IGX-112-H22-10-L

Unit Performance

Design Conditions

Elevation (ft) Summer Winter (°F) Supply (CFM) Outdoor Air (CFM)DB (°F) WB (°F) 1,027 93.8 77.2 20.7 3,200 3,200

Unit Specifications Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing Furnace ETL Listing

2 2,596 (+/- 5%) Packaged DX Indirect Gas Furnace Outdoor UL / cUL 1995 ANSI Z83.8 / CSA 2.6

Configuration Unit Orientation Unit Configuration Outdoor Air Intake Return Air Intake Supply Air Discharge

Horizontal Constant Volume 100% OA End - End

Cooling Specifications

Type Refrigerant Capacity (MBH) Lead Compressor

Type EER Performance (DB/WB)

Total Sensible Condensing Section

Design Condition EAT (°F) LAT (°F)

Packaged DX R-410a 131.7 75.9 Standard Scroll 11.6 11.8 93.8 / 77.2 72.3 / 66.9

Heating Specifications

Type Gas Type

Gas Pressure Capacity (MBH) Temperature Rise Turndown

Performance Min

(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT

(°F)

LAT

(°F)

Indirect Gas Furnace Natural 6 0.5 350.0 280.0 20.2 81.0 4:1 21.0 101.7

Air Performance

Type Total

Volume

(CFM)

External SP

(in. wg)

Total SP

(in. wg) RPM Operating

Power (hp) Fan

Qty Type Size (in.) Drive-Type Supply 3,200 1.8 2.093 1199 2.05 1 Forward Curve 12 Belt-Drive

Motor Specifications Motor Qty Size (HP) Enclosure Efficiency RPM

Supply Fan Motor 1 5 ODP NEMA Premium 1725

Electrical Specifications Power Supply Rating (V/C/P) MCA (A) MOP (A)

Unit 460/60/3 27.8 35

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

Generated by: esmith@holdenassoc.com CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 1 of 39

CONSTRUCTION FEATURES AND ACCESSORIES

Unit Unit Installation - Outdoor Std Unit Construction - Double Wall X Wall Insulation - 1in. fiberglass - Cool source on X Base Insulation - 1in. fiberglass - entire unit base pan Std Paneled Bottom - Sheet metal liner for base insulation Corrosion Resistant Fasteners Std Access and Connections - Right side when facing intake X Service Access - Hinged access doors X Unit Finish - Permatector ASTM B117 salt spray 2500 hours X Finish Color - Concrete Gray (RAL 7023) X Supply Fan - Belt-drive, forward-curved X Supply Fan and Motor Vibration isolation - Neoprene X

Controls Unit Controls - Terminal strip with remote panel X Remote Panel - Industrial (NEMA-1) X BMS Communication BMS Protocol Temperature Control X Supply Fan VFD Supply Fan Control Melink/Vari-Flow wiring package Recirculation Control Unoccupied Mode (Night Setback)

Control Accessories Remote display Heating Inlet Air Sensor X Cooling Inlet Air Sensor X Dirty Filter Switch Fire Stat Type III (Ships loose) 120V/24V Smoke Detector (Ships loose) Inlet Damper End Switch External Cooling Lockout Relay Freeze Protection (Supply Air Low Limit) X Auxiliary Supply Starter Contacts - Qty 1 X Auxiliary Exhaust Starter Contacts Airflow Proving Monitoring Contact

Accessories Factory Installed, Lockable, NEMA 3R Disconnect Std Weatherhood - Aluminum Mesh filtered X Supply Air Filters - 2" aluminum, 20x20x2 - (6) X Outdoor Air Inlet Damper Supply Air Outlet Damper - Low leakage X Return Air Damper Diffuser Roof Curb Combination Curb Electrofin Coil Coating Fan Bearing Extended Lube Lines Inlet Damper Module Spare Belts Spare Filters Motor with Shaft Grounding Service Outlet Service Lights

Gas Heating Accessories Furnace Venting - Outdoor X Venting Type - Power vented Std Furnace Venting Method - Standard X Concentric Venting Adapter Direct Spark Ignition Std Flame Sensing - Flame rod Std Heat Exchanger Material - Stainless steel X Furnace Controls - 4:1 Modulating X Agency Approval - ETL and IRI Std External Gas Pressure Regulator (Ships loose) X DDC Assisted Furnace Commisioning X

Warranty Options Unit Warranty - 1 Year X 5 Year Compressor Warranty 5 Year Heat Exchanger Warranty X 10 Year Heat Exchanger Warranty

Standard Option Std Not Included

Included X

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 2 of 39

Fan Charts And Performance

Supply Fan Performance

Total Volume

(CFM)

External SP

(in. wg)

Total SP

(in. wg) RPM Operating

Power (hp) Motor Fan

Qty Size (HP) Qty Type Drive-Type

3,200 1.8 2.093 1199 2.05 1 5 1 Forward Curve Belt

Pressure Drop (in. wg) Weatherhood Filter Damper Cooling Heating External Total

0.042 0.028 0.01 0.256 0.026 1.8 2.093

Sound Performance in Accordance with AMCA Sound Power by Octave Band Lwa dBA Sones62.5 125 250 500 1000 2000 4000 8000

82 73 75 72 73 66 65 54 76 65 13.1

Supply Fan

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 3 of 39

Cooling Specifications

Cooling Performance

Type Refrigerant Capacity (MBH) Lead Compressor

Type EER Performance (DB/WB)

Total Sensible Condensing Section

Design Condition EAT (°F) LAT (°F)

Packaged DX R-410a 131.7 75.9 Standard Scroll 11.6 11.8 93.8 / 77.2 72.3 / 66.9

Coil Information

PDX Coil Model Fins Per Inch Rows Deep Suction Temp. (°F)

Face Velocity (ft/min)

Refrigerant Velocity (ft/min)

DX38S02S10-30x44 10 2 44.1 349 1,906

Unit Details Refrigerant charges provided by the factory are approximate and may require field adjustment Refrigeration components servicable without affecting airflow Hermetic scroll type compressor(s) Compressor(s) mounted on neoprene vibration isolation Crankcase heater on compressor(s) Liquid-line filter drier Moisture-indicating sight glass

