Glen Erie South_For Bid Drawings_07.01.2025.pdf
PDF 1 MB Posted
- Solicitation number
- 250729-1
- Issued by
- Otero County, Colorado
About this file
These are bid set drawings for the Glen Erie South Water Storage Tank Rehabilitation Project, prepared by Western Water Solutions, LLC for the City of Craig, Colorado and the Colorado Department of Public Health. The project involves comprehensive rehabilitation of an existing above-grade, welded steel water storage tank with a 66-foot diameter, 20-foot height, and approximately 500,000-gallon capacity located at the corner of E 11th Street and Bryan Way in Craig. Key rehabilitation activities include replacing the column capital, roof vent, roof hatch, interior ladder, modifying the overflow weir, installing new patch plates, performing surface preparation and recoating of interior and exterior surfaces, and implementing a new cathodic protection system. The drawings are dated May 19, 2025, and provide detailed technical specifications, site plans, tank sections, and specific rehabilitation details.
The project drawings indicate a comprehensive rehabilitation approach that includes non-destructive testing of floor plates, welding inspections by an AWS certified welding inspector, and coating inspections by a NACE certified coating inspector. The contractor will be responsible for multiple technical submittals, including fabrication drawings, material certifications, welding procedures, and coating system documentation. The project requires specialized technical work, including lead abatement, surface preparation, welding, and installation of new components while maintaining strict quality control and inspection protocols. The drawings suggest the project will involve significant technical expertise in water storage tank rehabilitation, with specific requirements for materials, welding, surface preparation, and coating application to meet potable water design criteria established by the Colorado Department of Public Health.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Glen Erie South_For Bid Specifications_07.01.2025.pdf | ||
| Glen Erie South Water Storage Tank Ad _ signed.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing Date:
WESTERN WATER SOLUTIONS, LLC
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
COVER SHEET
G000
CITY OF CRAIG
GLEN ERIE SOUTH WATER STORAGE TANK REHABILITATION PROJECT
CRAIG, COLORADO
DRAWING SHEET INDEX
G000 COVER SHEET
G001 GENERAL NOTES AND ABBREVIATIONS
VICINITY MAP
NOT TO SCALE
PROJECT LOCATION
LOCATION MAP
NOT TO SCALE BID SET
S101 FLOOR AND ROOF PLANS
TANK DETAILS
DRAWING SCALES SHOWN BASED ON A 22x34 DRAWING
G002 GENERAL SITE PLAN
S001 STRUCTURAL GENERAL NOTES
S501
S301 TANK SECTIONS
S502 VENT DETAILS
MEEKER
PROJECT LOCATION
HWY 40
CRAIG
HWY 40
MAYBELL
HAYDEN
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
AutoCAD SHX Text Sheet Title
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
ABBREVIATIONS:
ADD'L
ALUM
ANSI
API
APPROX
ASCE
ASTM
AWS
AWWA
BAC
B.O.
CDOT
CDPHE
DIAM.
D.I.
EL/ELEV
EPA
EQ
EQUIV.
ETC.
EX / EXIST
FG
FL
FT
FY
GPM
HWL
HSS
IBC
I.D.
IN
K
KSI
LBS
MAX
MFL
MIN
MNFR
MPH
NACE
NO.
NSF
O.D.
OPNG
PE
PSF
PSI
QTY
RE:
RECT
REQ'D
SCH
SEAC
SEC
SP
SPEC
SQ
SS
SSPC
STD
T.O.
TYP
UE
USGS
W/ Ø
ADDITIONAL
ALUMINUM
AMERICAN NATIONAL STANDARDS INSTITUTE
AMERICAN PETROLEUM INSTITUTE
APPROXIMATELY
AMERICAN SOCIETY OF CIVIL ENGINEERS
AMERICAN SOCIETY OF TESTING AND MATERIALS
AMERICAN WELDING SOCIETY
AMERICAN WATER WORKS ASSOCIATION
BACTERIOLOGICAL
BOTTOM OF
COLORADO DEPARTMENT OF TRANSPORTATION
CO DEPARTMENT OF PUBLIC HEALTH AND ENVIRONMENT
DIAMETER
DUCTILE IRON
ELEVATION
ENVIRONMENTAL PROTECTION AGENCY
EQUAL
EQUIVALENT
ETCETERA
EXISTING
FINISHED GRADE
FLANGE
FOOT
YIELD STRENGTH
GALLONS PER MINUTE
HIGH WATER LEVEL
HOLLOW STEEL SECTION
INTERNATIONAL BUILDING CODE
INSIDE DIAMETER
INCH
THOUSAND
KIPS PER SQUARE INCH
POUNDS
MAXIMUM
MAGNETIC FLUX LEAKAGE
MINIMUM
MANUFACTURER
MILE PER HOUR
NATIONAL ASSOCIATION OF CORROSION ENGINEERS
NUMBER
NATIONAL SANITARY FOUNDATION
OUTSIDE DIAMETER
OPENING
PLAIN END
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
QUANTITY
REFERENCE
RECTANGULAR
REQUIRED
SCHEDULE
STRUCTURAL ENGINEERS ASSOCIATION OF COLORADO
SECOND
SPACING
SPECIFICATION
SQUARE
STAINLESS STEEL
SOCIETY FOR PROTECTIVE COATINGS
STANDARD
TOP OF
TYPICAL
UNDERGROUND ELECTRIC
U.S. GEOLOGICAL SURVEY
WITH
INCH
FOOT
CENTERLINE
DIAMETER
AND
PERCENT
DEGREE
NUMBER
GENERAL NOTES:
1. THE GLEN ERIE SOUTH TANK IS AN ABOVE-GRADE, WELDED STEEL
WATER STORAGE TANK WITH A DIAMETER OF 66 FEET AND HEIGHT OF 20
FEET FOR A TOTAL STORAGE CAPACITY OF APPROXIMATELY 500,000
GALLONS. THE TANK IS LOCATED ON THE CORNER OF E 11TH STREET
AND BRYAN WAY IN CRAIG, COLORADO.
2. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS AND BE SUBJECT TO CONSTRUCTION OBSERVATION BY
THIRD PARTY INSPECTORS, ENGINEER OF RECORD, AND CITY OF CRAIG
REPRESENTATIVES OR PERSONNEL.
3. WESTERN WATER SOLUTIONS AND CITY OF CRAIG DO NOT GUARANTEE
THE ACCURACY OF LOCATIONS OF EXISTING PIPELINES AND UTILITIES.
LOCATIONS, ELEVATIONS, AND DIMENSIONS OF EXISTING UTILITIES,
STRUCTURES, AND OTHER FEATURES ARE SHOWN ACCORDING TO THE
BEST INFORMATION AVAILABLE AT THE TIME OF THE PREPARATION OF
THESE DRAWINGS, BUT DO NOT PURPORT TO BE ABSOLUTELY CORRECT
OR ACCURATE. THE CONTRACTOR SHALL VERIFY THE LOCATIONS,
ELEVATIONS, AND DIMENSIONS OF ALL EXISTING UTILITIES, STRUCTURES,
AND OTHER FEATURES AFFECTING THE WORK. SHOULD THE
CONTRACTOR IDENTIFY ANY UTILITIES, STRUCTURES OR OTHER
FEATURES NOT SHOWN ON THE PLANS, THE CONTRACTOR SHALL NOTIFY
THE ENGINEER. ANYTHING NOT SHOWN ON THESE DRAWINGS SHALL NOT
CONSTITUTE AN EXTRA, UNLESS RECOMMENDED BY THE ENGINEER AND
APPROVED BY THE OWNER.
4. PROJECT SHALL BE CONSTRUCTED TO MEET THE REQUIREMENTS OF
THE STATE OF COLORADO DESIGN CRITERIA FOR POTABLE WATER
SYSTEMS PUBLISHED BY THE COLORADO DEPARTMENT OF PUBLIC
HEALTH AND ENVIRONMENTS WATER QUALITY CONTROL DIVISION,
LATEST EDITION.
5. ANY CHANGES OF MATERIAL OR DEVIATIONS FROM THE APPROVED
PLANS OR THE PROJECT SPECIFICATIONS MUST BE DONE WITH WRITTEN
PERMISSION FROM THE NTM DISTRICT ENGINEER.
6. ALL UTILITIES SHALL BE KEPT IN OPERATION EXCEPT WITH THE EXPRESS
WRITTEN CONSENT OF THE CITY OF CRAIG. IT IS THE CONTRACTORS
RESPONSIBILITY TO PRESERVE EXISTING UTILITIES. ANY AND ALL
DAMAGE TO EXISTING UTILITIES AS A RESULT OF THE CONTRACTOR'S
ACTIONS SHALL BE REPAIRED IMMEDIATELY AT THE CONTRACTOR'S
EXPENSE.
7. USE EXTREME CAUTION WHEN WORKING NEAR OVERHEAD OR
UNDERGROUND POWER, GAS, OR OTHER UTILITIES SO AS TO SAFELY
PROTECT ALL PERSONNEL AND EQUIPMENT.
8. ALL WORK IN THE RIGHT-OF-WAY SHALL INCLUDE TRAFFIC CONTROL. ALL
BARRICADING AND TRAFFIC CONTROL DEVICES OR METHODS USED
DURING CONSTRUCTION SHALL BE IN ACCORDANCE WITH LOCAL AND
CDOT STANDARDS.
9. THE CONTRACTOR SHALL CONTACT COLORADO 811 AT 1-800-922-1987
WITH REQUIRED NOTICE PRIOR TO ANY EXCAVATION TO OBTAIN UTILITY
LOCATES. UTILITY LOCATIONS, WHETHER OR NOT SHOWN ON THESE
DRAWINGS, IN NO WAY RELIEVES THE CONTRACTOR FROM THE
RESPONSIBILITY OF CALLING FOR AND OBTAINING UTILITY LOCATIONS
FROM THE APPROPRIATE AUTHORITIES PRIOR TO BEGINNING
EXCAVATION
10. THE NOTES ON THIS SHEET AND THE STRUCTURAL GENERAL NOTES ARE
GENERAL AND APPLY TO THE ENTIRE PROJECT. QUESTIONS SHOULD BE
SUBMITTED TO THE ENGINEER AND ANSWERED IN WRITING PRIOR TO
CONSTRUCTION.
11. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS.
SUBMIT REQUIRED CHANGES FOR APPROVAL.
12. CONTRACTOR TO COMPLY WITH THE LIMITS OF CONSTRUCTION.
13. CONTRACTOR WILL BE RESPONSIBLE FOR CLEANUP OF SEDIMENT AND
CONSTRUCTION DEBRIS TRACKED ONTO ADJACENT PAVED ROADS AND
ACCESS AREAS.
14. CITY OF CRAIG WILL REMOVE LEVEL SENSING INSTRUMENTATION AND
THE TANK MIXER FROM THE TANK PRIOR TO CONSTRUCTION.
15. REFER TO SHEET NOTES AND PROJECT SPECIFICATIONS FOR DETAILED
MATERIAL REQUIREMENTS.
16. NO HOLES, OPENINGS, OR ALTERATIONS TO THE TANK MAY BE MADE
WITHOUT PRIOR WRITTEN APPROVAL OF THE ENGINEER, OR AS SHOWN
ON THE DRAWINGS.
17. CONTRACTOR WILL BE RESPONSIBLE FOR RESTORING DISTURBED
AREAS PRIOR TO FINAL COMPLETION.
18. CLEANING AND DISINFECTION OF THE TANK IS THE CONTRACTORS
RESPONSIBILITY. DISINFECT THE TANK AND PIPING IN ACCORDANCE WITH
AWWA C652, LATEST EDITION.
