Forced Air Gas Furnace
Solicitation number
W912GY24Q0024
Issued by

About this file

The provided document appears to be the specifications for a Thermo-Cycler Industries GTC-400 or equal gas furnace. The key details are:

The gas furnace must have a fan section module with a full-length hinged access door, a 1 horsepower totally enclosed motor with a controlled motor soft start, and a factory-mounted control panel. The heat exchanger must be a non-condensing stainless steel design with a counterflow configuration. The burner shall have a maximum input capacity of up to 400 MbH and be capable of burning natural gas. The unit shall be factory assembled, tested, and shipped with operation and maintenance manuals. It shall carry a 2-year manufacturer warranty on parts and a 10-year limited warranty on the heat exchanger.

The related federal contract opportunity is for four forced air gas furnaces (Thermo-Cycler Industries GTR-486 or equal) for the Sierra Army Depot in Herlong, CA. The solicitation is expected to be released on 08/01/2024 as a small business set-aside using Simplified Acquisition Procedures. The North American Industrial Classification Code is 333415, with a related business size of 1,250 employees. The contract will be a firm-fixed price award by the Department of the Army Materiel Command Contracting Command Detroit Arsenal.

View the file

Other files

File Type Posted
GTR-486 or Equal Specs.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Thermo-Cycler Industries GTC-400 or equal. To be considered equal, the gas furnace must have the following specifications:

Fan Section Module

- A full-length hinged access door shall be provided on the front side for fan and motor accessibility. Access door will be furnished with locks to prevent unauthorized entry.

- 1 horsepower totally enclosed motor. Full load nameplate motor amperage rating shall not exceed 2.3 amps at 460 V. A controlled motor soft start, operating speed functions and overload protection.

- The control panel shall be factory mounted and include a locking cover, supplementary overload protector main switch, burner status operation lights, burner and fan control switches, factory wired control circuits, flexible conduit and plug-in wiring assembly for connection of fan section and heater section.

Heat Exchanger Section

- Heater section shall be internally insulated.

- The heat exchanger shall be a non-condensing stainless steel heat exchanger. Primary heat exchanger will be 14 ga. or heavier Type 430 stainless steel. Secondary heat exchanger pass will be 14 ga. or heavier Type 430 or Type 409 stainless steel. Heat exchanger will be a counterflow design.

- The burner shall have a maximum input capacity of up to 400 MbH and be capable of burning natural gas. The complete burner assembly and primary controls will be an independent UL Classified Component.

- The burner shall be contained within a factory mounted locking enclosure with a hinged front cover for burner access. The enclosure shall have 10" diameter combustion air intake on each side that will allow combustion air to be introduced from the building or that may be directly connected to the outside to meet local codes and actual building conditions.

General Unit Specifications

- The unit shall be assembled at the factory, test fired, and adjusted for proper burner operations at factory conditions.

- The unit shall be shipped on heavy shipping skids and fully protected from weather damage with plastic covering.

- The unit shall be shipped with operation and maintenance manual.

- All hardware needed for assembly will be provided.

- Each unit shall require a single source of electric current, single connection point for gas piping, and a single flue vent connection.

- An 8" diameter flue connection from the heat exchanger shall be provided on the burner side of the unit. The flue outlet centerline shall be a minimum of 8' 4" above finished floor surface.

- The unit will operate with a sound level of 74 db or less.

- All parts will carry standard 2-year manufacturer warranty and the heat exchanger will carry a manufacturer non-prorated 10-year limited warranty.