US GENERAL SERVICES ADMINISTRATION
PROPERTY OF THE UNITED STATES GOVERNMENT.
COPYING, DISSEMINATION, OR DISTIBUTION OF THESE DRAWINGS
AND / OR DOCUMENTS WITHOUT THE EXPLICIT PERMISSION OF THE
U.S. GENERAL SERVICES ADMINISTRATION IS PROHIBITED.
DISTRIBUTION TO THOSE WITH OTHER THAN A NEED TO KNOW IS
STRICTLY FORBIDDEN.
BBIX, LLC
ARCHITECTS & ENGINEERS
10 HIGH STREET - SUITE 402
BOSTON, MA 02110
NEW ENGLAND REGION (REGION 1)
PROJECT NUMBER: VMA00011
FINAL AMENDMENT DOCUMENTS
11/30/2012
DRAWING LIST:
ARCHITECTURAL:
A000 COVER SHEET
D101 6TH FLOOR DEMOLITION PLAN
D102 6TH FLOOR DEMOLITION REFLECTED CEILING PLAN
A001 6TH FLOOR LIFE SAFETY PLAN / CODE REVIEW
A002 PARTITION TYPES AND GENERAL INFO
A101 6TH FLOOR PLAN
A102 6TH FLOOR FINISH PLAN
A103 6TH FLOOR FURNITURE PLAN
A201 6TH FLOOR REFLECTED CEILING PLAN
A301 INTERIOR ELEVATIONS & DETAILS
A302 INTERIOR ELEVATIONS
A401 INTERIOR DETAILS
A801 DOOR SCHEDULE AND DETAILS
MECHANICAL:
M001 MECHANICAL DETAILS AND SCHEDULES
MD101 6TH FLOOR MECHANICAL DEMOLITION PLAN
M101 6TH FLOOR MECHANICAL PLAN
ELECTRICAL:
E001 ELECTRICAL SYMBOLS AND DETAILS
ED101 ELECTRICAL 6TH FLOOR DEMOLITION PLAN
E201 ELECTRICAL 6TH FLOOR NEW WORK LIGHTING PLAN
E301 ELECTRICAL 6TH FLOOR NEW WORK POWER PLAN
E401 6TH FLOOR NEW WORK FIRE ALARM PLAN
E501 ELECTRICAL SCHEDULES
TELECOMMUNICATIONS:
T001 SERVING ZONE, LEGEND & KEYS
TD100 TELECOMMUNICATION: DEMO PLAN
T100 TELECOMMUNICATION: 6TH FLOOR
T110 OPTION NO. 1 - SOUNDMASKING
T400 IDF 6-2-2, DETAILS AND SCHEDULES
T500 TELECOMMUNICATION DETAILS
T501 TELECOMMUNICATION DETAILS
T600 TELECOMMUNICATION: SCHEMATICS
SE100 SECURITY PLAN
SE500 SECURITY DETAILS & DIAGRAMS
SE600 SECURITY SYSTEMS RISERS
PLUMBING:
P100 PLUMBING PLANS & SCHEDULES
FIRE PROTECTION:
FP101 6TH FLOOR FIRE PROTECTION PLAN
CUSTOMS AND BORDER PROTECTION/OFFICE OF FIELD OPERATIONS
6TH FLOOR RENOVATION
THOMAS P. O'NEILL FEDERAL BUILDING
10 CAUSEWAY STREET
BOSTON, MA
BUILDING SITE
N
UP DN
2 3 4 5 6 7 8 9 10 11 12
G
H
J
K
L
PARTITION / PLAN LEGEND
EXISTING TO REMAIN
EXISTING TO BE REMOVED
REMOVE FLOORING, BASE AND
ALL ADHESIVES AND MASTICS,
REFER TO GENERAL NOTES,
SEE NOTE 14
EXISTING DOOR TO BE REMOVED
INDICATES EXISTING DOOR TO REMAIN
EXISTING CBP SPACE TO BE
RETURNED TO GSA
KEYED NOTES:
1 CONTRACTOR TO USE GREAT CARE IN THE REMOVAL AND
STORAGE OF EXISTING KITCHEN CABINETS (UPPER AND LOWER),
SINK, WATER HEATER, REFRIGERATOR, COUNTERTOP, SHELVING
AND HARDWARE ASSOCIATED WITH THIS LOCATION. PRODUCTS
SHOULD BE LABELED APPROPRIATELY FOR RE-USE IN THE NEW
KITCHENETTE LOCATION.
NOT IN SCOPE OF WORK
2 REMOVE DOOR, FRAME AND HARDWARE AND TURN OVER TO GSA
BUILDING MANAGEMENT
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
6TH FLOOR DEMOLITION PLAN
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JPD
MS
11/30/2012
D101
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
3/32" = 1'-0"1 6TH FLOOR DEMOLITION PLAN
THE FLOOR WILL REMAIN PARTIALLY OCCUPIED DURING DEMOLITION ACTIVITIES. DUST CONTROL PROVISIONS ARE REQUIRED TO ENSURE AGAINST MIGRATION OF ALL DUST AND DEMOLITION DEBRIS TO
OCCUPIED SPACES.
THE GC SHALL PROVIDE A DOUBLE CONTAINMENT POLY (MIN 6 MIL) AT ALL ENTRY AND EGRESS PATHS IN
AND OUT OF THE LIMIT OF WORK AREA. REPLACE AS OFTEN AS NEEDED TO ENSURE AGAINST
MIGRATION OF DUST AND CONSTRUCTION DEBRIS OUTSIDE OF THE WORK AREA.
THE GC SHALL PROVIDE A STEP-OFF PADS (TACK MATS) AT ALL ENTRY AND EGRESS PATHS IN AND OUT OF THE LIMIT OF WORK AREA. THE GC SHALL REPLACE THE POLY BARRIER AS OFTEN AS NEEDED, TO ENSURE AGAINST MIGRATION OF DUST AND CONSTRUCTION DEBRIS OUTSIDE OF THE WORK AREA.
THE GC SHALL PROVIDE DAILY REMOVAL OF ALL DEMOLITION DEBRIS. DO NOT STORE ANY DEMOLITION
DEBRIS ON THE FLOOR OVERNIGHT.
THE GC SHALL MAINTAIN A CLEAN AND SAFE WORK AREA THROUGHOUT THE PERIOD OF DEMOLITION.
THE GC SHALL, AT THE END OF EACH WORK DAY, REMOVE ALL DEMOLITION DEBRIS AND HAZARDOUS
AND POTENTIALLY DANGEROUS MATERIALS USED IN THE WORK.
THE GC SHALL COLLECT CONSTRUCTION MATERIAL AND DEBRIS FREQUENTLY AND DISPOSE OF DEBRIS
AND REFUSE AWAY FROM THE CENTER IN A LAWFUL MANNER.
THE GC SHALL CLEAN THE EXTERIOR PUBLIC AREAS IMPACTED BY CONSTRUCTION DUST, DIRT AND DEBRIS ON A DAILY BASIS. THE GC SHALL BE RESPONSIBLE FOR ALL FEES, PERMITS, ETC., REQUIRED
FOR WASTE DISPOSAL.
DUST CONTROL PROVISIONS:
THE FLOOR WILL REMAIN PARTIALLY OCCUPIED DURING DEMOLITION ACTIVITIES. NOISE CONTROL
PROVISIONS ARE REQUIRED TO ENSURE AGAINST DISTURBANCE OR DISRUPTION OF WORK
ACTIVITIES OF THE TENANTS ON THIS FLOOR, AND THOSE ON THE FLOORS ABOVE AND BELOW.
ANY PROPOSED INTERRUPTION TO TENANT OPERATIONS DURING DEMOLITION MUST HAVE PRIOR
APPROVAL FROM THE GSA BUILDING MANAGER WITH A MINIMUM OF 72 HOURS ADVANCE NOTICE.
THE DEMOLITION SUBCONTRACTOR SHALL ADOPT QUIETER TYPES OF DEMOLITION AS BEST
PRACTICABLE BY USING POWER TOOLS EQUIPPED WITH SILENCERS.
THE GC SHALL COORDINATE REASONABLE HOURS OF WORKING FOR NOISY OPERATIONS WITH THE
GSA BUILDING MANAGER. SOME WORK WILL HAVE TO BE DONE AFTER-HOURS OR ON WEEKENDS.
THE GC SHALL PROVIDE PROVISIONS TO ENSURE AGAINST SOUND AND VIBRATION NOISE TO
TENANTS ON THIS FLOOR, AND THOSE ON THE FLOORS ABOVE AND BELOW.
NOISE CONTROL PROVISIONS:
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ADHERE TO THE FOLLOWING:
1. ERECT AND MAINTAIN TEMPORARY STAGING, LIGHTS, BARRICADES, WARNING SIGNS, AND GUARDS NECESSARY TO PROTECT BUILDING OCCUPANTS, AND ADJOINING TENANTS FROM
INJURY, AND/OR DAMAGE, ALL IN ACCORDANCE WITH APPLICABLE RULES AND REGULATIONS.
2. DO NOT CLOSE OR OBSTRUCT THE PATH OF EGRESS, CORRIDORS, OR OTHER OCCUPIED OR USED SPACES OR FACILITIES WITHOUT THE WRITTEN PERMISSION OF THE OWNER AND THE AUTHORITIES HAVING JURISDICTION. DO NOT INTERRUPT UTILITIES WITHOUT THE WRITTEN PERMISSION OF THE AUTHORITIES HAVING JURISDICTION. IF NECESSARY PROVIDE TEMPORARY UTILITIES. PRIOR TO OBSTRUCTION OF EGRESS PATHS OR IMPAIRMENT OF FIRE/LIFE SAFETY COMPONENTS, THE NFPA 241 AND IMPAIRMENTS PLANS MUST BE SUBMITTED FOR APPROVAL BY DESIGN TEAM FIRE PROTECTION ENGINEER WHO IS LICENSED PROFESSIONAL ENGINEER (IN FIRE PROTECTION ENGINEERING) (DTFPEPE) AND GSA REGIONAL FIRE PROTECTION
ENGINEER (GSARFPE).
