Q & A Amendment No 3.pdf

PDF 517 KB Posted

Attached to
USMS 1st Floor Renovations & Vehicular Sally Port
Solicitation number
GS-05P-09-FB-C-0019
Issued by

About this file

Amendment #0003--Questions and Answers

View the file

Other files

File Type Posted
Amendment No 3 Drawings.zip ZIP file
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
PDF drawings.zip ZIP file
RFP GS05P09FBC0019.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USMS FIRST FLOOR SALLYPORT

UNITED STATES COURTHOUSE AND FEDERAL OFFICE BUILDING

DAYTON, OHIO

PBS-REG-5

ROH00033

AMENDMENT NO. 3 PROPERTY OF THE UNITED STATES

GOVERNMENT FOR OFFICIAL USE ONLY

Do not remove this Notice. Properly destroy documents when no longer needed.

AMENDMENT NO. 3

TO THE BIDDING DOCUMENTS FOR

GENERAL SERVICES ADMINISTRATION

OFFICE OF CUSTOMER SOLUTIONS

DAYTON USMS FIRST FLOOR SALLYPORT

ISSUE DATE: March 11, 2009

PART 1 - GENERAL

1.1 GENERAL

A. This Amendment covers changes to the Documents and in closing the Contract will become a part thereof. Each Bidder shall include these items to the extent they affect this Bid.

B. These items modify only the portion of the Documents specifically noted. All other wording and Drawings remain in effect.

1.2 BIDDER QUESTION RESPONSES

A. Are the ceilings in rooms 133, 134, and 116 to be replaced? General note 1 calls for the removal of all ceilings in rooms where partitions are to be removed, but there is nothing noting for them to be replaced in the finish schedule. Also note 18 calls for them to remain. In room

116 there is nothing indicated? (This was asked during the prebid) Yes, refer to amendment sheet A0401.

B. There is nothing specifying that the existing VCT flooring is to be removed. Is there going to be a note added via amendment since it calls for new flooring in these areas? Yes, refer to amendment sheet A0101. The floor tile and mastic located in the first floor work area has been tested for asbestos. Analytical results indicate that the floor tiles contain 3% chrysotile asbestos and the mastic contains 2% chrysotile asbestos. The black mastic located under carpeting also contains asbestos. The floor tiles and mastic will need to be abated by a licensed abatement contractor. Please see the amended Specification 02080, included herein, for further details.

C. Has all of the fireproofing been tested for asbestos? The fireproofing located on the first floor and basement has been tested for asbestos. Analytical results indicate that NO asbestos is present in the fireproofing.

D. There are doors shown to the plumbing chases at each of the (3) cells but there is no call number for the doors. Please refer to amendment specification section 08311, and amended specification section 08712 (for cylinder lock) included herein.

DAYTON, OHIO

Do not remove this Notice. Properly destroy

E. Do the bullet-proof panels in the Type 9 walls need to run all the way to the deck. The detail calls for the walls to, but do the underlying panels have to? Yes.

F. Can you clarify the extent of the chair rail and crown molding (all walls in a room etc…) and which rooms are to receive the wood trim(s)? Yes, refer to amendment sheet A1001.

G. Are there any drawings showing the construction of the existing postal lookout gallery that we could use when estimating the demolition? Yes, refer to original construction document sheet number 5-28, included herein.

H. Will we be allowed to use the existing toilet rooms (rooms 135 & 136) during construction?

The contractor must supply and maintain these rooms in order to use them. Their primary purpose is to serve building tenants. If at any time the Building Property Manager judges that these rooms are not being maintained, then the contractor’s privileges’ shall be revoked.

I. Drawing A401 has a note at the dock that reads “if no fireproofing then apply 2 hour rated assembly”. Since the area has an existing plaster ceiling and is not able to be viewed, should the contractor include or exclude fireproofing. It is permissible for the bidders to exclude items they cannot visibly verify at this time.

J. Specification 01310 Section 1.5 requires a “Full Time Project Coordinator, Full Time

Mechanical Coordinator and a Full Time Electrical Coordinator” in addition to the “Project

Superintendent”. Can the project coordinators and superintendent be the same person? Yes.

K. Specification 02080 Section 1.2 discusses the possibility of ACM pipe insulation inside air handling unit AHU-6. Will the A/E be responsible for identifying whether or not the pipe insulation is ACM? Who will test this material? If the material is found to be ACM, the contractor is required to give 10 days notification to the Ohio EPA. Will the 10 days be added onto the schedule duration? Please see the Amended Specification 02080 for details regarding all asbestos abatement activities. The Contractor will need to file notification to handle other ACM identified, so additional time for notification would not be necessary.

When access to the presumed asbestos containing materials (PACM) is available, the A/E shall work with the Contractor to obtain samples of the presumed materials. The

Contractor should provide a unit rate for the estimated quantity provided in the amended specification 02080.

L. How late can bidder questions be asked? Friday 3-6-09.

M. Is there space available in the building for the storage of materials? There is very limited storage space available inside the building. The building manager would have to approve any usage of existing space for storage other than the limits of the construction work area inside the building. GSA will vacate 13 parking spaces south of the dock that the contractor can use for staging materials or placing trailers. Contractor must keep the drive lanes open along with the three dock levelers.

N. Can contractors work during normal working hours (i.e. straight time)? Can contractors perform exterior work during normal business hours? All noisy and disruptive work must be performed during non-business hours. Business hours are defined as 7 AM to 5 PM.

DAYTON, OHIO

Do not remove this Notice. Properly destroy

Work can be performed during normal business hours provided it is not disruptive to the building tenants.

O. Is the existing 4,000 gallon underground water tank filled with water? Is a permit required to remove this tank? The tank is filled with potable (drinking) water. Contractor is responsible for draining and removing the tank.

