Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 1
SECTION 230900 - BUILDING AUTOMATION SYSTEM
PART 1 – GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions, and
Division 1, Division [23] [28], and Division [26] [27] [28] Specifications apply to this Section.
1.02 SUMMARY
A. The Contractor shall provide and install a system which shall provide Direct Digital Control, Energy
Management and Building Automation Functions for the Heating, Ventilating and Air Conditioning, (HVAC) systems, including interfacing with other microprocessor-based building subsystems, such as sub meters on gas, water, electric, and lighting automation, as shown on the drawings and as specified. The
Contractor shall furnish and install the necessary hardware, wiring, computing equipment and software as defined in this specification and as required to cause these systems to operate in accordance with the specified Sequence of Operation.
B. The BAS (Building Automation System) is an extension of the GSA Intranet, a U.S. Government
Information Technology Network with Security Requirements mentioned within this specification.
C. This specification shall be accompanied by the GSA R7 BAS Graphics Design Guide document and GSA
Region 7 BAS Point Naming Convention document that shall be strictly followed. These document(s) are complimentary by the GSA to remove risk or costly rework by the GSA acceptance of the BAS.
D. The system installed shall seamlessly connect devices other than HVAC throughout the building regardless of subsystem type, i.e. HVAC, lighting, and security devices should easily coexist on the same network channel without the need for gateways.
E. The system shall operate stand alone at the field network level, building network level, and building supervisor network level. The system shall be networked on a WAN to a remote GSA server; however, in the event of a WAN network failure, or server failure, such condition shall not affect the ability to operate the building from stand alone condition on a non-volatile flash memory platform described herein. The field level unitary controllers shall fail in last know command state until network connection resumes.
F. A “Fully Open BAS” selection defined from Section 1.04 of this document shall be made from
Paragraph 1.02,G (immediately below). for LonWorks protocol, or Paragraph 1.02 H (immediately below).
for BACnet protocol.
G. The BAS shall have a fully compliant LonMark® Certified LNS LonWorks architecture that utilizes the
ANSI/CEA 709.1. The entire system network shall be a Local Operating Network (LON) and installed by
LonMark® Certified Technicians during Installation. All nodes shall communicate with each other utilizing ANSI/CEA 709.1 There will be no consideration given to any network which does not use
LonWorks as the primary communications network. Controllers shall be capable of sharing SNVT
(standard network variable type) data with other LON-based devices. The system will consist of a flat, open architecture that utilizes the ANSI/CEA 709.1 (LonTalk™) Protocol as the common communication protocol between all controlled and controlling devices. Where necessary or desired, LonTalk packets may be encapsulated into TCP/IP messages to take advantage of existing infrastructure or to increase network bandwidth. Hierarchal systems consisting of master or global controllers that poll and/or control less intelligent unitary controllers on a secondary bus will not be considered.
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 2
H. The BAS shall use native BACnet MS/TP, BACnet TCP/IP architecture and be in strict accordance with
ASHRAE Standard 135. All controllers shall be BACnet Testing Labs (BTL) Certified. All BACnet points shall only use native BACnet BTL Certified standardized PICS (Protocol Implementation
Conformance Statement) and BIBBS (BACNET Interoperability Building Blocks). 100% of the physical and virtual points shall be programmed as BACnet Objects and Events without any exceptions.
I. 100% of Unitary Controllers for DDC HVAC Automation, Lighting Control, and Metering shall be fully programmable from a Niagara Framework Wizard engineering tool. Third party engineering tools and drivers are prohibited. Niagara Framework Engineering tools shall be embedded on the site JACEs and used during site integration.
J. More than one communication protocol such as Lon, BACnet, or Modbus shall not be used in the same building automation system nor in the same building without written consent from GSA. Wireless technology shall not be used in on a GSA project nor in a GSA facility without written consent from GSA
Region 7 FMSP Operations Director after review from GSA IT Department.
K. All 100% of the command able physical points shall be exposed from all field level network control devices up to the JACE level communications bus for 100% Fully Open BAS integrations, two-way communication, and modification/expansion to the system architecture.
L. The system shall communicate with another location as chosen by the Owner, via the Internet or an intranet. The BAS shall employ WEB based thin-client technology for efficient communication with remote sites. Operator interface devices shall utilize a standard WEB browser to communicate with the system server.
M. The BAS JACE front end shall be capable of expansion to encompass the entire facility. The intent of this project is to provide all hardware and software required to accommodate the future expansion of the BAS by multiple vendors.
At the end of the construction warranty period, 100% of the DDC unitary field level controllers shall have
20% spare capacity for growth and expansion and DDC Niagara supervisory controllers shall have 30% spare capacity for growth and expansion.
The BAS JACE front end shall employ FIPS 140-2 encryption licensing on 100% of the JACEs. FIPS 140-
2, level 1 conformance licenses which activate encryption are available from most Niagara vendors. It is incumbent of the controls contractor to choose a vendor that supplies FIPS 140-2 licenses for the Niagara
JACEs.
