IGX-112-H22-10-L
Unit Performance
Design Conditions
Elevation (ft) Summer Winter (°F) Supply (CFM) Outdoor Air (CFM)DB (°F) WB (°F) 1,027 93.8 77.2 20.7 3,200 3,200
Unit Specifications Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing Furnace ETL Listing
2 2,596 (+/- 5%) Packaged DX Indirect Gas Furnace Outdoor UL / cUL 1995 ANSI Z83.8 / CSA 2.6
Configuration Unit Orientation Unit Configuration Outdoor Air Intake Return Air Intake Supply Air Discharge
Horizontal Constant Volume 100% OA End - End
Cooling Specifications
Type Refrigerant Capacity (MBH) Lead Compressor
Type EER Performance (DB/WB)
Total Sensible Condensing Section
Design Condition EAT (°F) LAT (°F)
Packaged DX R-410a 131.7 75.9 Standard Scroll 11.6 11.8 93.8 / 77.2 72.3 / 66.9
Heating Specifications
Type Gas Type
Gas Pressure Capacity (MBH) Temperature Rise Turndown
Performance Min
(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT
(°F)
LAT
(°F)
Indirect Gas Furnace Natural 6 0.5 350.0 280.0 20.2 81.0 4:1 21.0 101.7
Air Performance
Type Total
Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg) RPM Operating
Power (hp) Fan
Qty Type Size (in.) Drive-Type Supply 3,200 1.8 2.093 1199 2.05 1 Forward Curve 12 Belt-Drive
Motor Specifications Motor Qty Size (HP) Enclosure Efficiency RPM
Supply Fan Motor 1 5 ODP NEMA Premium 1725
Electrical Specifications Power Supply Rating (V/C/P) MCA (A) MOP (A)
Unit 460/60/3 27.8 35
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
Generated by: esmith@holdenassoc.com CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 1 of 39
CONSTRUCTION FEATURES AND ACCESSORIES
Unit Unit Installation - Outdoor Std Unit Construction - Double Wall X Wall Insulation - 1in. fiberglass - Cool source on X Base Insulation - 1in. fiberglass - entire unit base pan Std Paneled Bottom - Sheet metal liner for base insulation Corrosion Resistant Fasteners Std Access and Connections - Right side when facing intake X Service Access - Hinged access doors X Unit Finish - Permatector ASTM B117 salt spray 2500 hours X Finish Color - Concrete Gray (RAL 7023) X Supply Fan - Belt-drive, forward-curved X Supply Fan and Motor Vibration isolation - Neoprene X
Controls Unit Controls - Terminal strip with remote panel X Remote Panel - Industrial (NEMA-1) X BMS Communication BMS Protocol Temperature Control X Supply Fan VFD Supply Fan Control Melink/Vari-Flow wiring package Recirculation Control Unoccupied Mode (Night Setback)
Control Accessories Remote display Heating Inlet Air Sensor X Cooling Inlet Air Sensor X Dirty Filter Switch Fire Stat Type III (Ships loose) 120V/24V Smoke Detector (Ships loose) Inlet Damper End Switch External Cooling Lockout Relay Freeze Protection (Supply Air Low Limit) X Auxiliary Supply Starter Contacts - Qty 1 X Auxiliary Exhaust Starter Contacts Airflow Proving Monitoring Contact
Accessories Factory Installed, Lockable, NEMA 3R Disconnect Std Weatherhood - Aluminum Mesh filtered X Supply Air Filters - 2" aluminum, 20x20x2 - (6) X Outdoor Air Inlet Damper Supply Air Outlet Damper - Low leakage X Return Air Damper Diffuser Roof Curb Combination Curb Electrofin Coil Coating Fan Bearing Extended Lube Lines Inlet Damper Module Spare Belts Spare Filters Motor with Shaft Grounding Service Outlet Service Lights
Gas Heating Accessories Furnace Venting - Outdoor X Venting Type - Power vented Std Furnace Venting Method - Standard X Concentric Venting Adapter Direct Spark Ignition Std Flame Sensing - Flame rod Std Heat Exchanger Material - Stainless steel X Furnace Controls - 4:1 Modulating X Agency Approval - ETL and IRI Std External Gas Pressure Regulator (Ships loose) X DDC Assisted Furnace Commisioning X
Warranty Options Unit Warranty - 1 Year X 5 Year Compressor Warranty 5 Year Heat Exchanger Warranty X 10 Year Heat Exchanger Warranty
Standard Option Std Not Included
Included X
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 2 of 39
Fan Charts And Performance
Supply Fan Performance
Total Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg) RPM Operating
Power (hp) Motor Fan
Qty Size (HP) Qty Type Drive-Type
3,200 1.8 2.093 1199 2.05 1 5 1 Forward Curve Belt
Pressure Drop (in. wg) Weatherhood Filter Damper Cooling Heating External Total
0.042 0.028 0.01 0.256 0.026 1.8 2.093
Sound Performance in Accordance with AMCA Sound Power by Octave Band Lwa dBA Sones62.5 125 250 500 1000 2000 4000 8000
82 73 75 72 73 66 65 54 76 65 13.1
Supply Fan
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 3 of 39
Cooling Specifications
Cooling Performance
Type Refrigerant Capacity (MBH) Lead Compressor
Type EER Performance (DB/WB)
Total Sensible Condensing Section
Design Condition EAT (°F) LAT (°F)
Packaged DX R-410a 131.7 75.9 Standard Scroll 11.6 11.8 93.8 / 77.2 72.3 / 66.9
Coil Information
PDX Coil Model Fins Per Inch Rows Deep Suction Temp. (°F)
Face Velocity (ft/min)
Refrigerant Velocity (ft/min)
DX38S02S10-30x44 10 2 44.1 349 1,906
Unit Details Refrigerant charges provided by the factory are approximate and may require field adjustment Refrigeration components servicable without affecting airflow Hermetic scroll type compressor(s) Compressor(s) mounted on neoprene vibration isolation Crankcase heater on compressor(s) Liquid-line filter drier Moisture-indicating sight glass
Thermal expansion valve Refrigerant low pressure switch (auto reset) Refrigerant high pressure switch (manual reset) Service/charging valves Low sound, direct drive condensing fans Insulated, double sloped, stainless steel drain pan Copper tube, aluminum fin coil construction
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 4 of 39
Heating Specifications
Heating Performance
Type Gas Type
Gas Pressure Capacity (MBH) Temperature Rise Turndown
Performance Min
(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT
(°F)
LAT
(°F)
Indirect Gas Furnace Natural 6 0.5 350.0 280.0 20.2 81.0 4:1 21.0 101.7
Heating Information
Heat Exch. Material Venting Venting Method Gas Pressure Regulators
Heat Exchanger Warranty
Stainless Steel Outdoor Standard 10 PSI 5 Year
Unit Details ANSI Standard Z83.8 and CSA 2.6 Direct Spark Ignition Stainless Steel Heat Exchanger Tubes
Power Venting 24 Volt Control Power 5 year heat exchanger warranty
Gas Connections
3/4" NPT GAS
CONNECTION
44.924
8.375
7.318
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 5 of 39
ELEVATION VIEW
47.139 24.086 59.598 52.238 33.196
44.924
Notes - Elevation View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
Order of unit sections is from intake of unit to discharge of unit.