3. CEASE OPERATION IF PUBLIC SAFETY OR REMAINING STRUCTURES ARE ENDANGERED. PERFORM TEMPORARY CORRECTIVE MEASURES UNTIL OPERATIONS CAN BE CONTINUED
PROPERLY.
4. IN COMPANY OF THE ARCHITECT AND OWNER, THE CONTRACTOR WILL VISIT THE SITE AND VERIFY THE EXTENT AND LOCATION OF SELECTIVE DEMOLITION REQUIRED PRIOR TO STARTING THE WORK. CAREFULLY IDENTIFY THE LIMITS OF SELECTIVE DEMOLITION. MARK INTERFACE SURFACES AS REQUIRED TO ENABLE THE WORKMEN TO ALSO IDENTIFY THE ITEMS
TO BE REMOVED AND STORED, AS WELL AS THE ITEMS TO BE LEFT IN PLACE INTACT.
5. USE MEANS NECESSARY TO PREVENT DUST FROM BECOMING A NUISANCE TO OTHER TENANTS OF THE BUILDING, THE PUBLIC, NEIGHBORING BUILDINGS, AND TO ANY OTHER WORK
BEING PERFORMED.
6. EXECUTE DEMOLITION WORK TO ENSURE THE SAFETY OF PERSONS AND ADJACENT PROPERTY AGAINST DAMAGE BY DEBRIS. CONTRACTOR WILL TAKE PROTECTIVE MEASURES TO
PREVENT DUST FROM GETTING INTO DUCTS.
7. IN THE EVENT OF DEMOLITION OF ITEMS NOT SO SCHEDULED TO BE DEMOLISHED, PROMPTLY REPLACE SUCH ITEMS TO THE APPROVAL OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO EXISTING FEATURES AS A RESULT OF THIS WORK. DAMAGED ITEMS SHALL BE REPLACED
IN KIND AND AT NO ADDITIONAL COST TO THE OWNER.
8. SHORE, BRACE AND SUPPORT EXISTING CONDITIONS AS REQUIRED FOR REMOVAL OF EXISTING CONSTRUCTION OR INSTALLATION OF THE NEW WORK.
9. COORDINATE THE REMOVAL, RELOCATION, REPLACEMENT, RE-USE, SHUT-OFF, STUB-OFF, CAPPING-OFF OR UPGRADING OF ALL EXISTING PLUMBING, SPRINKLERS, HVAC, SECURITY, ELECTRICAL SYSTEMS, AND TELECOM SYSTEMS EQUIPMENT, AND APPURTENANCES - INCLUDING, BUT NOT LIMITED TO , UTILITY LINES, DUCTS, CONNECTIONS, PANELS, VENTS, FANS, ELECTRICAL BASEBOARD HEAT, PIPING, DEVICES, CONTROLS, SWITCHES, OUTLETS, AND CONDUIT DURING THE CONSTRUCTION AS REQUIRED, AS SCHEDULED OR AS SPECIFIED IN
ACCORDANCE WITH ALL LOCAL, MUNICIPAL, STATE CODES.
10. THE CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF ANY HAZARDOUS MATERIALS AND IN DOING SO SHALL COMPLY WITH ALL APPLICABLE OSHA REGULATIONS AND ALL OTHER FEDERAL, STATE AND LOCAL GUIDELINES REGARDING ASBESTOS-CONTAINING MATERIAL REMOVAL AND DISPOSAL.
11. OWNER AND ARCHITECT SHALL NOT BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES FOR SAFETY PRECAUTIONS OR FOR THE CONTRACTORS FAILURE TO CARRY OUT THE WORK IN STRICT ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. OWNER SHALL NOT BE RESPONSIBLE FOR ERRORS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR THEIR AGENTS OR EMPLOYEES OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK.
12. THE CONTRACTOR SHALL COORDINATE ALL ABOVE CEILING MEP AND STRUCTURAL ELEMENTS PRIOR TO DEMOLITION OF WALLS AND/OR CEILING. THE CONTRACTOR SHALL OBTAIN THE GSA REGIONAL FIRE PROTECTION ENGINEER (GSARFPE) APPROVAL OF NFPA 241 SAFETY PLAN AND FIRE SPRINKLER FOR SHELL COVERAGE SUBMITTAL PRIOR TO START OF CEILING
REWORK, MODIFICATION, OR DEMOLITION.
13. COORDINATE, TERMINATE, AND RELOCATE ALL WALL & CEILING ELECTRICAL (TELECOM/POWER OUTLETS, SWITCHING, THERMOSTAT, ETC.) DEVICES THAT ARE LOCATED ON WALLS & CEILINGS SCHEDULED FOR REMOVAL. GC TO V.I.F. PRIOR TO THE COMMENCEMENT OF WORK. DISCONNECT AND MAKE SAFE EXISTING ELECTRICAL COMPONENTS TO BE REMOVED.
14. REMOVE EXISTING FLOORING & WALL ASSEMBLIES TO FACE OF EXISTING CONCRETE SLAB. THOROUGHLY CLEAN FLOOR OF ALL ADHESIVE MASTICS TO ACCEPT NEWLY SPECIFIED FLOORING FINISH. EXISTING FLOORING MATERIALS AND MISCELLANEOUS METALS TO BE RECYCLED BY GC. PATCH, REPAIR, AND LEVEL FLOORING TO MEET MANUFACTURER'S REQUIREMENTS OF THE NEW FLOORING AND WALL MATERIALS AS SPECIFIED. IT IS THE RESPONSIBILITY OF THE GC TO GRIND DOWN TO A SMOOTH FINISH ALL UNEVEN SURFACES OR
PATCH ALL CONCAVE FLOORING TO A LEVEL SURFACE REGARDLESS OF FLOORING UNEVENNESS.
15. PATCH ALL EXISTING WALLS ADJACENT TO ALL WALLS SCHEDULED FOR REMOVAL. PATCHWORK WILL BE CONSISTENT WITH THE WALL RATING. ANY STRUCTURAL STEEL DAMAGED OR MISSING SFRM SHALL BE REPLACED AFTER COMPLETION OF APPROPRIATE SURFACE PREPARATION WORK AND ITS INSPECTION BY DTFPEPE AND THE GSA FPE.
16. SUBMIT DEMOLITION SCHEDULE FOR APPROVAL INCLUDING SCHEDULE AND METHODS OF CAPPING AND CONTINUING UTILITY SERVICE.
17. THE CONTRACTOR SHALL COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS AND 29 CFR 1910.34, COVERAGE AND DEFINITIONS, 29 CFR 1910-35, COMPLIANCE WITH NFPA 101-2009, LIFE SAFETY CODE, 29 CFR 1910-36, DESIGN AND CONSTRUCTION REQUIREMENTS FOR EXIT ROUTES, 29 CFR 1910-37, MAINTENANCE, SAFEGUARDS, AND OPERATIONAL FEATURES FOR EXIT ROUTES. PBS P-100 2010 EDITION. THE CONTRACTOR SHALL ALSO COMPLY WITH THE GSA IMPAIRMENT PLAN
GUIDE ATTACHED TO THE SPECIFICATION 13195, WET PIPE SPRINKLER SYSTEM.
18. FIRE SPRINKLER SYSTEM SHALL BE RETURNED TO UPRIGHT SPRINKLER HEAD COVERAGE CONSISTENT WITH BUILDING SHELL COVERAGE PER NFPA 13.
19. CONTRACTOR SHALL CONSTRUCT TEMPORARY BARRIER IN ACCORDANCE WITH DUST CONTROL PROVISIONS, REVIEW LOCATION WITH GSA PROJECT MANAGER FOR FINAL APPROVAL.
20. CONTRACTOR SHALL REMOVE, AND CLEAN EXISTING WINDOW TREATMENT IN SCOPE OF WORK AREAS AND TURN OVER TO GSA.
21. CONTRACTOR SHALL REMOVE EXISTING HARDWARE, WHICH IS TO BE TURNED OVER TO THE GOVERNMENT.
22. ALL FIRE ALARM NOTIFICATION DEVICES, EXIT SIGNAGE AND EMERGENCY LIGHTING TO REMAIN OPERATIONAL DURING DEMOLITION AND CONSTRUCTION UNTIL WHICH POINT THAT
NEW FIRE ALARM SPEAKER STROBE DEVICES ARE READY TO BE INSTALLED AND ACTIVATED.
GENERAL DEMOLITION NOTES:
SPSP
SP
SP
SPSPSPSP
SP SP SP SP
SP SP SP
SP SP SP
SP
SP
2 3 4 5 6 7 8 9 10 11 12
G
H
J
K
L
F
F
F
F
HD
SEE KEYED NOTE 1
REFLECTED CEILING DEMOLITION PLAN LEGEND
EXISTING PARTITION TO BE REMOVED
EXISTING SPEAKER TO BE REMOVED, SEE NOTE #19 THIS PAGESP
NOT IN SCOPE
EXISTING 1X5 COMBINATION LIGHT AND
SUPPLY DIFFUSER TO BE REMOVED
REMOVE CEILING, LIGHTING, DEVICES AND
ALL ATTACHMENTS, UNLESS OTHERWISE
NOTED. PREP TO ACCEPT NEW CEILING.
REFLECTED CEILING DEMOLITION PLAN KEYED NOTES:
REMOVE WITH CARE AND STORE FOR REUSE: CEILING
TILE, ALL LIGHTING, FIRE ALARM DEVICES, DIFFUSERS,
ETC. TO BE REUSED IN ENCLOSED FILE & STORAGE
ROOMS IN NEW FIT-OUT. DO NOT REUSE DAMAGED
MATERIALS.
EXISTING 2X2 LIGHT TO BE SAVED AND REUSED.
REFER TO KEYED NOTE #1 THIS SHEET.
EXISTING CEILING MOUNTED SUPPLY DIFFUSER
TO BE REMOVED AND SAVED FOR REUSE AS
NOTED IN KEYED NOTE #1 THIS SHEET.