N. The BAS front end PC Desktop, PC Programming Laptop, and location provided by GSA shall be coordinated with the GSA property manager and or GSA BAS/AMS Program Manager.
O. GSA Region 7 Graphics Design Guide and BAS/AMS Point Naming Conventions shall be accompanying documents to this contract specification that shall be adhered to foster GSA R7 consistency. BAS/AMS
Point naming conventions shall be used the Unitary Field Level controls and the JACE Supervisory Level.
P. The BAS Web Supervisor Server(s) are located at the GSA Region 7 Regional Office Building and may be accessed with VPN remotely by coordination with GSA BAS/AMS Program Manager.
Q. Building Cat 6 switch and riser diagram/back bone shall be coordinated early on in the project with the
GSA IT Department in GSA Central Office, Washington D.C. The Government will provide IT engineering expertise to coordinate the installation of the IT infrastructure.
1.03 APPROVED MANUFACTURERS AND BIDDERS
A. The Contractor shall be an established supplier of control components consisting of all employees required to prepare the system installation drawings/submittal, acquire the product, install the system, calibrate, Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 3
program, adjust, troubleshoot and repair. The Contractor shall be adequately equipped and staffed to maintain a service organization capable of warranty maintenance, as well as to provide extended service on installed systems upon request and/or as specified hereinafter. Subject to compliance with the specification requirements, provide building automation/control systems by any Factory Authorized
Tridium JACE Systems Integrator whose credentials are authorized by the GSA Operations Branch and the Engineer of Record, and employ the use of JACE at front end of the BAS.
B. Multiple vendors may be located through the use of the following web links:
http://www.vykon.com/purchase#top (Open Market) http://www.gsaelibrary.gsa.gov/ElibMain/sinDetails.do?executeQuery=YES&scheduleNumber=03FAC&fl ag=&filter=&specialItemNumber=003+01 (GSA 03 FAC 003 01 Schedule, Smart Buildings System
Integrator)
1.04 DEFINITIONS
A. 10 Base T: The technical name for twisted pair Ethernet
B. BACnet: The Building Automation and Control networking communication protocol ANSI/ASHRAE, Standard 135-1995, developed by ASHRAE to provide a universal means by which building automation devices from various manufacturers can share data and work together.
C. BIBBS: BACNET Interoperability Building Blocks
D. Backbone: The high traffic density connectivity portion of the communication network.
E. Bridge: A device that connects two or more LAN segments at the physical and data link layers. This device may also perform message filtering if programmed to do so.
F. Browser: A computer program that accesses and displays information from the Internet or intranet.
G. Category 6 cable: A type of wiring used for twisted pair Ethernet. The electrical characteristics of Cat 6 wiring make it less susceptible to electrical interference than lower categories.
H. Client: A system or device that makes use of another device for some particular purpose through a system request.
I. Chiller Plant Optimization: A group of BAS software routines designed to cause a chiller plant to operate with maximum efficiency.
J. Conformance Classes: The set of requirements to be met in order for a device to conform to BACnet.
BACnet defines six (6) levels of required support for standard objects and services. The higher the
Conformance Class, the greater number of services provided.
K. Control Devices: Valves, dampers, variable frequency drives, and other appurtenances that change the properties and henceforth vary the conditions of the controlled parameter, such as temperature, air flow, pressure, etc.
L. Controlled Parameter: Air, water, glycol, steam or other media whose conditions are maintained or varied by the automatic control system and the control devices.
M. Data Link Layer: Part of the Protocol Stack. The layer resides between the Physical Layer and the
Network Layer. It passes to the Network Layer only acceptable incoming BACnet messages received from the Physical Layer. The Data Link Layer is responsible for adding a code to outgoing messages to identify them as BACnet messages before passing them on to the Physical Layer.
http://www.vykon.com/purchase#top http://www.gsaelibrary.gsa.gov/ElibMain/sinDetails.do?executeQuery=YES&scheduleNumber=03FAC&flag=&filter=&specialItemNumber=003+01 http://www.gsaelibrary.gsa.gov/ElibMain/sinDetails.do?executeQuery=YES&scheduleNumber=03FAC&flag=&filter=&specialItemNumber=003+01
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 4
N. DDE: Dynamic Data Exchange.
O. Device (BACnet): A device, real or virtual, that supports digital communication using the BACnet protocol. Examples would be an operator terminal, router, unitary controller, etc.
P. Ethernet: Ethernet is a widely used Local Area Network (LAN). Ethernet, which conforms to IEEE
Standard 802.3.
Q. Events: Changes in the state of an object, typically between Normal, Off-Normal, and Fault Condition.
Events may be reported to other BACnet devices.
R. Fiber: An abbreviation for optical fiber.
S. Firewall: A security mechanism placed at the connection between networks and/or at networks outside connections. The firewall restricts access to the network.
T. Fully Open BAS: Building Automation System that all materials, hardware, firmware, software, and licenses can be procured through open market non-proprietary vendor warehouse distribution channels; in addition to being installed and maintained by any JACE factory authorized/qualified Building Automation and Controls Company. Single/sole vendor source materials, hardware, firmware, software, and licenses are prohibited from installation on GSA facilities.