Sections included on this unit: Weatherhood Section, Filter Section, Cooling Section, Blower Section, Furnace 1 Section Insulation: Double Wall, from Cooling Section through end of unit.
PLAN VIEW
INTAKE V-BANK FILTER
ACCESS SIDE
PDX COOLING
ACCESS SIDE
BLOWER
ACCESS SIDE
FURNACE
ACCESS SIDE
47.139 24.086
59.598
94.195
52.238
33.196
53.874
Notes - Plan View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 6 of 39
END VIEW
SUPPLY
DUCT
0.67041.000
39.000
3.875
44.12510.063 32.142
FOOTPRINT VIEW
142.250
CURB LENGTH
RECOMMENDED
40.500
CURB WIDTH
RECOMMENDED
Notes - Footprint View Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides. For example: If the duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.
Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb. For example: If the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.
The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design, to prevent water infiltration.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 7 of 39
Electrical Connections
ELECTRICAL
CONNECTION
15.000
50.250
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 8 of 39
Clearance Specifications
Recommended Minimum Combustible Clearances Floor (in.) Top (in.) Sides (in.) Ends (in.)
Indirect Fired Units 0 0 0 0
Notes - Combustible Clearances Clearance to combustibles is defined as the minimum distance required between the heating source and the adjacent combustible surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the ambient temperature.
Reference venting guidelines for combustion blower clearances.
Recommended Minimum Service Clearances Housing 32 and less (in.) Housing 35 and higher (in.)
42 on the controls side of the unit N/A
Notes - Service Clearances To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances should be 6 in. wider than the width of the module itself.
Reference the PDX Service Clearance guidelines (PDX IOM)
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 9 of 39
Wiring Diagram
CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
G
SDF
RT4 FREEZE PROTECTION
S4
HEAT ENABLE
TO IG FURNACE
RH
A2
A1
POST HEAT
Template Drawing: U10
SUPPLY FAN
MOTOR
ST1 O.L.
11 14
RT4
11 12
RT4
ST1 O.L.
CONTROL
COM NO
D2L
OFF
OUTLET DAMPERD2
ST1
A2 A1
SUPPLY FAN
RF
TS5
COM NO
THERMOSTAT CONTROLLER(S)24 VAC
OA-SENSOR
SENSOR COM
A2 A1
L3
L2
L1
DS1
M1
RF
A2 A1
SUPPLY FAN RELAY
RF
Y1
A2 A1
COOLING
TO 111 & 112 IN
FURNACE 1
DB1
CC# COMPRESSOR CONTACTOR
CF1 CONDENSER FAN CONTACTOR
CH# CRANK CASE HEATER
D2 OUTLET DAMPER
D2L OUTLET DAMPER LIMIT
DS1 MAIN DISCONNECT SWITCH
FSC FIRE SYSTEM CONTACT
FU# FUSE
HLC HIGH LIMIT CONTROL
HPS HIGH PRESSURE SWITCH
LPS LOW PRESSURE SWITCH
M# MOTOR
OL# MOTOR OVERLOAD
PM PHASE MONITOR
R10 COMP#1 INTERLOCK RELAY
R11 COMP#2 INTERLOCK RELAY
RC1 COOLING STAGE 1 RELAY
RC2 COOLING STAGE 2 RELAY
RF SUPPLY FAN RELAY
RH HEAT RELAY
RT4 FREEZE PROTECTION TIMER
SWITCH 1 and 4 DOWN - 2 and 3 UP / DIAL SET TO 4
S2 FAN SWITCH
S4 HEAT AND COOL SWITCH
S5 ROOM OVERRIDE
SDF SENSOR DISCHARGE - FREEZE
ST# MOTOR STARTER
TR# TRANSFORMER
TS5 INLET AIR SENSOR - COOL
JUMPER = COOL : DIFFERENTIAL = 5
TS6 INLET AIR SENSOR - COOL
JUMPER = COOL : DIFFERENTIAL = 5 : OFFSET = 10
GROUND
TO UNIT
MAIN POWER
460V
S2 FSC
TR1
CR
USER INDIRECT GAS FURNACE INTERFACE CONNECTIONS:
ROOM OVERRIDE CONNECTION
31 32
S5
FACTORY WIRED TO TERMINAL "32"
IN IG FURNACE COMPARTMENT
75 VA
111 112
T3
T2
T1
MOUNTED IN
FURNACE
24V
ST1
W1
PM
11 14
PM L2
L1
L3
L1 T1
L2 T2
L3 T3
THERMOSTAT(S) TS5 , TS6
DOC NUMBER: ---- REV: ----
FACTORY WIRED
TO "CC1" IN
COOLING MODULE
CONTROL CENTER
RC1
TS6
COM NO A2 A1
COOLING STAGE 2RC2
STAGE 1
RC1
RC2
14 CONTROL CENTER
TO R11 (11) IN COOLING MODULE
CONTROL CENTER
TO R10 (11) IN COOLING MODULE
IN COOLING MODULE
TO "R"
CONTROL CENTER
TO "C"
21 24
RT4
GI14C602A043F70AU10
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 10 of 39
Furnace Wiring Diagram
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
Wiring Template: S14
IR
CM
12 11
HIGH
LOW
RED
BLACK
TR5
FU8
120V 24V
WHITE
250VA
FU9
IG FURNACE WIRING
BOARD WIRING