Thermal expansion valve Refrigerant low pressure switch (auto reset) Refrigerant high pressure switch (manual reset) Service/charging valves Low sound, direct drive condensing fans Insulated, double sloped, stainless steel drain pan Copper tube, aluminum fin coil construction

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 4 of 39

Heating Specifications

Heating Performance

Type Gas Type

Gas Pressure Capacity (MBH) Temperature Rise Turndown

Performance Min

(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT

(°F)

LAT

(°F)

Indirect Gas Furnace Natural 6 0.5 350.0 280.0 20.2 81.0 4:1 21.0 101.7

Heating Information

Heat Exch. Material Venting Venting Method Gas Pressure Regulators

Heat Exchanger Warranty

Stainless Steel Outdoor Standard 10 PSI 5 Year

Unit Details ANSI Standard Z83.8 and CSA 2.6 Direct Spark Ignition Stainless Steel Heat Exchanger Tubes

Power Venting 24 Volt Control Power 5 year heat exchanger warranty

Gas Connections

3/4" NPT GAS

CONNECTION

44.924

8.375

7.318

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 5 of 39

ELEVATION VIEW

47.139 24.086 59.598 52.238 33.196

44.924

Notes - Elevation View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.

Order of unit sections is from intake of unit to discharge of unit.

Sections included on this unit: Weatherhood Section, Filter Section, Cooling Section, Blower Section, Furnace 1 Section Insulation: Double Wall, from Cooling Section through end of unit.

PLAN VIEW

INTAKE V-BANK FILTER

ACCESS SIDE

PDX COOLING

ACCESS SIDE

BLOWER

ACCESS SIDE

FURNACE

ACCESS SIDE

47.139 24.086

59.598

94.195

52.238

33.196

53.874

Notes - Plan View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 6 of 39

END VIEW

SUPPLY

DUCT

0.67041.000

39.000

3.875

44.12510.063 32.142

FOOTPRINT VIEW

142.250

CURB LENGTH

RECOMMENDED

40.500

CURB WIDTH

RECOMMENDED

Notes - Footprint View Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides. For example: If the duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.

Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb. For example: If the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.

The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design, to prevent water infiltration.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 7 of 39

Electrical Connections

ELECTRICAL

CONNECTION

15.000

50.250

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 8 of 39

Clearance Specifications

Recommended Minimum Combustible Clearances Floor (in.) Top (in.) Sides (in.) Ends (in.)

Indirect Fired Units 0 0 0 0

Notes - Combustible Clearances Clearance to combustibles is defined as the minimum distance required between the heating source and the adjacent combustible surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the ambient temperature.

Reference venting guidelines for combustion blower clearances.

Recommended Minimum Service Clearances Housing 32 and less (in.) Housing 35 and higher (in.)

42 on the controls side of the unit N/A

Notes - Service Clearances To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances should be 6 in. wider than the width of the module itself.

Reference the PDX Service Clearance guidelines (PDX IOM)

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 9 of 39

Wiring Diagram

CAUTION

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUCTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

G

SDF

RT4 FREEZE PROTECTION

S4

HEAT ENABLE

TO IG FURNACE

RH

A2

A1

POST HEAT

Template Drawing: U10

SUPPLY FAN

MOTOR

ST1 O.L.

11 14

RT4

11 12

RT4

ST1 O.L.

CONTROL

COM NO

D2L

OFF

OUTLET DAMPERD2

ST1

A2 A1

SUPPLY FAN

RF

TS5

COM NO

THERMOSTAT CONTROLLER(S)24 VAC

OA-SENSOR

SENSOR COM

A2 A1

L3

L2

L1

DS1

M1

RF

A2 A1

SUPPLY FAN RELAY

RF

Y1

A2 A1

COOLING

TO 111 & 112 IN

FURNACE 1

DB1

CC# COMPRESSOR CONTACTOR

CF1 CONDENSER FAN CONTACTOR

CH# CRANK CASE HEATER

D2 OUTLET DAMPER

D2L OUTLET DAMPER LIMIT

DS1 MAIN DISCONNECT SWITCH

FSC FIRE SYSTEM CONTACT

FU# FUSE

HLC HIGH LIMIT CONTROL

HPS HIGH PRESSURE SWITCH

LPS LOW PRESSURE SWITCH

M# MOTOR

OL# MOTOR OVERLOAD

PM PHASE MONITOR

R10 COMP#1 INTERLOCK RELAY

R11 COMP#2 INTERLOCK RELAY

RC1 COOLING STAGE 1 RELAY

RC2 COOLING STAGE 2 RELAY

RF SUPPLY FAN RELAY

RH HEAT RELAY

RT4 FREEZE PROTECTION TIMER

SWITCH 1 and 4 DOWN - 2 and 3 UP / DIAL SET TO 4

S2 FAN SWITCH

S4 HEAT AND COOL SWITCH

S5 ROOM OVERRIDE

SDF SENSOR DISCHARGE - FREEZE

ST# MOTOR STARTER

TR# TRANSFORMER

TS5 INLET AIR SENSOR - COOL

JUMPER = COOL : DIFFERENTIAL = 5

TS6 INLET AIR SENSOR - COOL

JUMPER = COOL : DIFFERENTIAL = 5 : OFFSET = 10

GROUND

TO UNIT

MAIN POWER

460V

S2 FSC

TR1

CR

USER INDIRECT GAS FURNACE INTERFACE CONNECTIONS:

ROOM OVERRIDE CONNECTION

31 32

S5

FACTORY WIRED TO TERMINAL "32"

IN IG FURNACE COMPARTMENT

75 VA

111 112

T3

T2

T1

MOUNTED IN

FURNACE

24V

ST1

W1

PM

11 14

PM L2

L1

L3

L1 T1

L2 T2

L3 T3

THERMOSTAT(S) TS5 , TS6

DOC NUMBER: ---- REV: ----

FACTORY WIRED

TO "CC1" IN

COOLING MODULE

CONTROL CENTER

RC1

TS6

COM NO A2 A1

COOLING STAGE 2RC2

STAGE 1

RC1

RC2

14 CONTROL CENTER

TO R11 (11) IN COOLING MODULE

CONTROL CENTER

TO R10 (11) IN COOLING MODULE

IN COOLING MODULE

TO "R"