EXISTING SPRINKLER HEAD TO BE
MODIFIED, COORDINATE WITH FP101
F EXISTING FIRE ALARM DEVICE TO BE
REMOVED, SEE NOTE #19 THIS PAGE
AREA TO BE RETURNED TO GSA BY USER
GROUP.
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
6TH FLOOR DEMOLITION RCP
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
D102
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
3/32" = 1'-0"1 6TH FLOOR DEMOLITION RCP
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ADHERE TO THE FOLLOWING:
1. ERECT AND MAINTAIN TEMPORARY STAGING, LIGHTS, BARRICADES, WARNING SIGNS, AND GUARDS NECESSARY TO PROTECT BUILDING OCCUPANTS, AND ADJOINING TENANTS FROM INJURY, AND/OR DAMAGE, ALL IN ACCORDANCE WITH APPLICABLE RULES AND REGULATIONS.
2. DO NOT CLOSE OR OBSTRUCT THE PATH OF EGRESS, CORRIDORS, OR OTHER OCCUPIED OR USED SPACES OR FACILITIES WITHOUT THE WRITTEN PERMISSION OF THE OWNER AND THE AUTHORITIES HAVING JURISDICTION. DO NOT INTERRUPT UTILITIES WITHOUT THE WRITTEN PERMISSION OF THE AUTHORITIES HAVING JURISDICTION. IF NECESSARY PROVIDE TEMPORARY UTILITIES. PRIOR TO OBSTRUCTION OF EGRESS PATHS OR IMPAIRMENT OF FIRE/LIFE SAFETY COMPONENTS, THE NFPA 241 AND IMPAIRMENTS PLANS MUST BE SUBMITTED FOR APPROVAL BY DESIGN TEAM FIRE PROTECTION ENGINEER WHO IS LICENSED PROFESSIONAL ENGINEER (IN FIRE PROTECTION ENGINEERING) (DTFPEPE) AND GSA
REGIONAL FIRE PROTECTION ENGINEER (GSARFPE).
3. CEASE OPERATION IF PUBLIC SAFETY OR REMAINING STRUCTURES ARE ENDANGERED. PERFORM TEMPORARY CORRECTIVE MEASURES UNTIL
OPERATIONS CAN BE CONTINUED PROPERLY.
4. IN COMPANY OF THE ARCHITECT AND OWNER, THE CONTRACTOR WILL VISIT THE SITE AND VERIFY THE EXTENT AND LOCATION OF SELECTIVE DEMOLITION REQUIRED PRIOR TO STARTING THE WORK. CAREFULLY IDENTIFY THE LIMITS OF SELECTIVE DEMOLITION. MARK INTERFACE SURFACES AS REQUIRED TO ENABLE THE WORKMEN TO ALSO IDENTIFY THE ITEMS TO BE REMOVED AND STORED, AS WELL AS THE ITEMS TO BE LEFT IN
PLACE INTACT.
5. USE MEANS NECESSARY TO PREVENT DUST FROM BECOMING A NUISANCE TO OTHER TENANTS OF THE BUILDING, THE PUBLIC, NEIGHBORING
BUILDINGS, AND TO ANY OTHER WORK BEING PERFORMED.
6. EXECUTE DEMOLITION WORK TO ENSURE THE SAFETY OF PERSONS AND ADJACENT PROPERTY AGAINST DAMAGE BY DEBRIS. CONTRACTOR
WILL TAKE PROTECTIVE MEASURES TO PREVENT DUST FROM GETTING INTO DUCTS.
7. IN THE EVENT OF DEMOLITION OF ITEMS NOT SO SCHEDULED TO BE DEMOLISHED, PROMPTLY REPLACE SUCH ITEMS TO THE APPROVAL OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO EXISTING FEATURES AS A RESULT OF THIS WORK. DAMAGED ITEMS SHALL BE REPLACED IN KIND AND AT NO ADDITIONAL COST TO THE OWNER.
8. SHORE, BRACE AND SUPPORT EXISTING CONDITIONS AS REQUIRED FOR REMOVAL OF EXISTING CONSTRUCTION OR INSTALLATION OF THE NEW
WORK.
9. COORDINATE THE REMOVAL, RELOCATION, REPLACEMENT, RE-USE, SHUT-OFF, STUB-OFF, CAPPING-OFF OR UPGRADING OF ALL EXISTING PLUMBING, SPRINKLERS (SEE #16 BELOW), HVAC, SECURITY, ELECTRICAL SYSTEMS, AND TELECOM SYSTEMS EQUIPMENT, AND APPURTENANCES - INCLUDING, BUT NOT LIMITED TO , UTILITY LINES, DUCTS, CONNECTIONS, PANELS, VENTS, FANS, ELECTRICAL BASEBOARD HEAT, PIPING , DEVICES, CONTROLS, SWITCHES, OUTLETS, AND CONDUIT DURING THE PHASED CONSTRUCTION AS REQUIRED, AS SCHEDULED OR AS SPECIFIED IN ACCORDANCE WITH ALL LOCAL, MUNICIPAL, STATE CODES AND THE CODES LISTED IN GENERAL DEMOLITION NOTE 15.
10. THE CONTRACTOR SHALL REMOVE AND LEGALLY DISPOSE OF ANY HAZARDOUS MATERIALS AND IN DOING SO SHALL COMPLY WITH ALL APPLICABLE OSHA REGULATIONS AND ALL OTHER FEDERAL, STATE AND LOCAL GUIDELINES REGARDING ASBESTOS-CONTAINING MATERIAL
REMOVAL AND DISPOSAL.
11. OWNER AND ARCHITECT SHALL NOT BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES FOR SAFETY PRECAUTIONS OR FOR THE CONTRACTORS FAILURE TO CARRY OUT THE WORK IN STRICT ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS. OWNER SHALL NOT BE RESPONSIBLE FOR ERRORS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR
THEIR AGENTS OR EMPLOYEES OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK.
12. THE CONTRACTOR SHALL COORDINATE ALL ABOVE CEILING MEP AND STRUCTURAL ELEMENTS PRIOR TO DEMOLITION OF WALLS AND/OR CEILING. THE CONTRACTOR SHALL OBTAIN THE GSA REGIONAL FIRE PROTECTION ENGINEER (GSARFPE) APPROVAL OF NFPA 241 SAFETY PLAN AND FIRE SPRINKLER FOR SHELL COVERAGE SUBMITTAL PRIOR TO START OF CEILING DEMOLITION.
13. COORDINATE, TERMINATE, RELOCATE ALL ASSOCIATED WALL & CEILING ELECTRICAL (TELECOM/POWER OUTLETS, SWITCHING, THERMOSTAT, ETC.) DEVICES THAT ARE LOCATED FOR WALLS & CEILINGS SCHEDULED FOR REMOVAL, GC TO V.I.F. PRIOR TO THE COMMENCEMENT OF WORK.
14. SUBMIT DEMOLITION SCHEDULE FOR APPROVAL INCLUDING SCHEDULE AND METHODS OF CAPPING AND CONTINUING UTILITY SERVICE.
15. THE CONTRACTOR SHALL COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS AND 29 CFR 1910.34, COVERAGE AND DEFINITIONS, 29 CFR 1910-35, COMPLIANCE WITH NFPA 101-2009, LIFE SAFETY CODE, 29 CFR 1910-36, DESIGN AND CONSTRUCTION REQUIREMENTS FOR EXIT ROUTES, 29 CFR 1910-37, MAINTENANCE, SAFEGUARDS, AND OPERATIONAL FEATURES FOR EXIT ROUTES. PBS P-100 CHAPTER 7, 2009. THE CONTRACTOR SHALL ALSO COMPLY WITH THE GSA IMPAIRMENT PLAN GUIDE
ATTACHED TO THE SPECIFICATION 13195, WET PIPE SPRINKLER SYSTEM.
16. FIRE SPRINKLER SYSTEM SHALL BE RETURNED TO UPRIGHT SPRINKLER HEAD COVERAGE CONSISTENT WITH BUILDING SHELL COVERAGE PER
NFPA 13.
17. CONTRACTOR SHALL CONSTRUCT TEMPORARY BARRIER IN ACCORDANCE WITH DUST CONTROL PROVISIONS, REVIEW WITH GSA PROJECT
MANAGER FOR FINAL APPROVAL.
18. 2X2 ACT CEILING TILES, WHERE SCHEDULED FOR REMOVAL, TO BE CAREFULLY REMOVED AND STORED FOR REUSE IN NEW CEILING
CONFIGURATION.
19. ALL FIRE ALARM NOTIFICATION DEVICES, EXIT SIGNAGE AND EMERGENCY LIGHTING TO REMAIN OPERATIONAL DURING DEMOLITION AND CONSTRUCTION UNTIL WHICH POINT THAT NEW FIRE ALARM SPEAKER STROBE DEVICES ARE READY TO BE INSTALLED AND ACTIVATED.
GENERAL DEMOLITION NOTES:
REFER TO PROJECT COORDINATION SPECIFICATION
1. THE FLOOR WILL REMAIN OCCUPIED DURING DEMOLITION ACTIVITIES.
NOISE CONTROL PROVISIONS ARE REQUIRED TO ENSURE AGAINST
DISTURBANCE OR DISRUPTION OF WORK ACTIVITIES OF THE TENANTS ON
THIS FLOOR, AND THOSE ON THE FLOORS ABOVE AND BELOW.
2. ANY PROPOSED INTERRUPTION TO TENANT OPERATIONS DURING
DEMOLITION MUST HAVE PRIOR APPROVAL FROM THE GSA BUILDING
MANAGER WITH A MINIMUM OF 72 HOURS ADVANCE NOTICE.
3. THE DEMOLITION SUBCONTRACTOR SHALL ADOPT QUIETER TYPES OF
DEMOLITION AS IS PRACTICAL BY USING POWER TOOLS EQUIPPED WITH
SILENCERS.
4. THE GC SHALL COORDINATE REASONABLE HOURS OF WORKING FOR
NOISY OPERATIONS WITH THE GSA BUILDING MANAGER. SOME WORK WILL
HAVE TO BE DONE AFTER-HOURS OR ON WEEKENDS.