FURNACE 1 - 4:1 MODULATING
TO TERMINALS "111" AND "112"
FACTORY WIRED
IN MAIN CONTROL CENTER
112111
INDIRECT GAS WIRING DIAGRAM
WHITE
BLUE
BLUE
RH
HEAT
ENABLE
MAIN CONTROL CENTER
ORANGE
PURPLE
BLACK
BLACK
S5
ROOM
OVERRIDE
CM COMBUSTION BLOWER MOTOR
FU# FUSE(S)
HLC HIGH TEMPERATURE LIMIT CONTROL
IC1 IGNITION CONTROL
IR INDUCTION RELAY
MDV MODULATING VALVE
MV MAIN GAS VALVE
PS2 COMBUSTION AIR PROVING SWITCH
PS5 HIGH SPEED PRESSURE SWITCH
R5 MAIN GAS VALVE MONITORING
R6 LOW SPEED PRESSURE SWITCH
R7 IGNITION CONTROLLER ALARM MONITORING
SC1 STAGE CONTROLLER
TR# TRANSFORMER(S)
TS1 OUTDOOR AIR TEMP SENSOR
TS2 DISCHARGE AIR TEMP SENSOR
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
GND
MV MV
MV
PS2
HLC
(VLV/24V)
PSW
TH
VALVE
IC1
24V
SENSOR
SPARKSPARK
SENSE
BLWR
MDV
120/240V
IR
A1A2
SC1
C1/2
GO
NO1
NO2
G
U10
GND
U1
PS5
ON
NOC
NOC
BLACK
BROWN
PURPLE
RED
PURPLE
BLUE
YELLOW
WHITE
RED
LT. BLUE
WHITE
WHITE
RED
W H
IT
E P
IN
K
U4ORANGE
PURPLE U8
O
RED
OFF
WHITE
GND
(LINE) (BURNER)
(N.O.)
24V+ _
ALARM YELLOW R7
A1A2
WHITE
R5 A1A2
WHITE
R6 A1A2
WHITE
GND
U2
U5
U3
U6 RED
U7 BROWN
U9 PINK
11 14
R5
WHITE
11 14
R6
WHITE
11 14
R7
WHITE
B
LA
C K
SIG+ _
ORANGE
BLUE
TS1
TS2
WHITE
WHITE
GND
FU8/9 3A,250V
SUPPLEMENTARY
BUSSMANN FNM-3
FU7
2A,600V
CLASS
CC
C3/4/5
C6
RED
GSF X
DDC Code: Version - IGFv1.02
XR
DOC NUMBER: ---- REV: ----
R8 A1A2
WHITE
R8
RED LT. BLUE
G6K11P1MX1000GS14
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 11 of 39
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
Wiring Template: S14
CC# COMPRESSOR CONTACTOR
CF# CONDENSER FAN CONTACTOR
CH# CRANK CASE HEATER
DB1 DISTRIBUTION BLOCK
HPS# HIGH PRESSURE SWITCH
LPS# LOW PRESSURE SWITCH
M# MOTOR
R# CONTROL RELAY
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
DOC NUMBER: ---- REV: ----
PDX WIRING DIAGRAM
CH1 CH2
R C
DB1
FACTORY WIRED TO TERMINAL
"R" AND "C" IN MAIN
R C
CONTROL CENTER
FACTORY WIRED TO "DB1"
IN MAIN CONTROL CENTER
LPS1 HPS1
CC1
CC2
LPS2 HPS2
COMPRESSOR INTERLOCKSR11
R10
CF1
A2
A2
A2
A1
A1
A1
CONDENSING FAN 1
COMPRESSOR 2CC2
A2 A1
COMPRESSOR 1CC1
A2 A1
R11
11 14
R10
11 14
13 14
13 14
54 55
CF1 O.L
TB TB
COMPRESSOR INTERLOCKS
RC2
11 14
RC1
11 14
RC1, RC2 CONTACTS
LOCATED ON MAIN
CONTROL BOARD
COMPRESSOR 2
CC2
CF1
COMPRESSOR 1
CC1
CONDENSING
FAN 1
M8
M7
M6 T2
T3
T1
L2
L3
L1
T2
T3
T1
L2
L3
L1
T2
T3
T1
L2
L3
L1
G621100XX0000PS14
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 12 of 39
QTY WIDTH HEIGHT
1 41 in. 39 in.
Width
Height
5 in.
1.25 in.
max.
(typical)
Channel Frame
The model VCD-33 is a low leakage control damper for application as an automatic control or manual balancing damper. This model is intended for applications in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators are available. Non-jackshafted dampers will be supplied with a blade drive lever for internal actuator mounting. When external actuator mounting is specified, an extension pin with clip kit will be provided. Note: The extension pin with clip kit includes the extension pin and clip.
Notes: All dimensions shown are in units of inches. Width & Height furnished approximately 0.25 under size. Installation instructions available at www.greenheck.com. Customer supplied actuators configured with a jackshaft will be provided with a jackshaft this is one inch in diameter.
Application & Design
Ratings Pressure: Up to 10 in. wg pressure differential Velocity: 4,000 ft/min Leakage: Class 1A @ 1 in. wg, Class 1 @ up to 8 in. wg Temperature: Up to 250F
OUTLET DAMPER
**NOTE: Width and Height are shown in nominal dimensions**
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 13 of 39
Corner Weights 686 lb 739 lb
563 lb 607 lb
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 14 of 39
TSCP - Remote Control Panel
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Template Drawing: T02 DOC NUMBER: ---- REV: ----
BLOWER
50 60 70 80 90
HEAT
COOL
SUMMER OFF WINTER
13.50"
10.34" 4.50"
TSCP
REMOTE CONTROL PANEL G4BC11X1XA1AXXT02
Standard Construction Features And Notes Location of switches, lights and controls may vary.