CONTROL CENTER

TO "C"

21 24

RT4

GI14C602A043F70AU10

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 10 of 39

Furnace Wiring Diagram

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

Wiring Template: S14

IR

CM

12 11

HIGH

LOW

RED

BLACK

TR5

FU8

120V 24V

WHITE

250VA

FU9

IG FURNACE WIRING

BOARD WIRING

FURNACE 1 - 4:1 MODULATING

TO TERMINALS "111" AND "112"

FACTORY WIRED

IN MAIN CONTROL CENTER

112111

INDIRECT GAS WIRING DIAGRAM

WHITE

BLUE

BLUE

RH

HEAT

ENABLE

MAIN CONTROL CENTER

ORANGE

PURPLE

BLACK

BLACK

S5

ROOM

OVERRIDE

CM COMBUSTION BLOWER MOTOR

FU# FUSE(S)

HLC HIGH TEMPERATURE LIMIT CONTROL

IC1 IGNITION CONTROL

IR INDUCTION RELAY

MDV MODULATING VALVE

MV MAIN GAS VALVE

PS2 COMBUSTION AIR PROVING SWITCH

PS5 HIGH SPEED PRESSURE SWITCH

R5 MAIN GAS VALVE MONITORING

R6 LOW SPEED PRESSURE SWITCH

R7 IGNITION CONTROLLER ALARM MONITORING

SC1 STAGE CONTROLLER

TR# TRANSFORMER(S)

TS1 OUTDOOR AIR TEMP SENSOR

TS2 DISCHARGE AIR TEMP SENSOR

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

GND

MV MV

MV

PS2

HLC

(VLV/24V)

PSW

TH

VALVE

IC1

24V

SENSOR

SPARKSPARK

SENSE

BLWR

MDV

120/240V

IR

A1A2

SC1

C1/2

GO

NO1

NO2

G

U10

GND

U1

PS5

ON

NOC

NOC

BLACK

BROWN

PURPLE

RED

PURPLE

BLUE

YELLOW

WHITE

RED

LT. BLUE

WHITE

WHITE

RED

W H

IT

E P

IN

K

U4ORANGE

PURPLE U8

O

RED

OFF

WHITE

GND

(LINE) (BURNER)

(N.O.)

24V+ _

ALARM YELLOW R7

A1A2

WHITE

R5 A1A2

WHITE

R6 A1A2

WHITE

GND

U2

U5

U3

U6 RED

U7 BROWN

U9 PINK

11 14

R5

WHITE

11 14

R6

WHITE

11 14

R7

WHITE

B

LA

C K

SIG+ _

ORANGE

BLUE

TS1

TS2

WHITE

WHITE

GND

FU8/9 3A,250V

SUPPLEMENTARY

BUSSMANN FNM-3

FU7

2A,600V

CLASS

CC

C3/4/5

C6

RED

GSF X

DDC Code: Version - IGFv1.02

XR

DOC NUMBER: ---- REV: ----

R8 A1A2

WHITE

R8

RED LT. BLUE

G6K11P1MX1000GS14

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 11 of 39

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

Wiring Template: S14

CC# COMPRESSOR CONTACTOR

CF# CONDENSER FAN CONTACTOR

CH# CRANK CASE HEATER

DB1 DISTRIBUTION BLOCK

HPS# HIGH PRESSURE SWITCH

LPS# LOW PRESSURE SWITCH

M# MOTOR

R# CONTROL RELAY

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

DOC NUMBER: ---- REV: ----

PDX WIRING DIAGRAM

CH1 CH2

R C

DB1

FACTORY WIRED TO TERMINAL

"R" AND "C" IN MAIN

R C

CONTROL CENTER

FACTORY WIRED TO "DB1"

IN MAIN CONTROL CENTER

LPS1 HPS1

CC1

CC2

LPS2 HPS2

COMPRESSOR INTERLOCKSR11

R10

CF1

A2

A2

A2

A1

A1

A1

CONDENSING FAN 1

COMPRESSOR 2CC2

A2 A1

COMPRESSOR 1CC1

A2 A1

R11

11 14

R10

11 14

13 14

13 14

54 55

CF1 O.L

TB TB

COMPRESSOR INTERLOCKS

RC2

11 14

RC1

11 14

RC1, RC2 CONTACTS

LOCATED ON MAIN

CONTROL BOARD

COMPRESSOR 2

CC2

CF1

COMPRESSOR 1

CC1

CONDENSING

FAN 1

M8

M7

M6 T2

T3

T1

L2

L3

L1

T2

T3

T1

L2

L3

L1

T2

T3

T1

L2

L3

L1

G621100XX0000PS14

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 12 of 39

QTY WIDTH HEIGHT

1 41 in. 39 in.

Width

Height

5 in.

1.25 in.

max.

(typical)

Channel Frame

The model VCD-33 is a low leakage control damper for application as an automatic control or manual balancing damper. This model is intended for applications in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators are available. Non-jackshafted dampers will be supplied with a blade drive lever for internal actuator mounting. When external actuator mounting is specified, an extension pin with clip kit will be provided. Note: The extension pin with clip kit includes the extension pin and clip.

Notes: All dimensions shown are in units of inches. Width & Height furnished approximately 0.25 under size. Installation instructions available at www.greenheck.com. Customer supplied actuators configured with a jackshaft will be provided with a jackshaft this is one inch in diameter.

Application & Design

Ratings Pressure: Up to 10 in. wg pressure differential Velocity: 4,000 ft/min Leakage: Class 1A @ 1 in. wg, Class 1 @ up to 8 in. wg Temperature: Up to 250F

OUTLET DAMPER

**NOTE: Width and Height are shown in nominal dimensions**

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 13 of 39

Corner Weights 686 lb 739 lb

563 lb 607 lb

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 14 of 39

TSCP - Remote Control Panel

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUCTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

Template Drawing: T02 DOC NUMBER: ---- REV: ----

BLOWER

50 60 70 80 90

HEAT

COOL

SUMMER OFF WINTER

13.50"

10.34" 4.50"

TSCP

REMOTE CONTROL PANEL G4BC11X1XA1AXXT02

Standard Construction Features And Notes Location of switches, lights and controls may vary.

