Generac_100KW_Natural_Gas_-_Spec.pdf_FY26.pdf
PDF 48 KB Posted
- Attached to
- Generac Generator - Mayfield Village
- Solicitation number
- SRC0000034835
- Issued by
- Cuyahoga County, Melrose Village, Ohio
About this file
This is a product specification document for a Generac 100 kilowatt natural gas-powered generator intended for the Mayfield Village Fire Department in Mayfield Village, Ohio. The project involves the purchase of a replacement generator with associated installation and removal of the existing unit located at 770 S.O.M Centre Drive, Mayfield Village, Ohio 44143.
The specified generator is a 100 kilowatt unit rated for 120/208 volts, three-phase output operating at 60 hertz frequency on natural gas fuel. Key specifications include a permanent magnet excitation system, EPA certification, standard aluminum enclosure with white paint finish, 925CCA 4D battery with 10-amp battery charger, standard 1500-watt block heater, H100 control panel, standard main load circuit breaker (MLCB), 400-amp UL circuit breaker, and a 21-light annunciator panel with eight function relays. Additional accessories include remote emergency stop capability, 120-volt GFCI outlet, 240-volt outlet, and flexible fuel line. The generator is designated for standby duty with a standard one-year parts/labor/travel and two-year parts warranty. The specification document does not contain information regarding pricing, response dates, bid submission deadlines, site visits, bidder meetings, award dates, contract term, funding sources, or other procurement timeline details.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Generac 100KW Natural Gas-Powered Generator - Spec
100 KW 120/208 Generac Outdoor Generator
AGENCY APPROVAL: Select Type: - UL2200
VOLTAGE: Select One: - 120/208 3 phase
FUEL: Select Type: - Natural Gas 7-11"
EXCITATION: Select Type: - Permanent Magnet Excitation
KW: Select desired Rating: - 100 KW
REGULATORY OPTIONS: Select: - EPA Certified
ENCLOSURE: Select Type: - STD Enclosure - Aluminum
ENCLOSURE: Opt Accessories: - No Enclosure Accessory
ENCLOSURE: Select Paint Color: - White
ALTERNATOR: Optional Upsize: - No Alternator upsize
ALTERNATOR: Select Size: - 100 KW
BATTERY: Select Type: - 925CCA, 4D Inst
BATTERY: Select Charger Type: - 10 Amp Battery Charger
BLOCKHEATER: Select Type: - Block heater STD 1500W
MLCB: Select Type/Accs: - Std MLCB
ACCESSORIES: Alarm Relay: - No Alarm Relay Panel
ACCESSORIES: Annunciator: - 21 Light Ann-Surf W/ 8 Fun Rly
ACCESSORIES: Emergency stop: - Remote E-Stop - Surface
ACCESSORIES: Electrical: - No Light Kit
ACCESSORIES: Misc: - 120V GFCI and 240V Outlet
ACCESSORIES: Misc: - Flex Fuel Line
MANUAL: Select # of Copies: - Std set of 3 Manuals
WARRANTY Options: - STANDARD - 1YR P/L/T, 2 YR P
SPECIAL OPT select if required - Special Options NOT required
Emission Compliance Period - NA
Subtransient Values - 0.15
Transient Values - 0.17
UL CIRCUIT BREAKER Size: - 400 A
FLS: Select Output on Tank - N/A Fuel Level Sender Supplied
Catalyst Required? - CATALYST REQUIRED
CONTROL PANEL: - H100 Control Panel
DUTY: Select Type: - Standby
ENCLOSURE: Heater: - NONE
FREQUENCY: Select One: - 60 Hz
File details come from the government source that posted it. Updated .