This document contains General Specifications for Cummins Inc. Rugged Mobile Power (RMP) generators across five power ratings, establishing the technical requirements for a potential future federal procurement. The Government seeks commercially available, HEMP-hardened generators in 5 kW, 10 kW, 15 kW, 30 kW, and 60 kW configurations to support mission-critical C4I and NC3 systems across 42 OCONUS USAFE installations. The procurement mechanism is anticipated to be a flexible, multiple-year Blanket Purchase Agreement (BPA) with undetermined quantities; this is currently a Sources Sought pre-solicitation for market research purposes, not a formal solicitation.

All generators must conform to MIL-DTL-32496, operate across environmental extremes from -50°F to 135°F, comply with MIL-STD-461F EMC standards, and be multi-fuel capable (JP-8, JP-4, DF-1, DF-2, DF-A). The 10 kW configuration must be either the Cummins 10RMP-1040A or 10RMP-1041A model, or an equivalent that has successfully passed HEMP survivability testing at NAWCAD Patuxent River or an equivalent DoD HEMP qualification program. All generators must feature rugged 4-cycle industrial diesel engines, 24-volt NATO slave connection starting systems, NBC contamination survivability, low infrared and acoustic signatures, rated power output at altitude, and automatic load control with 3% voltage regulation. The Army Corps of Engineers is the contracting agency, with the Air Force identified as the end-user agency. No response deadline, pricing information, or award timeline is specified in this specifications document.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

General Specifications Table 1. The generators shall conform to the following technical specifications across all five RMP models:

Parameter
5 kW
10 kW
15 kW
30 kW
60 kW
Model
5RMP-1030A
10RMP-1040A/1041A
15RMP-1050A/1051A
30RMP-1060A/1061A
60RMP-1070A/1071A
Power (60 Hz)
5 kW
10 kW
15 kW
30 kW
60 kW
Power (50 Hz)
5.2 kVA
10.4 kVA
15.6 kVA
31 kVA
62.5 kVA
Frequency
50/60 Hz
50/60/400 Hz
50/60/400 Hz
50/60/400 Hz
50/60/400 Hz
Dimensions (L×W×H)
45×32×36 in
55×32×36 in
65×36×53 in
75×36×53 in
82×36×53 in
Weight (dry)
780 lbs (355 kg)
1010 lbs (459 kg)
1550 lbs (705 kg)
2215 lbs (1007 kg)
2985 lbs (1357 kg)

https://www.cummins.com/en-na/generators/products/rugged-mobile-power

Table 2. Additional RMP Model Specifications The Government’s minimum requirement for the 10 kW configuration is the Cummins Rugged Mobile Power (RMP) model 10RMP‑1040A or 10RMP‑1041A, or an equivalent Cummins RMP 10 kW configuration that has been subjected to and successfully passed HEMP survivability testing at NAWCAD Patuxent River or an equivalent formal DoD HEMP qualification program, with test results and certifications acceptable to the Government.

Common specifications for all models:

Parameter
Specification
Manufacturer
Cummins Inc. (BRAND NAME OR EQUAL)
Military Standard
MIL-DTL-32496
Fuel Type
Multi-fuel capable (JP-8, JP-4, DF-1, DF-2, DF-A)
Operating Environment
All environmental extremes (-50°F to 135°F)
EMC Compliance
MIL-STD-461F

https://www.cummins.com/en-na/generators/products/rugged-mobile-power

Table 3: Common Technical Specifications (All Models) Additional required features include:

• Rugged 4-cycle industrial diesel engine

• 24-volt starting system with NATO slave connection

• Nuclear, biological, and chemical (NBC) contamination survivability

• Battlefield mobility and ruggedized construction

• Low infrared and acoustic signatures

• Rated power output at altitude

• Automatic load control and voltage regulation (±3% no-load to full-load)