE LIGHTING FIXTURE
FIXTURE TYPE (SEE LIGHT FIXTURE SCHEDULE)
FLOOD LIGHT
WALL WASH LIGHT FIXTURE
EXIT SIGN, CEILING MOUNTED
EXIT SIGN, WALL MOUNTED
DUAL HEAD EMERGENCY LIGHT BATTERY PACK
REMOTE EMERGENCY LIGHTING HEAD
EXTERIOR TRAPEZOID WALL PACK
OCCUPANCY SENSOR
ALL CEILING MOUNTED ARE 360 DEGREE
UNLESS OTHERWISE NOTED
HOME RUN
3-WAY TOGGLE SWITCH
4-WAY TOGGLE SWITCH
SINGLE POLE TOGGLE SWITCH
DIMMER SWITCH, INCANDESCENT OR FLUORESCENT AS
REQUIRED.
SINGLE POLE DOUBLE THROW TOGGLE SWITCH, CENTER
POSITION OFF
OCCUPANCY SENSOR SWITCH
INDICATES THE NUMBER OF PUSH BUTTONS, IF MORE THAN
1.
TOGGLE SWITCH WITH PILOT LIGHT
TIMER SWITCH, SPRING WOUND
SWITCH, WEATHER PROOF
DAYLIGHT SENSOR
LIGHTING CONTACTOR
OCCUPANCY SENSOR RELAY
PHOTO CONTROL
TIME CLOCK
ASSOCIATED CONTROL DEVICE
Aa
FIXTURE TYPE (SEE LIGHT FIXTURE SCHEDULE)
SHADING INDICATES SIGN FACE
ARROW INDICATES EGRESS DIRECTION
S3
S4
Sa
INDICATES CONTROLLED FIXTURE
SD
SDT
SOS
SP
ST
SWP
DS
LC
OSR
PC
TC
POWER
FOR ALL FUSED DISCONNECTS AND COMBINATION START
DISCONNECTS AN "*" IN THE FUSE RATING DESIGNATES THE
FUSE SHALL BE SIZED PER MANUFACTURER'S
RECOMMENDATIONS.
OL
J
CB
100A
WEATHER PROOF
E - INSTALLED ON EMERGENCY CIRCUIT (TYP.)
IG - ISOLATED GROUND
S - SWITCHED RECEPTACLE
XP - EXPLOSION PROOF
XP
20/1
60A (4)
(4)1
AMPERE RATING
NEMA ENCLOSURE
NEMA ENCLOSURE
NEMA SIZE (TYP.)
ONE-LINE DIAGRAM
MOLDED CASE CIRCUIT
DISCONNECT, ISOLATION OR SAFETY SWITCH
GROUND
FUSE
POWER TRANSFORMER
OA - LIQUID TYPE SELF COOLED
AA - DRY TYPE SELF COOLED
FA - FAN COOLED
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
GROUND FAULT CURRENT TRANSFORMER
TRANSFER SWITCH
MAGNETIC MOTOR STARTER
FVNR UNLESS OTHERWISE NOTED
FVR - FULL VOLTAGE REVERSING
RVAT -REDUCING VOLTAGE AUTO
TRANSFORMER
2S - TWO SPEED
GENERATOR
METER
A - AMMETER
HZ - FREQUENCY METER
KWH - KILOWATT HOUR
KVAR - KILOVAR METER
PZ - POWER FACTOR METER
V - VOLT METER
VAR - VAR METER
W - WATT METER
WH - WATT HOUR METER
ELECTRONICALLY OPERATED
GROUND FAULT
SHUNT TRIP
SURGE SUPPRESSION DEVICE
EO
GF
ST
SPD
20A
AMPS
CONNECTION
RATIO
NUMBERED REQUIRED
400/120V1
RATIO
NUMBERED REQUIRED
600/52
ATS - AUTOMATIC
MTS - MANUALATS
NEMA SIZE
KWH
AMP
AFC
AFF
AFG
AHJ
AIC
AWG
BB
BFG
BLDG
BOS
CATV
CB
CCTV
CDF
CI
CLG
CP
CPT
CT
CU
DACT
DB
DISC
DN
EMT
EWC
EQP
EXIST
FAA
FACP
FBB
FBO
FLR
FO
FPP
FWE
FU
FVNR