GENERAL NOTES CONTINUED:
19. OWNER TO HIRE A THIRD-PARTY COATING INSPECTOR AND WELDING
INSPECTOR. CONTRACTOR RESPONSIBLE FOR SCHEDULING INSPECTORS
AND PROVIDING NECESSARY ACCESS TO PERFORM INSPECTIONS.
20. CONTRACTOR WILL BE RESPONSIBLE FOR THE COMPLETION OF RECORD
DRAWINGS. A SET OF FOR-CONSTRUCTION DRAWINGS SHALL BE KEPT ON
SITE WITH REDLINES FOR AS-CONSTRUCTED CONDITION OF NEW WORK.
SUBMITTALS TO BE PROVIDED FOR ENGINEER REVIEW:
REFER TO PROJECT SPECIFICATIONS FOR SUBMITTAL REQUIREMENTS. NOT
ALL REQUIRED SUBMITTALS ARE LISTED BELOW.
1. LOCATION AND SIZE OF DOOR SHEET, ILLUSTRATING LOCATION OF
NEARBY VERTICAL AND HORIZONTAL WELD SEAMS. DOOR SHEET TO
COMPLY WITH THE REQUIREMENTS OF API 653-14 FOR SHELL PLATE
INSTALLATION.
2. FABRICATION AND ERECTION DRAWINGS SHOWING A COMPLETE
MATERIAL LIST WITH ASTM DESIGNATION AND WELD SYMBOLS,
INDICATING SHOP VERSUS FIELD WELDING FOR ALL COMPONENTS OF
THE CENTER COLUMN CAPITAL, HATCH RISER, VENT RISER, DRAIN SUMP,
AND WELDED ON PATCH PLATES.
3. PRODUCT DATA SHEETS FOR INTERIOR AND EXTERIOR COATING
SYSTEMS.
4. PRODUCT DATA SHEETS FOR EXTERIOR JOINT REPAIR SYSTEM.
5. PRODUCT DATA SHEET FOR FLEXIBLE JOINT SEALANT.
6. NONDESTRUCTIVE TESTING COMPANY QUALIFICATIONS,
CERTIFICATIONS, AND COMPLETE MAGNETIC FLUX LEAKAGE SCAN
REPORT WITH AUTOCAD FILE OF FLOOR PLATE AND RECOMMENDED
REPAIRS.
7. WELDER QUALIFICATIONS, PROCEDURES, CERTIFICATIONS AND WELD
MATERIALS.
8. VENT AND ACCESS HATCH FABRICATION DRAWINGS AND WARRANTY
INFORMATION.
9. CENTER COLUMN CAPITAL AND DRAIN SUMP FABRICATION SHOP
DRAWINGS.
10. COMPLETE DESIGN AND INSTALLATION SUBMITTAL FOR AN IMPRESSED
CURRENT CATHODIC PROTECTION SYSTEM.
11. TANK AND PIPING DISINFECTION PLAN.
INSPECTION, TESTING, AND QUALITY ASSURANCE:
1. STRUCTURAL STEEL CONSTRUCTION WILL BE INSPECTED IN
ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE (IBC) SECTION
1704.3, AND TABLE 1704.3.
2. THE OWNER WILL HIRE AN AWS CERTIFIED WELDING INSPECTOR TO
PERFORM WELD INSPECTIONS AS NOTED IN IBC TABLE 1704.3, ITEM 4 AND
5, IN ADDITION TO ITEMS NOTED IN THE DOCUMENTS TO BE INSPECTED
BY A WELD INSPECTOR.
3. SURFACE PREPARATION AND COATINGS SHALL BE INSPECTED BY A NACE
CERTIFIED COATING INSPECTOR HIRED BY THE OWNER.
GENERAL NOTES
AND
ABBREVIATIONS
G001
BID SET
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
N
SCALE BASED ON FULL-SIZE
22x34 DRAWING SHEET
1" = 200'
0 200' 400'
EXISTING 10"Ø INLET / OUTLET
BR
YA
N
W
AY
EXISTING 8"Ø
DRAIN / OVERFLOW
GLEN ERIE
NORTH TANK
EXISTING 8" DRAIN / OVERFLOW;
FLAP GATE INSTALLED AT DAYLIGHT
GLEN ERIE
SOUTH TANK
E 11TH ST
LOCKED
ACCESS GATE
GENERAL SITE
PLAN
G002
SECURITY FENCING, TYP
BID SET
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
STRUCTURAL STEEL INSTALLATION AND INSPECTION (CONTINUED):
5. FIELD WELDING SHALL BE INSPECTED VISUALLY AND BY NON-DESTRUCTIVE TESTING BY AN AWS
CERTIFIED WELDING INSPECTOR.
6. ACCEPTANCE CRITERIA FOR VISUALLY INSPECTED WELDS SHALL BE IN ACCORDANCE WITH
TABLE 6.1 OF AWS D1.1.
7. 100% OF THE FIELD INSTALLED FILLET WELDS SHALL BE VISUALLY INSPECTED UNLESS THE
WELDING INSPECTOR IDENTIFIES GROUNDS FOR MORE RIGOROUS INSPECTION AND NDS
TESTING.
GENERAL TANK NOTES:
1. ACCESS SHALL BE LIMITED TO AUTHORIZED PERSONNEL ONLY, WITH APPROPRIATE SIGNAGE.
2. ALL ACCESS LADDERS SHALL BE FITTED WITH A LOCKING SECURITY GATE.
3. ALL ROOF ACCESS HATCHES AND VENTS SHALL BE FITTED WITH OWNER SUPPLIED LOCKS.
4. LEVEL SENSING EQUIPMENT TO BE PROVIDED BY THE OWNER.
5. ALL MATERIALS USED IN CONSTRUCTION SHALL BE ANSI/NSF 61 AND ANSI/NSF 600 CERTIFIED.
6. OVERFLOW WEIR SHALL PROVIDE A MINIMUM OF 1'-0" FREEBOARD.
7. VENTS MUST BE SCREENED WITH 12 OR 16 MESH SCREEN (OPENINGS LESS THAN 0.07 INCHES).
ABOVE GRADE TANK VENTS MUST PROVIDE A MINIMUM OF 24-INCHES OF CLEARANCE FROM THE
ROOF SURFACE TO THE VENT OPENING.