All dimensions shown are in units of inches.

Galvanized steel with baked enamel finish.

Numbered terminal strip to match unit wiring.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 15 of 39

Remote Panel Wiring Requirements

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUCTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

Template Drawing: T02 DOC NUMBER: ---- REV: ----

G

G

G

BLOWER LIGHT

HEAT LIGHT

COOL LIGHT

R C

W1

Y1

RED

WHITE

YELLOW

BLACK

WHITE

WHITE

GYELLOW

THERMOSTAT**

ROOM OVERRIDE

S5 32BLUE BLUE

WINTER

SUMMER

OFF

SUMMER/OFF/WINTER SWITCH

Y1

W1

ORANGE

BLACK

WINTER

SUMMER

OFFS2

GYELLOW

G4WC11X1XA1AXXT02

The wiring drawings details the number of the wires and the type of wire that needs to be run from the unit control center to the panel. A detailed wiring schematic will be provided with the panel when the unit ships.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 16 of 39

SEQUENCE OF OPERATIONS

Unit Controls The unit shall be provided from the factory with:

• 24VAC Transformer

• Terminal Strip

• Supply fan motor starter (contactor and overload)

• Factory provided, field installed supply air non-insulated outlet damper with actuator

• Remote Control Panel

• Phase Monitor

Remote Control Panel A Permatector coated NEMA-1 rated remote control panel shall be shipped loose to control the basic operation of the unit. The panel shall contain the following:

• Summer / Off / Winter Switch Summer: Supply fan is enabled, heat is disabled, and cooling is enabled.

Off: Supply fan is disabled.

Winter: Supply fan is enabled, heat is enabled, and cooling is disabled.

• Blower Light

• Heat Light

• Cool Light

• Supply temperature set point dial.

• Room override thermostat

Unit Start-Up Sequence

• Supply Fan Enable Is Received

• Supply air outlet damper actuator is energized

• Supply air outlet damper actuator limit switch is proven closed

• Supply Fan Is Enabled

Supply Fan Sequence The supply fan is configured for constant volume operation. The fan speed is set to the design fan RPM at the factory through the use of belts and sheaves. Adjustment or replacement of belts/sheaves is necessary to balance the supply airflow. The supply fan speed is not to be modulated.

Heating Control A heating enable signal must be present and the supply fan must enabled before the unit will enable heating.

Heating Inlet Air Sensor (Heating Lockout) The heating will be locked out when the outside air temperature is above the heating inlet air sensor set point (typical 65 F, adj.)

Indirect Gas Fired Heating (Modulating Control) A Programmable Logic Controller (PLC) furnace controller shall modulate the furnace to maintain a supply air temperature set point. The controller shall include a LCD display and keypad for changing set points and monitoring furnace operation. A built-in commissioning sequence assists with proper and accurate start-up.

This controller is responsible for furnace control only and does not control any other function of the unit.

Additionally it has no Building Management System (BMS) communication capability. The supply temperature set point shall be controlled as follows:

Discharge Temperature Control The heating supply temperature set point must be set locally at the controller.

Room Override A room override thermostat shall elevate the supply air temperature set point 5 F-40 F (adj.) upon a call for heat from the space.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 17 of 39

Cooling Control A cooling enable signal must be present and the supply fan must be enabled before the unit will enable cooling.

Cooling Inlet Air Sensor (Cooling Lockout) The cooling will be locked out when the outside air temperature is below the cooling inlet air sensor set point (typical 80 F, adj.)

Packaged DX Cooling The packaged DX cooling system is provided with 2 refrigerant circuits each with a standard scroll compressor. Cooling is staged on and off based upon the outside air temperature:

• Stage 1 is enabled at 85 F (adj.)

• Stage 2 is enabled at 95 F (adj.)

• Stage 2 is disabled at 90 F (adj.)

• Stage 1 is disabled at 80 F (adj.)

• In Variable Air Volume applications a supply air temperature sensor disables the second stage of cooling when supply air falls below 55 F (adj.). The second stage of cooling is allowed to re-energize when supply air temperature rises above 75 F (adj.).

Building Freeze Protection If the supply air temperature drops below 35 F for 300s (adj.), the supply fan will be disabled. Cycling the fan enable will reset the timer. This sequence is intended to prevent the unit from supply cold air into the building.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 18 of 39

Warranty Statement for Make-Up Air

Unit Warranty Greenheck warrants the equipment to be free from defects in material and workmanship for a period of 1 year (standard) from the shipment date.

Heat Exchanger Extended Warranty Greenheck warrants the stainless steel heat exchanger to be free from defects in material and workmanship for a period of 5 years from the shipment date.

Warranty Notes Any component which proves defective during the warranty period will be repaired or replaced at Greenheck’s sole option when returned to our factory, transportation prepaid. All warranties do not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. These warranties are exclusive and are in lieu of all other warranties, whether written, oral, or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose. No person (including any agent or salesperson) has authority to expand Seller's obligation beyond the terms of this warranty, or to state that the performance of the product is other than that published by Seller.

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.

Tempered Air Products (TAP) Statement 2018

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-1Mark:

IGX-112-H22-10-LModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 19 of 39

IGX-115-H32-16-O

Unit Performance

Design Conditions

Elevation (ft) Summer Winter (°F) Supply (CFM) Outdoor Air (CFM)DB (°F) WB (°F) 1,027 93.8 77.2 20.7 6,900 6,900

Unit Specifications Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing Furnace ETL Listing

2 3,906 (+/- 5%) Packaged DX Indirect Gas Furnace Outdoor UL / cUL 1995 ANSI Z83.8 / CSA 2.6

Configuration Unit Orientation Unit Configuration Outdoor Air Intake Return Air Intake Supply Air Discharge

Horizontal Constant Volume 100% OA End - End

Cooling Specifications

Type Refrigerant Capacity (MBH) Lead Compressor

Type EER Performance (DB/WB)

Total Sensible Condensing Section

Design Condition EAT (°F) LAT (°F)

