02 Pentagon Fire Alarm
| J-C1 Pentagon Fire Protection Systems | | | | |
| HQ0034-11-R-0056 | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| Simplex 4100U | | Annually | NFPA 72§10.4.2.2 | 51 |
| Lamps, LEDs test | test | | | |
| Secondary power supply battery tests | test | | | |
| Local mode audio | test | | | |
| Simplex 4100+ | | Annually | NFPA 72§10.4.2.2 | 0 |
| Lamps, LEDs test | test | | | |
| Secondary power supply battery tests | test | | | |
| Local mode audio | test | | | |
| Simplex 4020 | | Annually | NFPA 72§10.4.2.2 | 3 |
| Lamps, LEDs test | test | | | |
| Secondary power supply battery tests | test | | | |
| Local mode audio | test | | | |
| Simplex 4009 NAC Panel | | Annually | NFPA 72§10.4.2.2 | 21 |
| Secondary power supply battery tests | test | | | |
| Integrated Management System | | Annually | NFPA 72§10.4.2.2 | 15 |
| Secondary UPS power supply test | test | | | |
| Edwards | | Annually | NFPA 72§10.4.2.2 | 2 |
| Secondary power supply battery tests | test | | | |
| | Fire Alarm Inititating Devices | | |
| Duct detectors | test | Annually | NFPA 72§10.4.2.2 | 462 |
| Kitchen extinguishing system switches | test | Annually | NFPA 72§10.4.2.2 | 32 |
| Gas detectors | test | Annually | NFPA 72§10.4.2.2 | 4 |
| Heat detectors | test | Annually | NFPA 72§10.4.2.2 | 327 |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 1395 |
| Smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 6193 |
| Aspirating smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 1 |
| Supervisory Tamper switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 1214 |
| Waterflow devices | test | Semi-Annually | NFPA 72§10.4.2.2 | 655 |
| High/low pressure switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 75 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 1009 |
| Speaker circuit isolation module tests | test | Annually | NFPA 72§10.4.2.2 | 425 |
| Strobe circuit visibitity tests | test | Annually | NFPA 72§10.4.2.2 | 1319 |
| | Fire Alarm Controls | | |
| Magnetic door holders | test | Annually | NFPA 72§10.4.2.2 | 201 |
| WON doors | test | Annually | NFPA 72§10.4.2.2 | 109 |
| Elevator recall functions | test | Annually | NFPA 72§10.4.2.2 | 102 |
| Elevator shunt-trip functions | test | Annually | NFPA 72§10.4.2.2 | 28 |
| Fire alarm door release interlocks | test | Annually | NFPA 72§10.4.2.2 | 48 |
| AHU shutdown | test | Annually | NFPA 72§10.4.2.2 | 395 |
| Motorized dampers | test | Annually | NFPA 72§10.4.2.2 | 56 |
| Smoke curtains | test | Semi-Annual | NFPA 72§10.4.2.3 | 3 |
| | Firefigher phones | | |
| Firefighter phone transmission test | test | Annually | NFPA 72§10.4.2.2 | 273 |
03 Pentagon Water Based Item Activity Task Frequency Reference Qty
| Electrical system conditions | Inspection | CTR Annually | NFPA 25, §8.2.2(3) | 4 |
| Flow test | Test | Annually | NFPA 25, §8.3.3.1 | 4 |
Hose connections and piping and cabinets Inspection Annually NFPA 25, §6.2.1 360
| Flow and Hydrostatic Tests | | 5 years | NFPA 25, §6.3.1 | 2 |
| Flow test | Test | | | |
| Alarm Devices | | | 400 |
| Waterflow and supervisory devices | Test | Quaterly | |
| Waterflow Vane type | Test | Semi-annually | |
| inspection and test | Test | Annually | |
| Control Valves | | CTR Annually* | NFPA 25, §12.3.3.1 | 974 |
| Position and operation | Test | | | |
| Preaction and Deluge Valves | | CTR Annually* | NFPA 25, §12.4.3.1 | 7 |
| Valve enclosure | Inspection | | | |
| Dry Pipe Valves/Quick Opening Devices | | CTR Annually* | NFPA 25, §12.4.4.1.1 | 9 |
| Valve enclosure | Inspection | | | |
| Hose Valves | | Annually | NFPA 25, §12.5.5.2.1 | 360 |
| Class I and III standpipe hose valves | Test | | | |
| Fire department connections | Inspection | Quarterly | NFPA 25, §12.7.1 | 9 |
| CTR Annually* = GOV to perform the service except for the annual checkup | | | | |
02 PHRP Fire Alarm
| PHRP Plant Fire Alarm System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| EST FAST Panel's | | Annually | NFPA 72§10.4.2.2 | 1 |
| Secondary power supply battery tests | test | | | |