MATERIAL NOTES:
STRUCTURAL STEEL MATERIALS:
1. REFER TO THE DIVISION 05 SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. NEW STRUCTURAL STEEL ITEMS SHALL CONFORM TO THE FOLLOWING STANDARDS AND
REQUIREMENTS.
CARBON STEEL WIDE FLANGES: ASTM A992, FY = 50 KSI
CARBON STEEL CHANNELS, ANGLES, PLATES: ASTM A36, FY = 36 KSI
PIPES: ASTM A53, GRADE B, FY = 35 KSI
HSS: ASTM A500, GRADE B, FY 46 KSI
WELDING ELECTRODES: E7018, AWS A5.1
2. NEW 316 STAINLESS STEEL ITEMS SHALL CONFORM TO THE FOLLOWING STANDARDS AND
REQUIREMENTS.
STAINLESS STEEL BOLT ASSEMBLIES: BOLTS: ASTM F593
STAINLESS STEEL FLAT PLATE: ASTM A240
STAINLESS STEEL SOLID ROUND BAR: ASTM A276
WELDING PROCEDURE SPECIFICATION: AWS D1.6.
WELDING ELECTRODES: E316L-16 (SMAW, AWS A5.4), ER316L (GTAW TIG FILLER ROD, AWS A5.9)
AND ER316L (GMAW MID WIRE, AWS A5.9)
3. FIELD WELDING WILL BE INSPECTED VISUALLY BY THIRD-PARTY OWNER HIRED AWS CERTIFIED
WELDING INSPECTOR.
ALUMINUM:
1. STRUCTURAL ALUMINUM YIELD STRENGTH, FY = 36 KSI.
2. ALUMINUM ALLOY 6061-T6.
3. WELDING PROCEDURE SPECIFICATION: AWS D1.2.
4. WELDING ELECTRODES: ER5356 (AWS A5.10).
SURFACE PREPARATION AND COATINGS:
1. REFER TO SPECIFICATION 09 97 13 FOR SURFACE PREPARATION AND COATING REQUIREMENTS.
2. FIELD APPLIED COATINGS SHALL BE INSPECTED BY OWNER HIRED NACE CERTIFIED INSPECTOR.
ACCESS HATCHES:
1. BILCO 30"x36" ALUMINUM, SINGLE-LEAF ROOF ACCESS HATCH. ALL HATCH HARDWARE AND
COMPONENTS TO BE 316 STAINLESS STEEL.
2. AVOID CONTACT BETWEEN CONCRETE AND ALUMINUM SURFACES TO PREVENT ADVERSE
CHEMICAL REACTION AND PRODUCT FAILURE. INSULATE AREAS BY COATING ALUMINUM
MEMBERS AS REQUIRED IN THE SPECIFICATIONS.
CATHODIC PROTECTION SYSTEM:
1. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM DESIGNED AND INSTALLED BY
QUALCORR ENGINEERING.
STRUCTURE DESIGN LOADS:
1. THE FOLLOWING DESIGN CODES AND STANDARDS WERE USED.
2. DESIGN CODES:
A. INTERNATIONAL BUILDING CODE (IBC), 2018.
B. ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
C. AWWA D100 WELDED CARBON STEEL TANKS FOR WATER STORAGE.
D. API 653 TANK INSPECTION, REPAIR, ALTERATION, AND RECONSTRUCTION.
3. DESIGN LOADS:
A. DEAD LOAD MEMBER SELF WEIGHT
B. ROOF LIVE LOAD 48 PSF
C. MINIMUM ROOF SNOW LOAD 40 PSF (CITY OF CRAIG)
EXPOSURE FACTOR 0.9
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.20
D. WIND
WIND SPEED 115 MPH (3-SECOND GUST)
EXPOSURE B
SURFACE ROUGHNESS B
TOPOGRAPHIC FACTOR 1.0
WIND PRESSURES ±30.0 PSF (SIDEWALL), AWWA D100
±30.0 PSF (ROOF), AWWA D100
E. SEISMIC
OCCUPANCY IV
IMPORTANCE FACTOR, Ie 1.50
SOIL SITE CLASS D, ASSUMED
Ss 0.332g
S1 0.077g
SDS 0.340g
SD1 0.123g
SEISMIC DESIGN CATEGORY B (CITY OF CRAIG)
MAGNETIC FLUX LEAKAGE SCAN AND FLOOR PLATE REPAIR NOTES:
1. FOLLOWING INTERIOR CLEANING, CONTRACTOR TO DRY FLOOR PLATES AND ALLOW ACCESS TO PREMIERE NDT SERVICES, INC. TO PERFORM MFL TESTING. RESULTS WILL BE REVIEWED WITH
OWNER AND ENGINEER. ENGINEER WILL DEVELOP A REPAIR PLAN BASED ON RESULTS OF MFL
SCAN.
2. ALL BOTTOM SURFACE DISCONTINUITIES SHALL BE PATCHED WITH WELDED ON PATCH PLATES PER THE REQUIREMENTS OF API 653-14 AND THE DIRECTION OF THE ENGINEER. TOP SURFACE
DISCONTINUITIES WILL BE REPAIRED WITH WELDED ON PATCH PLATES OR BY DEPOSITION OF
WELD METAL FOLLOWED BY EXAMINATION TESTING IN ACCORDANCE WITH API 653-14, SECTION
12.1.7.3 AND PER DIRECTION OF THE ENGINEER.
3. QUANTITIES LISTED IN THE BID FORM ARE ESTIMATED FOR BIDDING PURPOSES. PER THE
REQUIREMENTS OF API 653-14, FLOOR PATCH PLATE SIZES WILL VARY BASED ON LOCATION OF
DISCONTINUITY TO WELD SEAM, SHELL PLATE, OTHER PATCH PLATES, ETC. PAYMENT
APPLICATIONS SHALL BE BASED ON THE QUANTITY AND TOTAL SQUARE FOOTAGE OF WELDED
ON PATCH PLATES AND NUMBER OF DEPOSITION OF WELD METAL REPAIRS. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING EXISTING CONDITIONS AND QUANTITIES BASED ON ACTUAL FIELD
CONDITIONS AS MARKED BY THE THIRD-PARTY NON-DESTRUCTIVE TESTING COMPANY.