All dimensions shown are in units of inches.
Galvanized steel with baked enamel finish.
Numbered terminal strip to match unit wiring.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 15 of 39
Remote Panel Wiring Requirements
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Template Drawing: T02 DOC NUMBER: ---- REV: ----
G
G
G
BLOWER LIGHT
HEAT LIGHT
COOL LIGHT
R C
W1
Y1
RED
WHITE
YELLOW
BLACK
WHITE
WHITE
GYELLOW
THERMOSTAT**
ROOM OVERRIDE
S5 32BLUE BLUE
WINTER
SUMMER
OFF
SUMMER/OFF/WINTER SWITCH
Y1
W1
ORANGE
BLACK
WINTER
SUMMER
OFFS2
GYELLOW
G4WC11X1XA1AXXT02
The wiring drawings details the number of the wires and the type of wire that needs to be run from the unit control center to the panel. A detailed wiring schematic will be provided with the panel when the unit ships.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 16 of 39
SEQUENCE OF OPERATIONS
Unit Controls The unit shall be provided from the factory with:
• 24VAC Transformer
• Terminal Strip
• Supply fan motor starter (contactor and overload)
• Factory provided, field installed supply air non-insulated outlet damper with actuator
• Remote Control Panel
• Phase Monitor
Remote Control Panel A Permatector coated NEMA-1 rated remote control panel shall be shipped loose to control the basic operation of the unit. The panel shall contain the following:
• Summer / Off / Winter Switch Summer: Supply fan is enabled, heat is disabled, and cooling is enabled.
Off: Supply fan is disabled.
Winter: Supply fan is enabled, heat is enabled, and cooling is disabled.
• Blower Light
• Heat Light
• Cool Light
• Supply temperature set point dial.
• Room override thermostat
Unit Start-Up Sequence
• Supply Fan Enable Is Received
• Supply air outlet damper actuator is energized
• Supply air outlet damper actuator limit switch is proven closed
• Supply Fan Is Enabled
Supply Fan Sequence The supply fan is configured for constant volume operation. The fan speed is set to the design fan RPM at the factory through the use of belts and sheaves. Adjustment or replacement of belts/sheaves is necessary to balance the supply airflow. The supply fan speed is not to be modulated.
Heating Control A heating enable signal must be present and the supply fan must enabled before the unit will enable heating.
Heating Inlet Air Sensor (Heating Lockout) The heating will be locked out when the outside air temperature is above the heating inlet air sensor set point (typical 65 F, adj.)
Indirect Gas Fired Heating (Modulating Control) A Programmable Logic Controller (PLC) furnace controller shall modulate the furnace to maintain a supply air temperature set point. The controller shall include a LCD display and keypad for changing set points and monitoring furnace operation. A built-in commissioning sequence assists with proper and accurate start-up.
This controller is responsible for furnace control only and does not control any other function of the unit.
Additionally it has no Building Management System (BMS) communication capability. The supply temperature set point shall be controlled as follows:
Discharge Temperature Control The heating supply temperature set point must be set locally at the controller.
Room Override A room override thermostat shall elevate the supply air temperature set point 5 F-40 F (adj.) upon a call for heat from the space.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 17 of 39
Cooling Control A cooling enable signal must be present and the supply fan must be enabled before the unit will enable cooling.
Cooling Inlet Air Sensor (Cooling Lockout) The cooling will be locked out when the outside air temperature is below the cooling inlet air sensor set point (typical 80 F, adj.)
Packaged DX Cooling The packaged DX cooling system is provided with 2 refrigerant circuits each with a standard scroll compressor. Cooling is staged on and off based upon the outside air temperature:
• Stage 1 is enabled at 85 F (adj.)
• Stage 2 is enabled at 95 F (adj.)
• Stage 2 is disabled at 90 F (adj.)
• Stage 1 is disabled at 80 F (adj.)
• In Variable Air Volume applications a supply air temperature sensor disables the second stage of cooling when supply air falls below 55 F (adj.). The second stage of cooling is allowed to re-energize when supply air temperature rises above 75 F (adj.).
Building Freeze Protection If the supply air temperature drops below 35 F for 300s (adj.), the supply fan will be disabled. Cycling the fan enable will reset the timer. This sequence is intended to prevent the unit from supply cold air into the building.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 18 of 39
Warranty Statement for Make-Up Air
Unit Warranty Greenheck warrants the equipment to be free from defects in material and workmanship for a period of 1 year (standard) from the shipment date.
Heat Exchanger Extended Warranty Greenheck warrants the stainless steel heat exchanger to be free from defects in material and workmanship for a period of 5 years from the shipment date.