| | Fire Alarm Inititating Devices | | |
| Duct detectors | test | Annually | NFPA 72§10.4.2.2 | 15 |
| Heat detectors | test | Annually | NFPA 72§10.4.2.2 | 16 |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 19 |
| Smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 26 |
| Supervisory Tamper switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 21 |
| Waterflow devices | test | Semi-Annually | NFPA 72§10.4.2.2 | 7 |
| High/low pressure switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 2 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 48 |
| | Fire Alarm Controls | | |
| Elevator recall functions | test | Annually | NFPA 72§10.4.2.2 | 1 |
| Elevator shunt-trip functions | test | Annually | NFPA 72§10.4.2.2 | 1 |
| AHU shutdown | test | Annually | NFPA 72§10.4.2.2 | 15 |
03 PHRP Water Based
| PHRP PLANT Water Base System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| Diesel system conditions | Inspection | CTR Annually* | NFPA 25, §8.2.2(4) | 1 |
| Flow test | Test | Annually | NFPA 25, §8.3.3.1 | 1 |
Hose connections and piping Inspection Annually NFPA 25, §6.2.1 10
| Preaction and Deluge Valves | | CTR Annually* | NFPA 25, §12.4.3.1 | 2 |
| Valve enclosure | Inspection | | | |
| Dry Pipe Valves/Quick Opening Devices | | CTR Annually* | NFPA 25, §12.4.4.1.1 | 1 |
| Valve enclosure | Inspection | | | |
| Fire department connections | Inspection | Quarterly | NFPA 25, §12.7.1 | 1 |
| CTR Annually* = GOV to perform the service except for the annual checkup | | | | |
02 PHRP Screen Fire Alarm
| PHRP SCREEN Fire Alarm System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| Notifier AFP-200 Panel's | | Annually | NFPA 72§10.4.2.2 | 1 |
| Secondary power supply battery tests | test | | | |
| | Fire Alarm Inititating Devices | | |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 2 |
| Smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 1 |
| Supervisory Tamper switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 2 |
| Waterflow devices | test | Semi-Annually | NFPA 72§10.4.2.2 | 1 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 4 |
| | Firefigher phones | | |
| Firefighter phone transmission test | test | Annually | NFPA 72§10.4.2.2 | 0 |
02 I Moc Fire Alarm
| I MOC Fire Alarm System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| Fire Lite MS-5024 | | Annually | NFPA 72§10.4.2.2 | 1 |
| Secondary power supply battery tests | test | | | |
| | Fire Alarm Inititating Devices | | |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 5 |
| Supervisory Tamper switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 2 |
| Waterflow devices | test | Semi-Annually | NFPA 72§10.4.2.2 | 1 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 8 |
03 I Moc Water Based
| I-MOC Water Base System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| Fire department connections | Inspection | Quarterly | NFPA 25, §12.7.1 | 1 |
| CTR Annually* = GOV to perform the service except for the annual checkup | | | | |
02 T Moc Fire Alarm
| T-MOC Fire Alarm System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| Fire Lite MS-5024 | | | | 1 |
| Secondary power supply battery tests | test | Annually | NFPA 72§10.4.2.2 | |
| | Fire Alarm Inititating Devices | | |
| Heat detectors | test | Annually | NFPA 72§10.4.2.2 | 17 |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 2 |
| Smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 1 |
| Supervisory Tamper switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 2 |
| Waterflow devices | test | Semi-Annually | NFPA 72§10.4.2.2 | 1 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 6 |
03 Incinerator Water Based
| Incinerator Plant Water Base System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| Dry Pipe Valves/Quick Opening Devices | | CTR Annually* | NFPA 25, §12.4.4.1.1 | 1 |
| Valve enclosure | Inspection | | | |
| Valve enclosure, with low temperature alarms | Inspection | | | |
Fire department connections Inspection Quarterly NFPA 25, §12.7.1 1
CTR Annually* = GOV to perform the service except for the annual checkup