5. THE GC SHALL PROVIDE PROVISIONS TO ENSURE AGAINST SOUND AND
VIBRATION NOISE TO TENANTS ON THIS FLOOR, AND THOSE ON THE FLOORS
ABOVE AND BELOW.
NOISE CONTROL PROVISIONS:
REFER TO PROJECT COORDINATION SPECIFICATION
1. THE FLOOR WILL REMAIN PARTIALLY OCCUPIED DURING DEMOLITION
ACTIVITIES. DUST CONTROL PROVISIONS ARE REQUIRED TO ENSURE
AGAINST MIGRATION OF ALL DUST AND DEMOLITION DEBRIS TO
OCCUPIED SPACES.
2. THE GC SHALL PROVIDE A DOUBLE CONTAINMENT POLY (MIN 6 MIL) AT
ALL ENTRY AND EGRESS PATHS IN AND OUT OF THE LIMIT OF WORK AREA.
REPLACE AS OFTEN AS NEEDED TO ENSURE AGAINST MIGRATION OF DUST
AND CONSTRUCTION DEBRIS OUTSIDE OF THE WORK AREA. THE
CONTRACTOR SHALL COMPLY WITH THE MARKING OF EGRESS IN
ACCORDANCE WITH THE CODE REQUIREMENT THROUGHOUT THE
DEMOLITION.
3. THE GC SHALL PROVIDE DAILY REMOVAL OF ALL DEMOLITION DEBRIS.
DO NOT STORE ANY DEMOLITION DEBRIS ON THE FLOOR OVERNIGHT.
4. THE GC SHALL MAINTAIN A CLEAN AND SAFE WORK AREA
THROUGHOUT THE PERIOD OF DEMOLITION. THE GC SHALL, AT THE END
OF EACH WORK DAY, REMOVE ALL DEMOLITION DEBRIS AND HAZARDOUS
AND POTENTIALLY DANGEROUS MATERIALS USED IN THE WORK.
5. THE GC SHALL COLLECT CONSTRUCTION MATERIAL AND DEBRIS
FREQUENTLY AND DISPOSE OF OR RECYCLE DEBRIS AND REFUSE AWAY
FROM THE CENTER IN A LAWFUL MANNER.
6. THE GC SHALL CLEAN THE EXTERIOR PUBLIC AREAS IMPACTED BY
CONSTRUCTION DUST, DIRT AND DEBRIS ON A DAILY BASIS. THE GC
SHALL BE RESPONSIBLE FOR ALL FEES, PERMITS, ETC., REQUIRED FOR
WASTE DISPOSAL.
DUST CONTROL PROVISIONS:
R
EF
LIFE SAFETY PLAN LEGEND:
FIRE EXTINGUISHER
ILLUMINATED EXIT SIGN
PATH OF EGRESS TRAVEL
FE
CEILING/WALL MOUNTED SPEAKER/STROBE
1 HOUR RATED PARTITION
F
4 5 6 7 8 9 10 11 12
G
H
J
K
L
AREA PORT
DIRECTOR
APD
CONFERENCE
ROOM
APD SUITE
OPEN OFFICE
FP&F PROCESS
ROOM
ASST AREA
PORT
DIRECTOR
IMPORT
SUPERVISOR
IMPORT
SUPERVISOR
CORRIDOR
OPEN OFFICE
CONFERENCE
ROOM
BREAK ROOM
NTEU
CORRIDOR
MEDIUM DENSITY
FILE ROOM
IMPORT
SUPERVISOR
DOCUMENT
HANDLING ROOM
C O
R R
ID
O
R
FP&F OFFICER
OFFICE
TE
LE
W
IR
IN
G
C
LO
SE
T
ENTRY
SUPERVISOR
PARALEGAL
SPEC OFFICE
ENTRY
SUPERVISOR
C O
R R
ID
O
R
VISITOR
OFFICE
SECO
OPEN OFFICE
SUPPLIES/GENERAL
STORAGE ROOM
CONFERENCE
ROOM
PUBLIC ENTRY
COUNTER
CASHIER'S
OFFICE
LACTATION ROOM
PIV CARD
STATION
ELEC
TELE
STAIR #2
M
IN
3'
8" 130'111'
128'
81'
73'
FE
FE
F F
F
F
F
F
F
F F
F
F
F F
F F
FFF
F
F
F
F
FF
FF
F
F
F
FF
F
F
F
F
F
F
F
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
LIFE SAFETY PLAN AND CODE REVIEW
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
A001
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
2009 IBC - ICC INTERNATIONAL CODE
ADAAG - ADA ACCESSIBILITY GUIDELINES
NFPA 101-2009, NFPA 72-2012, NFPA 13-2012
PBS P100 - NOV. 2010 EDITION
BUILDING OCCUPANCY PER IBC BUSINESS GROUP B
BUILDING FLOOR AREA
BUSINESS 14278 SF
TOTAL BUILDING FLOOR AREA 14278 SF
REQUIRED RATING
MEDIUM DENSITY FILE ROOM 1 HOUR RATED PARTITION
AUTOMATIC SPRINKLER SYSTEM PROVIDED THROUGHOUT
OCCUPANT LOAD FACTOR
BUSINESS 100 SF/PERSON
OCCUPANT LOAD FLOOR AREA OCCUPANT
BUSINESS 14278 SF @ 100 GROSS = 143
EXITS REQUIRED MINIMUM ACTUAL
BUSINESS 2 2
MAX. ALLOWABLE TRAVEL DISTANCE
SHALL NOT EXCEED 300' (SPRINKLERED)
MAXIMUM ALLOWABLE DEAD END 50'
MAXIMUM ALLOWABLE COMMON MAXIMUM ACTUAL
PATH OF TRAVEL 100' 42'
LIFE SAFETY CODE SUMMARY:
1/8" = 1'-0"1 6TH FLOOR LIFE SAFETY PLAN
1/4" MIN. FIRESTOPPING
FILL MATERIAL APPLIED
ON BOTH SIDES OF
PARTITION
DEFLECTION TRACK
DEFLECTION TRACK
1/4" MIN. FIRESTOPPING
FILL MATERIAL APPLIED
ON BOTH SIDES OF
PARTITION
CONCRETE FILLED DECKING
3 5/8", 20 GA. METAL STUD
5/8" TYPE "X" GWB.
UL DESIGN SYSTEM
No. HW-D-0103
DEFLECTION TRACK DETAIL AT RATED AND SMOKE ENCLOSURE CONDITIONS
RATED WALL HORIZONTAL TO DECK FLUTES RATED WALL PERPENDICULAR TO DECK FLUTES 3'
4"
5'
6"
1'
6"
4'
0"
6'
8"
FIRE PULL
FIRE HORN
CL -ALIGN - FIRE PULL & FIRE HORN
CL DOOR & EXIT LIGHT
EXIT SIGN FIELD
LOCATE CONSULT
ARCHITECT FOR FINAL
LAYOUT APPROVAL
THERMOSTAT
(ALIGN CENTER WITH
LIGHT SWITCH IN
OFFICE AND
CONFERENCE
LOCATIONS)
FIRE
EXTINGUISHER
LIGHT
SWITCH
OUTLET
(DATA & POWER)
6"
OFFICE
DIMENSION LINE
PARTITION TAG
SYMBOL LEGEND
NORTH ARROW
BREAK MARK
GRID LINE
ELEVATION/DETAIL
TITLE REFERENCE
ROOM DESIGNATION
ROOM NUMBER
PLAN DETAIL TAG
SECTION CUT TAG
COLUMN DESIGNATION
ELEVATION DESIGNATION
X'-X"
X'-X"
X'-X"
DOOR AND DOOR
TAG
SCALE:
XX SF SQUARE FOOTAGE (IF USED)
XX
X
X
XXXX
x
A
ACT
ADA
ADJ
AFF
AL
ALT
AP
ARCH
AUTO
B
BD
BIT
BLDG
BL
BM
BR
BSMT
BTW
C
CAB
CPT
CER
CFCI
CFOI
CG
CJ
CLO
CLR
CMU
COL
COMB
CON
CONC
COND
CONF
CONN
CONT
CONST
COOD
CORR
CW
D
DBL
DEG
DEMO
DEPT
DET
DF
DIA
DIAG
DIFF
DIM
DIR
DN
DR
DS
DTFPEPE
DW
DWG
E
EA
EJ
EL
ELEC
ELEV
EMG
EMP
ENCL
EOAE
ES
EQ
EQUIP
EXH
EX
EXT
A
ACOUSTIC CEILING TILE
AMERICANS WITH DISABILITIES ACT
ADJUSTABLE
ABOVE FINISH FLOOR
ALUMINUM
ALTERNATE
ACCESS PANEL
ARCHITECTURAL
AUTOMATIC
B
BOARD
BITUMINOUS
BUILDING
BLOCKING
BEAM
BRICK
BASEMENT
BETWEEN
C
CABINET
CARPET
CERAMIC
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CONTRACTOR FURNISHED OWNER INSTALLED
CORNER GUARD
CONTROL JOINT
CLOSET
CLEAR
CONCRETE MASONRY UNIT
COLUMN
COMBUSTIBLE
CONDITION
CONCRETE
CONDUIT
CONFERENCE
CONNECTION
CONTINUOUS
CONSTRUCTION
COORDINATE
CORRIDOR
COLD WATER
D
DOUBLE
DEGREE
DEMOLISH
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
DIAGONAL
DIFFUSER
DIMENSION
DIRECTOR
DOWN
DOOR
DOWNSPOUT
DESIGN TEAM FIRE PROTECTION ENGINEER
PROFESSIONAL ENGINEER
DISH WASHER
DRAWING
E
EACH
EXPANSION JOINT
ELEVATION
ELECTRIC
ELEVATOR
EMERGENCY
EMERGENCY POWER
ENCLOSED
EQUIVALENT OR APPROVED EQUAL
EACH SIDE
EQUAL
EQUIPMENT
EXHAUST
EXISTING
EXTERIOR
M
MFR
MIN
MIR
MISC
MLDG
MLWK
MO
MOD
MT
MTD
MTL
MUL
N N
NIC
NO
NTS
O
OA
OAE
OC
OD
OFCI
OFF
OFOI
OH
OPP
P
PBD
PCC
PED
PERF
PER
PERM
PERP
PG
PH
PL
P-LAM
PLWD
PNL
POL
PORT
PRNT
PROJ
PROP
PT
PTD
PTW
PAV
PWR
Q
QT
QTR
QUAN
R R
RB
RCP
RECP
RECT
RECV
REQ
RES
RET
REV
RFPE
RM
RND
RO
RTU
M
MANUFACTURER
MINIMUM
MIRROR
MISCELLANEOUS
MOULDING
MILLWORK
MASONRY OPENING
MODULAR
MOUNT
MOUNTED
METAL
MULLION
N
NORTH
NOT IN CONTRACT
NUMBER
NOT TO SCALE
O
OVERALL
OR APPROVED EQUAL
ON CENTER
OUTSIDE DIAMETER
OWNER FURNISHED CONTRACTOR INSTALLED
OFFICE
OWNER FURNISHED OWNER INSTALLED
OPPOSITE HAND
OPPOSITE
P
PARTICLEBOARD
PRECAST CONCRETE
PEDESTAL
PERFORATED
PERIMETER
PERMANENT
PERPENDICULAR
PLATE GLASS
PHASE
PLATE
PLASTIC LAMINATE
PLYWOOD
PANEL
POLISHED
PORTABLE
PRINTER
PROJECT
PROPERTIES
PRESSURE TREATED
PAINTED
PRESSURE TREATED WOOD
PAVEMENT
POWER
Q
QUARRY TILE
QUARTER
QUANTITY
R
RADIUS
RUBBER BASE
REFLECTED CEILING PLAN
RECEPTION
RECTANGULAR
RECEIVING
REQUIRED
RESILIENT
RETURN
REVISION
REGIONAL FIRE PROTECTION ENGINEER
ROOM
ROUND
ROUGH OPENING
ROOF TOP UNIT
S
SAN
SB
SC
SCHED
SD
SDT
SECT
SF
SGPL
SHEA
SHT
SI
SIM
SPEC
SPK
SPC
SQ
SS
STD
STL
STOR
STR
STRUC
SUP
SURF
SV
SYM
SYN
T T1 T2
TF
TBD
TEL
TEMP
T&G
TO
TOIL
TOL
TRD
TWS
TYP
U
UBC
UON
U.S.