Warranty Notes Any component which proves defective during the warranty period will be repaired or replaced at Greenheck’s sole option when returned to our factory, transportation prepaid. All warranties do not include labor costs associated with troubleshooting, removal, or installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation of any Greenheck product. These warranties are exclusive and are in lieu of all other warranties, whether written, oral, or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose. No person (including any agent or salesperson) has authority to expand Seller's obligation beyond the terms of this warranty, or to state that the performance of the product is other than that published by Seller.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Tempered Air Products (TAP) Statement 2018
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-1Mark:
IGX-112-H22-10-LModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 19 of 39
IGX-115-H32-16-O
Unit Performance
Design Conditions
Elevation (ft) Summer Winter (°F) Supply (CFM) Outdoor Air (CFM)DB (°F) WB (°F) 1,027 93.8 77.2 20.7 6,900 6,900
Unit Specifications Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing Furnace ETL Listing
2 3,906 (+/- 5%) Packaged DX Indirect Gas Furnace Outdoor UL / cUL 1995 ANSI Z83.8 / CSA 2.6
Configuration Unit Orientation Unit Configuration Outdoor Air Intake Return Air Intake Supply Air Discharge
Horizontal Constant Volume 100% OA End - End
Cooling Specifications
Type Refrigerant Capacity (MBH) Lead Compressor
Type EER Performance (DB/WB)
Total Sensible Condensing Section
Design Condition EAT (°F) LAT (°F)
Packaged DX R-410a 208.6 131.3 Standard Scroll 12.2 13.2 93.8 / 77.2 76.5 / 69.8
Heating Specifications
Type Gas Type
Gas Pressure Capacity (MBH) Temperature Rise Turndown
Performance Min
(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT
(°F)
LAT
(°F)
Indirect Gas Furnace Natural 6 0.5 600.0 480.0 8.0 64.4 8:1 21.0 85.1
Air Performance
Type Total
Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg) RPM Operating
Power (hp) Fan
Qty Type Size (in.) Drive-Type Supply 6,900 1.8 2.525 1228 7.09 1 Forward Curve 15 Belt-Drive
Motor Specifications Motor Qty Size (HP) Enclosure Efficiency RPM
Supply Fan Motor 1 7-1/2 ODP NEMA Premium 1725
Electrical Specifications Power Supply Rating (V/C/P) MCA (A) MOP (A)
Unit 460/60/3 43.2 50
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 20 of 39
CONSTRUCTION FEATURES AND ACCESSORIES
Unit Unit Installation - Outdoor Std Unit Construction - Double Wall X Wall Insulation - 1in. fiberglass - Cool source on X Base Insulation - 1in. fiberglass - entire unit base pan Std Paneled Bottom - Sheet metal liner for base insulation Corrosion Resistant Fasteners Std Access and Connections - Right side when facing intake X Service Access - Hinged access doors X Unit Finish - Permatector ASTM B117 salt spray 2500 hours X Finish Color - Concrete Gray (RAL 7023) X Supply Fan - Belt-drive, forward-curved X Supply Fan and Motor Vibration isolation - Neoprene X
Controls Unit Controls - Terminal strip with remote panel X Remote Panel - Industrial (NEMA-1) X BMS Communication BMS Protocol Temperature Control X Supply Fan VFD Supply Fan Control Melink/Vari-Flow wiring package Recirculation Control Unoccupied Mode (Night Setback)
Control Accessories Remote display Heating Inlet Air Sensor X Cooling Inlet Air Sensor X Dirty Filter Switch Fire Stat Type III (Ships loose) 120V/24V Smoke Detector (Ships loose) Inlet Damper End Switch External Cooling Lockout Relay Freeze Protection (Supply Air Low Limit) X Auxiliary Supply Starter Contacts - Qty 1 X Auxiliary Exhaust Starter Contacts Airflow Proving Monitoring Contact
Accessories Factory Installed, Lockable, NEMA 3R Disconnect Std Weatherhood - Aluminum Mesh filtered X Supply Air Filters - 2" aluminum, 20x25x2 - (10) X Outdoor Air Inlet Damper Supply Air Outlet Damper - Low leakage X Return Air Damper Diffuser Roof Curb Combination Curb Electrofin Coil Coating Fan Bearing Extended Lube Lines Inlet Damper Module Spare Belts Spare Filters Motor with Shaft Grounding Service Outlet Service Lights
Gas Heating Accessories Furnace Venting - Outdoor X Venting Type - Power vented Std Furnace Venting Method - Standard X Concentric Venting Adapter Direct Spark Ignition Std Flame Sensing - Flame rod Std Heat Exchanger Material - Stainless steel X Furnace Controls - 8:1 Modulating X Agency Approval - ETL and IRI Std External Gas Pressure Regulator (Ships loose) X DDC Assisted Furnace Commisioning X
Warranty Options Unit Warranty - 1 Year X 5 Year Compressor Warranty 5 Year Heat Exchanger Warranty X 10 Year Heat Exchanger Warranty
Standard Option Std Not Included
Included X
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 21 of 39
Fan Charts And Performance
Supply Fan Performance
Total Volume
(CFM)
External SP
(in. wg)
Total SP
(in. wg) RPM Operating
Power (hp) Motor Fan
Qty Size (HP) Qty Type Drive-Type
6,900 1.8 2.525 1228 7.09 1 7-1/2 1 Forward Curve Belt
Pressure Drop (in. wg) Weatherhood Filter Damper Cooling Heating External Total
0.099 0.029 0.036 0.62 0.203 1.8 2.525
Sound Performance in Accordance with AMCA Sound Power by Octave Band Lwa dBA Sones62.5 125 250 500 1000 2000 4000 8000
93 100 93 90 86 81 78 73 92 81 41
Supply Fan
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 22 of 39
Cooling Specifications
Cooling Performance
Type Refrigerant Capacity (MBH) Lead Compressor
Type EER Performance (DB/WB)
Total Sensible Condensing Section
Design Condition EAT (°F) LAT (°F)
Packaged DX R-410a 208.6 131.3 Standard Scroll 12.2 13.2 93.8 / 77.2 76.5 / 69.8
Coil Information
PDX Coil Model Fins Per Inch Rows Deep Suction Temp. (°F)
Face Velocity (ft/min)
Refrigerant Velocity (ft/min)
DX38S02H10-36x54 10 2 47.2 511 1,549
Unit Details Refrigerant charges provided by the factory are approximate and may require field adjustment Refrigeration components servicable without affecting airflow Hermetic scroll type compressor(s) Compressor(s) mounted on neoprene vibration isolation Crankcase heater on compressor(s) Liquid-line filter drier Moisture-indicating sight glass
Thermal expansion valve Refrigerant low pressure switch (auto reset) Refrigerant high pressure switch (manual reset) Service/charging valves Low sound, direct drive condensing fans Insulated, double sloped, stainless steel drain pan Copper tube, aluminum fin coil construction
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 23 of 39
Heating Specifications
Heating Performance
Type Gas Type
Gas Pressure Capacity (MBH) Temperature Rise Turndown
Performance Min
(in. wg) Max (PSI) Input Output Min (°F) Max (°F) EAT
(°F)
LAT
(°F)
Indirect Gas Furnace Natural 6 0.5 600.0 480.0 8.0 64.4 8:1 21.0 85.1
Heating Information
Heat Exch. Material Venting Venting Method Gas Pressure Regulators
Heat Exchanger Warranty
Stainless Steel Outdoor Standard 10 PSI 5 Year
Unit Details ANSI Standard Z83.8 and CSA 2.6 Direct Spark Ignition Stainless Steel Heat Exchanger Tubes
Power Venting 24 Volt Control Power 5 year heat exchanger warranty
Gas Connections
3/4" NPT GAS
CONNECTION
48.723
8.480
8.486
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 24 of 39
ELEVATION VIEW
48.678 25.750 70.071 65.948 66.384
48.723
Notes - Elevation View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
Order of unit sections is from intake of unit to discharge of unit.