Packaged DX R-410a 208.6 131.3 Standard Scroll 12.2 13.2 93.8 / 77.2 76.5 / 69.8

Heating Specifications

Type Gas Type

Gas Pressure Capacity (MBH) Temperature Rise Turndown

Performance Min

(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT

(°F)

LAT

(°F)

Indirect Gas Furnace Natural 6 0.5 600.0 480.0 8.0 64.4 8:1 21.0 85.1

Air Performance

Type Total

Volume

(CFM)

External SP

(in. wg)

Total SP

(in. wg) RPM Operating

Power (hp) Fan

Qty Type Size (in.) Drive-Type Supply 6,900 1.8 2.525 1228 7.09 1 Forward Curve 15 Belt-Drive

Motor Specifications Motor Qty Size (HP) Enclosure Efficiency RPM

Supply Fan Motor 1 7-1/2 ODP NEMA Premium 1725

Electrical Specifications Power Supply Rating (V/C/P) MCA (A) MOP (A)

Unit 460/60/3 43.2 50

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 20 of 39

CONSTRUCTION FEATURES AND ACCESSORIES

Unit Unit Installation - Outdoor Std Unit Construction - Double Wall X Wall Insulation - 1in. fiberglass - Cool source on X Base Insulation - 1in. fiberglass - entire unit base pan Std Paneled Bottom - Sheet metal liner for base insulation Corrosion Resistant Fasteners Std Access and Connections - Right side when facing intake X Service Access - Hinged access doors X Unit Finish - Permatector ASTM B117 salt spray 2500 hours X Finish Color - Concrete Gray (RAL 7023) X Supply Fan - Belt-drive, forward-curved X Supply Fan and Motor Vibration isolation - Neoprene X

Controls Unit Controls - Terminal strip with remote panel X Remote Panel - Industrial (NEMA-1) X BMS Communication BMS Protocol Temperature Control X Supply Fan VFD Supply Fan Control Melink/Vari-Flow wiring package Recirculation Control Unoccupied Mode (Night Setback)

Control Accessories Remote display Heating Inlet Air Sensor X Cooling Inlet Air Sensor X Dirty Filter Switch Fire Stat Type III (Ships loose) 120V/24V Smoke Detector (Ships loose) Inlet Damper End Switch External Cooling Lockout Relay Freeze Protection (Supply Air Low Limit) X Auxiliary Supply Starter Contacts - Qty 1 X Auxiliary Exhaust Starter Contacts Airflow Proving Monitoring Contact

Accessories Factory Installed, Lockable, NEMA 3R Disconnect Std Weatherhood - Aluminum Mesh filtered X Supply Air Filters - 2" aluminum, 20x25x2 - (10) X Outdoor Air Inlet Damper Supply Air Outlet Damper - Low leakage X Return Air Damper Diffuser Roof Curb Combination Curb Electrofin Coil Coating Fan Bearing Extended Lube Lines Inlet Damper Module Spare Belts Spare Filters Motor with Shaft Grounding Service Outlet Service Lights

Gas Heating Accessories Furnace Venting - Outdoor X Venting Type - Power vented Std Furnace Venting Method - Standard X Concentric Venting Adapter Direct Spark Ignition Std Flame Sensing - Flame rod Std Heat Exchanger Material - Stainless steel X Furnace Controls - 8:1 Modulating X Agency Approval - ETL and IRI Std External Gas Pressure Regulator (Ships loose) X DDC Assisted Furnace Commisioning X

Warranty Options Unit Warranty - 1 Year X 5 Year Compressor Warranty 5 Year Heat Exchanger Warranty X 10 Year Heat Exchanger Warranty

Standard Option Std Not Included

Included X

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 21 of 39

Fan Charts And Performance

Supply Fan Performance

Total Volume

(CFM)

External SP

(in. wg)

Total SP

(in. wg) RPM Operating

Power (hp) Motor Fan

Qty Size (HP) Qty Type Drive-Type

6,900 1.8 2.525 1228 7.09 1 7-1/2 1 Forward Curve Belt

Pressure Drop (in. wg) Weatherhood Filter Damper Cooling Heating External Total

0.099 0.029 0.036 0.62 0.203 1.8 2.525

Sound Performance in Accordance with AMCA Sound Power by Octave Band Lwa dBA Sones62.5 125 250 500 1000 2000 4000 8000

93 100 93 90 86 81 78 73 92 81 41

Supply Fan

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 22 of 39

Cooling Specifications

Cooling Performance

Type Refrigerant Capacity (MBH) Lead Compressor

Type EER Performance (DB/WB)

Total Sensible Condensing Section

Design Condition EAT (°F) LAT (°F)

Packaged DX R-410a 208.6 131.3 Standard Scroll 12.2 13.2 93.8 / 77.2 76.5 / 69.8

Coil Information

PDX Coil Model Fins Per Inch Rows Deep Suction Temp. (°F)

Face Velocity (ft/min)

Refrigerant Velocity (ft/min)

DX38S02H10-36x54 10 2 47.2 511 1,549

Unit Details Refrigerant charges provided by the factory are approximate and may require field adjustment Refrigeration components servicable without affecting airflow Hermetic scroll type compressor(s) Compressor(s) mounted on neoprene vibration isolation Crankcase heater on compressor(s) Liquid-line filter drier Moisture-indicating sight glass

Thermal expansion valve Refrigerant low pressure switch (auto reset) Refrigerant high pressure switch (manual reset) Service/charging valves Low sound, direct drive condensing fans Insulated, double sloped, stainless steel drain pan Copper tube, aluminum fin coil construction

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 23 of 39

Heating Specifications

Heating Performance

Type Gas Type

Gas Pressure Capacity (MBH) Temperature Rise Turndown

Performance Min

(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT

(°F)

LAT

(°F)

Indirect Gas Furnace Natural 6 0.5 600.0 480.0 8.0 64.4 8:1 21.0 85.1

Heating Information

Heat Exch. Material Venting Venting Method Gas Pressure Regulators

Heat Exchanger Warranty

Stainless Steel Outdoor Standard 10 PSI 5 Year

Unit Details ANSI Standard Z83.8 and CSA 2.6 Direct Spark Ignition Stainless Steel Heat Exchanger Tubes

Power Venting 24 Volt Control Power 5 year heat exchanger warranty

Gas Connections

3/4" NPT GAS

CONNECTION

48.723

8.480

8.486

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 24 of 39

ELEVATION VIEW

48.678 25.750 70.071 65.948 66.384

48.723

Notes - Elevation View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.