P. Contractor asked how they can transport AHU-6 into the basement. Contractors are permitted to use the freight elevator.

Q. Sheet a1001 – Door Schedule – Hardware set 18 is scheduled for cell doors 120, 121, & 122.

Which is the same as scheduled for Door 105C. Is this correct? The specs only lists 105C for

Hardware set 18. Cell Doors 120, 121, 122 and 123 shall be Hardware set 19, add via this amendment. Refer to amended specification section 08712.

R. No hardware is scheduled for the cell door in Room 117 – Isolation cell. The Cell door has been amended to be Door 123. Cell Doors 120, 121, 122 and 123 shall be Hardware set 19, add via this amendment. Refer to amended specification section 08712.

S. Drawing A0202 – coded sheet note #1 calls out to “provide 6” cmu partition from top of existing wall to underside of deck…” Is there an existing partition above 15’ elevation that needs to be demolished and if so what is the material? No partition above 15’ elevation.

T. Drawing A0202 – The 4 detention cells show a shaded area that we are assuming to be the benches (detail 3 on A0801). Since the void under the benches is to be filled with insulation (3

A0801) do you want the bench ends at the wire mesh partitions to be open and let the insulation show? No, provide 12 Ga. stainless steel end closure panels at all exposed end conditions.

U. Drawing A0501 – elevations 1 & 2 and Drawing A0802 – On the public side of the bullet proof windows drawing A0501 elevations show stainless steel countertop while drawing A0802 calls out polymer resin. Also if a polymer resin is required will there be any supports or attachments to the bullet proof window frame? The countertop is polymer resin; the document pass-through (deal tray) shall be stainless steel. Disregard the notes on sheet A0501 –

Elevations 1 & 2. Final detailing per cabinet maker. Refer to amendment sheet A0501.

V. My problem is that the specs for the security ceilings (09549) and the Reflected Ceiling Plan

(A0401) do not match up in data. The specs call for 14 gauge 2’x4’ Lockdown panels. The drawings do not show Lockdown. They show 24” wide Cel-Line planks 84” to 144” long. I need to know what is actually being bid here. If it is Lockdown, I will either need the square footage or corrected drawings to show me what to quote. If it is Cel-Line the drawings I have are fine but I will need the specs corrected. Thank you for your help on this. Please let me know if there is any other information that I can provide. Please bid 2’ wide security plank (refer to amended sheet A0401) and refer to amended specification 09549, included herein.

W. In reviewing the drawings we unable to locate the details for the “security ceiling”? Please provide manufacturers standard details. Refer to Spec 09549.

X. On the wall details there is a symbol 1’ – 4” c/c, please explain. URS does not understand this question.

DAYTON, OHIO

Do not remove this Notice. Properly destroy

Y. On drawing S0101 you have a floor drain shown but no connection point or oil interceptor. This is the only place I find the floor drain. It does not show up on the plumbing plans or the plumbing schedule. Please advise. Refer to sheets P0200 and P0201 in the Bid Set. He new floor drain is indicated between columns L and J, and approximately 25 ft south of column

17.

Z. Good mourning Fred, I have a question on the VAV box piping hook up. On the drawings there are no details on the piping and pipe specialties. So the question is does the piping just hook up to the units with no specialties or valves or anything or a typical installation with valves and control valves, straines, pt, thermometers, return loop, etc. please clarify and specify which you prefer, thanks, Kris Williams @ Precision Piping, Inc. Refer to revised sheet M0500, a detail has been added to indicate the requirements for the reheat coils at VAV boxes.

AA. Concerning carpet spec --- atlas cpt 1 26 oz. (integral pad) ----cpt 2 Tandus 38 oz (integral pad).

I haven’t talked to the atlas rep yet but I have the tandus re. She did not understand integral pad.

Here’s is a list of teir backing systems: 1.)Superlok backing no minumums—no overages, 2.)

Lifelong backing 150 yard min + 5% overage, 3.) Ergo step attached cushion 150 yd min +5%--

-total yards needed 123. Can you clarify please----Thank you. The words "integral pad" are deleted from the finish legend on drawing A1001. The specification for the Atlas Carpet backing changes from "Enhancer III" to "Action Back". “Double stick” installation is not

“tackless” installation.

BB. Sarah, we understand that the building is to remain operation, with the amount of plumbing, electric and duct work to be possibly relocated temporarily, has there been a thought process of how this is to happen and keep the building in full operation. The contractor shall perform all new and temporary connections to existing systems during unoccupied periods. Each connection shall ensure systems are capable of operation before the next normal period of building operation. All proposed interruptions in services shall be approved and scheduled beforehand by the Contracting Officer.

CC. Can you provide the specification section that applies to the Detention Hollow Metal Doors and

Frames indicated on the Door Schedule as DHM? Refer to Specification 08114 Custom Steel

Doors and Frames.

DD. Also, please provide the specification section for the Custom Cell Doors at openings 120, 121 and 122. The door schedule refers us to section 6/A0801. However I am looking for the locking

/ hinge mechanisms, etc/. Cell Doors 120, 121, 122 and 123 shall be Hardware set 19, add via this amendment. Refer to amended specification section 08712.

EE. The type “J” Fixtures call for Dimming Ballast’s in the Fixture Schedule but no dimmer is shown on the Drawings for these type “J” fixtures. Please advise? “Dimming” will be deleted for this amendment.

FF. The Fixture Schedule does shown Emergency Ballast’s in some of the Fixtures in the Schedule but not on the Type’s “K, K1 and L” fixtures which are shown half shaded on the drawings and the legend says that half shaded fixtures are supposed to be provided with an Emergency

Ballast: Do the Fixture types K, K1 and L require Emergency Ballast’s. See Lighting Fixture

Schedule, Fixture’s indicate battery pack and charger.