STRUCTURAL STEEL INSTALLATION AND INSPECTION:
1. FURNISH AND INSTALL TEMPORARY BRACING FOR NEW FRAMING AS NECESSARY TO PROVIDE
STABILITY DURING ERECTION AND TO PREVENT DAMAGE OR DISTORTION TO THE FRAME DUE TO
WIND, SEISMIC, OR ERECTION FORCES. REMOVE TEMPORARY BRACING WHEN ERECTION IS
COMPLETE.
2. UNLESS OTHERWISE NOTED, ALL BOLTED CONNECTIONS ARE BEARING TYPE, AND SHALL BE
TIGHTENED TO THE SNUG TIGHT CONDITION.
3. ALL HIGH STRENGTH BOLTS SHALL HAVE THE TURNED PORTION MARKED WITH REFERENCE TO
THE STEEL BEING CONNECTED AFTER THE NUT HAS BEEN MADE SNUG AND PRIOR TO FINAL
TIGHTENING.
4. FIELD WELDING SHALL BE DONE ONLY WHERE SHOWN ON THE DRAWINGS OR SPECIFIED AND
ONLY BY WELDERS CURRENTLY QUALIFIED AND APPROVED FOR THE PROCEDURES USED. NO
WELDING SHALL BE COMPLETED WHEN SURFACES ARE WET, EXPOSED TO RAIN OR WIND, OR
WHEN WELDERS ARE EXPOSED TO INCLEMENT CONDITIONS THAT WILL AFFECT THE QUALITY OF
WORKMANSHIP.
THREADED ANCHOR STUDS, WEDGE ANCHORS, AND EPOXY ADHESIVE:
1. DRILL AND EPOXY ANCHORS: HILTI HEADED ANCHOR STUDS 316 STAINLESS STEEL.
2. WEDGE ANCHORS: HILTI KWIK BOLT TZ2 WEDGE ANCHOR 316 STAINLESS STEEL.
3. EPOXY ADHESIVE SHALL BE HILTI HIT-RE 500 V3.
WELDED STEEL PIPE AND FLANGES:
1. STEEL PIPE FLANGES FOR WATERWORKS SERVICES PER AWWA C207, CLASS B OR D.
WELDED STEEL PIPE, SCHEDULE 40 PER AWWA C200.
TANK SCOPE OF WORK NOTES:
1. THE FOLLOWING IS AN OUTLINE OF THE KEY PROJECT SCOPE OF WORK TASKS. THE COMPLETE
PROJECT SCOPE OF WORK INCLUDES OTHER ITEMS WHICH MAY BE DOCUMENTED IN OTHER
PORTIONS OF THE REHABILITATION DOCUMENTS. THE ACTIVITIES LIST PRESENTS SCOPE OF
WORK ONLY. SEQUENCING OF THE WORK IS THE RESPONSIBILITY OF THE CONTRACTOR. SOME
OF THESE ITEMS ARE CONSIDERED BID ALTERNATES, REFER TO THE BID FORM.
A. FOLLOWING THE OWNER'S DRAINING OF THE TANK, THE CONTRACTOR MAY CREATE
ACCESS TO THE TANK INTERIOR TO BEGIN REHABILITATION WORK BY CUTTING A DOOR
SHEET. A DOOR SHEET SUBMITTAL IS REQUIRED FOR REVIEW AND APPROVAL PRIOR TO
CREATING ACCESS.
B. CLEAN ALL INTERIOR SURFACES AND PIPING. CLEAN AND DRY FLOOR PLATES.
C. PREMIERE NDT SERVICES, INC. TO PERFORM A MAGNETIC FLUX LEAKAGE (MFL) SCAN OF
THE TANK FLOOR PLATES.
D. ENGINEER TO REVIEW THE MFL SCAN RESULTS AND PREPARE A FLOOR PLATE REPAIR
PLAN.
E. INSTALL 1
4" THICK WELDED ON PATCH PLATES PER DEVELOPED REPAIR PLAN. INSTALL
WELD DEPOSITION REPAIRS PER THE FLOOR PLATE REPAIR PLAN.
F. DEMO AND REMOVE EXISTING COLUMN CAPITAL; FABRICATE AND INSTALL BY WELDING
NEW OPEN FRAMING COLUMN CAPITAL.
G. DEMO AND REMOVE EXISTING ROOF VENT AND STEEL RISER; FABRICATE AND INSTALL BY
WELDING NEW VENT RISER AND VENT.
H. DEMO AND REMOVE EXISTING ROOF HATCH AND RISER; FABRICATE AND INSTALL BY
WELDING NEW HATCH RISER AND NEW ROOF ACCESS HATCH.
I. DEMO AND REMOVE EXISTING INTERIOR LADDER; FABRICATE AND INSTALL BY WELDING
NEW INTERIOR LADDER.
J. MODIFY EXISTING OVERFLOW WEIR.
K. SELECTIVELY DEMOLISH EXISTING FLOOR PLATE AROUND DRAIN PIPE; INSTALL BY
WELDING NEW RECESSED DRAIN SUMP.
L. SURFACE PREPARE AND RECOAT THE COMPLETE INTERIOR OF THE TANK AND PIPING PER
SPECIFICATION 09 97 13. INSTALL FLEXIBLE SEALANT TO THE UNDERSIDE OF ROOF PLATE
UNWELDED SEAMS AND ROOF TO SHELL PERIMETER.