V
VP
VAR
VB
VCT
VERT
VEST
VIF
W W/ W/O
WD
WDC
W/D
WIN
WG
WH
WK
S
SANITARY
BACKPAINTED SPANDREL INSULATING GLASS
SOLID CORE
SCHEDULE
SOAP DISPENSER
STATIC DISSIPATIVE TILE
SECTION
SQUARE FEET
STRUCTURAL GRADE PLASTIC LUMBER
SHEATHING
SHEET
SPANDREL INSULATING GLASS
SIMILAR
SPECIFICATION
SPEAKER
SPECIAL
SQUARE
STAINLESS STEEL
STANDARD
STEEL
STORAGE
STRAIGHT
STRUCTURAL
SUPPORT
SURFACE
SHEET VINYL
SYMMETRICAL
SYNTHETIC
T
TEMPERED GLASS
TEMPERED INSULATING GLASS
TEMPERED INSULATING W/ APPLIED FILM
TO BE DETERMINED
TELEPHONE
TEMPORARY
TONGUE AND GROOVE
TOP OF
TOILET
TOLERANCE
TREAD
TEACHER WORK STATION
TYPICAL
U
UNIFORM BUILDING CODE
UNLESS OTHERWISE NOTED
UNDERSIDE OF STRUCTURE
V
VAPOR
VARIABLE
VINYL BASE
VINYL COMPOSITE TILE
VERTICAL
VESTIBULE
VERIFY IN FIELD
W
WITH
WITHOUT
WOOD
WOOD W/ COPPER CLADDING
WASHER/DRYER
WINDOW
WIRE GLASS
WATER HEATER
WORK
F
FA
FDN
FE
FEC
FF
FHC
FIN
FLASH
FLEX
FLR
FLOUR
FP
FPEPE
FRZ
FT
FURR
G
GALV
GB
GC
GL
GRND
GWB
GYP
H
HC
HCWD
HDWD
HDWR
HDR
HM
HORZ
HR
HT
HTR
HVAC
HW
I
IBC
ID
IN
INCD
INCL
INFO
INSUL
INT
J
JAN
K
KD
KO
KP
L
LAB
LAUN
LAV
LF
LIN
LT
M
MAS
MAT
MAX
MDF
MDO
MDX
MECH
F
FIRE ALARM
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH FLOOR
FIRE HOSE CABINET
FINISHED
FLASHING
FLEXIBLE
FLOOR
FLUORESCENT
FIRE PROOFING
FIRE PROTECTION ENGINEER/PROF. ENGINEER
FREEZER
FEET,FOOT
FURRING
G
GALVANIZED
GRAB BAR
GENERAL CONTRACTOR
GLASS
GROUND
GYPSUM WALLBOARD
GYPSUM
H
HANDICAP
HOLLOW CORE WOOD
HARDWOOD
HARDWARE
HEADER
HOLLOW METAL
HORIZONTAL
HOUR
HEIGHT
HEATER
HEATING, VENTILATION, AIR CONDITIONING
HOT WATER
I
INTERNATIONAL BUILDING CODE
INSIDE DIAMETER
INCH
INCANDESCENT
INCLUDED
INFORMATION
INSULATION
INTERIOR
J
JANITOR
K
KNOCK DOWN
KNOCK OUT
KICK PLATE
L
LABORATORY
LAUNDRY
LAVATORY
LINEAR FEET
LINEAR
LIGHT
M
MASONRY
MATERIAL
MAXIMUM
MEDIUM DENSITY FIBERBOARD
MEDIUM DENSITY OVERLAY
MEDIUM DENSITY OVERLAY EXTERIOR GRADE
MECHANICAL
ARCHITECTURAL ABBREVIATIONS LIST:
1" COMPRESSIBLE NEOPRENE
GASKET
3 5/8" MTL STUD 20 GA.
5/8" GWB
SOUND ATT. BATT
INSULATION
EXISTING GLAZING
PROFILE OF SILL BELOW
(HEADER ABOVE SIMILAR)
CORNER
BEAD WITH
COMPOUND
FU
LL
H
EI
G
H T
W
AL
L R
EF
ER
T O
/D
W
AL
L
IN
FI
LL
R
ES
TS
O
N S
IL
L
AN
D
A
TT
AC
H
ES
TO
H
EA
D
ER
5/8" GWB FULL HEIGHT BOTH SIDES - PRIME &
PAINT - MOISTURE RESISTANT IN DAMP AREAS
4" BASE REFER TO SPECS FOR PROFILE AND
COLOR, TYPICAL.
NEW/REWORKED
ACOUSTICAL
CEILING TILE
3 5/8" 20 GAUGE MTL. STUDS @ 16" O.C.
UNDERSIDE OF
STRUCTURAL DECK
CONTINUOUS 3 5/8" METAL STUD TRACK
SECURE TRACK TO FLOOR WITH POWDER
ACTUATED FASTENERS - TYPICAL ALL
NEW PARTITIONS
FLOOR LINE
APPLY TAPE AND
JOINT COMPOUND
AT ALL JOINTS TO
ACHIEVE A SMOOTH
FLAT SURFACE
12 GA. HANGER WIRE
ANCHORED TO
STRUCTURE ABOVE
6"
NEW ACT EDGE GRID EACH SIDE - ENTIRE LENGTH OF
NEW WALL. TYP BOTH SIDES OF PARTITION.FRICTION FIT SOUND
BATT INSULATION @
EACH STUD SPACE
5/8" GWB
4" BASE REFER TO SPECS FOR PROFILE AND
COLOR, TYPICAL.
NEW/REWORKED
ACOUSTICAL
CEILING TILE
3 5/8" 20 GAUGE MTL. STUDS @ 16" O.C.
UNDERSIDE OF
STRUCTURAL DECK
CONTINUOUS 3 5/8" METAL STUD TRACK
SECURE TRACK TO FLOOR WITH POWDER
ACTUATED FASTENERS - TYPICAL ALL
NEW PARTITIONS
NEW ACT EDGE GRID EACH
SIDE - ENTIRE LENGTH OF
NEW WALL - TYP. BOTH
SIDES OF PARTITION
FLOOR LINE
APPLY TAPE AND
JOINT COMPOUND
AT ALL JOINTS TO
ACHIEVE A SMOOTH
FLAT SURFACE
FRICTION FIT SOUND
BATT INSULATION @
EACH STUD SPACE
CONTINUOUS FIRE &
SMOKE SEALANT TO BOTH
SIDES OF STEEL RUNNERS
(TOP & BOTTOM)
3-5/8" X 20 GA SLIP TRACK
CONNECTION, TYP.
NOTE: PROTECT AND SEAL
ALL PENETRATIONS
THROUGH A RATED WALL
WITH AN APPROVED
THROUGH-PENETRATION
FIRESTOP SYSTEM
PARTITION TYPE 2A - 5/8" GWB ON ONE SIDE ONLY
PARTITION TYPE 2B - 1 HR RATED W/ 5/8" TYPE X GWB TYPICAL
5/8" TYPE X GWB
4" BASE REFER TO SPECS FOR PROFILE AND
COLOR, TYPICAL.
NEW/REWORKED
ACOUSTICAL
CEILING TILE
3 5/8" 20 GAUGE MTL. STUDS @ 16" O.C.
UNDERSIDE OF
STRUCTURAL DECK
CONTINUOUS 3 5/8" METAL STUD TRACK
SECURE TRACK TO FLOOR WITH POWDER
ACTUATED FASTENERS - TYPICAL ALL
NEW PARTITIONS
NEW ACT EDGE GRID EACH
SIDE - ENTIRE LENGTH OF
NEW WALL - TYP. BOTH
SIDES OF PARTITION
FLOOR LINE
APPLY TAPE AND JOINT
COMPOUND AT ALL JOINTS
TO ACHIEVE A SMOOTH FLAT
SURFACE
FRICTION FIT SOUND
BATT INSULATION @
EACH STUD SPACE
CONTINUOUS FIRE &
SMOKE SEALANT TO BOTH
SIDES OF STEEL RUNNERS
(TOP & BOTTOM)
3-5/8" X 20 GA SLIP TRACK
CONNECTION, TYP.