02 Incinerator Fire Alarm
| Incinerator Plant Fire Alarm System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| Faraday MPC-2000 | | Annually | NFPA 72§10.4.2.2 | 1 |
| Secondary power supply battery tests | test | | | |
| | Fire Alarm Inititating Devices | | |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 7 |
| Smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 1 |
| Waterflow devices | test | Semi-Annually | NFPA 72§10.4.2.2 | 0 |
| High/low pressure switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 0 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 4 |
Moc BLGD 100 Water Base
| Moc BLGD 100 Water Base System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| Alarm Devices | | | | |
| Water-flow devices | Test | Quarterly | NFPA 25, §5.3.3.1 | 1 |
| Vane-type waterflow devices | Test | Semi-annually | NFPA 25, §5.3.3.2 | 1 |
CTR Annually* = GOV to perform the service except for the annual checkup
Moc BLGD 104 Water Base
| Moc BLGD 104 Water Base System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| Alarm Devices | | | | |
| Water-flow devices | Test | Quarterly | NFPA 25, §5.3.3.1 | 1 |
| Vane-type waterflow devices | Test | Semi-annually | NFPA 25, §5.3.3.2 | 1 |
| CTR Annually* = GOV to perform the service except for the annual checkup | | | | |
C Moc Fire Alarm
| C Moc Fire Alarm System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| Fire Lite MS-5024 | | Annually | NFPA 72§10.4.2.2 | 1 |
| Secondary power supply battery tests | test | | | |
| | Fire Alarm Inititating Devices | | |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 5 |
| Smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 16 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 8 |
C Moc Water Base
| C Moc Water Base System's | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| Alarm Devices | | | | |
| Water-flow devices | Test | Quarterly | NFPA 25, §5.3.3.1 | 1 |
| Vane-type waterflow devices | Test | Semi-annually | NFPA 25, §5.3.3.2 | 1 |
CTR Annually* = GOV to perform the service except for the annual checkup
Haz Mat Facility Fire Alarm
| Hazardous Material Facility | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| | Fire Alarm Panels | | |
| Simplex 4100U | | Annually | NFPA 72§10.4.2.2 | 1 |
| Lamps, LEDs test | test | | | |
| Secondary power supply battery tests | test | | | |
| Local mode audio | test | | | |
| | Fire Alarm Inititating Devices | | |
| Duct detectors | test | Annually | NFPA 72§10.4.2.2 | 2 |
| Heat detectors | test | Annually | NFPA 72§10.4.2.2 | 5 |
| Manual pull stations | test | Annually | NFPA 72§10.4.2.2 | 9 |
| Smoke detectors | test | Annually | NFPA 72§10.4.2.2 | 5 |
| Supervisory Tamper switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 10 |
| Waterflow devices | test | Semi-Annually | NFPA 72§10.4.2.2 | 5 |
| High/low pressure switches | test | Semi-Annually | NFPA 72§10.4.2.2 | 1 |
| | Alarm Notification Appliances | | |
| Speaker circuit decibel audibility tests | test | Annually | NFPA 72§10.4.2.2 | 8 |
| Strobe circuit visibitity tests | test | Annually | NFPA 72§10.4.2.2 | 15 |
| | Fire Alarm Controls | | |
| Elevator recall functions | test | Annually | NFPA 72§10.4.2.2 | 1 |
| Elevator shunt-trip functions | test | Annually | NFPA 72§10.4.2.2 | 1 |
| AHU shutdown | test | Annually | NFPA 72§10.4.2.2 | 2 |
Haz Mat Facility Water Base
| Hazardous Material Facility | | | | |
| Item | Activity | Task Frequency | Reference | Qty |
| Electrical system conditions | Inspection | CTR Annually* | NFPA 25, §8.2.2(4) | 1 |
| Flow test | Test | Annually | NFPA 25, §8.3.3.1 | 1 |
Hose connections and piping Inspection Annually NFPA 25, §6.2.1 4
| Preaction and Deluge Valves | | CTR Annually* | NFPA 25, §12.4.3.1 | 0 |
| Valve enclosure | Inspection | | | |
| Dry Pipe Valves/Quick Opening Devices | | CTR Annually* | NFPA 25, §12.4.4.1.1 | 1 |
| Valve enclosure | Inspection | | | |
| Fire department connections | Inspection | Quarterly | NFPA 25, §12.7.1 | 1 |
| CTR Annually* = GOV to perform the service except for the annual checkup | | | | |