DAYTON, OHIO

Do not remove this Notice. Properly destroy

GG. The Fixture type K1” shown in the Sally Port has a small “a” by the Fixture: Where is the “a”

Switching for this Fixture located? Key operated switch will be added via this amendment.

HH. For the “Rough-In only” of the Security Devices, do we have stub up a conduit from these

Security Outlets to above the Ceiling, or? If yes, what size conduit do you want us to utilize for these Conduit Stub Up’s? If no, please advise what you want us to do for these Security Outlet

Rough In’s. See General Notes: Auxiliary Systems, note 4, on sheet E0501.

II. The specifications have an extensive Section on the Fire alarm System, but the Drawings do

NOT SHOW any Fire alarm System Devices to be removed, relocated, or Installed New. Is there any Fire alarm System work on this Project, and if there is, please advise what Fire Alarm

System Devices are required and where are they supposed to be located? See sheets F0101, F0201, and F0301.

JJ. In reviewing the electrical drawings there is work to be done with the elevator electric panels

(relocating) to the command room. Who does that work, do we need an elevator company to do that work? Electrical Contractor shall include all elevator work for bidding. Coordinate this work with current elevator maintenance contractor “Kone”.

KK. Reference Plumbing note 2 on Sheet P 00 00. “Lavatory waste line must be installed as high as possible, as close to wall pas possible anchored to wall and be chrome placed.”

• The plumbing fixture schedule shows the lavatories to be handicapped under counter china fixtures.

• The foot note below the fixture schedule states: Lavatories shall have P-traps and supplies installed with “Truebro’ insulation kits model #102 (or approved equal).

1. Please clarify the intent of this note. Disregard the note.

2. Is this note only to apply to the waste area and trap from the wall to the lavatory or will there be exposed sanitary piping that will be required to be chromed? Applies to waster area and trap, no other exposed san.

3. Will the waste arm need to be chrome, as specified, as it will be covered with the Truebro insulation kit? This a minor cost issue! Provide chrome plated waste as indicated on drawing.

LL. Reference Specification 15413-2 paragraph 2.2 Combination units and specification 15413-3 paragraph 2.3 showers. 15413-3 Showers specify Willoughby as an approved manufacture for the security showers. 15413-2 Combination Units do not list Willoughby as an approved item.

Can Willoughby be used as an approved equal for the Combination Units? Yes Willoughby

Security Fixtures can be provided for the combination units.

MM. Reference Plumbing Drawing P 02 01 First Floor Plumbing and P 00 00 Fixture Schedule.

Drawing P02 01 indicates a new electric water cooler labeled EWC-1 located in Squad Room

105. This drawing does not give a model number. Drawing P00 00 does not indicate a new water cooler on the schedule. The Specification calls for an ARI 1010 (Air Conditioning and

Refrigeration Institute ARI) standard, which is the specification that the water cooler is designed

to. The specification also states that the water cooler shall by type PB (Pressure bubbler) and

Style W (Wall hung). Is there a model number and manufacture for the basis of design? EWC-

1: Shall be similar to “Halsey-Taylor” HVRB ADA or comparable manufacturer SS cooler top and sides, ASDA compliant, vandal-resistant bubbler, water filter 120V 1 PH.

DAYTON, OHIO

Do not remove this Notice. Properly destroy

NN. Reference plumbing specification 15430-4 paragraph 2.6A Floor Drains and specification

15430-5 Floor Cleanouts Paragraph 2.6B Floor Cleanouts. Wart drainage products is listed as a listed manufacturer for the floor cleanouts but is not listed as an acceptable manufacture for floor drains. Is Watts Drainage Products an accepted manufacturer for floor drain? The manufacturer “Watts” is acceptable but must meet the requirements of the specification.

OO. The International Building code (OHIO) required seismic sway bracing for buildings with an importance factor greater than 1. Will seismic sway bracing be required for HVAC pipe, duct, equipment, electrical fire protection etc? If seismic is required will there be a specification and guideline issued for the seismic requirements. This building is a Seismic Occupancy

Category 2, and a Building Design Category “B”. ASCE-7-05 13.1.4 exemptions (II) does not require the use of seismic restraints on mechanical and electrical systems.

PP. 1. What duration of down time is acceptable to remove the existing AH-6 install new structural steel and reinstall the new AH-6 unit without affecting the operations of the occupied spaces that SH-6 will serve? The 40” x 20” temporary supply duct from AHU-1 is large enough to support the occupied spaces for an extended period of time on a continuous basis. The contractor shall coordinate the installation of the floor reinforcement system such that the construction schedule is not impacted by method and construction sequences implemented. Contractor shall submit a schedule for this work.

2. Will the temporary 40” x 20” duct be sufficient during warm weather? The 40” x 20” duct is sufficient.

QQ. With such strict open flame and hot work regulations for the building as brought up in the first pre-bid walk-thru, would flameless piping jointing methods be considered for the hydronic and plumbing piping? More specifically would a grooved system on 2-1/2” and up steel piping and a press fit system for 2” and down copper be considered for piping systems? Hydronic piping and plumbing piping: Grooved joint mechanical couplings shall be allowed for steel piping 2-1/2” and larger manufacturer’s – Victaulic/Groove Lock. Plumbing Piping: 2” and smaller, Pressure Seal 2” and smaller, fittings such as Viega “Pro-Press” are acceptable.