U. Gbps: Gigabits per second. A unit of data transfer speed equal to 1024 Mbps.
V. GUI: Graphical User Interface, a type of Operator Interface Device for a BAS.
W. Half Router: A device or node that can participate as one partner in an RS-232 point-to-point (PTP) connection. The Half Router partners that form an active PTP connection act as a single router for as long as the PTP connection between the two is active.
X. Hardware address: The address assigned to a computer or DDC controller that attaches to a network. A data frame sent from one hardware device to another hardware device must contain the recipient’s address.
A hardware address is also called the physical address.
Y. Hertz: A unit of measure equal to an oscillation per second.
Z. HTML: The source form used for documents on the Internet or on an intranet. HTML embeds commands that determine formatting along with the text to be displayed.
AA. Instance: A number which uniquely identifies an object within a device (e.g., Analog Input No.1, No. 2, etc.). Device Objects are required to have an instance number that is unique to their internetwork.
Instance numbers may range from 0 to 4194303.
BB. ID: Identification (name, number, plate, or tag).
CC. I/P: Internet Protocol.
DD. Internetwork: Two or more networks connected by routers (the Internet itself and internetwork), up to
65,535 interconnected networks are allowed by BACnet. A BACnet internetwork provides only one message path between two devices. Internetworks may contain similar or dissimilar physical types, so an internetwork may consist of two Ethernet LANs, or an Ethernet LAN and several MS/TP LANs, etc.
EE. Intranet: A computer network with restricted access, as within a corporation, that uses software and protocols developed for the Internet.
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 5
FF. IP: Internet Protocol. The protocol that defines both the format of packets used on a TCP/IP internet or intranet and the mechanism for routing a packet to its destination.
GG. IP address: A 32-bit address assigned to a device that uses TCP/IP protocols.
HH. Java: A programming language defined by Sun Microsystems for use in Internets.
II. JACE: JAVA Application Control Engine.
JJ. Kbps: A unit of data transfer equal to 1024 bits per second.
KK. LAN: A LAN is a network of interconnected hardware devices sharing resources within a relatively small geographic area.
LL. LonTalk: A LAN using a proprietary device called a neuron chip for communication. It can operate over a variety off physical media including twisted pair, power line carrier, and wireless transfers.
MM. LPDU: Link Protocol Data Units are packets created and read by the Data Link Layer. They contain a 3-byte header which identifies the packets as having been created by, and intended to be read by, a BACnet system. The header is followed by the BACnet LPDU.
NN. Mbps: A unit of data transfer equal to 1024 Kbps.
OO. MS/TP: The Master-Slave/Token-Passing EIA-485 LAN developed for BACnet by ASHRAE. Operates at
9600, 19.2K, 38.4K and 76.8 K BPS. Master nodes (devices) pass around a speaking token which entitles the holder to initiate BACnet messages. Slave nodes can only respond to messages from Masters.
PP. Native BACnet: A Building Automation System that uses the BACnet protocol for its data transfer between hardware devices.
QQ. NIST: The National Institute of Standards and Technology is developing a BACnet device-compliance testing facility in Gaithersburg, MD.
RR. NODE: A computer or digital device connected to a network, with an address on that network.
SS. OBJECT (BACnet): BACnet objects represent, in a standardized way, the information required for a building automation control system. The analog input object, for example, represents sensor inputs such as temperature sensors.
TT. Optical Carrier (OC): A set of standards adopted by common carriers for the high speed transmission of digital information over optical fiber.
UU. Optical fiber: Glass fiber used in digital networks.
VV. Optical modem: A modem that uses modulated light waves to provide digital communication.
WW. Object Identifier: A 32-bit number which uniquely identifies an object within a device, or the device object internetwork-wide. 10 bits represent the object type and 22 bits the instance number.
XX. OSI: Open System Interconnection standards.
YY. Packet: A small, self-contained parcel of data sent across a digital network.
ZZ. PAD (Packet-Assembler-Disassemblers): A device that sends BACnet messages across BACnet incompatible networks. The sending PAD receives the message from a BACnet network, encapsulates it
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 6
in the correct format, and sends it on the non-compatible network to a receiving PAD. The receiving PAD removes the message from its encapsulation and transmits it on another BACnet network.
AAA. PC: Personal Computer.
BBB. Peer-to-Peer Communication: Communication between equals. In BACnet, application programs
(performing the functions of the BACnet devices on which they run) in devices of the appropriate conformance class talk to each other as peers, using the Protocol Stacks to deliver their message to each other. Likewise, Network Layers may talk as peers to determine how to route messages.
CCC. Physical Segment: A single continuous medium 9-wire to which BACnet nodes are attached.
DDD. PICS (Protocol Implementation Conformance Statement): A written document identifying the particular
BACnet objects and services and other capabilities that are implemented in the device (see also Section
1.3.C, “Conformance Classes”).
EEE. PID: Proportional Integral and Derivative.