M. PROVIDE ACCESS TO THIRD PARTY COATING INSPECTOR FOR SURFACE PREPARATION
AND COATING INSPECTIONS. TO INCLUDE HOLIDAY TESTING OF ALL INTERIOR SURFACES.
N. CURE INTERIOR PER MANUFACTURER REQUIREMENTS. HEAT AND VENTILATION ARE THE
RESPONSIBILITY OF THE CONTRACTOR, IF REQUIRED, TO MEET COMPLETION DATES.
O. COORDINATE DESIGN AND INSTALLATION OF NEW IMPRESSED CURRENT CATHODIC
PROTECTION SYSTEM WITH QUALCORR ENGINEERING.
P. EXTERIOR: PERFORM LEAD ABATEMENT, SURFACE PREPARE AND RECOAT THE COMPLETE
EXTERIOR AND APPURTENANCES PER SPECIFICATION 09 97 13.
Q. EXTERIOR: FABRICATE AND INSTALL A SWINGING AND LOCKING SECURITY GATE AT THE
BASE OF THE EXISTING LADDER CAGE.
R. FOLLOWING FINAL INSPECTION BY OWNER, ENGINEER AND INSPECTOR, PERFORM FINAL
CLEAN AND DISINFECT.
S. EXPOSE CONCRETE RINGWALL AND COMPLETE EXTERIOR JOINT REPAIR. VISCOTAQ TANK
CHIME SEALING SYSTEM. REFER TO TECHNICAL SPECIFICATIONS.
STRUCTURAL
GENERAL NOTES
S001
BID SET
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
SCALE BASED ON FULL-SIZE
22x34 DRAWING SHEET
1/8" = 1'-0"
FLOOR PLAN
SCALE: 1/8" = 1'-0"
N
ROOF PLAN
SCALE: 1/8" = 1'-0"
TANK
TANK INSIDE DIAM 66'-0"
8"Ø CENTER COLUMN
AND FOOTING
EXISTING 24"Ø
SHELL MANWAY
EXISTING 24"Ø
SHELL MANWAY
TANK INSIDE DIAM 66'-0"
ROOF
FRAMING
VIEW
ROOF
SHELL
VIEW
ROOF
FRAMING
VIEW
ROOF
SHELL
VIEW
NEW 30" x 36" BILCO S-50
ROOF ACCESS HATCH ON
NEW STEEL RISER W/ NEW
INTERIOR LADDER BELOW,
RE: 1 AND 5/S501
NEW 24" ALUMINUM VENT
ON NEW STEEL RISER,
RE: 2/S501 AND S502
0 8' 16'4'B S301
EXISTING WIDE FLANGE ROOF
FRAMING RAFTERS, QTY 34
10"Ø COMMON
INLET/OUTLET W/
6" SILT STOP
8"Ø DRAIN AND NEW
RECESSED DRAIN
SUMP, RE: 3/S501
8"Ø OVERFLOW
A S301
EXISTING EXTERIOR
LADDER AND CAGE
EXISTING ROOF HANDRAIL
TANK
EXISTING 24"Ø
SHELL MANWAY
EXISTING 24"Ø
SHELL MANWAYC
S301
FLOOR AND ROOF
PLANS
S101
BID SET
A S301
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
SCALE BASED ON FULL-SIZE
22x34 DRAWING SHEET
A SECTION
SCALE: 1/4" = 1'-0"
1/4" = 1'-0"
NOTES:
1. PERFORM LEAD ABATEMENT ON EXTERIOR.
2. SURFACE PREPARE INTERIOR AND EXTERIOR OF TANK TO SSPC-SP 10 TO BARE METAL.
3. COAT TANK, PIPING, AND APPURTENANCES PER SPECIFICATION 09 97 13.
4. INSTALL SIKAFLEX 1A FLEXIBLE SEALANT ON THE UNDERSIDE OF UNWELDED ROOF
PLATES AND THE ROOF-TO-SHELL JOINT.
TANK SECTIONS
S301
TANK INSIDE DIAM 66'-0"
EXISTING
FINISH GRADE
EXISTING W6 ROOF FRAMING
GIRDERS, QTY OF 34
3/4
EXISTING 8"Ø
CENTER COLUMN
SLOPE SLOPE
EXISTING FLOOR PLATE
VISCOTAQ TANK CHIME REPAIR,
RE: SPECIFICATIONS
TANK
NEW 24"Ø ALUMINUM
ROOF VENT, RE: S502
NEW 24"Ø CARBON
STEEL RISER, RE: 2/S501
DEMO EXISTING SOLID CONE CAPITAL
AND INSTALL NEW OPEN FRAMING
CAPITAL, RE: B/S301
B SECTION
SCALE: 3/8" = 1'-0"
0 4' 6'2'
0 4' 8'2'
3/8" = 1'-0"
NEW 24"Ø ALUMINUM VENT,
RE: S502
NEW 24"Ø CARBON
STEEL RISER
3'-0" EXISTING ROOF PLATE BEYOND
L4x4x1/4 ROLLED ANGLE
L3x3x3/16 - QTY 8 EQUALLY
SPACED AROUND ROLLED ANGLE
1/4
5'-0"
2'-6"
NOTES:
1. HEIGHT OF NEW COLUMN CAPITAL SHALL BE
FIELD VERIFIED PRIOR TO FABRICATION.
HEIGHT TO MATCH REMOVED CONE.
2. OPEN FRAMING CENTER COLUMN CAPITAL
SHALL BE FABRICATED FROM CARBON
STEEL (ASTM A36) ANGLES AND FLAT PLATE.
3. SURFACE PREPARE FRAMING TO SSPC-SP 10
TO BARE METAL TO REMOVE MIL SCALE.