DAYTON, OHIO

Do not remove this Notice. Properly destroy

PROJECT MANUAL REVISIONS

A. TABLE OF CONTENTS

1. DIVISION 8: Add Section 08311 Access Doors and Frames

B. Section 02080 – Asbestos Abatement

1. Replace section in its entirety.

C. Section 08311 – Access Doors and Frames

1. Add section in its entirety.

D. Section 08712 –Door Hardware

1. Add Hardware Sets 19 and 20

E. Section 09549 – Security Ceiling Systems

1. Replace Section in its entirety.

F. Section 09680 – Carpet

1. Part2.1.A.1.c - revise backing from The Enhancer III to Action Back.

G. Section 15083 – Pipe Insulation

1. Replace Section in its entirety.

H. Section 16511 – Interior Lighting

1. Replace Section in its entirety.

1.3 DRAWING REVISIONS

A. Drawing A0101.

B. Drawing A0201

C. Drawing A0401

D. Drawing A0501

E. Drawing A0802

F. Drawing A1001

G. Drawing F0201

H. Drawing M0100

I. Drawing M0101

J. Drawing M0201

DAYTON, OHIO

Do not remove this Notice. Properly destroy

K. Drawing M0500

L. Drawing M0600

M. Drawing E0101

N. Drawing E0201

O. Drawing E0601

1.4 APPROVED SUBSTITUTION REQUESTS

A. Section 08114 – Custom Steel Doors and Frames

1. Trussbilt Detention Security is accepted as equal

B. Section 09549 – Security Ceiling Systems

1. Trussbilt BarrierDek is accepted to bid.

C. Section 10155 – Toilet Partitions

1. Accurate is accepted to bid as equal

D. Section 10505 – Metal Lockers

1. ASI is accepted to bid as equal

** END OF AMENDMENT NO. 3 **

USMS FIRST FLOOR SALLYPORT PBS-REG-5

UNITED STATES COURTHOUSE AND FEDERAL OFFICE BUILDING ROH 00033

DAYTON, OHIO

PROPERTY OF THE UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

Do not remove this Notice

Properly destroy documents when no longer needed

TABLE OF CONTENTS TOC - 2

DIVISION 5 – METALS

Section 05120 Structural Steel

Section 05210 Steel Joist

Section 05310 Steel Deck

Section 05500 Metal Fabrications

Section 05521 Pipe and Tube Railings

DIVISION 6 – WOOD AND PLASTICS

Section 06402 Interior Architectural Woodwork

DIVISION 7 – THERMAL AND MOISTURE PROTECTION

Section 07531 EPDM Membrane Roofing

Section 07841 Through Penetration Firestop Systems

Section 07811 Sprayed Fire Resistive Materials

Section 07920 Joint Sealants

DIVISION 8 – DOORS AND WINDOWS

Section 08110 Steel Doors and Frames

Section 08114 Custom Steel Doors and Frames

Section 08211 Flush Wood doors

Section 08311 Access Doors and Frames

Section 08331 Overhead Coiling Doors

Section 08411 Aluminum Framed Entrances and Storefronts

Section 08712 Door Hardware

Section 08800 Glazing

Section 08801 Security Glazing

DIVISION 9 – FINISHES

Section 09260 Gypsum Board Assemblies

Section 09310 Ceramic Tile

Section 09402 Resinous Matrix Terrazzo Flooring

Section 09511 Acoustical Panel Ceilings

Section 09549 Security Ceiling Systems

Section 09651 Resilient Tile Flooring

Section 09680 Carpet

Section 09900 Painting

ASBESTOS ABATEMENT 02080 - 1

SECTION 02080 – ASBESTOS ABATEMENT

TABLE OF CONTENTS

PART 1 GENERAL

1.1 DESCRIPTION OF ASBESTOS ABATEMENT

1.2 SUMMARY OF WORK

1.3 RELATED WORK

1.4 DIFFERING SITE CONDITIONS

1.5 CONTRACTOR’S SUBMITTALS

1.6 JOB CONDITIONS

1.7 MEETINGS

1.8 AUTHORITY TO STOP WORK

1.9 REFERENCES

1.10 DEFINITIONS

PART 2 PRODUCTS

2.1 PERSONAL PROTECTIVE EQUIPMENT

2.2 WARNING SIGNS AND LABELS

2.3 TOOLS AND EQUIPMENT

2.4 TEMPORARY ELECTRICITY

2.5 TEMPORARY WATER

2.6 TEMPORARY HEAT

2.7 SANITARY FACILITIES

2.8 MATERIALS

PART 3 EXECUTION

3.1 WORK AREA PREPARATION

3.2 GENERAL ACM REMOVAL PROCEDURES

3.3 CLEANING OF THE ASBESTOS REGULATE AREA

3.4 VISUAL INSPECTION

3.5 ENCAPSULATION

3.6 FINAL CLEANING OF THE ASBESTOS REGULATED AREA FOR NON-INTACT

REMOVAL

3.7 FINAL CLEANING OF THE ASBESTOS REGULATED AREA FOR INTACT REMOVAL

3.8 CLEARANCE AIR SAMPLING FOR NON-INTACT REMOVAL

3.9 RE-ESTABLISHMENT OF THE WORK AREA FOR NON-INTACT REMOVAL

3.10 RE-ESTABLISHMENT OF THE WORK AREA FOR INTACT REMOVAL

3.11 WASTE DISPOSAL

3.12 CERTIFICATE OF COMPLETION

FORM 02080A CERTIFICATE OF WORKER’S ACKNOWLEDGMENT

FORM 02080B CERTIFICATE OF VISUAL INSPECTION

ASBESTOS ABATEMENT 02080 - 2

FORM 02080C POST-ABATEMENT FINAL INSPECTION/AIR SAMPLING FORM

FORM 02080D CERTIFICATE OF COMPLETION

ASBESTOS ABATEMENT 02080 - 3

PART 1 GENERAL

1.1 DESCRIPTION OF ASBESTOS ABATEMENT

A. Asbestos abatement includes demolition or salvage of structures where asbestos is present; removal, encapsulation or enclosure of materials containing asbestos; alteration, repair, maintenance or renovation of structures, substrates or portions thereof, that contain asbestos; asbestos spill/emergency cleanup; and transportation, disposal, storage, containment of and housekeeping activities involving asbestos or products containing asbestos.