Order of unit sections is from intake of unit to discharge of unit.

Sections included on this unit: Weatherhood Section, Filter Section, Cooling Section, Blower Section, Furnace 1 Section, Furnace 2 Section Insulation: Double Wall, from Cooling Section through end of unit.

PLAN VIEW

INTAKE V-BANK FILTER

ACCESS

SIDE

ACCESS SIDE

PDX COOLING

BLOWER

ACCESS SIDE

FURNACE

ACCESS SIDEACCESS SIDE

48.678 25.750

69.973

134.098

65.948

52.166

66.384

Notes - Plan View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 25 of 39

END VIEW

SUPPLY

DUCT

30.000

16.899

1.17541.000

52.16612.565 35.340

FOOTPRINT VIEW

199.500

CURB LENGTH

RECOMMENDED

48.500

CURB WIDTH

RECOMMENDED

Notes - Footprint View Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides. For example: If the duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.

Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb. For example: If the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.

The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design, to prevent water infiltration.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 26 of 39

Electrical Connections

ELECTRICAL

CONNECTION

15.000

63.997

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 27 of 39

Clearance Specifications

Recommended Minimum Combustible Clearances Floor (in.) Top (in.) Sides (in.) Ends (in.)

Indirect Fired Units 0 0 0 0

Notes - Combustible Clearances Clearance to combustibles is defined as the minimum distance required between the heating source and the adjacent combustible surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the ambient temperature.

Reference venting guidelines for combustion blower clearances.

Recommended Minimum Service Clearances Housing 32 and less (in.) Housing 35 and higher (in.)

42 on the controls side of the unit N/A

Notes - Service Clearances To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances should be 6 in. wider than the width of the module itself.

Reference the PDX Service Clearance guidelines (PDX IOM)

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 28 of 39

Wiring Diagram

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUCTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

G

SDF

RT4 FREEZE PROTECTION

S4

HEAT ENABLE

TO IG FURNACE

RH

A2

A1

POST HEAT

Template Drawing: U10

SUPPLY FAN

MOTOR

ST1 O.L.

11 14

RT4

11 12

RT4

ST1 O.L.

CONTROL

COM NO

D2L

OFF

OUTLET DAMPERD2

ST1

A2 A1

SUPPLY FAN

RF

TS5

COM NO

THERMOSTAT CONTROLLER(S)24 VAC

OA-SENSOR

SENSOR COM

A2 A1

L3

L2

L1

DS1

M1

RF

A2 A1

SUPPLY FAN RELAY

RF

Y1

A2 A1

COOLING

TO 111 & 112 IN

FURNACE 1

, TS6

DB1

CC# COMPRESSOR CONTACTOR

CF1 CONDENSER FAN CONTACTOR

CH# CRANK CASE HEATER

D2 OUTLET DAMPER

D2L OUTLET DAMPER LIMIT

DS1 MAIN DISCONNECT SWITCH

FSC FIRE SYSTEM CONTACT

FU# FUSE

HLC HIGH LIMIT CONTROL

HPS HIGH PRESSURE SWITCH

LPS LOW PRESSURE SWITCH

M# MOTOR

OL# MOTOR OVERLOAD

PM PHASE MONITOR

R10 COMP#1 INTERLOCK RELAY

R11 COMP#2 INTERLOCK RELAY

RC1 COOLING STAGE 1 RELAY

RC2 COOLING STAGE 2 RELAY

RF SUPPLY FAN RELAY

RH HEAT RELAY

RT4 FREEZE PROTECTION TIMER

SWITCH 1 and 4 DOWN - 2 and 3 UP / DIAL SET TO 4

S2 FAN SWITCH

S4 HEAT AND COOL SWITCH

S5 ROOM OVERRIDE

SDF SENSOR DISCHARGE - FREEZE

ST# MOTOR STARTER

TR# TRANSFORMER

TS5 INLET AIR SENSOR - COOL

JUMPER = COOL : DIFFERENTIAL = 5

TS6 INLET AIR SENSOR - COOL

JUMPER = COOL : DIFFERENTIAL = 5 : OFFSET = 10

GROUND

TO UNIT

MAIN POWER

460V

S2 FSC

TR1

CR

USER INDIRECT GAS FURNACE INTERFACE CONNECTIONS:

ROOM OVERRIDE CONNECTION

31 32

S5

FACTORY WIRED TO TERMINAL "32"

IN IG FURNACE COMPARTMENT

75 VA

MOUNTED IN END

FURNACE

111 112

T3

T2

T1

24V

ST1

W1

PM

11 14

PM L2

L1

L3

L1 T1

L2 T2

L3 T3

THERMOSTAT(S) TS5

DOC NUMBER: ---- REV: ----

FACTORY WIRED

TO "CC1" IN

COOLING MODULE

CONTROL CENTER

RC1

TS6

COM NO A2 A1

COOLING STAGE 2RC2

STAGE 1

RC1

RC2

14 CONTROL CENTER

TO R11 (11) IN COOLING MODULE

CONTROL CENTER

TO R10 (11) IN COOLING MODULE

IN COOLING MODULE

TO "R"

CONTROL CENTER

TO "C"

21 24

RT4

GI24C602A043G70AU10

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 29 of 39

Furnace Wiring Diagram

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

Wiring Template: S14

VALVE

IC1

(VLV/24V)

HLC

NO

PS2

24V

TH

PSW SPARKSPARK

SENSORSENSE

X

TR5

INDIRECT GAS WIRING DIAGRAM

C

40 VA

24VAC

GND

R2

HEAT

RELAY

R3

HEAT

RELAY

FURNACE 2

4:1 MODULATING

NO

T3

C

MV

HI

C

LO

T3

B

IN MAIN CONTROL CENTER

FURNACE 1 - 2 STAGE

FACTORY WIRED

S

AYELLOW

LT. BLUE

BROWN

Y E

LL

O

W

LT

. B

LU

E

B R

O W

N

IG FURNACE WIRING

OFF BOARD WIRING

BASAAA

CM

CR

A2 A1

CR

L1

L3 T3

T1

TO TERMINALS "111" AND "112"

112111

112111

120/240V

BLWR

GND

(LINE)

(N.O.)