Sections included on this unit: Weatherhood Section, Filter Section, Cooling Section, Blower Section, Furnace 1 Section, Furnace 2 Section Insulation: Double Wall, from Cooling Section through end of unit.
PLAN VIEW
INTAKE V-BANK FILTER
ACCESS
SIDE
ACCESS SIDE
PDX COOLING
BLOWER
ACCESS SIDE
FURNACE
ACCESS SIDEACCESS SIDE
48.678 25.750
69.973
134.098
65.948
52.166
66.384
Notes - Plan View Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 25 of 39
END VIEW
SUPPLY
DUCT
30.000
16.899
1.17541.000
52.16612.565 35.340
FOOTPRINT VIEW
199.500
CURB LENGTH
RECOMMENDED
48.500
CURB WIDTH
RECOMMENDED
Notes - Footprint View Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides. For example: If the duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.
Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb. For example: If the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.
The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design, to prevent water infiltration.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 26 of 39
Electrical Connections
ELECTRICAL
CONNECTION
15.000
63.997
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 27 of 39
Clearance Specifications
Recommended Minimum Combustible Clearances Floor (in.) Top (in.) Sides (in.) Ends (in.)
Indirect Fired Units 0 0 0 0
Notes - Combustible Clearances Clearance to combustibles is defined as the minimum distance required between the heating source and the adjacent combustible surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the ambient temperature.
Reference venting guidelines for combustion blower clearances.
Recommended Minimum Service Clearances Housing 32 and less (in.) Housing 35 and higher (in.)
42 on the controls side of the unit N/A
Notes - Service Clearances To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances should be 6 in. wider than the width of the module itself.
Reference the PDX Service Clearance guidelines (PDX IOM)
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 28 of 39
Wiring Diagram
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
G
SDF
RT4 FREEZE PROTECTION
S4
HEAT ENABLE
TO IG FURNACE
RH
A2
A1
POST HEAT
Template Drawing: U10
SUPPLY FAN
MOTOR
ST1 O.L.
11 14
RT4
11 12
RT4
ST1 O.L.
CONTROL
COM NO
D2L
OFF
OUTLET DAMPERD2
ST1
A2 A1
SUPPLY FAN
RF
TS5
COM NO
THERMOSTAT CONTROLLER(S)24 VAC
OA-SENSOR
SENSOR COM
A2 A1
L3
L2
L1
DS1
M1
RF
A2 A1
SUPPLY FAN RELAY
RF
Y1
A2 A1
COOLING
TO 111 & 112 IN
FURNACE 1
, TS6
DB1
CC# COMPRESSOR CONTACTOR
CF1 CONDENSER FAN CONTACTOR
CH# CRANK CASE HEATER
D2 OUTLET DAMPER
D2L OUTLET DAMPER LIMIT
DS1 MAIN DISCONNECT SWITCH
FSC FIRE SYSTEM CONTACT
FU# FUSE
HLC HIGH LIMIT CONTROL
HPS HIGH PRESSURE SWITCH
LPS LOW PRESSURE SWITCH
M# MOTOR
OL# MOTOR OVERLOAD
PM PHASE MONITOR
R10 COMP#1 INTERLOCK RELAY
R11 COMP#2 INTERLOCK RELAY
RC1 COOLING STAGE 1 RELAY
RC2 COOLING STAGE 2 RELAY
RF SUPPLY FAN RELAY
RH HEAT RELAY
RT4 FREEZE PROTECTION TIMER
SWITCH 1 and 4 DOWN - 2 and 3 UP / DIAL SET TO 4
S2 FAN SWITCH
S4 HEAT AND COOL SWITCH
S5 ROOM OVERRIDE
SDF SENSOR DISCHARGE - FREEZE
ST# MOTOR STARTER
TR# TRANSFORMER
TS5 INLET AIR SENSOR - COOL
JUMPER = COOL : DIFFERENTIAL = 5
TS6 INLET AIR SENSOR - COOL
JUMPER = COOL : DIFFERENTIAL = 5 : OFFSET = 10
GROUND
TO UNIT
MAIN POWER
460V
S2 FSC
TR1
CR
USER INDIRECT GAS FURNACE INTERFACE CONNECTIONS:
ROOM OVERRIDE CONNECTION
31 32
S5
FACTORY WIRED TO TERMINAL "32"
IN IG FURNACE COMPARTMENT
75 VA
MOUNTED IN END
FURNACE
111 112
T3
T2
T1
24V
ST1
W1
PM
11 14
PM L2
L1
L3
L1 T1
L2 T2
L3 T3
THERMOSTAT(S) TS5
DOC NUMBER: ---- REV: ----
FACTORY WIRED
TO "CC1" IN
COOLING MODULE
CONTROL CENTER
RC1
TS6
COM NO A2 A1
COOLING STAGE 2RC2
STAGE 1
RC1
RC2
14 CONTROL CENTER
TO R11 (11) IN COOLING MODULE
CONTROL CENTER
TO R10 (11) IN COOLING MODULE
IN COOLING MODULE
TO "R"
CONTROL CENTER
TO "C"
21 24
RT4
GI24C602A043G70AU10
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 29 of 39
Furnace Wiring Diagram
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
Wiring Template: S14
VALVE
IC1
(VLV/24V)
HLC
NO
PS2
24V
TH
PSW SPARKSPARK
SENSORSENSE
X
TR5
INDIRECT GAS WIRING DIAGRAM
C
40 VA
24VAC
GND
R2
HEAT
RELAY
R3
HEAT
RELAY
FURNACE 2
4:1 MODULATING
NO
T3
C
MV
HI
C
LO
T3
B
IN MAIN CONTROL CENTER
FURNACE 1 - 2 STAGE
FACTORY WIRED
S
AYELLOW
LT. BLUE
BROWN
Y E
LL
O
W
LT
. B
LU
E
B R
O W
N
IG FURNACE WIRING
OFF BOARD WIRING
BASAAA
CM
CR
A2 A1
CR
L1
L3 T3
T1
TO TERMINALS "111" AND "112"
112111
112111
120/240V
BLWR
GND
(LINE)
(N.O.)