B. This Contract entails removal and disposal of asbestos-containing materials (ACM) from the basement mechanical room and hallways located at the United States Courthouse and Federal Office Building, 200 West Second Street in Dayton, Montgomery County, Ohio.

1.2 SUMMARY OF WORK

A. This Section includes the removal, handling, and disposal of ACM to support the renovations of the United Stated Marshals Service (USMS) First Floor Salleyport project. All asbestos hazard abatement work shall be conducted in accordance with all enclosed Contract Documents and forms, and in compliance with all applicable federal, state, and local regulations and "state of the art" technology.

B. The following materials were identified as containing asbestos at the Facility. The Scope of

Work includes the removal of only those materials highlighted in bold.

Material Type Location Estimated

Quantity

Analytical

Results

(% by volume)

White Tape on existing duct insulation joints

Basement and First

Floor

Every Duct

Joint 4% Chrysotile

Duct Sealant (between metal joint) Basement and First

Floor

Every Duct

Joint 2% Chrysotile

Plaster Soffit Above Rooms 112 and 113

590 SF PACM

Fire Doors First Floor 18 PACM

Vibratory Bands Basement and First

Floor 20 (estimate) PACM

Pipe Insulation Inside AHU 6

50 LF

(estimate)

PACM

ASBESTOS ABATEMENT 02080 - 4

Material Type Location Estimated

Quantity

Analytical

Results

(% by volume)

12” x 12” White with dark gray streaks, light blue, and pink floor tiles First Floor 5,830 SF 3% Chrysotile

Black Mastic and floor leveler under 12” x

12” light blue floor tile with white and gray streaks

First Floor 5,830 SF 2% Chrysotile

12” x 12” tan floor tile with brown and white streaks

8% Chrysotile

Black Mastic under 12” x 12” tan floor tile with brown and white streaks

Basement and First Floor Hallways

3% Chrysotile

NOTE: The following materials were also sampled and tested for asbestos: ceiling tiles, Ceiling tiled glue, drywall, join compound, mortar, plaster (inside work area), burlap, tar paper, and fireproofing. Analytical results indicated that these materials did not contain asbestos.

C. The Scope of Work includes the removal and disposal of confirmed and presumed ACM and asbestos-contaminated fiberglass insulation in areas of the US Courthouse and Federal Office Building affected by the USMS First Floor Sallyport project (See Drawings). If any other materials are found, which are suspected of containing asbestos, notify the Environmental Consultant immediately.

1. First Floor, USMS Center:

a. White tape on existing duct insulation joints and duct sealant (between metal joint) are known to be ACM and are to be removed. Areas above hard ceilings or acoustical ceiling tiles were not observed; therefore, materials may be located above these surfaces. If materials are encountered during demolition, these materials must be abated.

b. Plaster soffit was observed above Rooms 112 and 113. Due to the height of this soffit (15 feet above finished floor) a sample could not be collected. This material is presumed to be ACM (PACM). The plaster soffit shall be removed in accordance with all federal, state, and local regulations unless the Contractor can identify that this material is NOT ACM.

c. Approximately 18 Fire Doors require removal per specifications. These doors are PACM. The fire doors shall be removed in accordance with all federal, state, and local regulations unless the Contractor can identify that this material is NOT

ACM.

d. Vibratory bands were observed on duct work located in the project area. Sample of this material could not be collect while the unit was in operation; therefore, these materials are presumed to be ACM (PACM). The vibratory bands shall be

ASBESTOS ABATEMENT 02080 - 5

removed in accordance with all federal, state, and local regulations unless the Contractor can identify that this material is NOT ACM.

e. Floor tiles and floor tile mastics located throughout the first floor work area are ACM. These materials are classified as Category I non-friable ACM and must be removed in accordance with all federal, state, and local regulations.

f. The Contractor will clean all asbestos debris accumulated on the all surfaces and debris collected on the all components (mechanical, electrical, etc.) to be demolished.

2. Basement Mechanical Room, AHU 6:

a. White tape on existing duct insulation joints and duct sealant (between metal joint) are known to be ACM and are to be removed. If materials are encountered during demolition, these materials must be abated.

b. Three vibratory bands were observed on AHU 6. Sample of this material could not be collect while the unit was in operation; therefore, these materials are presumed to be ACM (PACM). The vibratory bands shall be removed in accordance with all federal, state, and local regulations unless the Contractor can identify that this material is NOT ACM.

c. Due to the operation of this unit, a complete inspection of the interior was not possible. ACM pipe insulation has been identified in other AHUs at this facility.

It is possible that the Contractor may encounter ACM pipe insulation. If suspect insulation is encountered, the Owner’s Representative shall be notified immediately.

d. The Contractor will clean all asbestos debris accumulated on the floor surface and debris collected on the valves and mechanical components to be demolished.

C. Coordination and Scheduling

1. The Contractor must begin and complete all Work within the time established in the Contract and the Notice to Proceed issued by Government Services Administration (GSA) to the Contractor. The Contractor shall provide preconstruction submittals as specified in Subparagraph 1.5.B through 1.5.I of this Section for review and approval at least 24 hours prior to onsite asbestos hazard abatement work.

2. The Contractor shall coordinate with GSA, Environmental Consultant, and other contractors for the successful completion of the Work.

3. All work within asbestos regulated area(s) not related to asbestos abatement shall cease and shall not commence until asbestos hazard abatement operations are complete to the satisfaction of the Environmental Consultant.