(BURNER)

CM COMBUSTION BLOWER MOTOR

CR COMBUSTION BLOWER RELAY

HLC HIGH TEMPERATURE LIMIT CONTROL

IC1 IGNITION CONTROL

MV MAIN GAS VALVE

PS2 COMBUSTION AIR PROVING SWITCH

T3 HIGH FIRE TIMER

TR# TRANSFORMER(S)

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

DOC NUMBER: ---- REV: ----

G6LX4P1MX1000GS14

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 30 of 39

Furnace 2 Wiring Diagram

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

Wiring Template: S14

TO TERMINALS "111" AND "112"

FACTORY WIRED

IN FURNACE 1

NO3

NO4

R2 A1A2

R3 A1A2

BROWN

ORANGE

FURNACE 2 - 4:1 MODULATING

11 14

R3

BROWN

SB

11 14

R2

YELLOWLT. BLUE

A

FURNACE 1 FURNACE 2

2 STAGE 4:1 MODULATING

IG FURNACE WIRING

OFF BOARD WIRING

AIRFLOW

112111

INDIRECT GAS WIRING DIAGRAM

TR5

FU8

120V 24V

250VA

FU9

IR

CM

12 11

HIGH

LOW

RED

BLACK

WHITE

WHITE

BLUE

BLUE

BA SA AA

RH

HEAT

ENABLE

MAIN CONTROL CENTER

ORANGE

PURPLE

BLACK

BLACK

S5

ROOM

OVERRIDE

CM COMBUSTION BLOWER MOTOR

FU# FUSE(S)

HLC HIGH TEMPERATURE LIMIT CONTROL

IC1 IGNITION CONTROL

IR INDUCTION RELAY

MDV MODULATING VALVE

MV MAIN GAS VALVE

PS2 COMBUSTION AIR PROVING SWITCH

PS5 HIGH SPEED PRESSURE SWITCH

R2 FURNACE 1 STAGE 1 HEAT RELAY

R3 FURNACE 1 STAGE 2 HEAT RELAY

R5 MAIN GAS VALVE MONITORING

R6 LOW SPEED PRESSURE SWITCH

R7 IGNITION CONTROLLER ALARM MONITORING

SC1 STAGE CONTROLLER

TR# TRANSFORMER(S)

TS1 OUTDOOR AIR TEMP SENSOR

TS2 DISCHARGE AIR TEMP SENSOR

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

GND

MV MV

MV

PS2

HLC

(VLV/24V)

PSW

TH

VALVE

IC1

24V

SENSOR

SPARKSPARK

SENSE

BLWR

MDV

120/240V

IR

A1A2

SC1

C1/2

GO

NO1

NO2

G

U10

GND

U1

PS5

ON

NOC

NOC

BLACK

BROWN

PURPLE

RED

PURPLE

BLUE

YELLOW

WHITE

RED

LT. BLUE

WHITE

WHITE

RED

W H

IT

E P

IN

K

U4ORANGE

PURPLE U8

O

RED

OFF

WHITE

GND

(LINE) (BURNER)

(N.O.)

24V+ _

ALARM YELLOW R7

A1A2

WHITE

R5 A1A2

WHITE

R6 A1A2

WHITE

GND

U2

U5

U3

U6 RED

U7 BROWN

U9 PINK

11 14

R5

WHITE

11 14

R6

WHITE

11 14

R7

WHITE

SIG+ _

ORANGE

BLUE

TS1

TS2

WHITE

WHITE

GND

FU8/9 3A,250V

SUPPLEMENTARY

BUSSMANN FNM-3

FU7

2A,600V

CLASS

CC

C3/4/5

C6

RED

GS XE

DDC Code: Version - IGFv1.02

XR

DOC NUMBER: ---- REV: ----

R8 A1A2

WHITE

R8

RED LT. BLUE

G6L12P1MX1000GS14

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 31 of 39

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

Wiring Template: S14

CC# COMPRESSOR CONTACTOR

CF# CONDENSER FAN CONTACTOR

CH# CRANK CASE HEATER

DB1 DISTRIBUTION BLOCK

HPS# HIGH PRESSURE SWITCH

LPS# LOW PRESSURE SWITCH

M# MOTOR

R# CONTROL RELAY

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

DOC NUMBER: ---- REV: ----

PDX WIRING DIAGRAM

CH1 CH2

R C

DB1

FACTORY WIRED TO TERMINAL

"R" AND "C" IN MAIN

R C

CONTROL CENTER

FACTORY WIRED TO "DB1"

IN MAIN CONTROL CENTER

LPS1 HPS1

CC1

CC2

LPS2 HPS2

COMPRESSOR INTERLOCKSR11

R10

CF1

A2

A2

A2

A1

A1

A1

CONDENSING FAN 1 & 2

COMPRESSOR 2CC2

A2 A1

COMPRESSOR 1CC1

A2 A1

R11

11 14

R10

11 14

13 14

13 14

54 55

CF2 O.L

TB TB

58 59

CF1 O.L

TB TB

COMPRESSOR INTERLOCKS

RC2

11 14

RC1

11 14

RC1, RC2 CONTACTS

LOCATED ON MAIN

CONTROL BOARD

COMPRESSOR 2

CC2

CF1

COMPRESSOR 1

CC1

CONDENSING

FAN 1

M8

M7

M6

CONDENSING

FAN 2

M9

T2

T3

T1

L2

L3

L1

T2

T3

T1

L2

L3

L1

T2

T3

T1

L2

L3

L1

G622100XX0000PS14

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 32 of 39

QTY WIDTH HEIGHT

1 41 in. 30 in.

Width

Height

5 in.

1.25 in.

max.