FFF. Property: A particular characteristic of a BACnet object. Examples of properties are Description (a text description of what the object represents, such as OSA for outside air, and analog input object), Present
Value (22 for the same input) and engineering units (degrees Celsius).
GGG. Protocol: A design that specifies the details of how digital devices interact.
HHH. Protocol Address: A number assigned to a digital device that is used as the destination address in packets sent to that device.
III. Protocol Stack: The four layers through which BACnet messages pass when sent to or from a BACnet device. The Protocol stack provides data encoding, packetizing, sequencing, segmenting, routing and communication services.
JJJ. PTP: The Point-To-Point protocol provides serial communications between two BACnet half-router devices, typically for dial-up communications over-the-phone modems. It may be also applied as a hard-wired interface. For the duration of the connections, messages may be passed between networks on either side of the PTP connections.
KKK. Repeater: A device that connects two or more physical segments of a LAN at the physical layer and exactly reproduces the electrical signals on either side so that nodes on either side of the repeater are considered to be on the same network.
LLL. Router: A device which connects two or more networks, of same or different types, so that a BACnet message may be transferred across the appropriate networks to reach its destination.
MMM. RS-232-C: The technical name of the standard for serial data connections such as those between a computer and a keyboard.
NNN. Server: A computer or hardware device which stores the resources accessed by other computers or hardware devices (clients).
OOO. Services (BACnet): BACnet defines 26 standard services; some services read or write properties of objects in the receiving device, others convey notification of alarms or other special events, others read and write files, and so on.
PPP. SNMP: Simple Network Management Protocol. The protocol that specifies how a network management station communicates with agent software in remote devices such as routers. SNMP defines the format of messages and their meaning.
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 7
QQQ. SMTP: Simple Mail Transfer Protocol. E-mail or text message application. Often resides on a server.
RRR. TCP/IP: The protocol suite used in the Internet. Although the suite contains many protocols, TCP and
IP are two of the most important.
SSS. Thinnet: A term used for the version of Ethernet that uses thinner coaxial cable.
TTT. Thin-client architecture: A term used to describe server/client system architectures in which one or more powerful hardware devices (servers) store the resources accessed by other less powerful hardware devices (clients).
UUU. Token Ring Network: A Token Ring Network is a Local Area Network (LAN) in which each of the computers are connected in a ring or a star topology and a bit, or a token-passing scheme, is used in order to prevent the collision of data between two computers that want to send messages at the same time. The token ring protocol is the second most widely used pattern after the Ethernet. A typical arrangement is as follows:
1. Empty information frames are continuously circulated on the ring;
2. When a computer has a message to send, it inserts a token in an empty frame (this may consist of simply changing a 0 to a 1 in the token bit of the frame) and inserts a message and a destination identifier in the frame;
3. The frame is then examined by each successive workstation. If the workstation sees that it is the destination for the message, it copies the message from the frame and changes the token back to 0. When the frame gets back to the originator, it sees the token has been changed to 0 and the message has been copied and received. It removes the message from the frame. The frame continues to circulate as an empty frame, ready to be taken by workstation when it has a message to send.
VVV. TP Ethernet: Twisted pair Ethernet.
WWW. Unitary Controller: Devices which controls and/or monitors a single piece of equipment.
XXX. WEB: A synonym for the World Wide Web. In modern usage pertains to both the Internet and to intranets using the TCP/IP Protocol.
1.05 SYSTEM DESCRIPTION
A. The system shall consist of a series of digital controllers interconnected by the LAN. One or more operator interface devices (OIDs) shall be connected to the LAN to provide access to the controllers for the purpose of receiving information or issuing commands. The controllers shall be located adjacent to the equipment they monitor or control and shall be sized for the task assigned to them. The system shall utilize distributed processing architecture and one controller shall be provided for each major piece of equipment controlled or monitored except that the equipment associated with the chiller plant and the heating plant shall be controlled from two controllers, thereby permitting half of the system to continue working in the event of a panel failure.
B. The communication network between general purpose digital field controllers shall be BACnet over
Ethernet or BACnet over ARCNET. The communication network between unitary or terminal unit controllers shall be BACnet MS/TP over EIA-485 or BACnet over LonTalk. BACnet Point-To-Point may be used for communication between the network and modems, line drivers or other data communication equipment.
C. The BAS software shall be based on a server/thin-client architecture, designed around the open standards of web technology. The BAS server shall communicate using the ASHRAE BACnet/IP protocol, and in addition, offer concurrent support over the same data-link of the following protocols: LonWorks, MODBUS, and SNMP. The Server shall be accessed using a web browser.
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 8
The intent of the thin-client architecture is to provide the operator(s) complete access to the BAS via a web browser. The thin-client web browser Graphical User Interface (GUI) shall support Microsoft and browser
(8.x or later versions), and Windows 7/8 Operating System. No special software shall be required for the
PC’s used to access the BAS via a web browser. Graphical User Interface (GUI) shall support software current versioning of software languages such as JAVA, XML, HTTP.