4. COAT PER SPECIFICATION 09 97 13.
C SECTION
SCALE: 1/4" = 1'-0"
20'-0"
SHELL
HEIGHT
EXISTING ROOF PLATE
3/4
EXISTING TANK
FLOOR EXISTING FINISH GRADE
CARBON STEEL RISER FLANGE TO
MATCH VENT FLANGE, RE: S502
6"
EXISTING ROOF HANDRAIL,
EACH SIDE OF LADDER
NEW 30" x 36" BILCO S-50 ALUMINUM
ACCESS HATCH ON NEW CARBON
STEEL RISER, RE:1/S501
3'-0"
6"
3'-6" EXISTING EXTERIOR
LADDER AND CAGE
INSTALL FABRICATED SWINGING
AND LOCKING SECURITY GATE,
RE: 4/S501
EXISTING TANK SHELL
EXISTING ROOF PLATE
EXISTING 8"Ø COLUMN
20'-0"
SHELL
HEIGHT
33'-0" 33'-0"
6" DEMO AND REMOVE
3'-0"
3'-10"
1'-0" FREEBOARD
*SELECTIVELY DEMOLISH THE
TOP 6" OF THE EXISTING
OVERFLOW WEIR TO PROVIDE A
MINIMUM OF 12" OF FREEBOARD
FROM ROOF TO SHELL JOINT
EXISTING CIRCULAR WEIR
EXISTING WEIR SUPPORTS
EXISTING 8"Ø OVERFLOW PIPE
3/16 3/16 1/4
1" THICK x 18"Ø PLATE
L3x3x3/16, QTY 8, EQUALLY
SPACED AS SHOWN
1" THICK x
18"Ø PLATE
8"Ø CENTER
COLUMN,
BELOW
BID SET
NEW INTERIOR
LADDER, RE:5/S501
5"
2 - 1/2"Ø BOLTS PER RAFTER
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
1 DETAIL
SCALE: 1" = 1'-0"
SCALE BASED ON FULL-SIZE
22x34 DRAWING SHEET
2 DETAIL
SCALE: 1/2" = 1'-0"
3/8" = 1'-0"
1" = 1'-0"
HATCH
EXISTING
HANDRAIL
GASKET PROVIDED BY
HATCH MANUFACTURER
STAINLESS STEEL
BOLTS; QTY AND SIZE
PER HATCH
MANUFACTURER
30" x 36" ALUMINUM BILCO
S-50 ACCESS HATCH
SELECTIVELY DEMO
EXISTING ROOF PLATE TO
CREATE A 30" x 36" OPNG AT
EXISTING 24" SQUARE OPNG
NOTES:
1. HATCH RISER SHALL BE FABRICATED OF ASTM A36 CARBON STEEL 1/4" FLAT PLATE.
2. PROVIDE A MINIMUM OF 4" OF CLEARANCE ON THE LOW SIDE.
3. FRAME FLANGE TO BE 3-1/2" WIDE TO MATCH BILCO HATCH FLANGE.
4. WELD FRAME TO EXISTING ROOF PLATE.
5. FIELD LOCATE OPENING BETWEEN ROOF FRAMING RAFTERS, CONFIRM LOCATION
WITH OWNER AND ENGINEER PRIOR TO INSTALLATION.
6. SURFACE PREPARE RISER FRAME TO SSPC-SP 10 TO REMOVE MIL SCALE. COAT PER
SPECIFICATION 09 97 13.
7. ALUMINUM HATCH TO BE SURFACE PREPARED AND COATED PER SPECIFICATION 09
97 13.
NEW ALUMINUM VENT,
RE: S502
TANK
1/4
NEW 1/4" STEEL RISER
NOTES:
1. VENT RISER SHALL BE FABRICATED OF ASTM A36 CARBON STEEL 1/4" FLAT
PLATE OR SCHEDULE 40 STEEL PIPE.
2. WELD RISER TO EXISTING ROOF PLATE.
3. SURFACE PREPARE RISER TO SSPC-SP 10 TO REMOVE MIL SCALE. COAT PER
SPECIFICATION 09 97 13.
4. ALUMINUM VENT TO BE SURFACE PREPARED AND COATED PER SPECIFICATION
09 97 13.
5. REFER TO DRAWING SHEET S502 FOR VENT DETAILS.
0 1' 2'1/2'
1/4
1'-6"
FIELD VERIFY
3'-0"
4" 3'-0"
6"
3'-6"
2'-0"
DIAM
MIN 1/8" NEOPRENE GASKET
8 - 3/4"Ø SS BOLTS
3 DETAIL
SCALE: 1/2" = 1'-0" 5 DETAIL
SCALE: 3/8" = 1'-0"
NOTES:
1. ALL LADDER COMPONENTS SHALL BE ASTM A36 CARBON STEEL.
2. FIELD VERIFY DIMENSIONS PRIOR TO PREPARATION OF FABRICATION SHOP DRAWINGS.
3. LENGTH OF SUPPORTS WILL DEPEND ON LOCATION OF FIELD LOCATED HATCH OPENING.
4. FIELD WELD TO EXISTING TANK SHELL.
5. SURFACE PREPARE NEW EXTERIOR LADDER AND SUPPORTS TO SSPC-SP 10 TO BARE
METAL TO REMOVE MIL SCALE.
6. COAT PER SPECIFICATION 09 97 13.
20 LADDER
RUNGS, EQ
SPACED, 12"
MAX SPACING
LADDER
1'-4"
20'-11"
1/4
LADDER SUPPORT,
3/8" x 3" x 2'-0" PLATE
SIDE RAILS,
3/8" x 3" PLATE
3'-0"
6 LADDER
SUPPORTS EQ
SPACED AT 3'-6"
EXISTING
FLOOR PLATE
1'-11" FIELD VERIFY 9"
4"
1/2" = 1'-0" 0 2' 4'1'
0 4' 6'2'
PIPE
PIPE
EXISTING CONCRETE
RINGWALL
EXISTING CONCRETE
RINGWALL
EXISTING TANK SHELL
EXISTING TANK SHELL
1/4" x 24"Ø DOUBLER PLATE
4'-0"
4'-0"
~3'-0" FIELD VERIFY
EXISTING 8"Ø DRAIN
EXISTING FLOOR PLATE
6"
NOTES:
1. PRIOR TO CUTTING FLOOR PLATE, AND PRIOR TO FABRICATION OF NEW RECESSED STEEL DRAIN
SUMP, FIELD MEASURE TO LAYOUT DIMENSIONED SUMP.