(BURNER)
CM COMBUSTION BLOWER MOTOR
CR COMBUSTION BLOWER RELAY
HLC HIGH TEMPERATURE LIMIT CONTROL
IC1 IGNITION CONTROL
MV MAIN GAS VALVE
PS2 COMBUSTION AIR PROVING SWITCH
T3 HIGH FIRE TIMER
TR# TRANSFORMER(S)
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
DOC NUMBER: ---- REV: ----
G6LX4P1MX1000GS14
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 30 of 39
Furnace 2 Wiring Diagram
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
Wiring Template: S14
TO TERMINALS "111" AND "112"
FACTORY WIRED
IN FURNACE 1
NO3
NO4
R2 A1A2
R3 A1A2
BROWN
ORANGE
FURNACE 2 - 4:1 MODULATING
11 14
R3
BROWN
SB
11 14
R2
YELLOWLT. BLUE
A
FURNACE 1 FURNACE 2
2 STAGE 4:1 MODULATING
IG FURNACE WIRING
OFF BOARD WIRING
AIRFLOW
112111
INDIRECT GAS WIRING DIAGRAM
TR5
FU8
120V 24V
250VA
FU9
IR
CM
12 11
HIGH
LOW
RED
BLACK
WHITE
WHITE
BLUE
BLUE
BA SA AA
RH
HEAT
ENABLE
MAIN CONTROL CENTER
ORANGE
PURPLE
BLACK
BLACK
S5
ROOM
OVERRIDE
CM COMBUSTION BLOWER MOTOR
FU# FUSE(S)
HLC HIGH TEMPERATURE LIMIT CONTROL
IC1 IGNITION CONTROL
IR INDUCTION RELAY
MDV MODULATING VALVE
MV MAIN GAS VALVE
PS2 COMBUSTION AIR PROVING SWITCH
PS5 HIGH SPEED PRESSURE SWITCH
R2 FURNACE 1 STAGE 1 HEAT RELAY
R3 FURNACE 1 STAGE 2 HEAT RELAY
R5 MAIN GAS VALVE MONITORING
R6 LOW SPEED PRESSURE SWITCH
R7 IGNITION CONTROLLER ALARM MONITORING
SC1 STAGE CONTROLLER
TR# TRANSFORMER(S)
TS1 OUTDOOR AIR TEMP SENSOR
TS2 DISCHARGE AIR TEMP SENSOR
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
GND
MV MV
MV
PS2
HLC
(VLV/24V)
PSW
TH
VALVE
IC1
24V
SENSOR
SPARKSPARK
SENSE
BLWR
MDV
120/240V
IR
A1A2
SC1
C1/2
GO
NO1
NO2
G
U10
GND
U1
PS5
ON
NOC
NOC
BLACK
BROWN
PURPLE
RED
PURPLE
BLUE
YELLOW
WHITE
RED
LT. BLUE
WHITE
WHITE
RED
W H
IT
E P
IN
K
U4ORANGE
PURPLE U8
O
RED
OFF
WHITE
GND
(LINE) (BURNER)
(N.O.)
24V+ _
ALARM YELLOW R7
A1A2
WHITE
R5 A1A2
WHITE
R6 A1A2
WHITE
GND
U2
U5
U3
U6 RED
U7 BROWN
U9 PINK
11 14
R5
WHITE
11 14
R6
WHITE
11 14
R7
WHITE
SIG+ _
ORANGE
BLUE
TS1
TS2
WHITE
WHITE
GND
FU8/9 3A,250V
SUPPLEMENTARY
BUSSMANN FNM-3
FU7
2A,600V
CLASS
CC
C3/4/5
C6
RED
GS XE
DDC Code: Version - IGFv1.02
XR
DOC NUMBER: ---- REV: ----
R8 A1A2
WHITE
R8
RED LT. BLUE
G6L12P1MX1000GS14
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 31 of 39
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
Wiring Template: S14
CC# COMPRESSOR CONTACTOR
CF# CONDENSER FAN CONTACTOR
CH# CRANK CASE HEATER
DB1 DISTRIBUTION BLOCK
HPS# HIGH PRESSURE SWITCH
LPS# LOW PRESSURE SWITCH
M# MOTOR
R# CONTROL RELAY
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
DOC NUMBER: ---- REV: ----
PDX WIRING DIAGRAM
CH1 CH2
R C
DB1
FACTORY WIRED TO TERMINAL
"R" AND "C" IN MAIN
R C
CONTROL CENTER
FACTORY WIRED TO "DB1"
IN MAIN CONTROL CENTER
LPS1 HPS1
CC1
CC2
LPS2 HPS2
COMPRESSOR INTERLOCKSR11
R10
CF1
A2
A2
A2
A1
A1
A1
CONDENSING FAN 1 & 2
COMPRESSOR 2CC2
A2 A1
COMPRESSOR 1CC1
A2 A1
R11
11 14
R10
11 14
13 14
13 14
54 55
CF2 O.L
TB TB
58 59
CF1 O.L
TB TB
COMPRESSOR INTERLOCKS
RC2
11 14
RC1
11 14
RC1, RC2 CONTACTS
LOCATED ON MAIN
CONTROL BOARD
COMPRESSOR 2
CC2
CF1
COMPRESSOR 1
CC1
CONDENSING
FAN 1
M8
M7
M6
CONDENSING
FAN 2
M9
T2
T3
T1
L2
L3
L1
T2
T3
T1
L2
L3
L1
T2
T3
T1
L2
L3
L1
G622100XX0000PS14
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 32 of 39
QTY WIDTH HEIGHT
1 41 in. 30 in.
Width
Height
5 in.
1.25 in.
max.