The web browser GUI shall provide a completely interactive user interface and must offer the following features as a minimum:
1. Trending
2. Scheduling
3. Downloading Memory to field devices.
4. Real time “live” Graphic Programs
5. Tree Navigation
6. Parameter change of properties
7. Set point Adjustments
8. Alarm / Event information
9. Configuration of operators
10. Execution of global commands
D. Input devices such as temperature sensors, humidity sensors, pressure sensors, motor current sensors, relays and other devices to sense or measure conditions of equipment or space, shall be provided as part of the system to meet the requirements of the sequences of operation or input list.
E. Output devices such as valves, dampers, damper operators, relays, solenoids, transducers, or other devices to control equipment, shall be utilized as part of the system to meet the requirements of the sequences of operation or output list.
F. Control System includes: [Sequence of Operations as indicated in the construction drawings.] [Sequence of Operations as specified in SECTION 230901 – SECQUENCE OF OPERATION FOR HVAC
CONTROLS.]
G. System Software:
1. Provide and install the software indicated in Part 2 of this specification. The database required for implementation shall be provided, including point description, alarm limit, calibration variable graphics, report, and point summaries.
2. The system described herein is a distributed processing system, which utilizes DDC to perform each logic and control decision and operation for each piece of HVAC equipment. An OID shall not be required to operate the system. Each item of large equipment, such as air handling units, boilers and PDDU units, shall be provided with a separate digital controller panel (DCP) with readout capability. Each equipment shall be controlled by a separate application-specific field controller (ASC).
H. Labeling:
1. Provide a comprehensive labeling system for each wiring and component using the designations shown on the approved submittals. All labeling of room names and equipment shall correspond with the actual room numbers not necessarily the construction document room numbers, contractor shall confirm with signage/architectural drawings prior to issuing control submittals.
I. Electrical Work:
1. This shall include power requirements for control panels, field controllers, sensors and other control devices. Provide transformers necessary to step down from the available voltage to the voltage required to operate the control system products and control devices.
J. Other Work:
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 9
1. The work included under this Division shall include the drawings, specifications, submittals, equipment, labor, materials, technical supervision, transportation, training services, documentation, warranty, and other appurtenant work as required to furnish and install a fully operational system to monitor and control, set forth, in strict accordance with these specifications and subject to the terms and conditions of the Contract. An apparatus, appliance, material or work not shown on the drawings but mentioned in the specifications, or vice versa, or incidental accessories necessary to make the work entirely complete and ready for operation, even if not particularly specified, shall be furnished, delivered and installed by the Contractor without additional expense to the Owner.
K. Completion:
1. It is the intention of the specifications and drawings to call for furnished work, tested, and ready for operation. Wherever the word “provide” is used, it shall mean “provide and install complete and ready for use.”
L. Omissions:
1. Minor details not usually shown or specified but necessary for proper installation and operations shall be included, as if herein specified and/or shown.
M. Contractor’s Esoteric Omissions:
1. The omission of hardware, firmware, and software components required to satisfy the specified configuration(s), but not specified due to the esoteric requirements of a particular manufacturer’s product design shall not relieve the Contractor from the responsibilities of providing and installing omitted apparatuses, (i.e. feed-back circuits, calibration resistors, and override detection interface devices).
1.06 APPLICABLE CODES
A. The following issues of the publications referred to thereafter by basic designations only, form a part of this specification. Inclusion in this listing is intended to cal particular attention to the subject matter covered:
1. FIPS: Federal Information Processing Standards Publications: FIPS PUB 15: Subsets of the
Standard Codes for Information Exchange.
2. ANSI: American National Standards Institute Publications:
1. B31.1-1977 Power Piping (including addenda) B31.1b (1971); B31.1c (1972); and
B31.1d (1972).
2. C2-1981 National Electrical Safety Code.
3. C12-1975 Electricity Metering.
4. C57.13 1968 Requirements for Instrument Transformers.
3. EIA: Electronic Association Standards: RS-232C Interface between data terminal equipment and data communication equipment employing serial binary data exchange. 1.
4. AWS: American Welding Society Publication: B30-77 Welding Procedures and Performance
Qualification.
5. NFPA: National Fire Protection Association Publication: 70 and National Electrical Code.
6. NEMA: National Electrical Manufacturer’s Association (NEMA): ED 20-75, Watt-hour Meters.
1.07 OPEN PROTOCOL
A. All 100% of the physical and virtual points shall be exposed to the either a non-proprietary LON communication network bus OR non-proprietary BACnet communication network bus for integration or expansion for the JACE. Both protocols shall not be used in the same building automation system in the same building without written consent from GSA.
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 10
B. BACnet Selection: Each component of the system, including the LANs and software, shall be in full compliance with ASHRAE Standard 135, commonly referred to as BACnet. The BAS shall use native
BACnet MS/TP, BACnet TCP/IP architecture and be in strict accordance with ASHRAE Standard 135.