(typical)

Channel Frame

The model VCD-33 is a low leakage control damper for application as an automatic control or manual balancing damper. This model is intended for applications in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators are available. Non-jackshafted dampers will be supplied with a blade drive lever for internal actuator mounting. When external actuator mounting is specified, an extension pin with clip kit will be provided. Note: The extension pin with clip kit includes the extension pin and clip.

Notes: All dimensions shown are in units of inches. Width & Height furnished approximately 0.25 under size. Installation instructions available at www.greenheck.com. Customer supplied actuators configured with a jackshaft will be provided with a jackshaft this is one inch in diameter.

Application & Design

Ratings Pressure: Up to 10 in. wg pressure differential Velocity: 4,000 ft/min Leakage: Class 1A @ 1 in. wg, Class 1 @ up to 8 in. wg Temperature: Up to 250F

OUTLET DAMPER

**NOTE: Width and Height are shown in nominal dimensions**

Manufacturer reserves right to change, alter, or improve this product at any time.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 33 of 39

Corner Weights 1,100 lb 1,116 lb

839 lb 852 lb

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 34 of 39

TSCP - Remote Control Panel

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUCTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

Template Drawing: T02 DOC NUMBER: ---- REV: ----

BLOWER

50 60 70 80 90

HEAT

COOL

SUMMER OFF WINTER

13.50"

10.34" 4.50"

TSCP

REMOTE CONTROL PANEL G4BC11X1XA1AXXT02

Standard Construction Features And Notes Location of switches, lights and controls may vary.

All dimensions shown are in units of inches.

Galvanized steel with baked enamel finish.

Numbered terminal strip to match unit wiring.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 35 of 39

Remote Panel Wiring Requirements

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUCTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.

FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.

FIELD WIRED

FACTORY SUPPLIED AND WIRED

GREENHECK

WIRE COLOR CODE

Building Value in Air.

Wiring Diagram Code:

BK BLACK BL BLUE BR BROWN

GY GRAY LT BL LIGHT BLUE O ORANGE

PK PINK PR PURPLE R RED

W WHITE Y YELLOW

Template Drawing: T02 DOC NUMBER: ---- REV: ----

G

G

G

BLOWER LIGHT

HEAT LIGHT

COOL LIGHT

R C

W1

Y1

RED

WHITE

YELLOW

BLACK

WHITE

WHITE

GYELLOW

THERMOSTAT**

ROOM OVERRIDE

S5 32BLUE BLUE

WINTER

SUMMER

OFF

SUMMER/OFF/WINTER SWITCH

Y1

W1

ORANGE

BLACK

WINTER

SUMMER

OFFS2

GYELLOW

G4WC11X1XA1AXXT02

The wiring drawings details the number of the wires and the type of wire that needs to be run from the unit control center to the panel. A detailed wiring schematic will be provided with the panel when the unit ships.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 36 of 39

SEQUENCE OF OPERATIONS

Unit Controls The unit shall be provided from the factory with:

• 24VAC Transformer

• Terminal Strip

• Supply fan motor starter (contactor and overload)

• Factory provided, field installed supply air non-insulated outlet damper with actuator

• Remote Control Panel

• Phase Monitor

Remote Control Panel A Permatector coated NEMA-1 rated remote control panel shall be shipped loose to control the basic operation of the unit. The panel shall contain the following:

• Summer / Off / Winter Switch Summer: Supply fan is enabled, heat is disabled, and cooling is enabled.

Off: Supply fan is disabled.

Winter: Supply fan is enabled, heat is enabled, and cooling is disabled.

• Blower Light

• Heat Light

• Cool Light

• Supply temperature set point dial.

• Room override thermostat

Unit Start-Up Sequence

• Supply Fan Enable Is Received

• Supply air outlet damper actuator is energized

• Supply air outlet damper actuator limit switch is proven closed

• Supply Fan Is Enabled

Supply Fan Sequence The supply fan is configured for constant volume operation. The fan speed is set to the design fan RPM at the factory through the use of belts and sheaves. Adjustment or replacement of belts/sheaves is necessary to balance the supply airflow. The supply fan speed is not to be modulated.

Heating Control A heating enable signal must be present and the supply fan must enabled before the unit will enable heating.

Heating Inlet Air Sensor (Heating Lockout) The heating will be locked out when the outside air temperature is above the heating inlet air sensor set point (typical 65 F, adj.)

Indirect Gas Fired Heating (Modulating Control) A Programmable Logic Controller (PLC) furnace controller shall modulate the furnace to maintain a supply air temperature set point. The controller shall include a LCD display and keypad for changing set points and monitoring furnace operation. A built-in commissioning sequence assists with proper and accurate start-up.

This controller is responsible for furnace control only and does not control any other function of the unit.

Additionally it has no Building Management System (BMS) communication capability. The supply temperature set point shall be controlled as follows:

Discharge Temperature Control The heating supply temperature set point must be set locally at the controller.

Room Override A room override thermostat shall elevate the supply air temperature set point 5 F-40 F (adj.) upon a call for heat from the space.

07/31/2019Printed Date:

USDA SE Poultry with Packaged DXJob:

MUA-2Mark:

IGX-115-H32-16-OModel:

CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 37 of 39

Cooling Control A cooling enable signal must be present and the supply fan must be enabled before the unit will enable cooling.

Cooling Inlet Air Sensor (Cooling Lockout) The cooling will be locked out when the outside air temperature is below the cooling inlet air sensor set point (typical 80 F, adj.)

Packaged DX Cooling The packaged DX cooling system is provided with 2 refrigerant circuits each with a standard scroll compressor. Cooling is staged on and off based upon the outside air temperature:

• Stage 1 is enabled at 85 F (adj.)

• Stage 2 is enabled at 95 F (adj.)

• Stage 2 is disabled at 90 F (adj.)

• Stage 1 is disabled at 80 F (adj.)

• In Variable Air Volume applications a supply air temperature sensor disables the second stage of cooling when supply air falls below 55 F (adj.). The second stage of cooling is allowed to re-energize when supply air temperature rises above 75 F (adj.).

Building Freeze Protection If the supply air temperature drops below 35 F for 300s (adj.), the supply fan will be disabled. Cycling the fan enable will reset the timer. This sequence is intended to prevent the unit from supply cold air into the building.

07/31/2019Printed…