D. This specification is based on an Asbestos and Lead-Based Paint Survey of the site conducted by Versar in February, 2006. URS conducted inspections of the work areas within the building on May 15 and 22, 2008 and March 6, 2009.

ASBESTOS ABATEMENT 02080 - 6

E. The Owner will provide all items and services in regards to security, access, utilities, or process assistance, as outlined in this paragraph.

1. The GSA will allow access to the site by the Contractor for all shifts required to meet

Contract completion requirements stipulated.

2. The GSA will provide access upon written request to electrical distribution, which shall not be metered.

3. The GSA will provide a non-metered connection point for potable water as close to the Work as presently exists.

4. The Owner will allow access to the site daily for the duration of Work unless otherwise indicated.

5. The Owner may have an on-site representative to verify compliance with governing regulations and Contract Documents. The furnishing of this representative shall not make the Owner responsible for Contractor's failure to perform work in accordance with regulations and/or the Contract Documents.

F. The Owner's Representative shall provide all items and services in accordance with this

Paragraph.

1. While performing asbestos abatement work, the Contractor shall be subject to on-site inspection by the Owner's Representative. If the Work is in violation of Contract Documents or regulatory requirements, the Owner, through the Owner's Representative, will issue a stop work order to be in effect immediately and until the violation is corrected. Standby time and expenses required to correct the violation shall be at the Contractor's expense. The Contractor shall resume Work only upon receiving written authorization from the Owner's Representative.

2. The Owner's Representative may procure personal air samples of Contractor's or

Owner's Representative's employees to measure work area exposures. If the air monitoring in the work area indicates a fiber concentration above one-tenth of a fiber per cubic centimeter (0.1 f/cc) TWA8 or one fiber per cubic centimeter (1.0 f/cc) for a 30 minute period, the Contractor shall implement appropriate engineering controls in an attempt to reduce concentrations to or below this level.

3. The Owner's Representative may perform air monitoring outside of and adjacent to the work areas. If these measurements indicate contamination (greater than or equal to 0.01 f/cc) or background level, whichever is higher, outside of the work area from asbestos hazard abatement work, the Owner's Representative may notify the Owner to direct the Contractor to immediately cease operations until the presence of contamination is verified and corrected to the satisfaction of the Owner's Representative. Standby time and costs required for corrective action shall be at the Contractor’s expense.

ASBESTOS ABATEMENT 02080 - 7

4. The Owner's Representative is responsible for furnishing and maintaining air monitoring equipment and supplies in connection with monitoring, testing, and reporting performed by the Owner's Representative. The Owner's Representative shall bear these costs except to the extent that the air monitoring indicates contamination outside of the work area due to the Contractor's work.

G. The Asbestos Abatement Contractor shall provide all items and services in accordance with this Paragraph.

1. The Contractor shall examine all Contract Documents, including without limitations the technical specifications and drawings for the Work. Failure of the Contractor to be acquainted with the amount and nature of Work as required in all Contract Documents and presented in the Pre-bid meeting and walkthrough will not be considered as a basis for additional compensation.

2. Prior to beginning work, the Contractor shall be responsible for documenting existing conditions of adjoining construction that might later be misconstrued as damage caused by the Contractor’s work. The Contractor shall be responsible for repairing damage to adjoining construction caused by Contractor’s work.

3. The Contractor shall bear complete responsibility for worker safety and adherence to all applicable federal, state, and local laws, regulations and standards. The Contractor shall hold the Owner and Owner’s Representative harmless for failure to comply with the applicable laws and regulations.

4. The Contractor shall provide all labor, equipment, materials, appurtenances, and incidentals required for the complete removal, containment, transportation, and disposal of ACM as listed in Paragraph 1.2A and B, to include the cleaning/decontamination and/or collection and disposal of adjacent materials which may become contaminated during the removal process.

5. The Contractor shall work whatever shifts required to meet Contract completion requirements stipulated. The Contractor shall notify the Owner and Owner’s Representative no later than the pre-construction meeting of what shifts will be worked.

The Owner and Owner’s Representative shall be notified of any changes to the shift schedule at least 72 hours prior to any changes in work shifts. This shall be coordinated with and included in Contractor’s construction progress schedule.

6. The Contractor shall secure the immediate work area(s) for the duration of the Work as required by the Contract Documents and all federal, state and local regulations. Only authorized personnel directly involved with the abatement work may enter the work area(s). The Contractor is totally responsible for all safety and security of Contractor's equipment.

7. The Contractor shall conduct personal air monitoring for Contractor's employees in compliance with OSHA regulations. It is the Contractor's responsibility to furnish and

ASBESTOS ABATEMENT 02080 - 8

maintain air-monitoring equipment required to determine worker exposure. The Contractor shall bear costs in connection with exposure monitoring and reporting required.

8. The Contractor shall be responsible for controlling Contractor’s vehicular and pedestrian traffic without endangering other contractors and the public during the transfer of ACM.

9. The Contractor shall be responsible for providing temporary electricity as follows:

a. Contractor is responsible for providing electricity and for making all arrangements necessary to accomplish the Work. A licensed electrician shall perform all work.

b. Provide lighting to reach a minimum of 50 foot-candles throughout the work area(s) and decontamination units.

c. Provide an auxiliary gasoline- or diesel-powered generator outside of the work area arranged so that in case of a power failure, the generator automatically starts and supplies power to at least 50% of the negative air machines.

d. The Contractor shall provide at least two, 20-amp, 120 VAC electrical circuits for Owner’s Representative’s use during clearance air monitoring.

10. The Contractor shall be responsible for providing temporary water as follows:

a. The Contractor shall make whatever connections or arrangements for water deemed necessary for its operations. A backflow preventer at the initial connection point is mandatory and shall be provided by the Contractor. All items required for the connection, including hoses, etc., shall be provided by the Contractor. The Contractor shall be responsible for the shutdown of all water sources when not in use.

b. The Contractor shall provide a UL-rated, 150-liter minimum (40-gallon) electrical hot water heater to supply hot water at a minimum of 38 °C (100 °F) to the shower(s) of the personal decontamination area.

