GEN_As-Builts_JCI_AUMS_7.13.18.pdf

PDF 2 MB Posted

Attached to
Z2DA--* T4 554-23-110 Reconfigure and Repair AUMS Meters (VA-22-00091334)
Solicitation number
36C25922Q0650
Issued by

View the file

Other files

File Type Posted
010000 - General Requirements.docx DOCX document
013216.15 - Project Schedules.docx DOCX document
014219 - Reference Standards.docx DOCX document
DRAFT ICRA Form.docx DOCX document
017419 - Construction Waste Management.doc DOC document
AUMS Meter Recommission List.xlsx XLSX spreadsheet
000110 - Table of Contents.docx DOCX document
220711 - Plumbing Insulation.docx DOCX document
013526 - Safety Requirements.docx DOCX document
36C25922Q0650_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Kiewit-Turner a Joint Venture

Project Name:

Subcontractor Name: Submittal Date:

Contact Name: E-mail: Return By Date:

Contact Phone(s): Review Days: 7

Number: Name:

1.8 A N/A Y N Y Y

X

7200 S. Alton Way, Suite A-300, Englewood, CO 80112

Phone: 303-930-9000 FAX: 303-930-9001 thomas.b.schottgen@jci.com 07/23/18

Reviewed By DateEvan Brophy 7/16/2018

Submittal is in Compliance

Submittal is in Compliance with Variances from Specifications Evan Brophy Signature

SUBMITTAL INDEX & COVER SHEET

Department of Veteran's Affairs

Replacement Medical Center

Johnson Controls, Inc. 07/16/18

Thomas Schottgen

303-548-8106

Specification Section: 25 10 10 GEN Advanced Utility Metering System

S p e c S u b m it ta l

P a ra g ra p h

S p e c P ro d u c t

P a ra g ra p h

S p e c if ie d o r

L is te d

M a n u fa c tu re r?

I n

T h is P a c k a g e

Johnson Controls, Inc. Closeout Submittals

Submittal Type

Submittal Item Description Manufacturer M e e ts

A ll S p e c

R e q u ir e m e n ts

E x c e p ti o n s o r

V a ri a n c e s f ro m

S p e c

A p p ro v e r

In fo rm a ti o n

N e e d e d

SubmittalIndexForm_041009 Page 1 of 1

Date: July 13, 2018

BUILDING AUTOMATION SYSTEM

AS-BUILT DRAWINGS

Denver Replacement VA Medical Center Section 25 10 10

AUMS

As-Built

Submitted To:

Jim Johnson

Kiewett - Turner A Joint Venture 13611 E. Colfax Ave.

Aurora, CO 80045

Submitted By:

Jacob Tateoka

Systems Engineer

JCI Contract: 3429-0001

Johnson Controls, Inc.

3250 Quentin Street, Suite 112

Aurora, CO 80011 Tel: 303-932-3712 Fax: 813-635-2238

STAMPS

Creating a better climate for business.

Environmental Control System

Air Conditioning

Heating

Diagnostic Services

Coil Cleaning

Refrigeration

Automatic Temperature Controls

Facility Management Systems

Fire Management

Security Management

Building Operations and Management

Water Treatment

Electrical Equipment

Emergency Generator / Lighting Equipment

Industrial Controls / Recording / Indication Equipment

Facility Management System

Air and Water System Balancing

Fire Management System

Security System

Lighting Services

Instrumentation System Installation

Building Operations Management

Energy Conservation Control

Training Programs

Performance Contracting

Planned Service Agreements

LEGEND

2/183

Wire Symbol indicating:

Cable number (3), Number of wires and size

(E.G. 2 #18 wires)

S

Main Air Supply Tube at 20 PSIG

D-N 15-20

Dual Air Supply Tube at

15/20 PSIG

Day=15, Night=20

S

High Pressure Air

Supply Tube at 80 PSIG

Air line or Electrical

Wire

Connected Lines or

Wires

Crossing Lines or

Wires, Not Connected

Pneumatic Tube indicating Tube Number

2/18

Wire Symbol indicating:

number of wires and size (E.G. 2 #18 wires)

Electrical Wire Terminal with Appropriate

Number

Item Located on Panel

Face

In-Line Restrictor

Opposed Blade

Damper

Parallel Blade

Damper

Air Flow Measuring

Station

Filter

Humidifier

Fan

Pump

Heating or Cooling Coil

Ductwork or Piping with

Flow Direction Shown

Drawing Revision

Symbol with

Appropriate Number

Gage

Current Sensing Switch or Combination Current

Sensing switch &

Command Relay

Duct Detector

(Smoke, CO, CO2)

2-Way Valve with

Actuator

N C

3-Way Valve with

Actuator

N 0

C N C

Vapor Tension

Temperature Sensing

Element (Low Limit)

Vapor Tension

Element (Hi Limit)

Paddle Type Flow

Switch

Pressure Sensing

Device

Bulb Type Temperature

Sensing Element

Located inside

Separable Socket/Well

Strap-on Bulb Type

Element

Combination Bulb Type

Element and Humidity

Sensor (Duct Mount)

Humidity Sensing

Element Located under

Shield in Outside air

Located under Shield in

Outside air

Device H

C N O

N O

Denver Replacement VA Medical Center

PROJECT TITLE

ARCHITECT

H+L Architecture 1755 Blake Street

Denver, CO 80202

Phone: 303.298.4700

ENGINEER

Cator, Ruma & Associates 896 Tabor Street

Lakewood, CO 80401

Phone: 303.232.6200

MECHANICAL CONTRACTOR

RK Mechanical

3800 Xanthia St

Denver, CO 80238 Phone: 303.355.9696

ELECTRICAL CONTRACTOR

Sturgeon Electric Company 12150 E. 112 th Avenue

Henderson, CO 80640

Phone: 303-286-8000

3429-0001

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

DATE

Branch Information

CONTRACT NUMBER

E. Daniels

APPLICATION ENGINEER

7/1/2013

PROJECT MANAGERSALES ENGINEER

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

G. SonjuS. Nixon

Advanced Utility Monitoring System

N/A 4 CON Dwg and FO Meters 7/28/2015 MJS

SF1-FLT

Wire Symbol indicating:

Device Software or Tag

Name

PAGE DESCRIPTION

1000-1.00 AUMS RFI Index Page 1

2000-1.00 AUMS Network Layout

4000-1.00 Steam Meter Wiring 4001-1.00 Hot Water BTU Meter Wiring 4002-1.00 Solar Water BTU Meter Wiring 4003-1.00 Snowmelt Water BTU Meter Wiring 4004-1.00 Condensate BTU Meter Wiring

5000-1.00 Chilled Water BTU Meter Wiring 5001-1.00 Chilled Water Meter Wiring

8000-1.00 Natural Gas Meter Wiring

8001-1.00 AUMS Electrical Meters 8001-1.50 CON Electrical Meter Wiring 8001-2.00 RES Electrical Meter Wiring 8001-3.00 DAT North (A) Electrical Meter Wiring 8001-4.00 DAT South (B) Electrical Meter Wiring 8001-5.00 IBS Electrical Meter Wiring 8001-6.00 IBN Electrical Meter Wiring 8001-7.00 ENC Electrical Meter Wiring 8001-8.00 CBN Electrical Meter Wiring 8001-9.00 CBC Electrical Meter Wiring 8001-10.00 CBS Electrical Meter Wiring 8001-11.00 PSN Electrical Meter Wiring 8001-12.00 PVN Electrical Meter Wiring 8001-13.00 PVS Electrical Meter Wiring

9000-1.00 Domestic Water Meter

11000-1.00 AUMS Meter Schedule 11000-2.00 AUMS Meter Schedule 11000-3.00 AUMS Meter Schedule 11000-4.00 AUMS Meter Schedule 11000-5.00 AUMS Meter Schedule

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

5A

N/A 5A Multiple Changes 11/13/2015 MJS

Berg Sumittals 6 JSI-091 and General Updates 1/16/2016 MJS

Field 15 As-Built 10/27/2017 SM

Advanced Utility Monitoring System (AUMS)

Creating a better climate for business.