2. USE 14" PLATE TO FABRICATE RECESSED DRAIN SUMP AND DOUBLER PLATES.
3. SEAL WELD ALL AROUND DRAIN PIPE AND FABRICATED DRAIN SUMP.
4. THIRD PARTY WELD INSPECTOR TO INSPECT WELDS AND PERFORM DYE-PENETRATE TESTING.
5. TRIM EXISTING DRAIN PIPE TO APPROXIMATELY 1" ABOVE NEW DOUBLER. PLATE.
TANK DETAILS
S501
BID SET4 DETAIL
SCALE: 1" = 1'-0"
1'-33 4"
R1'-2"
HINGE
HINGE
FABRICATE SECURITY GATE
FROM 1/4" x 2" FLAT PLATE
NOTES:
1. FIELD VERIFY EXISTING LADDER CAGE DIMENSIONS.
2. FABRICATE A CARBON STEEL LOCKING AND SWINGING SECURITY GATE TO CONNECT TO
AND FIT WITHIN THE EXISTING LADDER CAGE.
3. SURFACE PREPARE RISER TO SSPC-SP 10 TO REMOVE MIL SCALE. COAT PER SPECIFICATION
09 97 13.
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
PO BOX 3741
BASALT, COLORADO 81621
COLORADO DEPARTMENT OF PUBLIC
HEALTH
4300 CHERRY CREEK DRIVE SOUTH, B2
DENVER, COLORADO 80246-1530
GLEN ERIE SOUTH
WATER STORAGE
TANK
REHABILITATION
PROJECT
CITY OF CRAIG
300 W 4TH ST
CRAIG, COLORADO 81625
Revision/Issue Date
Checked By:
Drawn By:
Project No.:
No.
2025-COC-GES
TAW
WWS
05.19.2025
SCALE BASED ON FULL-SIZE
22x34 DRAWING SHEET
1-1/2" = 1'-0"
0 1' 1 1/2'1/2'EXISTING TANK ROOF PLATE
ASTM A36 1/4"
STEEL PLATE OR
24"Ø SCHEDULE 40
STEEL PIPE
1/4 1/4
3/16 3/16A
S502
VENT
ASTM A36 1/4"
STEEL PLATE
1/8" GASKET
8-1/2"Ø x 2" STAINLESS STEEL BOLTS
6061 ALUMINUM 0.19" PLATE
4" 6061 ALUMINUM PLATE
1/4" STAINLESS STEEL ROLLED PLATE
HOLE FOR OWNER SUPPLIED PADLOCK
B S502
DETAIL 1
DETAIL 2
A SECTION
SCALE: 1-1/2" = 1'-0"
1 DETAIL
SCALE: 1-1/2" = 1'-0"
B SECTION
SCALE: 1-1/2" = 1'-0" C SECTION
SCALE: 1-1/2" = 1'-0"
2 DETAIL
SCALE: 1-1/2" = 1'-0"
24" INSIDE DIAMETER
3'-0"
6"
4 - 14" WIDE x 12" TALL
OPENINGS
4" 6061 ALUMINUM
PLATE
VENT
6061 ALUMINUM
0.19" PLATE
C S502
B S502
A S502
16 MESH STAINLESS STEEL
SCREEN; ATTACH TO RISER
WITH 2 PIPE CLAMPS
2'-3"
24" INSIDE
DIAMETER
8"
STAINLESS STEEL SCREEN:
316 STAINLESS STEEL MESH SCREEN: 16 x 16 SQUARE, 0.0455" x 0.0455" OPENING, 0.018" THICK WIRE DIAMETER, 51% OPEN AREA AS MANUFACTURED BY McNICHOLS OR
APPROVED EQUAL.
BIRD SCREEN:
3/4-INCH NO. 051 FLATTENED EXPANDED ALUMINUM
METAL BIRD SCREEN AS MANUFACTURED BY McNICHOLS
OR APPROVED EQUAL.
BIRD SCREEN
VENT
1/4" STAINLESS
STEEL ROLLED PLATE
1" TALL x 18" THICK
PLASTIC; RIVET TO
ALUMINUM RISER
6061 ALUMINUM
0.19" PLATE
2'-10" OUTSIDE
DIAMETER
2'-4"
3'-0" OUTSIDE
DIAMETER
4"
2'-0" I.D.
2'-7" O.D.
2'-5" BOLT DIAM.
8 - 9/16"Ø HOLES,
EQUALLY SPACED
STEEL FLANGE: ASTM A36
1/4" STEEL PLATE
ALUMINUM FLANGE: 6061
ALUMINUM 1/4" PLATE
6061 ALUMINUM 0.19" PLATE
STAINLESS STEEL 16 MESH SCREEN
VENT
1'-10" INSIDE
DIAM
2'-03
8" OUTSIDE
DIAMETER
VENT
6061 ALUMINUM
1" x 1/4" FLAT BAR
3/16 3/16
6061 ALUMINUM
0.19" PLATE
1"Ø SOLID BAR 6061
ALUMINUM
3/16 3/16
2'-03
8" OUTSIDE
DIAM
VENT DETAILS
S502
BID SET
AutoCAD SHX Text Prepared For
AutoCAD SHX Text Project
AutoCAD SHX Text Client
AutoCAD SHX Text Sheet No
| Sheets and Views |
| G000 COVER SHEET |
| G001 GENERAL NOTES AND ABBREVIATIONS |
| G002 GENERAL SITE PLAN |
| S001 STRUCTURAL GENERAL NOTES |
| S101 FLOOR AND ROOF PLANS |
| S301 TANK SECTIONS |
| S501 TANK DETAILS |
| S502 VENT DETAILS |
File details come from the government source that posted it. Updated .