GEN
GFCI
GFE
GND
HP
HTR
IG
IMC
KCMIL
KV
KVA
KVAR
KW
KWH
LA
LTG
METAL CLAD
MAIN CIRCUIT BREAKER
MANUFACTURER
MINERAL INSULATED
MAIN LUG ONLY
MOUNTED
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NEGATIVE
NEUTRAL
NON FUSED
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POWER FACTOR
PRIMARY GROUND
PHASE
PRIVATELY OWNED VEHICLE
POLYVINYL CHLORIDE
ROOM
RIGID STEEL CONDUIT
RESISTANCE TEMPERATURE
DETECTOR
SECONDARY GROUND
SOLID NEUTRAL
SINGLE MODE
SINGLE MODE FIBER OPTIC
SURGE SUPPRESSION DEVICE
SHIELDED TWISTED PAIR
SHIELDED TWISTED TRIPLET
SWITCHBOARD
SWITCHGEAR
THERMOPLASTIC HIGH-HEAT
NYLON COATED
THERMOPLASTIC HEAT & WATER
RESISTANT
TRAFFIC LIGHT
TRAFFIC LIGHT CONTROLLER
TRAFFIC LIGHT SWITCH
TELECOMMUNICATIONS MAIN
GROUNDING BUS BAR
VOLT
VOLT-AMPERE
VOLT-AMPERE REACTIVE
WATT METER
WEATHER PROOF
TRANSFORMER
EXPLOSION PROOF
AMPERE
AVAILABLE FAULT CURRENT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTHORITY HAVING JURISDICTION
AMPERE INTERRUPTING CAPACITY
AMERICAN WIRE GAUGE
BATTERY BOX
BELOW FINISHED GRADE
BOTTOM OF STEEL
CONDUIT, CONDUCTOR
CABLE TELEVISION
CONTROL BOX
CLOSED CIRCUIT TELEVISION
CONTROL DENSITY FILL
(LEAN CONCRETE)
CONTRACTOR INSTALLED
CEILING
CONTRACTOR PROVIDED
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
COPPER
DIGITAL ALARM COMMUNICATOR
TRANSMITTER
DIRECT BURIED
DISCONNECT
DOWN
ELECTRICAL METALLIC TUBING
ELECTRIC WATER COOLER
EQUIPMENT
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL PANEL
FIBER BREAK OUTBOX
FURNISHED BY OTHERS
FLOOR
FIBER OPTIC
FIBER PATCH PANEL
FURNISHED WITH EQUIPMENT
FUSE
FULL VOLTAGE NON REVERSING
GROUND CONDUCTOR
GROUND FAULT CIRCUIT BREAKER
GOVERNMENT FURNISHED EQUIPMENT
GROUND
HORSEPOWER
HEATER
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
KILO
THOUSAND CIRCULAR MILS
KILOVOLT
KILOVOLT-AMPERE
KILOVOLT-AMPERE REACTIVE
KILOWATT
KILOWATT-HOUR
LIGHTNING ARRESTER
LIGHTING
MC
MCB
MFR
MI
MLO
MTD
MTS
MV
NC
NEC
NEG
NEUT
NF
NIC
NL
NO
NTS
PF
PG
PH
POV
PVC
RM
RSC
RTD
SN
SM
SMFO
SPD
STP
STT
SWBD
SWGR
THHN
THWN
TL
TLC
TLS
TMGB
VA
VAR
WM
XFMR
XP
GENERAL NOTES
1. ALL GENERAL NOTES, SYMBOLS LISTS AND DETAILS SHALL BE
CONSIDERED AS APPLICABLE TO ALL ELECTRICAL DRAWINGS FOR
THIS PROJECT. SYMBOLS AND ABBREVIATIONS SHOWN ON THIS
SHEET ARE FOR REFERENCE ONLY AND DO NOT INDICATE THEIR
INCORPORATION IN THE DESIGN.