Environmental Control System

Air Conditioning

Heating

Diagnostic Services

Coil Cleaning

Refrigeration

Automatic Temperature Controls

Facility Management Systems

Fire Management

Security Management

Building Operations and Management

Water Treatment

Electrical Equipment

Emergency Generator / Lighting Equipment

Industrial Controls / Recording / Indication Equipment

Facility Management System

Air and Water System Balancing

Fire Management System

Security System

Lighting Services

Instrumentation System Installation

Building Operations Management

Energy Conservation Control

Training Programs

Performance Contracting

Planned Service Agreements

Denver Replacement VA Medical Center

PROJECT TITLE

ARCHITECT

H+L Architecture 1755 Blake Street

Denver, CO 80202

Phone: 303.298.4700

ENGINEER

Cator, Ruma & Associates 896 Tabor Street

Lakewood, CO 80401

Phone: 303.232.6200

MECHANICAL CONTRACTOR

RK Mechanical

3800 Xanthia St

Denver, CO 80238 Phone: 303.355.9696

ELECTRICAL CONTRACTOR

Sturgeon Electric Company 12150 E. 112 th Avenue

Henderson, CO 80640

Phone: 303-286-8000

1000-1.00

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

DATE

Branch Information

DRAWING NUMBER

A. Campos

APPLICATION ENGINEER

10/9/2014

PROJECT MANAGERSALES ENGINEER

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

G. SonjuS. Nixon

Advanced Utility Monitoring System

Rev Variance/KT-RFI# Answered Description Drawings Affected

1 026 (VR #290) 3/14/2014 Removal of Emergency Load Shedding from AUMS Specification Information Only

1 027 (VR #296) 3/26/2014 Server hardware processor speed & HD size revision to match standard offering 2000-1.00

1 028 (VR #295) 3/26/2014 Removal of ASCII communication requirements Information Only

1 029 (VR #289) 3/17/2014 Removal of JCI remote control of breakers Information Only

1 030 (VR #NA) VOID Exclusion of non-standard options for UPS 2000-1.00

1 031 (VR #299) 5/7/2014 Reduction of Workstation UPS backup time Information Only

1 032 (VR #287) 3/17/2014 Exclusion of factory wiring for electrical metering communications Information Only

1 033 (VR #294) 3/26/2014 Timestamps of historical data to be displayed in 1.0 vs 0.1 second increments Information Only

1 034 (VR #288) 3/17/2014 Veris Sub-metering to be Modbus vs Bacnet 8001-1.00

1 035 (VR #297) 5/7/2014 GE Waveform Technical Sample Sizes Modified Information Only

1 2724 (VA #2757) 1/14/2014 Revisions to Steam Meter Design 11001-1.00

1 2732 (VR #2758) 1/14/2014 Revisions to NG Meter Design 11001-2.00

1 5835 (VR #5129) 11/6/2014 ENC – Domestic Water Meters Information Only

1 6228 1/13/2015 ENC – Chilled Water Meter Clarification (adds Meter) Information Only

1 6457 2/25/2015 CAMPUS WIDE – Line Size Reduction For AUMS Steam Meters Information Only

1 6515 3/4/2015 Div 25 – AUMS Domestic Water Meter List Clarification Information Only

1 6612 3/13/2015 ENC - Div 25 - #300 Flange Coordination Information Only

1 6880 4/1/2015 IBN - Div 25 – Steam Meter 05-STM-1 Minimum Flow (Approved) Information Only

1 6879 4/24/2015 VA Wide Server Data Storage (Answered) Information Only

1 7647 7/14/2015 08-CWFM-1 Pipe / Meter Sizing Mismatch 11001-1.00

1 7273 6/9/2015 Confirmation of RAID Hard Drive Storage Information Only

1 7274 6/2/2015 Location of Fieldserver Integrator 8001-1.00

1 8451 n/a Confirmation that Data Reporting to AUMS Corporate Data Center will utilize Information Only the information coordinated with Schneider Electric to match existing data.

1 JSI-91 7/7/14 Removal of the Solar PV meters from monitoring scope. See Title Pg – Rev6

1 10049 4/24/2017 CON-Div25-26-Veris Meter for Panel 10-NLS4 8001-1.50

Creation 1 7/8/2015 MJS

RFI 8451 & JSI-91 1/6/2016 MJS

2 Dates/#s 1/22/2015 MJS

Field 15 As-Built 10/27/2017 SM

AUMS – RFI Index

INTERNET

CONNECTION &

FIREWALL

(Provided by VA)

CON BUILDING

3429-0001

Drawing Title

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 1/14/2014

REFERENCE DRAWING

AUMS Network Layout

JT 10/27/2017

2000-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

PSN BUILDING

PVN BUILDING

AUMS Data Server

CBN BUILDING

Control Center:

11/2/17 at 8:35 AM

Filename: 2000-1.00.vsd Last Modified:

ENC BUILDING

Control Center: LS-203 (06-SV-F3-01)

Workstation #1

SWITCHGEAR AND

ELECTRICAL METERS

WATER

METER

GAS

METER

WM GM

STEAM

METER

SM

BacNet

TYPICAL PER BUILDING

SWITCH

ATS

SWITCH

RMP

(RTU#)

REMOTE

MONITORING

PANEL

EM

Modbus/RTU

SUBSTATION EM

FIBER IN

FIBER OUT

LEGEND

Fiber (N/A)

Protocol: Wiring

Ethernet (8/24)

Modbus RTU (4/18)

FIBER OUT

FIBER IN

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Workstation Field Devices:

Monitor 1 P2412H Dell Professional P2412H - LED monitor - 24"

Printer 1 M551n HP LaserJet Enterprise M551n - printer - color - l

Workstation 1 MS-OFFICE Microsoft Office Suite

1 Optiplex3040 Dell Desktop Computer

1 Symantec Endpoi Symanted Endpoint Virus Protection

2 Viewnode GE Viewpoint Software to monitor Wafeforms

1 Viewpoint GE Viewpoint Software to monitor Wafeforms

AUMS Server Field Devices:

AUMS Server 1 MS-NIE8500-0 NAE-8500 Server

1 Symantec Endpoi Symanted Endpoint Virus Protection

AUMS Server 1 MS-15KUPG-0 15K UPGRADE NX85/LCS85

MOD

HUB

Fieldserver 1

See Drawing:

‘ELEC-1’ for details and BOM

BACnet (3/22)

NAE

AUMS NETWORK RISER DIAGRAM

RFI-7274 4 Field Server 7/14/2015 MJS

Field 15 As-Built 10/27/2017 SM

IBN BUILDING

IBS BUILDING

DAT NORTH

BUILDING

DAT SOUTH

BUILDING

RES BUILDING

CBC BUILDING

CBS BUILDING

PVS BUILDING

Berg Submittals 3 Veris Mtrs moved from Modbus 4/23/2015 MJS

3429-0001

Drawing Title

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Steam Meter Wiring

JT 10/27/2017

4000-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

10/31/17 at 11:20 AM

Filename: 4000-1.00.vsd Last Modified:

H

N

T4

Shield

D-100 Series Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

4-20 mA +

Onicon 2600 Series Meter

Loop Pwr +

Loop Pwr -4-20 mA -

TERMINATE SHIELD AT

D-100. LEAVE SHIELD

UN-TERMINATED AT

THE METER

RJ45CAT5EREFER TO 11000-XXX FOR

TELECOM TERMINATION

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

STEAM - Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Steam Meter 1 F-26xx Onicon Steam Meter

Approved For Contstruction 2 12/30/2014 ED

20/2 – Shielded: AlphaWire

M5365 Or equal.

Field 15 As-Built 10/27/2017 SM

STEAM METER WIRING DETAIL

3 Addition of Wire P/N 10/30/2015 MJS

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Hot Water BTU Meter Wiring

JT 10/27/2017

4001-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

10/31/17 at 2:17 PM

Filename: 4001-1.00.vsd Last Modified:

H

N

T3

BTUS-T

Sig

Ref

Sig

Ref

Shld

Red

Blk

T4

Shield

Freq +

SYSTEM-10 Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

BTUR-T

Red

Blk

Freq -

T5

4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Onicon 3100 Series Meter

9 4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Shield

Freq +

Freq -

S

H

N

TERMINATE SHIELD AT D-100. LEAVE

SHIELD UN-TERMINATED AT THE METER

RJ45CAT5E

REFER TO 11000-XXX FOR

TELECOM TERMINATION

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

HW - Field Devices:

Water Meter 1 F-31xx Onicon Mag Meter

1 System-10 BTU Meter and Comm

Approved For Contstruction 2 12/30/2014 ED

20/6 – Shielded: AlphaWire

M5365 Or equal.

Field 15 As-Built 10/27/2017 SM

HOT WATER BTU METER WIRING DETAIL

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Solar Water BTU Meter Wiring

JT 10/27/2017

4002-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

10/31/17 at 2:17 PM

Filename: 4002-1.00.vsd Last Modified:

H

N

T3

BTUS-T

Sig

Ref

Sig

Ref

Shld

Red

Blk

T4

Shield

Freq +

SYSTEM-10 Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

BTUR-T

Red

Blk

Freq -

T5

4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Onicon 3100 Series Meter

9 4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Shield

Freq +

Freq -

S

H

N

TERMINATE SHIELD AT D-100. LEAVE

SHIELD UN-TERMINATED AT THE METER

RJ45CAT5E

REFER TO 11000-XXX FOR

TELECOM TERMINATION

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

SOLAR HW - Field Devices:

Water Meter 1 F-31xx Onicon Mag Meter

1 System-10 BTU Meter and Comm

3 Addition of Wire P/N 10/30/2015 MJS

20/6 – Shielded: AlphaWire

M5365 Or equal.

Mfgr IOM 4 Supply/Return Temp Terminals 3/23/2016 MJS

Field 15 As-Built 10/27/2017 SM

SOLAR WATER BTU METER WIRING DETAIL

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Snowmelt Water BTU Meter Wiring

JT 10/27/2017

4003-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

10/31/17 at 2:17 PM

Filename: 4003-1.00.vsd Last Modified:

H

N

T3

BTUS-T

Sig

Ref

Sig

Ref

Shld

Red

Blk

T4

Shield

Freq +

SYSTEM-10 Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

BTUR-T

Red

Blk

Freq -

T5

4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Onicon 3100 Series Meter

9 4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Shield

Freq +

Freq -

S

H

N

TERMINATE SHIELD AT D-100. LEAVE

SHIELD UN-TERMINATED AT THE METER

RJ45CAT5E

REFER TO 11000-XXX FOR

TELECOM TERMINATION

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

SNMLT HW - Field Devices:

Water Meter 1 F-31xx Onicon Mag Meter

1 System-10 BTU Meter and Comm

Approved For Contstruction 2 12/30/2014 ED

20/6 – Shielded: AlphaWire

M5365 Or equal.

Field 15 As-Built 10/27/2017 SM

SNOWMELT WATER BTU METER WIRING DETAIL

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Condensate BTU Meter Wiring

JT 10/27/2017

4004-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Filename: 4004-1.00.vsd Last Modified:

H

N

T3

BTUS-T

Sig

Ref

Sig

Ref

Shld

Red

Blk

T4

Shield

Freq +

SYSTEM-10 Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

BTUR-T

Red

Blk

Freq -

T5

4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Onicon 3100 Series Meter

9 4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Shield

Freq +

Freq -

S

H

N

TERMINATE SHIELD AT D-100. LEAVE

SHIELD UN-TERMINATED AT THE METER

RJ45CAT5E

REFER TO 11000-XXX FOR

TELECOM TERMINATION

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

CONDENSATE - Field Devices:

Water Meter 1 F-31xx Onicon Mag Meter

1 System-10 BTU Meter and Comm

Approved For Contstruction 2 12/30/2014 ED

20/6 – Shielded: AlphaWire

M5365 Or equal.

Field 15 As-Built 10/27/2017 SM

CONDENSATE BTU METER WIRING DETAIL

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Chilled Water BTU Meter Wiring

JT 10/27/2017

5000-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

10/31/17 at 2:17 PM

Filename: 5000-1.00.vsd Last Modified:

H

N

T3

BTUS-T

Sig

Ref

Sig

Ref

Shld

Red

Blk

T4

Shield

Freq +

SYSTEM-10 Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

BTUR-T

Red

Blk

Freq -

T5

4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

9 4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Shield

Freq +

Freq -

S

H

N

TERMINATE SHIELD AT D-100. LEAVE

SHIELD UN-TERMINATED AT THE METER

RJ45CAT5E

REFER TO 11000-XXX FOR

TELECOM TERMINATION

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

CHW - Field Devices:

Water Meter 1 F-31xx Onicon Mag Meter

1 System-10 BTU Meter and Comm

Approved For Contstruction 2 12/30/2014 ED

20/6 – Shielded: AlphaWire

M5365 Or equal.