All controllers shall be BACnet Testing Labs (BTL) Certified. All BACnet points shall only use native
BACnet BTL Certified standardized PICS (Protocol Implementation Conformance Statement) and BIBBS
(BACNET Interoperability Building Blocks). All physical and virtual points shall be programmed as
BACnet Objects and Events without any exceptions.
C. LON Selected Selection: LON LNS architecture that utilizes the ANSI/CEA 709.1. The LON architecture shall consist of LonMark® Certified controllers and shall be programmed and installed by LonMark®
Certified professionals.
1.08 SUBMITTALS/DELIVERABLES
A. Submit each item in this Article according to the Conditions of the Contract, Division 1 Specification
Sections.
B. IT Riser Diagram: The contractor shall submit a full detail IT riser diagram depicting the following items by room number and floor: GSA Desktop PC, GSA Laptop Connection zone, GSA Switch location(s), control wire type (Cat 6, Two conductor, Fiber optic) with length of Cat 6 and Fiber illustrated from GSA switch(s), BAS or lighting controller field level and supervisory controller end device(s) manufacturer/model number (for manufacture and model use legend for simplicity), GSA T-1 Circuit and
Main Switch.
C. Product Data for Each Type of Product Specified. Include manufacturer’s technical Product Data for each control device furnished, indicating dimensions, capacities, performance characteristics, and electrical characteristics, finishes of materials, installation instructions, and start-up instructions.
D. Equipment: Shop drawings from manufacturer, detailing equipment assemblies and indicating dimensions, weights, loadings, required clearances, method of field assembly, components, and location and size of each field connection. Submit damper leakage and flow characteristics, plus size schedule for control dampers and control valves.
E. Control System Shop Drawings: Submit shop drawings containing the following information for each control system:
1. Schematic flow diagram, showing fans, pumps, coils, dampers, valves, and control devices.
2. Each control device, labeled with setting or adjustable range of control.
3. Details of control panel, including controls, instruments, and labeling.
4. Trunk cable schematic, showing programmable control unit locations and trunk data conductors.
5. Listing of connected data points, including connected control unit and input device.
6. System graphics, indicating monitored systems, data (connected and calculated) point reading and setpoint values, and operator notations.
7. System configuration, showing peripheral devices, batteries, power supplies, diagrams, modems, and interconnections.
8. Software description and sequence of operation.
9. Provide graphic flow diagram for each software program, and a separate graphic for each system’s data point addresses.
F. Wiring Devices. Submit wiring diagrams, detailing wiring for power, signal, and control systems and differentiating clearly between manufacturer/manufacturer’s installed and field installed wiring.
G. Sample Covers: Submit samples of each type of space humidity and temperature sensor cover for approval prior to ordering the covers
H. Field Test Reports: Submit procedure and certification of control system.
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 11
I. Testing and Adjusting During and After Installation: The testing and adjusting submittal includes the submission of a test plan which describes in detail the method by which each component, subsystem, and system will be tested, calibrated, adjusted, and retested after installation in accordance with the specified sequences of operation and other characteristics of the control system.
J. Reporting and Demonstration: This phase shall include the submission of a written report describing the actions taken during the testing phase, including the set points and operating ranges of each piece of equipment and a demonstration that the system performs in accordance with contract requirements.
K. Operating Instructions and Training: This phase includes the training of operating personnel, utilizing written operating instructions, prepared and approved under the “Submittals” paragraph of this Section, and the mounting of laminated control diagrams where directed.
L. JACE License Forms: Submit with final shop drawings.
M. Engineering Tools: Workbench version 4.0 or higher and all Field Level programming tools shall be installed on the GSA Government Laptop designated for the site. The contractor shall provide the appropriate quantity of legal copies of all software tools, configuration tools, management tools, and utilities used during system commissioning and installation. All tools shall be generally available in the market. No closed and/or unavailable tools will be permitted. Contractor shall convey all software tools and their legal licenses at project close out.
N. JACE Programming Files: All programming files associated with each JACE shall be backed up and neatly organized by the floor number/site designation number for easy recognition on the Government Laptop.
O. Proprietary and Non-Proprietary Programming Files: All programming files associated with each field level device shall be backed up and neatly organized by equipment item for easy recognition on the Government
Laptop.
P. Backup Disks: Provide labeled backup disks (1ea copies) of Workbench version 4.0 or higher and Field
Level programming tools licensed to GSA Region 7. Provide (3ea copies) labeled JACE Programming Files, and Site Field Level Programming files. Upon job completion provide all drawings, product information, complete and functional LNS databases, resource files, configuration files, etc on standard recordable media
(CD, DVD).
Q. For LON Systems, a complete and fully commissioned LNS database must be delivered for use with the GUI as a specific deliverable as defined on the project schedule. This database must include ALL node definitions, ALL channel and subnet definitions, all router and repeater definitions, and all bindings etc.
1.09 DOCUMENTATION
A. General: A description of the material to be included in the reference manuals is contained in the following paragraphs. Three (3) copies of the manuals bound in hardback, loose-leaf binders or an approved equivalent shall be provided to the Owner. In addition the manuals shall be furnished in Acrobat 7 X
(PDF) Electronic formant. One complete set of manuals shall be furnished before the contract is complete.