(typical)
Channel Frame
The model VCD-33 is a low leakage control damper for application as an automatic control or manual balancing damper. This model is intended for applications in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators are available. Non-jackshafted dampers will be supplied with a blade drive lever for internal actuator mounting. When external actuator mounting is specified, an extension pin with clip kit will be provided. Note: The extension pin with clip kit includes the extension pin and clip.
Notes: All dimensions shown are in units of inches. Width & Height furnished approximately 0.25 under size. Installation instructions available at www.greenheck.com. Customer supplied actuators configured with a jackshaft will be provided with a jackshaft this is one inch in diameter.
Application & Design
Ratings Pressure: Up to 10 in. wg pressure differential Velocity: 4,000 ft/min Leakage: Class 1A @ 1 in. wg, Class 1 @ up to 8 in. wg Temperature: Up to 250F
OUTLET DAMPER
**NOTE: Width and Height are shown in nominal dimensions**
Manufacturer reserves right to change, alter, or improve this product at any time.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 33 of 39
Corner Weights 1,100 lb 1,116 lb
839 lb 852 lb
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 34 of 39
TSCP - Remote Control Panel
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Template Drawing: T02 DOC NUMBER: ---- REV: ----
BLOWER
50 60 70 80 90
HEAT
COOL
SUMMER OFF WINTER
13.50"
10.34" 4.50"
TSCP
REMOTE CONTROL PANEL G4BC11X1XA1AXXT02
Standard Construction Features And Notes Location of switches, lights and controls may vary.
All dimensions shown are in units of inches.
Galvanized steel with baked enamel finish.
Numbered terminal strip to match unit wiring.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 35 of 39
Remote Panel Wiring Requirements
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
GREENHECK
WIRE COLOR CODE
Building Value in Air.
Wiring Diagram Code:
BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW
Template Drawing: T02 DOC NUMBER: ---- REV: ----
G
G
G
BLOWER LIGHT
HEAT LIGHT
COOL LIGHT
R C
W1
Y1
RED
WHITE
YELLOW
BLACK
WHITE
WHITE
GYELLOW
THERMOSTAT**
ROOM OVERRIDE
S5 32BLUE BLUE
WINTER
SUMMER
OFF
SUMMER/OFF/WINTER SWITCH
Y1
W1
ORANGE
BLACK
WINTER
SUMMER
OFFS2
GYELLOW
G4WC11X1XA1AXXT02
The wiring drawings details the number of the wires and the type of wire that needs to be run from the unit control center to the panel. A detailed wiring schematic will be provided with the panel when the unit ships.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 36 of 39
SEQUENCE OF OPERATIONS
Unit Controls The unit shall be provided from the factory with:
• 24VAC Transformer
• Terminal Strip
• Supply fan motor starter (contactor and overload)
• Factory provided, field installed supply air non-insulated outlet damper with actuator
• Remote Control Panel
• Phase Monitor
Remote Control Panel A Permatector coated NEMA-1 rated remote control panel shall be shipped loose to control the basic operation of the unit. The panel shall contain the following:
• Summer / Off / Winter Switch Summer: Supply fan is enabled, heat is disabled, and cooling is enabled.
Off: Supply fan is disabled.
Winter: Supply fan is enabled, heat is enabled, and cooling is disabled.
• Blower Light
• Heat Light
• Cool Light
• Supply temperature set point dial.
• Room override thermostat
Unit Start-Up Sequence
• Supply Fan Enable Is Received
• Supply air outlet damper actuator is energized
• Supply air outlet damper actuator limit switch is proven closed
• Supply Fan Is Enabled
Supply Fan Sequence The supply fan is configured for constant volume operation. The fan speed is set to the design fan RPM at the factory through the use of belts and sheaves. Adjustment or replacement of belts/sheaves is necessary to balance the supply airflow. The supply fan speed is not to be modulated.
Heating Control A heating enable signal must be present and the supply fan must enabled before the unit will enable heating.
Heating Inlet Air Sensor (Heating Lockout) The heating will be locked out when the outside air temperature is above the heating inlet air sensor set point (typical 65 F, adj.)
Indirect Gas Fired Heating (Modulating Control) A Programmable Logic Controller (PLC) furnace controller shall modulate the furnace to maintain a supply air temperature set point. The controller shall include a LCD display and keypad for changing set points and monitoring furnace operation. A built-in commissioning sequence assists with proper and accurate start-up.
This controller is responsible for furnace control only and does not control any other function of the unit.
Additionally it has no Building Management System (BMS) communication capability. The supply temperature set point shall be controlled as follows:
Discharge Temperature Control The heating supply temperature set point must be set locally at the controller.
Room Override A room override thermostat shall elevate the supply air temperature set point 5 F-40 F (adj.) upon a call for heat from the space.
07/31/2019Printed Date:
USDA SE Poultry with Packaged DXJob:
MUA-2Mark:
IGX-115-H32-16-OModel:
CAPS 4.29.1685 C:\Users\esmith\Desktop\USDA SE Poultry with Packaged DX.gfcj Page 37 of 39
Cooling Control A cooling enable signal must be present and the supply fan must be enabled before the unit will enable cooling.
Cooling Inlet Air Sensor (Cooling Lockout) The cooling will be locked out when the outside air temperature is below the cooling inlet air sensor set point (typical 80 F, adj.)
Packaged DX Cooling The packaged DX cooling system is provided with 2 refrigerant circuits each with a standard scroll compressor. Cooling is staged on and off based upon the outside air temperature:
• Stage 1 is enabled at 85 F (adj.)
• Stage 2 is enabled at 95 F (adj.)
• Stage 2 is disabled at 90 F (adj.)
• Stage 1 is disabled at 80 F (adj.)
• In Variable Air Volume applications a supply air temperature sensor disables the second stage of cooling when supply air falls below 55 F (adj.). The second stage of cooling is allowed to re-energize when supply air temperature rises above 75 F (adj.).
Building Freeze Protection If the supply air temperature drops below 35 F for 300s (adj.), the supply fan will be disabled. Cycling the fan enable will reset the timer. This sequence is intended to prevent the unit from supply cold air into the building.
07/31/2019Printed…