GEN_As-Builts_JCI_AUMS_7.13.18.pdf
PDF 2 MB Posted
- Solicitation number
- 36C25922Q0650
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 010000 - General Requirements.docx | DOCX document | |
| 013216.15 - Project Schedules.docx | DOCX document | |
| 014219 - Reference Standards.docx | DOCX document | |
| DRAFT ICRA Form.docx | DOCX document | |
| 017419 - Construction Waste Management.doc | DOC document | |
| AUMS Meter Recommission List.xlsx | XLSX spreadsheet | |
| 000110 - Table of Contents.docx | DOCX document | |
| 220711 - Plumbing Insulation.docx | DOCX document | |
| 013526 - Safety Requirements.docx | DOCX document | |
| 36C25922Q0650_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Kiewit-Turner a Joint Venture
Project Name:
Subcontractor Name: Submittal Date:
Contact Name: E-mail: Return By Date:
Contact Phone(s): Review Days: 7
Number: Name:
1.8 A N/A Y N Y Y
X
7200 S. Alton Way, Suite A-300, Englewood, CO 80112
Phone: 303-930-9000 FAX: 303-930-9001 thomas.b.schottgen@jci.com 07/23/18
Reviewed By DateEvan Brophy 7/16/2018
Submittal is in Compliance
Submittal is in Compliance with Variances from Specifications Evan Brophy Signature
SUBMITTAL INDEX & COVER SHEET
Department of Veteran's Affairs
Replacement Medical Center
Johnson Controls, Inc. 07/16/18
Thomas Schottgen
303-548-8106
Specification Section: 25 10 10 GEN Advanced Utility Metering System
S p e c S u b m it ta l
P a ra g ra p h
S p e c P ro d u c t
P a ra g ra p h
S p e c if ie d o r
L is te d
M a n u fa c tu re r?
I n
T h is P a c k a g e
Johnson Controls, Inc. Closeout Submittals
Submittal Type
Submittal Item Description Manufacturer M e e ts
A ll S p e c
R e q u ir e m e n ts
E x c e p ti o n s o r
V a ri a n c e s f ro m
S p e c
A p p ro v e r
In fo rm a ti o n
N e e d e d
SubmittalIndexForm_041009 Page 1 of 1
Date: July 13, 2018
BUILDING AUTOMATION SYSTEM
AS-BUILT DRAWINGS
Denver Replacement VA Medical Center Section 25 10 10
AUMS
As-Built
Submitted To:
Jim Johnson
Kiewett - Turner A Joint Venture 13611 E. Colfax Ave.
Aurora, CO 80045
Submitted By:
Jacob Tateoka
Systems Engineer
JCI Contract: 3429-0001
Johnson Controls, Inc.
3250 Quentin Street, Suite 112
Aurora, CO 80011 Tel: 303-932-3712 Fax: 813-635-2238
STAMPS
Creating a better climate for business.
Environmental Control System
Air Conditioning
Heating
Diagnostic Services
Coil Cleaning
Refrigeration
Automatic Temperature Controls
Facility Management Systems
Fire Management
Security Management
Building Operations and Management
Water Treatment
Electrical Equipment
Emergency Generator / Lighting Equipment
Industrial Controls / Recording / Indication Equipment
Facility Management System
Air and Water System Balancing
Fire Management System
Security System
Lighting Services
Instrumentation System Installation
Building Operations Management
Energy Conservation Control
Training Programs
Performance Contracting
Planned Service Agreements
LEGEND
2/183
Wire Symbol indicating:
Cable number (3), Number of wires and size
(E.G. 2 #18 wires)
S
Main Air Supply Tube at 20 PSIG
D-N 15-20
Dual Air Supply Tube at
15/20 PSIG
Day=15, Night=20
S
High Pressure Air
Supply Tube at 80 PSIG
Air line or Electrical
Wire
Connected Lines or
Wires
Crossing Lines or
Wires, Not Connected
Pneumatic Tube indicating Tube Number
2/18
Wire Symbol indicating:
number of wires and size (E.G. 2 #18 wires)
Electrical Wire Terminal with Appropriate
Number
Item Located on Panel
Face
In-Line Restrictor
Opposed Blade
Damper
Parallel Blade
Damper
Air Flow Measuring
Station
Filter
Humidifier
Fan
Pump
Heating or Cooling Coil
Ductwork or Piping with
Flow Direction Shown
Drawing Revision
Symbol with
Appropriate Number
Gage
Current Sensing Switch or Combination Current
Sensing switch &
Command Relay
Duct Detector
(Smoke, CO, CO2)
2-Way Valve with
Actuator
N C
3-Way Valve with
Actuator
N 0
C N C
Vapor Tension
Temperature Sensing
Element (Low Limit)
Vapor Tension
Element (Hi Limit)
Paddle Type Flow
Switch
Pressure Sensing
Device
Bulb Type Temperature
Sensing Element
Located inside