2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH NFPA-70,
NATIONAL ELECTRICAL CODE (NEC), LATEST ADDITION ADOPTED.
3. ALL MOTOR SAFETY SWITCHES, DISCONNECTS AND MOTOR
STARTERS ARE PROVIDED BY DIVISION 26000 UNLESS NOTED AS
FURNISHED WITH EQUIPMENT (FWE).
4. UNLESS OTHERWISE NOTED CONVENIENCE RECEPTACLES SHALL
BE MOUNTED 36" AFF AND LIGHTING TOGGLE SWITCHES; U.N.O.
5. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND
PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRE SEALANT
MATERIAL TO MAINTAIN THE RATING OF SEPARATION.
6. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED
WITH EVERY FEEDER AND BRANCH CIRCUIT.
7. UNLESS OTHERWISE NOTED WIRING SHALL BE 2#12 AWG
CONDUCTORS AND #12 GND. HOME RUNS FED FROM 20A-1P
CIRCUITS IN EXCESS OF 100' SHALL BE #10 AWG.
8. FLEXIBLE CONNECTIONS TO MOTORS SHALL BE LIQUID TIGHT
FLEXIBLE METAL CONDUIT, UNLESS OTHERWISE NOTED.
9. ALL WIRING SHALL BE 600V, COPPER WITH THHN/THWN
INSULATION.
10. ALL UNDERGROUND CONDUITS SHALL BE SCHEDULE 80 PVC. ALL
EXTERIOR SERVICE MOUNT CONDUIT SHALL BE RIGID GALVANIZED
STEEL. ALL CONDUITS INSTALLED WITHIN EXISTING BUILDINGS
SHALL BE EMT. ALL CONDUITS AND RACEWAYS WITHIN THE BMF
INTERIOR SHALL BE SCHEDULE 80 PVC AND LIQUID TIGHT
FLEXIBLE METAL CONDUIT OR RIGID GALVANIZED STEEL WHERE
SUSECTABLE TO PHYSICAL DAMAGE.
LINE TYPES
NEW
DEMOLITION
PARTPLAN OUTLINE
MATCHLINE
FUSED SAFETY SWITCH, TOP NUMBER
INDICATES SWITCH AMPERE RATING, LOWER
NUMBER INDICATES FUSE RATING
MAGNETIC MOTOR STARTER, FVNR UNLESS
INDICATED OTHERWISE
COMBINATION FUSED DISCONNECT/MAGNETIC
MOTOR STARTER. NUMBER INDICATES
DISCONNECT AMPERE RATING/FUSE
RATING/NEMA STARTER SIZE
MOTORIZED DAMPER
ELECTRIC MOTOR
CONDUIT TURNING UP
CONDUIT TURNING DOWN
EY CONDUIT SEAL
SINGLE RECEPTACLE, NEMA 5-20R
DUPLEX RECEPTACLE, NEMA 5-20R
DOUBLE DUPLEX (QUADRUPLEX) RECEPTACLE,
NEMA 5-20R
GFCI DUPLEX RECEPTACLE, NEMA 5-20R
SINGLE RECEPTACLE, NEMA 5-20R
FLOOR OUTLET, UNLESS OTHERWISE NOTED
DUPLEX RECEPTACLE, NEMA 5-20R
FLOOR OUTLET, UNLESS OTHERWISE NOTED
DOUBLE DUPLEX (QUADRUPLEX) RECEPTACLE,
NEMA 5-20R, FLOOR OUTLET, UNLESS
OTHERWISE NOTED
POWER RECEPTACLE FOR PORTABLE 400HZ
POWER RECEPTACLE, 400HZ
PANELBOARD, NORMAL POWER
ENCLOSED CIRCUIT BREAKER
JUNCTION BOX
MANUAL MOTOR STARTER, TOGGLE OPERATED,
SINGLE PHASE, 1 OR 2 POLE AS REQUIRED
(NO OVERLOAD PROTECTION)
MANUAL MOTOR STARTER, TOGGLE OPERATED,
S…