CHILLED WATER BTU METER WIRING DETAIL

Onicon 3100 Series Meter

Field 15 As-Built 10/27/2017 SMField 15 As-Built 10/27/2017 SM

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Chilled Water Meter Wiring

JT 10/27/2017

5001-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Filename: 5001-1.00.vsd Last Modified:

H

N

T4

Shield

Freq +

D-100 Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

Freq -

T5

4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

9 4-20 mA +

AI Common

(B) Scaled +

(B) Scaled -

Freq +

Freq -

H

N

TERMINATE SHIELD AT D-100. LEAVE

SHIELD UN-TERMINATED AT THE METER

RJ45CAT5E

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

CHW - Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

Approved For Contstruction 2 12/30/2014 ED

20/6 – Shielded:

AlphaWire M5365 Or equal.

CHILLED WATER METER WIRING DETAIL

Onicon 3100 Series Meter

Field 15 As-Built 10/27/2017 SM

REFER TO 11000-XXX FOR

TELECOM TERMINATION

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 10/27/2017

REFERENCE DRAWING

Natural Gas Meter Wiring

JT 10/27/2017

8000-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

10/31/17 at 11:37 AM

Filename: 8000-1.00.vsd Last Modified:

H

N

T4

Shield

D-100 Series Enclosure

120V

POWER FEED BY DIV-26

PANEL _______

CIRCUIT ______

4-20 mA +

Onicon 5200 Series Meter

4-20 mA -

TERMINATE SHIELD AT

D-100. LEAVE SHIELD

UN-TERMINATED AT

THE METER

RJ45CAT5EREFER TO 11000-XXX FOR

TELECOM TERMINATION

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

NG - Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Nat Gas Meter 1 F52xx Onicon Nat Gas Meter

24 VDC +

24 VDC -

T5

SCALED +

SCALED -

T4

T5

RED

BLACK

SHIELD

BLUE

BROWN

WHITE

ORANGE

Approved For Contstruction 2 12/30/2014 ED

20/6 – Shielded: AlphaWire

M5365 Or equal.

NOTE:

ENC located XCEL NG meter being provided by XCEL.

Field 15 As-Built 10/27/2017 SM

NATURAL GAS METER WIRING DETAIL

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/11/14

REFERENCE DRAWING

AUMS Electrical Meters

SM 10/27/2017

8001-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

GE Meters

“PQMII” Supplied with gear per Div 26

Low Voltage Switchgear and ATS Switches

DIAGRAM IS SCHEMATIC. DOES NOT

REPRESENT ALL NETWORK TIE INS REQUIRED.

Port1

Port2

Veris Meter

“E50H2” Meters

Supplied with gear per

Div 26

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Field Devices:

Fieldserver 1 FS-8704-03 Driver, Modbus TCP/IP

1 FS-8704-06 Driver, BACnet/IP

1 FS-8790-30 FS-X35 Upgrade to 5,000 points

1 FS-B3510-05 FieldServer Serial/Ethernet Multiport

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

HIGH LEVEL OVERVIEW

THESE METERS AND EQUIPMENT TYPICAL PER BUILDING

To SCADA system

(All work by others)

* Modbus RTU wiring is Belden 9841: 24AWG/2 shielded.

** Modbus/TCP & Bacnet/IP is: CAT6 (RJ45 connection)

*** Gateway Panels are shown on individual building risers with a BOM on those pages.

10/31/17 at 3:17 PM

Filename: 8001-1.00.vsd Last Modified:

JSI064R1 7 Addition of Mains 2/16/2016 MJS

Modbus/RTU

Gateway

Modbus/TCP**

FIELDSERVER

AUMS Data Server Integration (By Johnson Controls)

Modbus/TCP ** BACnet/IP

THIS EQUIPMENT LOCATED IN CBN DATA CENTER

120 VAC

Power

24 VAC

Power 120 VAC

Power

BACnet MS/TP

See DDC Network

Riser Diagrams for BAS

Tie In Locations

Medium Voltage Switchgear

“PQMII” Supplied with gear per Div 26

Port1

Port2

To SCADA system

(All work by others)

GE Meters

MultiNet Gateway

120 VAC

Power L

N

G com

PQMII / GATEWAY SPECIFIC WIRING DETAILS

Network Switches

Typical PQMII Meter On

Trunk

(c

Note 1

NOTE: 120 Ω, 1/4 watt terminating resistor and 1 Nf.

Note 1

Ground once per trunk at gateway only

To IT Closet

Network Switch

Last PQMII Meter On

Trunk

(c

VERIS SPECIFIC WIRING DETAILS

Typical Veris Meter

S (+

Ref FAN410 for grounding information.

Next Veris Device

Previous JCI Bacnet Device

(c o m

(S

NAEs (also used to bring in DDC information)

Network Switches

BACnet IP

Shield

Wire

Anixter Cable # CBL-22/3-FC-PVC (Non Plenum Applications)

Anixter Cable # CBL-22/3-FC-PLN (Plenum Applications)

Anixter Cable# _____ (600V Applications)

Mounted in Data Center –

Wall TBD

THIS EQUIPMENT LOCATED IN ENC

06-

ELEC-3

XCEL Provided “LMR-1”

Pulse Meters

Use same wiring type as all DDC ‘BI’

22/2

JCI Boiler Panel.

22/2

06-

ELEC-4

BLK

WHT

BLU

600V Wiring Where Required.

Next JCI Bacnet Device

BLK

WHT

BLU

(c o m

ORG

YEL

NOTE: EOL resistors still required at last device, even if it is a Veris.

(S h ld

(S h ld

BLU

BACnet/IP

AUMS ELECTRICAL

JSI064R1 7 Veris MS/TP Wire Colors 3/22/2016 MJS

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/26/14

REFERENCE DRAWING

CON Electrical Meter Wiring

JT 10/27/2017

8001-1.50

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Filename: 8001-1.50.vsd Last Modified:

Service Level

01-NHS1

01-NHS3

01-NHS5

01-NHS7

See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet

MS/TP Meters

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 CON 01-NHS1 Service Level CS-239 (01-SV-B2-E1) 1 5031

2 CON 01-NHS3 Service Level CS-205 (12-SV-A7-01) 11 7566

3 CON 01-NHS5 Service Level CS-175 (01-SV-C19-E5) 4 5778

4 CON 01-NHS7 Service Level CS-143 (01-SV-C29-E7) 6 6292

5 CON 01-LSH2 Service Level CS-215 (12-SV-A4-03) 1 5038

6 CON 01-LSH4 Service Level CS-189 (01-SV-C14-E4) 3 5523

7 CON 01-LSH6 Service Level CS-161 (01-SV-C24-E6) 5 6040

8 CON 01-LSH8 Service Level CS-135 (01-SV-C34-E8) 13 8089

9 CON 01-CHS2 Service Level CS-215 (12-SV-A4-03) 1 5039

10 CON 01-CHS4 Service Level CS-189 (01-SV-C14-E4) 3 5524

11 CON 01-CHS6 Service Level CS-161 (01-SV-C24-E6) 5 6032

12 CON 01-CHS8 Service Level CS-135 (01-SV-C34-E8) 13 8090

VERIS METER DETAILED INFO

01-LSH2

01-LSH4

01-LSH6

01-LSH8

01-CHS2

01-CHS4

01-CHS6

01-CHS8

Solar PV Meters No longer in scope6

JSI-91 2 Removal of Solar PV Monitoring 1/6/2016 MJS

CON BUILDING RISER

Solar PV Meters No longer in scope6

RFI-10049 3 Removal of 01-NLS4 5/2/2017 MJS

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/26/14

REFERENCE DRAWING

RES Electrical Meter Wiring

JT 10/27/2017

8001-2.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

02-ATS-LS1 (Mod Addr: 6)