NOTE: PROTECT AND SEAL
ALL PENETRATIONS
THROUGH A RATED WALL
WITH AN APPROVED
THROUGH-PENETRATION
FIRESTOP SYSTEM
9 GA 1 1/2" X 2" DIAMOND MESH
GRID EXPANDED METAL
REINFORCING. MECHANICALLY
FASTEN W/ TAMPERPROOF
FASTENERS HORIZONTALLY AND
VERTICALLY @ 6" INTERVALS.
MESH SPLICE SHALL OCCUR AT
STUDS ONLY.
EXISTING GWB
EXISTING WALL CONSTRUCTION
UNDERSIDE OF
STRUCTURAL DECK
NEW ACT EDGE GRID EACH SIDE -
ENTIRE LENGTH OF NEW WALL -
TYP. BOTH SIDES OF PARTITION
FLOOR LINE
APPLY TAPE AND JOINT COMPOUND
AT ALL JOINTS TO ACHIEVE A
SMOOTH FLAT SURFACE
CONTINUOUS FIRE &
SMOKE SEALANT TO BOTH
SIDES OF STEEL RUNNERS
(TOP & BOTTOM)
NOTE: PROTECT AND SEAL
ALL PENETRATIONS
THROUGH A RATED WALL
WITH AN APPROVED
THROUGH-PENETRATION
FIRESTOP SYSTEM
9 GA 1 1/2" X 2" DIAMOND MESH GRID
EXPANDED METAL REINFORCING.
MECHANICALLY FASTEN W/
TAMPERPROOF FASTENERS
HORIZONTALLY AND VERTICALLY @ 6"
INTERVALS. MESH SPLICE SHALL
OCCUR AT STUDS ONLY.
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
PARTITION TYPES AND GENERAL INFO
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
A002
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
1/2" = 1'-0"6 TYPICAL MOUNTING HEIGHTS
1 1/2" = 1'-0"4 DETAIL - WALL TO WINDOW MULLION
3" = 1'-0"5 TYPICAL DEFLECTION TRACK DETAIL AT RATED AND SMOKE ENCLOSURE CONDITIONS
1 1/2" = 1'-0"
PARTITION TYPE 1 - 6" ABOVE CEILING1 1 1/2" = 1'-0"
PARTITION TYPE 2 - FULL HEIGHT2 1 1/2" = 1'-0"
PARTITION TYPE 3 - SECURITY WALL3 1 1/2" = 1'-0"
PARTITION TYPE 3A - SECURITY MESH ON EXISTING WALL3A
EF
4 5 6 7 8 9 10 11 12
G
H
J
K
L
AREA PORT
DIRECTOR
APD
CONFERENCE
ROOM
APD SUITE
OPEN OFFICE
FP&F PROCESS
ROOM
ASST AREA
PORT
DIRECTOR
IMPORT
SUPERVISOR
IMPORT
SUPERVISOR
CORRIDOR
OPEN OFFICE
CONFERENCE
ROOM
BREAK ROOM
NTEU
CORRIDOR
MEDIUM DENSITY
FILE ROOM
IMPORT
SUPERVISOR
DOCUMENT
HANDLING ROOM
CORRIDOR
FP&F OFFICER
OFFICE
TELE WIRING
CLOSET
ENTRY
SUPERVISOR
PARALEGAL
SPEC OFFICE
ENTRY
SUPERVISOR
C O
R R
ID
O
R
VISITOR
OFFICE
SECO
OPEN OFFICE
SUPPLIES/GENERAL
STORAGE ROOM
CONFERENCE
ROOM
PUBLIC ENTRY
COUNTER
CASHIER'S
OFFICE
LACTATION ROOM
PIV CARD
STATION
ELEC
TELE
STAIR #2
6 7 8
15 16
A
A
5' - 0"
7'
6"
ALIGN
ALIGN
5' - 0"
ALIGN
4' - 1 1/2"6' - 10 1/2"EQ EQ
EQ
EQ
ALIGN
EQ
EQ
1"
ALIGN
ALIGN
H O
LD
3'
8"
H O
LD
3'
8"
ALIGN
8'
3" 2'
0"
5'
0"
1'
0" V
.I.
F.
5'
0"
ALIGN
7'
0"
7' - 6" 7'
0"
3'
0"
ALIGN
ALIGN
DIM. WITH FURN. VENDOR
HOLD 16' - 6" CONFIRM
ALIGN
1' - 0"
3'
8"
ALIGN
ALIGN
4'
6"
2' - 7"135.00°
C O
N
FI
R M
W
IT
H E
XI
ST
IN
G
C
AB
IN
ET
S
" C
LE
AR
M
IN
IM
U
M
ALIGN
90.00°
A3023
A3022
4'
7"
ALIGN
3' - 0"
13' - 9 1/2" V.I.F.
2B
2B 2B
2B
3 2
A002
TYP. AT
ALL SIM.
LOCATIONS
18" HOLD
2B
A301
A3021
EXISTING F.C.U.
2A2A
EX
3A3A3A
3A
4' - 0"
ENTRY CORRIDOR
B
A302
A301
SIM
3A
WALL ABOVE
AND TO SIDE
OF DOOR TO
BE PARTITION
TYPE 3
2 1
3A
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
6TH FLOOR PLAN
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
A101
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
1/8" = 1'-0"4 6TH FLOOR PLAN
GENERAL NOTES
1. ALL PARTITIONS TO BE TYPE "1" - U.O.N.
2. DO NOT SCALE DRAWINGS, REFER TO WRITTEN DIMENSIONS, WHERE WRITTEN DIMENSIONS ARE NOT
PROVIDED CONSULT ARCHITECT PRIOR TO AFFECTING WORK IN THAT AREA.
3. SEAL NEW AND EXISTING PENETRATIONS THROUGH EXISTING RATED PARTITIONS AND FLOORS TIGHTLY TO MAINTAIN FIRE RATINGS REQUIRED, SEAL TIGHT AROUND PIPING, CONDUITS AND DUCTS. APPLY PENETRATIONS
THROUGH PARTITIONS AND FLOORS WITH APPROVED FIRE/SMOKE STOPPING SYSTEM.
4. PROVIDE DEFLECTION TRACK AT PARTITION WHICH TERMINATES AT UNDERSIDE OF EXISTING STRUCTURE.
5. FACE OF WALL FINISH AT FILLED WALLS SHALL BE FLUSH WITH THE FACE OF EXISTING ADJACENT WALL.
6. ALL DIMENSIONS ARE FROM FACE OF EXISTING WALL TO FACE OF NEW PARTITION WALLS.
7. CONTRACTOR SHALL VERIFY ALL HOLLOW METAL FRAME THROAT DIMENSIONS PRIOR TO INSTALLATION OF
DOORS.
8. CONTRACTOR SHALL LAYOUT, ON CONCRETE, LOCATIONS OF ALL INTERIOR PARTITIONS AND WORK STATIONS PRIOR TO THE START OF FRAMING, CONSULT ARCHITECT WITH ANY QUESTIONS OR FIELD
DISCREPANCIES PRIOR TO COMMENCING WORK. LAYOUT TO BE APPROVED BY GSA.
9. CONCRETE SLAB TO BE PROPERLY FLASHED AND LEVELED TO MEET MANUFACTURER'S RECOMMENDATIONS FOR ALL SPECIFIED FLOORING PRODUCTS PRIOR TO INSTALLATION OF FLOORING MATERIALS. SLAB MUST BE STRUCTURALLY SOUND, FREE OF ALL DIRT, DUST, SEALING COMPOUND, AND OTHER SURFACE CONTAMINANTS PRIOR TO INSTALLATION. MAXIMUM VARIATION IN CONCRETE SLAB SHALL NOT EXCEED 1/8" IN 10'-0". CRACKS OF 1/8" OR MORE, HOLES AND OTHER UNEVENNESS MUST BE FILLED WITH LATEX BASED FLOOR FILLER. HIGH SPOTS MUST BE LEVELED. FLOOR MUST BE SWEPT CLEAN, WET MOPPED WITH WARM WATER, AND SWEPT
AGAIN. IF SWEEPING LEAVES RESIDUE, FLOORS SHALL BE VACUUMED.
10. ALL SADDLES, VINYL THRESHOLDS, AND/OR REDUCING STRIPS TO BE FURNISHED AND INSTALLED BY THE FLOORING CONTRACTOR. FLOORING CONTRACTOR TO SUBMIT SAMPLES FOR ARCHITECT AND AGENCY
APPROVAL PRIOR TO ORDER AND INSTALLATION.
11. FLOORING CONTRACTOR SHALL INSPECT THE SUBFLOOR BEFORE COMMENCEMENT OF THE WORK. HE SHALL NOTIFY THE AGENCY IN WRITING OF ANY CONDITIONS WHICH WILL PREVENT HIM FROM PRODUCING
SATISFACTORY FINISHED WORK.
12. FLOORING CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ANY UNACCEPTABLE FINISH WORK
CAUSED BY SUBFLOOR CONDITIONS.
13. REAPPLY/PATCH ALL AREAS WHERE SPRAY ON FIRE-PROOFING HAS BEEN REMOVED DURING DEMOLITION
OR CONSTRUCTION.
14. ALL DOORS TO BE LOCATED 4" FROM ADJACENT PARTITION TO DOOR HINGE, U.O.N.
15. CONTRACTOR TO COORDINATE AND INSTALL FIRE RETARDANT WALL BLOCKING AT EQUIPMENT AND VIDEO
WALL MONITOR LOCATIONS. COORDINATE WITH TELE DATA DRAWINGS.