11. Completion of all work, including all final documentation, shall occur within the time established in the Contract and the Notice to Proceed issued by the Owner to the Contractor.

1.3 DIFFERING SITE CONDITIONS

The total quantity and locations of ACM and/or contaminated materials shall be field verified by the Contractor during the Pre-bid walkthrough. If the Contractor finds any perceived conflict, error, omission, or discrepancy in the Contract Documents, the Contractor shall submit a written request for an interpretation or clarification prior to the Bid Opening as specified in Division 0 of the Contract Documents. The Contractor shall not, at any time after the Bid Opening, be compensated for a claim alleging insufficient data, incomplete Contract Documents, or incorrectly-assumed conditions regarding the amount or nature of Work, if no request for interpretation was made by the Contractor prior to the Bid Opening.

ASBESTOS ABATEMENT 02080 - 9

1.4 CONTRACTOR'S SUBMITTALS

A. All submittals shall conform completely to the requirements of the Contract Documents, including all requirements set forth in this Section.

B. As part of the Contractors’ bids, all prospective Contractors shall submit for approval, and as a condition under the Contract, the following documentation:

1. Proof of Ohio Asbestos Hazard Abatement Contractor license.

2. A notarized letter from an officer of the Contractor's organization stating that the prospective Contractor is thoroughly familiar with federal, state and local regulations, and "state of the art" technologies for the abatement, handling, transportation, and disposal of ACM.

3. Proof of successful completion of at least three projects where the volume of ACM removed was equal to or greater than 15,000 SF of asbestos-containing miscellaneous material within the last four years. The proof or documentation shall include:

a. Description of projects, including size and duration.

b. Project references for verification that abatement was performed in full compliance with all regulatory requirements.

c. All State certification requirements as applicable.

d. Statement of Performance Bond Eligibility.

4. Records to indicate that the asbestos-containing materials from at least three previous projects have been properly disposed of at an EPA approved and licensed landfill. The site must be authorized by the authority having jurisdiction to receive such wastes.

5. Records indicating that the prospective Contractor has knowledge or experience in proper engineering techniques, i.e., HEPA exhaust filtration, air locks, etc. needed to contain ACM and prevent the release of airborne asbestos fibers.

6. Documentation of any regulatory violations and associated penalties within the last five years.

C. Two week prior to commencing work and as a condition under the Contract, the Contractor shall document through the submittal process, the proof that Contractor's General Superintendent has:

1. Passed required medical examination.

2. Attended and successfully completed Asbestos Contractor/Supervisor training course, in accordance with AHERA regulation 40 CFR 763, Subpart E, Appendix C.

ASBESTOS ABATEMENT 02080 - 10

3. Current Ohio Department of Health Asbestos Hazard Abatement Specialist License.

4. Been fitted, tested and trained in the use and maintenance of the respirator equipment.

5. Had a minimum of two years on-the-job experience in asbestos abatement procedures.

6. Signed the Certificate of Worker’s Acknowledgment (Form 02080A).

The Contractor's General Superintendent shall be onsite on a full-time basis throughout the duration of the Work. In the absence of the Superintendent, the Contractor shall assign a similarly-qualified individual who will perform all required General Superintendent duties.

The General Superintendent shall remain until the project is complete; if removed from the job, the Contractor shall notify the Owner’s Representative immediately.

D. Two week prior to commencing work and as a condition under the Contract, the Contractor shall document through the submittal process, the proof that Contractor's workers have:

1. Passed required medical examination.

2. Attended and successfully completed Asbestos Worker or Asbestos Contractor/Supervisor training course.

3. Current Ohio Department of Health Asbestos Hazard Abatement Worker or Asbestos

Hazard Abatement Specialist License.

4. Been fitted, tested and trained in the use and maintenance of the respirator equipment.

5. Signed the Certificate of Worker’s Acknowledgment (Form 02080A).

No worker shall be permitted to work on this Project unless proper documentation is provided.

E. Two week prior to commencing work and as a condition under the Contract, the Contractor shall document through the submittal process, the proof that Contractor's Air Monitoring Technician has:

1. Attended and successfully completed Asbestos Building Inspector/Management Planner or Asbestos Hazard Abatement Air Monitoring Technician training course. Neither course is necessary if Contractor's Air Monitoring Technician is a Certified Industrial Hygienist (CIH), and such proof is provided.

2. Current Ohio Department of Health Asbestos Hazard Evaluation Specialist or Asbestos

Hazard Abatement Air Monitoring Technician License. Neither license is necessary if Contractor's Air Monitoring Technician is a CIH, and such proof is provided.

3. Signed the Certificate of Worker’s Acknowledgment (Form 02080A).

ASBESTOS ABATEMENT 02080 - 11

F. Two week prior to commencing work and as a condition under the Contract, the Contractor shall document through the submittal process, the proof that personnel performing PCM analysis of air monitoring cassettes for Contractor have:

1. Attended and successfully completed NIOSH 582 training course for sampling and evaluating airborne asbestos dust.

2. Proof of participation in Proficiency Analytical Testing (PAT) or equivalent program.

G. Prior to commencing work and as a condition under the Contract, the Contractor shall secure all necessary licenses and permits associated with asbestos abatement, transportation and disposal as required by Federal, State and local regulations. These documents include, but are not limited to, Ohio Department of Health Prior Notification of Asbestos Hazard Abatement Project, and Ohio Environmental Protection Agency Notification of Demolition and Renovation.