02-ATS-SB1 (Mod Addr: 14)

02-ATS-EQ1 (Mod Addr: 8)

02-ATS-EQ2 (Mod Addr: 10)

02-ATS-EQ3 (Mod Addr: 12)

Gateway Panel (16W x 20H x 6.5"D)

(~20 lbs)

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Field Devices:

EOL 2 EOL-RSTR EOL BACnet Resistor

Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

Modbus RTU

10/31/17 at 2:17 PM

Filename: 8001-2.00.vsd Last Modified:

Berg Submittals 3 Veris Mtrs moved from Modbus 7/14/2015 MJS

Penthouse

Lower Levels

EOL

02-NHP1 Feed

02-NHP2 Feed

02-NH31 Feed

02-NH21 Feed

02-NLDP1 Feed

02-NLDP2 Feed

02-NH11 Feed

02-NHS1 Feed

02-CLDP1 Feed

02-CLDP2 Feed

02-NDCP (Mod Addr: 3)

02-EMDCP (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 RES 02-NHP1 Penthouse BP-107 (02-PH-D3-E1) 23 10650

2 RES 02-NHP2 Penthouse BP-109 (02-PH-F3-E1) 19 9616

3 RES 02-NH11 Level 1 B1-106 (02-01-B2-E1) 15 865021

4 RES 02-NH21 Level 2 B2-104 (02-02-B2-E1) 16 8856

5 RES 02-NH31 Level 3 B3-118 902-03-G2-E2) 17 9241

6 RES 02-NHS1 Service Level BS-159 (02-SV-G2-E1) 14 8483

7 RES 02-NLDP1 Penthouse BP-107 (02-PH-D3-E1) 23 10649

8 RES 02-NLDP2 Penthouse BP-109 (02-PH-F3-E1) 19 9617

9 RES 02-CLDP-1 Penthouse BP-107 (02-PH-D3-E1) 23 10651

10 RES 02-CLDP-2 Penthouse BP-107 (02-PH-D3-E1) 23 10652

RES BUILDING RISER

Switch

Fiber Network

Modbus/IP

VERIS METER DETAILED INFO

See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet

MS/TP Meters

See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet

MS/TP Meters

4 Addition of Modbus Addressing 3/25/2016 MJS

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 3/1/14

REFERENCE DRAWING

DAT - North (A) Electrical Meter Wiring

JT 10/27/2017

8001-3.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

03-NDCP3 (Mod Addr: 3)

03-ATS-CR3 (Mod Addr: 14)

03-ATS-EQ3 (Mod Addr: 16)

03-ATS-EQ4 (Mod Addr: 18)

03-ATS-EQ5 (Mod Addr: 20)

03-ATS-EQ6 (Mod Addr: 24)

03-ATS-EQ8 (Mod Addr: 22)

Elec Gateway Panel (16W x 20H x 6.5"D)

(~20 lbs)

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Steam Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Steam Meter 1 F-26xx Onicon Steam Meter

CHW Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

Field Devices:

EOL 2 EOL-RSTR EOL BACnet Resistor

Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

10/31/17 at 2:14 PM

Filename: 8001-3.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

03-NHS5

03-NH15

03-NH25

03-NH35

03-NHP5

03-NLP5

03-NLP6

03-NLP7

Penthouse

Lower Levels

03-ATS-LS2 (Mod Addr: 12)

03-EMDCP2 (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 DAT 03-NHS5 Service Level FS-126 (03-SV-F1-E1) 25 11317

2 DAT 03-NH15 Level 1 F1-334A (03-01-F1-E2) 26 11557

3 DAT 03-NH25 Level 2 F2-262 (03-02-F1-E2) 85 26656

4 DAT 03-NH35 Level 3 F3-286 (03-03-F1-E2) 29 12212

5 DAT 03-NHP5 Penthouse FP-103 (03-PH-C4-E2) 33 13205

6 DAT 03-NLP5 Penthouse FP-103 (03-PH-C4-E2) 33 13204

7 DAT 03-NLP6 Penthouse FP-103 (03-PH-C4-E2) 33 13206

8 DAT 03-NLP7 Penthouse FP-103 (03-PH-C4-E2) 33 13207

Removal of Solar PV Monitoring6

Note:

• Original labels match contract ‘one-lines’

• Alternate Labels match the floorplan layout (and actual equip naming), and are matched as best as possible by JCI without any given documentation.

DAT - NORTH (A) BUILDING RISER

VERIS METER DETAILED INFO

See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet

MS/TP Meters

Switch

Fiber Network

Modbus/IP

See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet

MS/TP Meters

7 Addition of Modbus Addressing 3/25/2016 MJS

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/28/14

REFERENCE DRAWING

DAT - South (B) Electrical Meter Wiring

JT 10/27/2017

8001-4.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

03-ATS-EQ1 (Mod Addr: 30)

03-ATS-EQ2 (Mod Addr: 32)

03-ATS-EQ7 (Mod Addr: 34)

03-ATS-LS1 (Mod Addr: 36)

03-ATS-CR1 (Mod Addr: 26)

03-NLP3

03-NLP4

03-ATS-CR2 (Mod Addr: 28)

03-NLP1

03-NLP2

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Steam Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Steam Meter 1 F-26xx Onicon Steam Meter

CHW Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

NG - Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Nat Gas Meter 1 F26xx Onicon Nat Gas Meter

10/31/17 at 11:56 AM

Filename: 8001-4.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

Penthouse

Lower Levels

03-NHP1

03-NHP3

03-NH33

03-NHS3

03-NH23

03-NH13

03-NH31

03-NHS1

03-NH21

03-NH11

03-NDCP1 (Mod Addr: 3)

03-NDCP2 (Mod Addr: 5)

03-EMDCP1 (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 DAT 03-NLP4 Penthouse PH-A7-E3 43 15762

2 DAT 03-NHS3 Service Level SV-D4-01 25 11174

3 DAT 03-NH13 Level 1 01-B8-E5 27 11710

4 DAT 03-NH11 Level 1 01-D10-E7 27 11838

5 DAT 03-NH21 Level 2 02-D10-E7 28 11956

6 DAT 03-NH23 Level 2 02-C4-04 28 11955

7 DAT 03-NH31 Level 3 03-D10-E6 30 12471

8 DAT 03-NH33 Level3 03-B8-E6 30 12468

9 DAT 03-NHP1 Penthouse PH-A7-E3 43 15759

10 DAT 03-NHP3 Penthouse PH-A7-E3 43 15764

11 DAT 03-NLP1 Penthouse PH-A7-E3 43 15760

12 DAT 03-NLP2 Penthouse PH-A7-E3 43 15761

13 DAT 03-NLP3 Penthouse PH-A7-E3 43 15763

**FUTURE (No Wire/No graphic)

Removal of Solar PV Monitoring6

DAT - SOUTH (B) BUILDING RISER

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

VERIS METER DETAILED INFO

Switch

Fiber Network

Modbus/IP

Note:

• Original labels match contract ‘one-lines’

• Alternate Labels match the floorplan layout (and actual equip naming), and are matched as best as possible by JCI without any given documentation.