16. NEW INTERIOR PARTITIONS RUNNING PERPENDICULAR TO PERIMETER TO BE CENTERED ON EXISTING
WINDOW MULLION, UNLESS OTHERWISE NOTED.
17. CONTRACTOR SHALL REINSTALL CLEANED AND STORED WINDOW TREATMENT IN SCOPE OF WORK AREAS.
REFER TO D101 GENERAL DEMOLITION NOTE 20.
4 5 6 7 8 9 10 11 12
G
H
J
K
L
ALIGN
ALIGN
P3
THIS AREA AND CORRIDOR
P3
P2
P2
P3
P3
P3
P2
END P3 AT THIS CORNER
P3 PAINT TO COVER FRONT OF
GWB SOFFIT FOR CONTINUOUS
COLOR AT THIS LOCATION
P3 P3
P2
A401
TYP. AT ALL SIM.
LOCATIONS
A401
TYP. AT ALL SIM.
LOCATIONS
CPT1 - GENERAL - CARPET TILE
-NUMBER INDICATES EXTENT OF WALL FINISH. REFER
TO LEGEND & SPECIFICATIONSP#
FINISH PLAN LEGEND
- P1 - GENERAL WALL EGGSHELL FINISH, TYP U.O.N. REFER TO SPEC FOR COLOR
- P4 - PAINTED HOLLOW METAL DOORS & FRAMES - SEMI-GLOSS FINISH
- P5 - CEILING/SOFFIT
NOTES:
1. ALL WALLS TO BE PAINTED "P1" - U.O.N.
2. ALL GWB CEILINGS TO BE PAINTED "P5" FLAT - U.O.N.
3. ALL BASEBOARD HEATERS AND FAN COIL UNITS TO BE CLEANED, PRIMED, AND PAINTED. FINISH
TO MATCH ADJACENT WALL.
4. REFER TO SPECIFICATIONS FOR SELECTIONS:
SECTION 09910 FOR PAINT
SECTION 09650 FOR RESILIENT FLOORING
SECTION 09680 FOR CARPET
SECTION 06400 FOR ARCHITECTURAL MILLWORK
SECTION 08212 FOR FLUSH WOOD DOORS
5. ALL FLOORING MATERIAL TRANSITIONS SHALL OCCUR AT THE CENTERLINE OF DOOR WHEN
CLOSED. TRANSITIONS THAT OCCUR IN AREAS THAT DO NOT HAVE A DOOR, SHALL OCCUR AS
NOTED ON THE PLAN.
6. ALL FLOORING MATERIAL TRANSITIONS THAT HAVE A CHANGE OF HEIGHT (EX. CARPET TILE TO VCT, BUT NOT LIMITED TO THIS EXAMPLE), SHALL RECEIVE AN ADA COMPLIANT METAL TRANSITION
STRIP, SCHLUTER DECO OR RENO SERIES, OR APPROVED EQUAL.
7. ALL FLOORING TO BE CARPET TILE, CPT1, UNLESS OTHERWISE NOTED.
- P2 - GENERAL WALL EGGSHELL FINISH, ACCENT REFER TO SPEC FOR COLOR
- P3 - GENERAL WALL EGGSHELL FINISH, ACCENT 2 REFER TO SPEC FOR COLOR
VCT - VINYL COMPOSITE TILE
SDT - STATIC DISSIPATIVE TILE
EXISTING FLOORING TO REMAIN,
CONTRACTOR TO REPLACE TO
MATCH EXISTING AS REQUIRED
BY DEMOLITION WORK
CARPET TO MATCH EXISTING
LOBBY FLOORING
NOT IN SCOPE OF WORK
CPT2 - ACCENT - CARPET TILE
MCT - MARMOLEUM COMPOSITE TILE
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
6TH FLOOR FINISH PLAN
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
A102
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
1/8" = 1'-0"1 6TH FLOOR FINISH PLAN
G
H
J
K
L
AREA PORT
DIRECTOR
APD
CONFERENCE
ROOM
APD SUITE
OPEN OFFICE
FP&F PROCESS
ROOM
ASST AREA
PORT
DIRECTOR
IMPORT
SUPERVISOR
IMPORT
SUPERVISOR
CORRIDOR
OPEN OFFICE
CONFERENCE
ROOM
BREAK ROOM
NTEU
CORRIDOR
MEDIUM DENSITY
FILE ROOM
IMPORT
SUPERVISOR
DOCUMENT
HANDLING ROOM
C O
R R
ID
O
R
FP&F OFFICER
OFFICE
TE
LE
W
IR
IN
G
C
LO
SE
T
ENTRY
SUPERVISOR
PARALEGAL
SPEC OFFICE
ENTRY
SUPERVISOR
C O
R R
ID
O
R
VISITOR
OFFICE
SECO
OPEN OFFICE
SUPPLIES/GENERAL
STORAGE ROOM
CONFERENCE
ROOM
PUBLIC ENTRY
COUNTER
CASHIER'S
OFFICE
LACTATION ROOM
PIV CARD
STATION
ELEC
TELE
STAIR #2
M
IN
3'
8"
ALIGN ALIGN
M
IN
3'
8" ALIGN
ALIGN
ALIGN
ALIGN
M
IN
3'
8"
5' - 3 1/4" 33' - 3" 5' - 3 1/4"
4' - 1 1/2" 4' - 1 1/2"
ENTER ENTER
ENTER ENTER
ENTER ENTER
ENTER ENTER
ENTER
ENTRY CORRIDOR
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
6TH FLOOR FURNITURE PLAN
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
A103
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
1/8" = 1'-0"1 6TH FLOOR FURNITURE PLAN
SHOWN FOR REFERENCE ONLY, NOT IN SCOPE OF WORK
NOTES:
• ADA MINIMUM CLEARANCES REQUIRED
• DIMENSIONS NOTED ARE MINIMUMS FOR REFERENCE ONLY. PLAN IS BASED ON CLEAR INSIDE DIMENSIONS OF 8'x8' OR 8'x10' RESPECTIVELY
WITH A MAXIMUM OF 3" CLEAR PANEL WIDTH. PANEL WIDTH CANNOT EXCEED 3" MAXIMUM, OR LAYOUT WILL NOT WORK.
• LAYOUT NOTED SHOWS ENTRY TO MAXIMIZE NUMBER OF STATIONS WITHIN SPACE.
• USER GROUP TO CONFIRM LAYOUT & COORDINATE WITH CONTRACTOR/INSTALLER
• USER GROUP/VENDOR TO PROVIDE REQUIRED DIMENSIONS & POWER REQUIREMENTS FOR POWER/TELE-DATA PULLS FROM WALKER DUCT
SYSTEM AND/OR COLUMN ENCLOSURES
• COORDINATE ELECTRICAL AND CABLING REQUIREMENTS WITH ELECTRICAL AND TELECOMMUNICATION DRAWINGS.
SP
G
H
J
K
L
EQ
EQ
TYP.
EQ
TYP.
EQ
EQ EQ
ALIGN
ALIGN ALIGN
CENTER FIXTURE
IN GWB CEILING
ALIGN
ALIGNALIGN
ALIGN
ALIGN
ALIGN
ALIGN
ALIGN
ALIGN
EQ EQ
ALIGN
ALIGN
EQ EQ
ALIGN
EQ EQ
EQ
EQ
EQ EQ
EQ
EQ
EQ EQ
ALIGN WITH
CENTERLINE
OF COLUMN GRID
OS
OS
OS
OS
OS
OS OS
OS
OS OS
OS OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS OS
OSOS
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS OS OS
OS OS
OS OS
OS OS
OS OS
OS
OS
OS
OS
OS
OS
OS
8' - 0"
A401
TYP. AT ALL SIM.
LOCATIONS
8' - 0"
8' - 0"
A401
TYP. AT ALL SIM.
LOCATIONS
A401
SIM
OS
A401
OS
OS
GYPSUM WALL BOARD CEILING/SOFFIT
CEILING FINISH LEGEND
FT FULL TILE (NOTED FOR START POINT)
LIGHT FIXTURE LEGEND
SEE ELECTRICAL PLANS FOR LIGHT FIXTURE LAYOUT, RELOCATIONS,
SPECIFICATIONS, POWER, AND LAMPING REQUIREMENTS. FIXTURES
SHOWN HERE FOR GENERAL CONFIGURATION AND LOCATION ONLY.
MEP COMPONENT LEGEND
OS
SUPPLY REGISTER
STROBE
2 SIDED EXIT SIGN
OCCUPANCY SENSOR
GENERAL NOTES:
1. ALL NEW CEILINGS TO BE 8'-6" A.F.F. UNLESS OTHERWISE NOTED.
2. DIMENSIONS TO CENTERLINE OF FIXTURES UNLESS OTHERWISE NOTED
3. SOFFIT/BULKHEAD TO BE 8'-6" A.F.F. UNLESS OTHERWISE NOTED.
4. CONTRACTOR TO MAINTAIN EXISTING CEILING IN SPACE TO BE RETURNED TO GSA. CONTRACTOR IS RESPONSIBLE FOR THE REPLACEMENT OF ANY CEILING ELEMENTS DAMAGED DURING DEMOLITION WORK.
F
CEILING MOUNTED SPEAKER
NEW 2'x2' ACT CEILING
EXISTING LIGHT/DIFFUSER TO REMAIN
EXISTING 2X5, 1X5 ACT CEILING
EXHAUST FAN
1 SIDED EXIT SIGN
NOT IN SCOPE OF WORK
REFLECTED CEILING PLAN KEYED NOTES:
INFILL EXISTING CEILING TO MATCH AS REQUIRED BY
REMOVAL OF EXISTING WALLS, LIGHT FIXTURES OR
OTHER DEMOLISHED ELEMENTS. SEE DEMOLITION PLANS
FOR EXTENT OF DEMOLITION SCOPE.