The identification of contents in each manual shall be inscribed on the cover and the spine. The manuals shall include the name, address and telephone number of each subcontractor installing equipment and systems and of the local representative for each specific item of equipment and each system provided.
Manuals provided shall include:
1. Functional Design Manual.
2. Hardware Manual.
3. Software Manual.
4. Operations Manual
5. Maintenance Manual
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 12
System revisions and/or additions provided for or required under this contract shall be included in this documentation in the form of updated documents.
B. Functional Design Manual: The functional design manual shall identify the operational requirements for the system and explain the theory of operation, design philosophy, and specific functions. Hardware and software functions, interfaces, and requirements shall be provided for each system operating mode.
C. Hardware Manual: The hardware manual shall describe the system and each piece of equipment provided, as follows:
1. General description and specifications.
2. System architecture overview.
3. Hardware cut-sheets and product descriptions.
4. Installation, mounting and connection details for piece of field hardware and accessories.
5. Electrical schematics and layouts drawings.
6. Color-coded small scale building plans showing different colors for each HVAC system.
7. Commissioning, setup and emergency backup procedures for each system controller(s)/ accessories, and BAS software, and database.
8. Manufacturers’ repair parts lists indicating sources of supply.
9. Interface definition.
10. Listing of basic terminology, alarms/messages, error messages and frequently used commands or shortcuts.
11. An identification of the specific device, component, or system provided (for data sheets that include multiple options, clearly identify the one(s) actually provided for this project).
D. Software Manual: The software manual shall describe programming and testing, starting with a system overview and proceeding to a detailed description of each software module. The manual shall be oriented to programmers and shall describe calling requirements, data exchange requirements, data file requirements, and other information necessary to enable proper integration, loading, testing, and program execution. The manual’s organization shall be as follows:
1. A printout of each program, detailing the application to specific HVAC equipment and electrical/mechanical subsystems allowing for logical step-by-step analysis of the programs.
2. Graphical “flow chart” representation of the mechanical equipment hierarchy for the project including each piece of equipment controlled by the BAS. For example: a VAV terminal box may be the source for increased cooling demand and require the primary VAV AHU to operate which, in turn, requires the chillers to operate.
3. Description of the algorithms for the application programs.
4. Descriptions of communication protocols, including BACnet numbering and identifications.
5. Detailed listing of each alarm and event message programmed for designated mechanical/electrical equipment and required operator action.
E. Operations Manual: The Operations manual shall describe the operations of the complete system and include:
1. System overview.
2. Networking concepts.
3. Launching and use of a web browser from a networked PC and login.
4. Graphical User Interface (GUI) screen menus and their definitions.
5. Creating, modifying or deleting schedules.
6. Uploading and downloading software to the field hardware.
7. Creating historical trends, collecting trend data and generating trend graphs.
8. Enabling and assigning alarms and messages to reporting actions/groups.
9. Report generation and ‘third party software’.
10. Backing up software and data files.
F. Maintenance Manual: The maintenance manual shall provide descriptions of maintenance for each piece of equipment, including inspection, periodic preventative maintenance, fault diagnosis, and repair or replacement of defective components. The Maintenance Manual shall contain the following:
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 13
1. Maintenance instructions and lists of recommended spare parts for each type of control device.
2. Interconnection wiring diagrams with identified and numbered system components and devices.
3. Recommended inspection period, cleaning methods, cleaning materials, and calibration tolerances.
4. Calibration records and complete list of set points that were active at time of final acceptance.
G. Qualification Data: Include information considered essential to pre-qualify firms and persons specified in the Quality Assurance article.
1.10 QUALITY ASSURANCE
A. Products shall be standard manufacturer products having been in commercial or industrial use for at least one year prior to the bid date for this project. Products shall comply with the following as a minimum:
1. NFPA 90A, “Installation of Air Conditioning and Ventilation Systems.”
2. NISTIR 6392 for DDC system control components.
3. ANSI/ASHRAE Standard 135-1995 for BACnet compatible system control components.
4. Applicable provisions of NFPA code.
5. Applicable provisions of NEC.
6. ANSI/CEA 709.1 Standard LON
C. Each system component, such as digital controllers, LAN devices and OIDs shall be manufactured under
ISO 9001 standards for quality.
D. Contractor shall have been in business installing and maintaining the same brand of equipment as used on this project for at least three (3) years prior to the bid date of this project.
E. Installer Qualifications: Installer shall have at least 5 years experience installing BAS and JACE web-based BAS and shall be an experienced installer who is a certified installer of the BAS manufacturer for both installation and maintenance of products and systems required for this project.
F. Manufacturer Qualifications: A firm experienced in manufacturing products for BASs the same as or similar to those required for this project and with a record of successful in-service performance for a minimum of one year prior to the bid date for this project.