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 3/1/14

REFERENCE DRAWING

IBS Electrical Meter Wiring

JT 10/27/2017

8001-5.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Switch

04-ATS-EQ1 (Mod Addr: 10)

04-ATS-EQ2 (Mod Addr: 12)

04-ATS-LS1 (Mod Addr: 6)

04-ATS-CR1 (Mod Addr: 8)

04-NHP1

04-NHS1

04-NLP1

04-NLP2

04-NH12

04-NH22

Fiber Network

Elec Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Steam Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Steam Meter 1 F-26xx Onicon Steam Meter

CHW Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

NG - Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Nat Gas Meter 1 F26xx Onicon Nat Gas Meter

Modbus/IP

10/31/17 at 1:48 PM

Filename: 8001-5.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

Penthouse

Lower Levels

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters. See Detailed Information chart.

04-NH31

04-EQHK

04-EQLK SEC.1

04-NDCP (Mod Addr: 3)

04-EMDCP (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 IBS 04-NHP1 Penthouse HP-107 (04-PH-D1-E2) 53 18327

2 IBS 04-NHS1 Service Level HS-147 (04-SV-F3-E1) 47 16804

3 IBS 04-NLP1 Penthouse HP-107 (04-PH-D1-E2) 53 18325

4 IBS 04-NLP2 Penthouse HP-107 (04-PH-D1-E2) 53 18326

5 IBS 04-NH12 Level 1 H1-132 (04-01-F3-E2) 48 17086

6 IBS 04-NH22 Level 2 H2-329 (04-02-G2-02) 49 17453

7 IBS 04-NH31 Level 3 H3-215 (04-03-C3-E1) 50 17715

8 IBS 04-EQLK SEC.1 Service Level HS-100 (04-SV-A1-03) 47 16925

9 IBS 04-EQHK Service Level HS-100 (04-SV-A1-03) 47 16924

Removal of Solar PV Monitoring6

IBS BUILDING RISER

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters. See Detailed Information chart.

VERIS METER DETAILED INFO

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/15/14

REFERENCE DRAWING

IBN Electrical Meter Wiring

JT 10/27/2017

8001-6.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Steam Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Steam Meter 1 F-26xx Onicon Steam Meter

CHW Field Devices:

Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

10/31/17 at 1:48 PM

Filename: 8001-6.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

Switch

05-ATS-EQ1 (Mod Addr: 10)

05-ATS-EQ2 (Mod Addr: 12)

05-ATS-LS1 (Mod Addr: 6)

05-ATS-CR1 (Mod Addr: 8)

05-NHP1

05-NLP1

05-NLP2

Fiber Network

Elec Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

Modbus/IP

Penthouse

Lower Levels

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

05-NHS1

05-NH12

05-NH22

05-NH31

05-NDCP (Mod Addr: 3)

05-EMDCP (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 IBN 05-NHP1 Penthouse KP-107 (05-PH-D1-E2) 62 20632

2 IBN 05-NHS1 Service Level KS-111 (05-SV-C3-E2) 55 18852

3 IBN 05-NLP1 Penthouse KP-107 (05-PH-D1-E2) 62 20630

4 IBN 05-NLP2 Penthouse KP-107 (05-PH-D1-E2) 62 20631

5 IBN 05-NH31 Level 3 K3-219 (05-03-C3-E1) 58 19632

6 IBN 05-NH22 Level 2 K2-241 (05-02-F3-E2) 57 19505

7 IBN 05-NH12 Level 1 K1-145 (05-01-F3-E1) 56 19244

Removal of Solar PV Monitoring6

Modbus/RTU

IBN BUILDING RISER

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

VERIS METER DETAILED INFO

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/15/14

REFERENCE DRAWING

ENC Electrical Meter Wiring

JT 10/27/2017

8001-7.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

06-ATS-EQ4 (Mod Addr: 8)

06-ATS-CH4 (Mod Addr: 16)

06-ATS-CH2 (Mod Addr: 12)

06-ATS-CH3 (Mod Addr: 14)

06-ATS-CR (Mod Addr: 26)

06-ATS-EQ1 (Mod Addr: 2)

06-ATS-CH1 (Mod Addr: 10)

06-ATS-LS1 (Mod Addr: 18)

06-ATS-GEN (Mod Addr: 20)

Switch

Fiber Network

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

CHW Field Devices:

Comm Module 1 Bacnet IP D100 Onicon Bacnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

Elec Gateway Panel 2 Multinet4 GE Seriel to Ethernet Converter

2 PA0000001FH0 EXP PANEL 6X162X20 W/5

Workstation 1 See Riser Diagram

10/31/17 at 1:50 PM

Filename: 8001-7.00.vsd Last Modified:

Elec Gateway Panel #1 (North)

(16W x 20H x 6.5"D)

(~30 lbs)

Elec Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

06-NHDP12

06-NHDP11

06-CL11

Level 1

Service Level

06-CLS1

06-EMDCP3 (Mod Addr: 15)

06-NDCP4 (Mod Addr: 5)

06-EMDCP1 (Mod Addr: 11)

06-NDCPP1 (Mod Addr: 3)

06-EMDCP2 (Mod Addr: 13)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 ENC 06-NHDP11 Level 1 11-F2-E17 63 21010

2 ENC 06-NHDP12 Level 1 11-F2-E17 63 21011

3 ENC 06-CL11 Level 1 11-F2-E17 63 21009

4 ENC 06-CLS1 Service Level SV-F2-E1 63 20909

GEN BUS-A (Mod Addr: 6)

GEN BUS-B (Mod Addr: 7) Near Col 4.5/G

(level 1)

7 Modbus Addressing 3/25/2016 MJS

As-Built routing shown here.

06-ATS-EQ2 (Mod Addr: 4)

06-ATS-EQ3 (Mod Addr: 6)

06-NDCP3 (Mod Addr: 5)

06-NDCP2 (Mod Addr: 3)

06-EMDCP4 (Mod Addr: 17)

Entry Meter

(Provided by XCEL Energy)

ENC BUILDING RISER

As-Built routing shown here.