NEW RECESSED DOWNLIGHT
SP
CEILING ATTACHMENT LEGEND
NEW UNDER CABINET LIGHTING
NEW 2X2 LIGHT
RETURN REGISTER
EXISTING CEILING AND ALL
ATTACHMENTS TO REMAIN,
SPACE TO BE RETURNED TO GSA
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
6TH FLOOR REFLECTED CEILING PLAN
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
A201
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
1/8" = 1'-0"1 6TH FLOOR REFLECTED CEILING PLAN
T
A301
PUBLIC ENTRY
COUNTER
14' - 0"
A301
CONCEALED
BUTT HINGE
PROVIDE
SILENCERS
A301 A301
HOLD
1' - 0"
HOLD
1' - 6"
6'
1/
2"
3'
0"
MAXIMUM MAILBOX OPENING
6' - 8"
2A
2'
0" 1'
6"
A301
SCRIBE COUNTER
TO WING WALL,
CAULK AT ALL
EDGES.
1'
6"
A301
SIM
CONRACTOR TO COORDINATE WITH CBP AND GSA PROJECT MANAGER,
PRIOR TO FABRICATION AND FINAL INSTALLATION
2" GROMMET
LOCATIONS,
COORDINATE
WITH USER
SOLID SURFACE
COUNTERTOP TO WRAP
DOWN FRONT OF DESK
AS SHOWN
5/8" PAINTED GWB
4" VINYL BASE
FINISHED FLOOR
4" VINYL BASE
FINISHED FLOOR
FEDERAL BRACE ARROWWOOD
SUPPORT BRACKET OR APPROVED
EQUAL @ 36" O.C. MAX BEYOND
PROVIDE BLOCKING AS REQUIRED
TO SECURE BRACKETS
1/
2"
2'
6"
1' - 6"2' - 0"
4'
2"
6'
8"
STANDARD TRANSACTION
WINDOW WITH PASS THRU TRAY
AND TALK-AROUND FRAME.
INSTALL PER MANUFACTURER'S
RECOMMENDED INSTALLATION,
INCLUDING, BUT NOT LIMITED TO,
FINISH, TRIM, AND BLOCKING
REQUIREMENTS
PARTITION TYPE 3, REFER TO A002
MAILBOX SUPPORT WALL
1' - 5" CORNER OF
SEALANT
SOLID SURFACE ANGLE
SUPPORT FASTENED TO
TRANSACTION COUNTER, BOTH
SIDES
FEDERAL BRACE ARROWWOOD BRACKET
OR APPROVED EQUAL.
SOLID SURFACE TOP WITH NOSING ON 3/4" X 2
1/2" FRAME. SCRIBE TIGHT TO WALL. CAULK ALL
ALONG BACK OF COUNTER AT WALL.
FILE STORAGE BY OTHERS, AS REQUIRED
VINYL WALL BASE.
2'
6"
2' - 0"
FINISHED FLOOR
4" VINYL BASE
FEDERAL BRACE ARROWWOOD
SUPPORT BRACKET OR APPROVED
EQUAL @ 36" O.C. MAX. COORDINATE
SIZE OF BRACKET WITH COUNTER
DEPTH
SOLID SURFACE
COUNTERTOP
4" VINYL BASE
FINISHED FLOOR
PROVIDE BLOCKING AS
REQUIRED TO SECURE BRACKET
1/
2"
PARTITION TYPE 3, REFER TO A002
2'
6"
1' - 6"
PROVIDE (2) 2X4 TO
FRAME OPENING
PROVIDE NESTED METAL
STUD FRAMING TYPICAL
BOTH SIDES
PREMANUFACTURED
MAILBOX ASSEMBLY.
INSTALL PER
MANUFACTURER'S
RECOMMENDED
INSTALLATION, INCLUDING,
BUT NOT LIMITED TO, FINISH,
TRIM, AND BLOCKING
REQUIREMENTS
3'
4"
SOFFIT ABOVE MAILBOXES
SEAL SEAM BETWEEN
COUNTERS, ENSURE THAT SEAM
IS HIDDEN BELOW MAILBOXES.
A401
SIM
A301
A301
STEEL FRAMED TRANSACTION
WINDOW WITH TALK AROUND FRAME
AND UL 752 RATED PASS THRU TRAY
HORIZONTAL TYPE MAILBOXES,
8 ROWS OF 6 BOXES, MINIMUM
OF 3" TALL BY 12" WIDE.
MAILBOXES SHOULD BE
LOCKABLE ON PUBLIC SIDE AND
OPEN TO THE REAR.
1'
5"
WALL TO UNDERSIDE OF
COUNTER. ALIGN WITH
REAR EDGE OF MAILBOXES
AND SOFFIT ABOVE
REFER TO PARTITION TYPE 3 FOR WALL
CONSTRUCTION. EXPANDED METAL SECURITY
MESH TO RUN UNOBSTRUCTED THE ENTIRE
LENGTH OF THE WALL, EXCEPT FOR AT
MAILBOX OPENING
REFER TO PARTITION
TYPE 2A FOR WALL
CONSTRUCTION
CORNER BEAD
A/E CON. NO.
SHEET SIZE: 30x42
C
ER
TI
FI
C
AT
IO
N
S
KE
Y
PL
AN
MARK DATE DESCRIPTION
R
EV
IS
IO
N N
O
TE
S C
O N
TR
AC
TO
R
S
BU
IL
D
IN
G
PR
O
JE
C
T D
R
AW
IN
G
A/E TASK NO.
CONS. CONTR.
CONS. WORK
PRIME A/E
SUB A/E
CONSTR. CON.
NAME
STREET
CITY / ST. / ZIP
BUILDING NO.
OTHER
BUILDING NOs.
FACILITY CODE
PROJECT
TITLE
PROJECT
DESCRIPTION
PROJECT NO.
GSA PM
SUBMISSION
SUB. DATE
DRAWING TITLE
FILE NAME
FLOOR NO.
DRAWN BY
CHECKED BY
DRAWING NO.
DISCIPLINE SHEET TYPE SEQUENCE
BBIX, L.L.C.
GENERAL SERVICES ADMINISTRATION
NEW ENGLAND REGION (REGION 1)
PROPERTY OF THE UNITED
STATES GOVERNMENT FOR
OFFICIAL USE ONLY
GS-01P-09-BW-D-0037
BUILDING
NORTH
PROJECT
SPACE
10TH FLOOR
THOMAS P. O'NEILL FED. BUILDING
10 CAUSEWAY STREET
BOSTON, MA 02222
INTERIOR ELEVATIONS & DETAILS
SIXTH FLOOR RENOVATION -
CUSTOMS & BORDER PROTECTION
JD
MS
11/30/2012
A301
FINAL AMENDMENT DOCUMENTS
JAMES MICHIENZI
1/2" = 1'-0"1 ENLARGED 6TH FLOOR PLAN - PUBLIC COUNTER
1 1/2" = 1'-0"4 TRANSACTION WINDOW DETAIL SECTION AT PUBLIC COUNTER
1 1/2" = 1'-0"6 DESK/COUNTER AT WALL
1 1/2" = 1'-0"5 MAILBOXES AT PUBLIC COUNTER
1/2" = 1'-0"3 PUBLIC COUNTER ELEVATION
3" = 1'-0"2 BELOW COUNTER FRAMING DETAIL PLAN
REUSE EXISTING COUNTER-TOP/BACKSPLASH.
PROVIDE ADD/ALTERNATE TO PROVIDE NEW.
REUSE ALL EXISTING BREAKROOM MILLWORK
CABINETRY, IN KIND. INSTALL AS NOTED IN LAYOUT.
REUSE EXISTING
REFRIG.
EXISTING
F.C.U. TO
REMAIN
REUSE/RE-INSTALL
EXISTING SINK & FAUCET
ALIGN - TYPICAL
EXISTING CABINETRY TO BE RE-USED IN KIND. PLEASE NOTE, CURRENT LAYOUT MAY NOT MEET ADA GUIDELINES FOR MOUNTING OF CABINET/COUNTER HEIGHTS. GSA/CBP TO ADVISE IF CABINETS WILL BE RE-INSTALLED IN CONFIGURATION
AS CURRENTLY INSTALLED, OR IF NEW CABINETS ARE TO BE MADE TO MEET THESE GUIDELINES.
GC TO FIELD VERIFY OVERALL DIMENSION REQUIRED TO PROPERLY REINSTALL CABINETS AND EQUIPMENT AS NOTED.
V.I.F. 18' - 0" CABINETS ONLY
NOTE: REMOVE & REUSE EXISTING UNDER COUNTER INSTANTANEOUS
HOT WATER HEATER, REFER TO PLUMBING DRAWING
7'
0"
3' - 0" 3' - 0" 3' - 0"
2'
2'
6"
AREA BEYOND
COORDINATE HEIGHT OF
COUNTER WITH USERS
EQUIPMENT FOR THIS
LOCATION
A302
A302
MOUNT
POWER/TEL/DATA
ABOVE COUNTER AT
40" TO CENTERLINE
PROVIDE GROMMET IN
COUNTER TOP AND
INSTALL ELECTRICAL &
TEL/DATA BELOW
SOFFIT ABOVE CABINETS
2'
11' - 5 3/4" V.I.F.
MOUNT
POWER/TEL/DATA
ABOVE COUNTER AT
40" TO CENTERLINE
A302
2'
2'
6"
7'
0"
FLOOR PLAN
COORDINATE WITH
A302
SIM
VARIES, V.I.F.
2'
6"
3 1/4"
4" 2'
1/ 8"
3 1/2"
3/4" X 21/2" HARDWOOD BACK WEB
FRAME FASTENED TO STUDS.
SHELF W/ HARDWARE - SEE
DESCRIPTION OF SHELVES AT UPPER
CABINET.
3/4" PLYWOOD DRAWER FRONTS & TOP AND
BTM. DOORS W/ PLASTIC LAM. SURFACING
AT OUTSIDE FACES AND EDGES. PL.1 - TBD
SOLID SURFACE TOP WITH NOSING ON 3/4" X
2 1/2" FRAME. SCRIBE TIGHT TO WALL.
CAULK ALL ALONG BACK OF COUNTER AT
WALL.
3/4" PLYWOOD SHELVES WITH 1/2" X 3/4"
HARDWOOD EDGE STRIPS ON FRONT
AND REAR OF EACH, AND PLASTIC
LAMINAT…