G. Material Qualifications: Installer shall use Hardware, Software, and Firmware that is available for purchase during and after the project from multiple non-proprietary warehouse distribution channels and/or available for procurement from the GSA Advantage Federal Acquisition Services GSA Schedule.
H. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and certified and marked for intended use.
I. LON System Specification compliance Checklist:
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 14
1.11 DELIVERY, STORAGE AND HANDLING
A. Contractor shall receive, store and deliver to the jobsite the materials required for this project.
B. Materials that are specified to be factory-mounted in equipment furnished by others, such as components for terminal equipment, shall be shipped directly to the manufacturer of that equipment for factory installation.
C. Materials which are to be installed in sheet metal or piping systems, such as valves, wells, pressure taps, flow meters, dampers and sensors, shall be delivered directly to the sheet metal or piping contractor for
Installation.
1.12 COORDINATION
A. Coordinate material delivery to comply with project schedule.
B. Coordinate conduit, and wiring installation with other trades to avoid conflicts.
C. Coordinate panel locations and installation with other trades to avoid conflicts and to provide power and other requirements.
D. Coordinate equipment transmission systems and software protocols with Lighting Control System in Division 26 of the Specifications to achieve compatibility with equipment that interfaces with those systems.
E. Coordinate equipment, transmission systems and software protocols with the Sequence of Operations in
[the construction drawings] [SECTION 230901 – SECQUENCE OF OPERATION FOR HVAC
CONTROLS] of the Specifications to achieve compatibility with equipment that interfaces with that system.
1.13 MAINTENANCE AND SERVICE
A. Provide parts and labor repair during the warranty period at no cost to the Owner. Warranty period shall be not less than 1 year from the date of final acceptance of the total system.
Check
Architecture: Flat Peer to Peer Lon w/ Layer 3 routing only
Communication Protocol: LonTalk (ANSI/CEA 709.1)
Transceiver: ANSI/CEA 709.1a FTT-10 Free Topology Transceiver
Processor: Implements full ANSI/CEA 709.1 protocol
Network Operating System/Database Standard:
LonWorks Network Services(LNS)
Message Tags: LonMark Defined Standard Network Variable Types (SNVT) & Standard Configuration Property Types
(SCPT)
Use of Gateways: Pre-approved Only. For converting proprietary to LON Only
Network Management/Commissioning Tool:
LNS Based
Contractor Certification: Training certification requirements
Product Certification: LonMark Certified [3.2] or better
Media Type: Project specific – FTT, Powerline, Fiber
Twisted Pair Wiring Topology: Free Topology, Polarity Insensitive
Other Considerations: Must provide external interface file (XIF files) and device resource files for each device
Arkansas, Louisiana, New Mexico, Oklahoma, Texas Project No.
U.S. FOB, CH, POB, LPOE GSA Project No. GS-
BUILDING AUTOMATION SYSTEM 15900 - 15
1.14 NAMEPLATES AND LABELS
A. Label all controllers and control components in the control cabinet to match naming convention on control drawings using electronic label maker to clearly define different components in cabinet.
1.15 COMMISSIONING
A. The BAS shall be actively commissioned to be fully functioning prior to Demonstration and Acceptance
Periods and Contract Close Out. The contractor shall complete and turn over to the owner’s representative a commissioning report showing the date of commissioning and the technician name and telephone number for each input and output in the system. Report shall be signed by the technician performing the commissioning. The contractor shall start, test, adjust, and calibrate the work and/or systems under this
Contract, as described below:
1. Test, calibrate, and adjust each digital and analog sensing, and actuating device. Calibrate each sensor by making a comparison between the BAS display and the reading at the sensor, using an instrument traceable to the National Institute of Standards and Technology. This instrument shall be at least twice as accurate as the sensor to be calibrated. The measured value and displayed value for each sensor shall be in the ATC/BAS Pre-Commissioning Report.
2. Check and set zero and span adjustments for each actuating device. Manually activate damper and valve operators to verify free travel and fail condition. Check valve or damper to insure that it shuts off tight when the appropriate signal is applied to the operator.
3. Check each digital control point by making a comparison between the control command at the
OID and the status of the controlled device. Check each digital input point by making a comparison of the state of the sensing device and the OID display. Record the results for each device in the Commissioning Report.
4. Verify proper sequence and operation of each specified function.
5. Tune each control loop to obtain the fastest stable response without hunting, offset or overshoot.
1.16 DEMONSTRATION AND INSPECTION
A. System: The complete Building Automation System shall be demonstrated to the Owner’s representative to perform as specified, and Owner’s operating personnel shall be instructed in the operating procedures until they are familiar with the system.
B. Operation: Every BAS component, wiring, and control program installed under this section shall be demonstrated to the Owner’s representative to be in working condition. Once each component operation has been verified and the system has been properly commissioned with the rest of the equipment and building systems, the systems will be ready for final acceptance. At that time, the warranty period will begin and will extend only to the replacement of material with manufacturer’s defects, and to normal or recommended recalibration or adjustments.
1.17 ACCEPTANCE
A. Upon completion of the installation and commissioning of the systems, the contractor shall notify the owner’s…