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

See DDC NAE Risers for Integration of Veris BACnet

MS/TP MetersVERIS METER DETAILED INFO

Modbus/IP

Modbus/IP

As-Built 6 Routing of Modbus Trunks 1/6/2016 MJS

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/22/14

REFERENCE DRAWING

CBN Electrical Meter Wiring

JT 10/27/2017

8001-8.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

08-ATS-LS1 (Mod Addr: 6)

08-ATS-CR1 (Mod Addr: 8)

08-ATS-CR2 (Mod Addr: 12)

08-ATS-EQ1 (Mod Addr: 10)

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

AUMS Data Server

1 See Network Riser for BOM

10/31/17 at 1:54 PM

Filename: 8001-8.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

Switch

08-NHP1

08-NLP1

08-NLP2

Fiber Network

Elec Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

Modbus/IP

Penthouse

Lower Levels

08-NH11

08-NH21

08-NH31

08-CLP1

08-CLP2

08-CLP4

08-CH11

08-CH21

08-CH31

08-NDCP (Mod Addr: 3)

08-EMDCP (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 CBN 08-NHP1 Penthouse GP-107 (08-PH-E3-E1) 74 23701

2 CBN 08-NH11 Level 1 G1-317 (08-01-D2-E1) 69 22569

3 CBN 08-NH21 Level 2 G2-311 (08-02-D2-E1) 70 22690

4 CBN 08-NH31 Level 3 G3-313 (08-03-D2-E1) 71 23075

5 CBN 08-NLP1 Penthouse GP-107 (08-PH-E3-E1) 74 23702

6 CBN 08-NLP2 Penthouse GP-107 (08-PH-E3-E1) 74 23703

7 CBN 08-CH11 Level 1 G1-317 (08-01-D2-E1) 69 22571

8 CBN 08-CH21 Level 2 G2-311 (08-02-D2-E1) 70 22691

9 CBN 08-CH31 Level 3 G3-313 (08-03-D2-E1) 71 23076

10 CBN 08-CLP1 Penthouse GP-107A (08-PH-E4-E1) 74 23697

11 CBN 08-CLP2 Penthouse GP-107A (08-PH-E4-E1) 74 23699

12 CBN 08-CLP4 Penthouse GP-107A (08-PH-E4-E1) 74 23698

Removal of Solar PV Monitoring6

CBN BUILDING RISER

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

VERIS METER DETAILED INFO

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/24/14

REFERENCE DRAWING

CBC Electrical Meter Wiring

JT 10/27/2017

8001-9.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

10/31/17 at 1:54 PM

Filename: 8001-9.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

09-ATS-LS1 (Mod Addr: 6)

09-ATS-CR1 (Mod Addr: 8)

09-ATS-EQ1 (Mod Addr: 10)

Switch

09-NHP1

09-NLP1

09-NLP2

Fiber Network

Elec Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

Modbus/IP

Penthouse

Lower Levels

09-NH11

09-NH21

09-NH31

09-CLP1

09-CLP4

09-CH11

09-CH21

09-CH31

09-NDCP (Mod Addr: 3)

09-EMDCP (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 CBC 09-NHP1 Penthouse EP-107 (09-PH-E2-E1) 81 25491

2 CBC 09-NH11 Level 1 E1-311 (09-01-D2-E1) 76 24356

3 CBC 09-NH21 Level 2 E2-309 (09-02-D2-E1) 77 24615

4 CBC 09-NH31 Level 3 E3-309 (09-03-C2-E1) 78 24872

5 CBC 09-NLP1 Penthouse EP-107 (09-PH-E2-E1) 81 25496

6 CBC 09-NLP2 Penthouse EP-107 (09-PH-E2-E1) 81 25492

7 CBC 09-CH11 Level 1 E1-311 (09-01-D2-E1) 76 24357

8 CBC 09-CH21 Level 2 E2-309 (09-02-D2-E1) 77 24616

9 CBC 09-CH31 Level 3 E3-309 (09-03-C2-E1) 78 24873

10 CBC 09-CLP1 Penthouse EP-105 (PH-C2-E1) 79 24985

11 CBC 09-CLP4 Penthouse EP-105 (PH-C2-E1) 79 24986

Removal of Solar PV Monitoring6

CBC BUILDING RISER

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

VERIS METER DETAILED INFO See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/25/14

REFERENCE DRAWING

CBS Electrical Meter Wiring

JT 10/27/2017

8001-10.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

10/31/17 at 1:55 PM

Filename: 8001-10.00.vsd Last Modified:

Switch

Fiber Network

Elec Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

Modbus/IP

Penthouse

Lower Levels

10-NDCP (Mod Addr: 1)

10-EMDCP (Mod Addr: 2)

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

CBS BUILDING RISER

Berg Submittals 3 MV meters added into scope 7/13/2015 MJS

4 Modbus Addressing 3/25/2016 MJS

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/25/14

REFERENCE DRAWING

PSN Electrical Meter Wiring

JT 10/27/2017

8001-11.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

CHW - Field Devices:

Comm Module 1 Bacnet IP D100 Onicon Bacnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

10/31/17 at 3:14 PM

Filename: 8001-11.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

11-ATS-LS1 (Mod Addr: 4)

11-ATS-CR1 (Mod Addr: 6)

11-ATS-EQ1 (Mod Addr: 8)

Switch

11-NHS1

11-NLS1

11-EQLS1

Fiber Network

Elec Gateway Panel (16W x 20H x 6.5"D)

(~30 lbs)

Modbus/IP

Level P0

11-CLS1

11-LSLS1

11-NDCP (Mod Addr: 3)

11-EMDCP (Mod Addr: 1)

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 PSN 11-NHS1 Level P0 P0-G3-01 82 25747

2 PSN 11-NLS1 Level P0 P0-G3-01 82 25748

3 PSN 11-EQLS1 Level P0 P0-G2-03 82 25745

4 PSN 11-CLS1 Level P0 P0-G2-01 82 25742

5 PSN 11-LSLS1 Level P0 P0-G2-03 82 25746

Removal of Solar PV Monitoring6

PSN BUILDING RISER

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

VERIS METER DETAILED INFO

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/25/14

REFERENCE DRAWING

PVN Electrical Meter Wiring

JT 10/27/2017

8001-12.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

12-NDCP (Mod Addr: 3)

12-EMDCP (Mod Addr: 1)

GATEWAY

PANEL

(16W x 20H x 6.5"D)

(~30 lbs)

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter

1 PA0000001FH0 EXP PANEL 6X162X20 W/5

CHW - Field Devices:

Comm Module 1 Bacnet IP D100 Onicon Bacnet IP Comm Module

Water Meter 1 F-31xx Onicon Mag Meter

10/31/17 at 1:57 PM

Filename: 8001-12.00.vsd Last Modified:

JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS

12-ATS-LS1 (Mod Addr: 4)

12-ATS-EQ1 (Mod Addr: 8)

12-ATS-EQ2 (Mod Addr: 10)

12-ATS-CR1 (Mod Addr: 6)

PVN BUILDING RISER

Switch

Fiber Network Modbus/IP

E. DanielsG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 2/25/14

REFERENCE DRAWING

PVS Electrical Meter Wiring

JT 10/27/2017

8001-13.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

13-NH11

10/31/17 at 2:15 PM

Filename: 8001-13.00.vsd Last Modified:

Pending RFI 5 Addition of 5 PQMII 5/16/2016 MJS

Level P1

Switch

13-NDCP (Mod Addr: 3)

13-EMDCP (Mod Addr: 1)

Fiber Network GATEWAY

PANEL

(16W x 20H x 6.5"D)

(~30 lbs)

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

Elec Gateway Panel 2 Multinet4 GE Seriel to Ethernet Converter

2 PA0000001FH0 EXP PANEL 6X162X20 W/5

Modbus/IP

Sr. No. Building Equipment Level Room ID NAE# BACnet

1 PVS 13-NH11 Level P1 P1-A10-01 84 26260

South Mech Room:

South Mech Room

ATS-LS1 (Mod Addr: 4)

ATS-CR1 (Mod Addr: 6)

ATS-EQ1 (Mod Addr: 8)

ATS-EQ2 (Mod Addr: 10)

ATS-EQ3 (Mod Addr: 12)

North Mech

Room 5

GATEWAY

PANEL

(16W x 20H x 6.5"D)

(~30 lbs)

Modbus/IP

PVS BUILDING RISER

See DDC NAE Risers for Integration of Veris BACnet

MS/TP Meters

VERIS METER DETAILED INFO

Field Coordination 6 Addition of Multinet 7/18/2016 MJS

Matt StalkerG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

MJS 7/17/15

REFERENCE DRAWING

Domestic Water Meter

JT 10/27/2017

9000-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

BILL OF MATERIALS

Designation Qty Part Number Description / Manufacturer / Product Data Sheet

PANEL TYP PA0000004GC0 EXPANSION PANEL, 12x16x6.5. 5 POINT 24VAC ISTR TB, 40VA

To IT Closet

Reed Switch Transmitter

(RST)

// Domestic Water Meter

GENERAL NOTES:

• All 120V power is the responsibility of Div 26 to run, and of the Mechanical Contractors to Coordinate.

• Mounting of all transmitters and controllers is by others.

WHT/BLK WHT/BLK

Wires with RST. If extension needed, use Belden 1032A (or equivalent) Not

Polarity Sensitive

ER-420

With Display

9 10

G

Ground

120V N

120V H

Output Power

This chart provided for Owner Reference Only. Meter Installers/startup team to input appropriate K-Factors.

BASC-20R

1 2A C

“Chassis”

Power

UI2UI1

Ethernet

X1

VAC

X1

L1 L2

VAC

120V by Div 26

Up to 4 inputs available on UI1-UI-4.

A C

Smartwire: 027200-10IMS

(18/3 AWG)

Recommendation to MC: Password

Protect ER-420 with “VADOM” as the password

Mechanical Responsibility:

Provide all domestic water meters, Reed Switches, ER-420, BASC-20R and applicable programming/settings/setup.

UI2

FOR SINGLE METER APPLICATIONS:

UI-1: As needed

FOR TRIPLE METER APPLICATIONS:

UI-1: DCW Meter

UI-2: DHW Meter

UI3: DHWR Meter Typical

A C

Transformer supplied by JCI in pre-built panel.

To ER-420 To ER-420

BAS PANEL CONTENTS

120V by Div 26

DOMESTIC & MAKEUP WATER METER WIRING DETAIL

Dom Water Submittals 2 All 8/8/2015 MJS

Scope Change 3 All 5/2/2016 MJS

Field 15 As-Built 10/27/2017 SM

10/31/17 at 2:19 PM

Filename: 9000-1.00.vsd Last Modified:

A. CamposG. SonjuS. Nixon

Johnson Controls, Inc.

10289 W. Centennial Rd.

Littleton, CO 80127

Phone: 303.973.5930

Fax: 303.979.6847

SM 12/2/16

REFERENCE DRAWING

Fuel Oil System

ACG 12/2/16

8002-1.00

Project Title

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Denver Replacement VA Medical Center

FUEL OIL SYSTEM – SEQUENCE OF OPERATION

GENERAL: THE FUEL OIL SYSTEM WILL OPERATE UNDER MANUFACTURER CONTROLS AND SAFETIES.

THE BAS WILL INTERFACE TO THE FUEL OIL SYSTEM CONTROL PANEL. THE FOLLOWING LIST OF

POINTS WILL BE OBTAINED THROUGH INTEGRATION.

GEN2FO-S

(By Others)

N C

480/3Ø

FP03-S

(w/Fuel Oil) (By Others)

06-FP-03

480/3Ø

FP04-S

(w/Fuel Oil) (By Others)

06-FP-04

480/3Ø

FP01-S

(w/Fuel Oil) (By Others)

06-FP-01

480/3Ø

FP02-S

(w/Fuel Oil) (By Others)

06-FP-02

FT1BoilSV-S

N O

FT1BoilRV-S

N O

FT2BoilSV-S

N O

FT2BoilRV-S

N O

FT3BoilSV-S

N O

FT3BoilRV-S

N O

FT4BoilSV-S

N O

FUEL OIL TO

BOILERS

480/3Ø

06-FP-22

06FP22-S

(w/Fuel Oil) (By Others)

480/3Ø

06-FP-21

06FP21-S

(w/Fuel Oil) (By Others)

480/3Ø

06-FP-23

06FP23-S

(w/Fuel Oil) (By Others)

480/3Ø

06-FP-24

06FP24-S

(w/Fuel Oil) (By Others)

FCL1-S

FCL1-A

(w/Fuel Oil)

FCL2-S

FCL2-A

(w/Fuel Oil)

FCL3-S

FCL3-A

(w/Fuel Oil)

FCL4-S

FCL4-A

(w/Fuel Oil)

DAYTNKS-P

(By Others)

BLRS-P

10/23/17 at 10:44 AM

Filename: 06-8002-1.00.vsd Last Modified:

NOTE 1

NOTE 1

NOTE 1

NOTE 1

NOTES:

1. Points are provided with factory controls and shall be obtained through integration.

Field 9 Revised Construction Set 1/22/2016 SS

DT1LEAK-A

DT1LEVEL

(By Others)

DT2LEAK-A

DT2LEVEL

(By Others)

DT3LEAK-A

DT3LEVEL

(By Others)

DT3LEAK-A

DT3LEVEL

(By Others)

FT1LEAK-A

FT1LEVEL

(By Others)

FT2LEAK-A

FT2LEVEL

(By Others)

FT3LEAK-A

FT3LEVEL

(By Others)

FT4LEAK-A

FT4LEVEL

(By Others)

FP01-A

FP01FAULT

FP01HOAPOS

FP01Run-T (By Others)

FP01-A

FP01FAULT

FP01HOAPOS

FP01Run-T (w/Fuel Oil) (By Others)

FP03-A

FP03FAULT

FP03HOAPOS

FP03Run-T (By Others)

FP04-A

FP04FAULT

FP04HOAPOS

FP04Run-T (By Others)

06FP21-C

06FP21-A

06FP21FAULT

06FP21HOAPOS

06FP21Run-T (By Others)

06FP22-C

06FP22-A

06FP22FAULT

06FP22HOAPOS

06FP22Run-T (By Others)

06FP23-C

06FP23-A

06FP23FAULT

06FP23HOAPOS

06FP23Run-T (By Others)

06FP24-C

06FP24-A

06FP24FAULT

06FP24HOAPOS

06FP24Run-T (By Others)GENERATOR

PUMP

CONTROLLER

PNUEMERACTOR

PANEL

DAY TANK

CONTROLLER

MODBUS TCP/IP

MODBUS TCP/IP

MODBUS TCP/IP

MODBUS TCP/IP

MODBUS TCP/IP

MODBUS TCP/IP

MO…