H. Prior to commencing work and as a condition under the Contract, the Contractor shall provide copies of state and local licenses for the waste hauler, US EPA identification number of the waste hauler, name and address of the waste disposal facility, and copies of disposal facility licenses and permits.

I. Plan of Work Procedure

1. The Contractor shall submit to the Owner's Representative at least four weeks prior to commencement of Work, a detailed plan of the Work procedures to be used in the abatement of ACM. The plan shall include but not be limited to the following:

a. Plan overview of asbestos abatement.

b. Details of all equipment to be used, including negative pressure equipment, filters, showers, change rooms, clean rooms, disposal drums or containers, water filters and other miscellaneous items.

c. Sequence of operation for each work area, and a detailed schedule of Work within each work area that shall meet the constraints specified in Paragraph 1.2, and the Contract requirements. The Contractor's schedule must show all shift work and any known constraints caused by facility operations or access requirements.

d. Documentation of records, including copies of notification forms for intended asbestos removal to all Federal, State, or local regulatory agencies having jurisdiction over the project area, as required.

e. A detailed, narrative description of how the Work is to be accomplished. This shall include a description of any sealed areas, negative pressure equipment and filters, location of decontamination units, methods of actual asbestos removal, encapsulation and cleanup, transfer of asbestos waste, and all other operating procedures. Provide NPE system information to include

ASBESTOS ABATEMENT 02080 - 12

calculations for the number of negative air units, projected air flow within the work area(s) and anticipated pressure differential.

f. A detailed health and safety plan (HASP) to include all clothing, respirators, respirator cartridges and other equipment to be used by personnel who will be exposed to asbestos fibers. Provide details of the worker educational training programs. Provide a listing of all worker procedural and safety requirements.

g. An initial exposure assessment in accordance with 29 CFR 1926.1101 (f) (2).

h. Material Safety Data Sheets (MSDS) for all chemicals, detergents, solvents and encapsulants to be used for abatement activities.

i. Limits of operational parameters, including friable asbestos fiber concentrations inside and outside work areas, and negative-pressure limits within any enclosures.

j. A scaffolding plan for all scaffolding to be used on this project.

k. Proposed noise control measures.

l. Emergency procedures in the event that air monitoring outside of any work area should indicate asbestos fiber levels exceeding the allowable limit.

m. Contingency plan for emergencies including fire, accident, power failure, failure of negative air system, or any other event that may require modification of standard operating procedures during abatement.

2. This plan shall be either accepted or rejected by the Owner's Representative for compliance with applicable regulations and Contract Documents.

J. Special Reports: The Contractor shall submit special reports to the Owner’s Representative within one day of occurrence requiring special reports. Special reports shall include a listing of the chain of events, persons participating, response by Contractor’s personnel, evaluation of results or effects, and similar pertinent information. Special reports will be required to document the following circumstances:

1. Unusual events, including but not limited to failure of the negative pressure system, rupture of the negative pressure enclosure, or spills of asbestos debris.

2. Accidents, including events where personal injury is sustained, property loss of substance is sustained, or where the event posed a significant threat of loss or personal injury.

3. Discovered conditions, such as unusual conditions (leaks, termites, corrosion that was not anticipated) or additional suspect ACM.

K. Project Log

1. The Contractor will maintain a daily Project Log. The log will be used each day of the project to record the following information:

a. Name of General Superintendent, air monitoring technician, and actual time physically on job for both persons.

ASBESTOS ABATEMENT 02080 - 13

b. Brief description of daily Work accomplishments.

c. Listing of all employees on the job by position, trade, or responsibility.

d. Description of any significant events, incidents, or unusual occurrences, including but not limited to, deviations from plans, contract requirements, or specifications noted Owner's Representative, Air Monitoring Technician, or Contractor; emergencies, accidents or dangerous conditions; and steps taken to assure continued security of the Work area.

2. The log will also include copies of routine inspection reports, results of air monitoring and analysis, records of routine NPE pressure differential readings, project minutes, chain-of-custody forms and any other routine documents relating to project activities. The log for the project will be made immediately available for inspection by the Owner's Representative.

3. At the completion of the project, the Contractor shall forward one copy of the Project

Log to the Owner's Representative.

L. Project Visitor's Log: The Contractor shall maintain a Project Visitor's Log which will contain the following as a minimum.

1. Signatures with date and time, by all visitors, including the Owner's Representative, private or governmental inspectors, and Contractor's representatives not involved in the daily abatement activities.

2. All visitors who enter the regulated area, reason for entry, date and duration of time in the Work Area, activities in Work area, safety precautions used and safety equipment used.

3. Submit one complete copy of the Project Visitor's Log to the Owner's Representative upon completion of the Project.

M. Contractor's Compliance Data

1. Contractor shall submit to the Owner's Representative within 30 days after waste load-out, an original copy of the chain-of-custody forms signed by the disposal site operator, evidencing acceptance of the waste ACM.

2. The Contractor shall maintain a log of all personal air monitoring data gathered during the Work. The log format shall be: air monitoring form, air sampling log, laboratory results, summary of equipment used, and calibration data all bound in a complete packet. An updated copy of the log shall be submitted to the Owner's Representative at the end of each Work week. A complete log of air samples and results shall be submitted to the Owner's Representative at the completion of Work.

1.6 JOB CONDITIONS

ASBESTOS ABATEMENT 02080 - 14

A. During the Work, the Contractor shall confine his equipment and personnel to the work area(s) specified in this section and on drawings and as directed by the Owner's Representative. Interference with facility operations or personnel outside of the designated area(s) will not be permitted without Owner’s approval, and the Contractor must provide the Owner with written notice prior to such activities.

B. The asbestos work area(s) shall be made available to government personnel who have the authority to conduct inspections and test for regulatory compliance.

This is the start of the file's text. The full file is on GovTribe.