Separable Socket/Well
Strap-on Bulb Type
Element
Combination Bulb Type
Element and Humidity
Sensor (Duct Mount)
Humidity Sensing
Element Located under
Shield in Outside air
Located under Shield in
Outside air
Device H
C N O
N O
Denver Replacement VA Medical Center
PROJECT TITLE
ARCHITECT
H+L Architecture 1755 Blake Street
Denver, CO 80202
Phone: 303.298.4700
ENGINEER
Cator, Ruma & Associates 896 Tabor Street
Lakewood, CO 80401
Phone: 303.232.6200
MECHANICAL CONTRACTOR
RK Mechanical
3800 Xanthia St
Denver, CO 80238 Phone: 303.355.9696
ELECTRICAL CONTRACTOR
Sturgeon Electric Company 12150 E. 112 th Avenue
Henderson, CO 80640
Phone: 303-286-8000
3429-0001
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
DATE
Branch Information
CONTRACT NUMBER
E. Daniels
APPLICATION ENGINEER
7/1/2013
PROJECT MANAGERSALES ENGINEER
REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY
G. SonjuS. Nixon
Advanced Utility Monitoring System
N/A 4 CON Dwg and FO Meters 7/28/2015 MJS
SF1-FLT
Wire Symbol indicating:
Device Software or Tag
Name
PAGE DESCRIPTION
1000-1.00 AUMS RFI Index Page 1
2000-1.00 AUMS Network Layout
4000-1.00 Steam Meter Wiring 4001-1.00 Hot Water BTU Meter Wiring 4002-1.00 Solar Water BTU Meter Wiring 4003-1.00 Snowmelt Water BTU Meter Wiring 4004-1.00 Condensate BTU Meter Wiring
5000-1.00 Chilled Water BTU Meter Wiring 5001-1.00 Chilled Water Meter Wiring
8000-1.00 Natural Gas Meter Wiring
8001-1.00 AUMS Electrical Meters 8001-1.50 CON Electrical Meter Wiring 8001-2.00 RES Electrical Meter Wiring 8001-3.00 DAT North (A) Electrical Meter Wiring 8001-4.00 DAT South (B) Electrical Meter Wiring 8001-5.00 IBS Electrical Meter Wiring 8001-6.00 IBN Electrical Meter Wiring 8001-7.00 ENC Electrical Meter Wiring 8001-8.00 CBN Electrical Meter Wiring 8001-9.00 CBC Electrical Meter Wiring 8001-10.00 CBS Electrical Meter Wiring 8001-11.00 PSN Electrical Meter Wiring 8001-12.00 PVN Electrical Meter Wiring 8001-13.00 PVS Electrical Meter Wiring
9000-1.00 Domestic Water Meter
11000-1.00 AUMS Meter Schedule 11000-2.00 AUMS Meter Schedule 11000-3.00 AUMS Meter Schedule 11000-4.00 AUMS Meter Schedule 11000-5.00 AUMS Meter Schedule
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
N/A 5A Multiple Changes 11/13/2015 MJS
Berg Sumittals 6 JSI-091 and General Updates 1/16/2016 MJS
Field 15 As-Built 10/27/2017 SM
Advanced Utility Monitoring System (AUMS)
Creating a better climate for business.
Environmental Control System
Air Conditioning
Heating
Diagnostic Services
Coil Cleaning
Refrigeration
Automatic Temperature Controls
Facility Management Systems
Fire Management
Security Management
Building Operations and Management
Water Treatment
Electrical Equipment
Emergency Generator / Lighting Equipment
Industrial Controls / Recording / Indication Equipment
Facility Management System
Air and Water System Balancing
Fire Management System
Security System
Lighting Services
Instrumentation System Installation
Building Operations Management
Energy Conservation Control
Training Programs
Performance Contracting
Planned Service Agreements
Denver Replacement VA Medical Center
PROJECT TITLE
ARCHITECT
H+L Architecture 1755 Blake Street
Denver, CO 80202
Phone: 303.298.4700
ENGINEER
Cator, Ruma & Associates 896 Tabor Street
Lakewood, CO 80401
Phone: 303.232.6200
MECHANICAL CONTRACTOR
RK Mechanical
3800 Xanthia St
Denver, CO 80238 Phone: 303.355.9696
ELECTRICAL CONTRACTOR
Sturgeon Electric Company 12150 E. 112 th Avenue
Henderson, CO 80640
Phone: 303-286-8000
1000-1.00
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
DATE
Branch Information
DRAWING NUMBER
A. Campos
APPLICATION ENGINEER
10/9/2014
PROJECT MANAGERSALES ENGINEER
REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY
G. SonjuS. Nixon
Advanced Utility Monitoring System
Rev Variance/KT-RFI# Answered Description Drawings Affected
1 026 (VR #290) 3/14/2014 Removal of Emergency Load Shedding from AUMS Specification Information Only
1 027 (VR #296) 3/26/2014 Server hardware processor speed & HD size revision to match standard offering 2000-1.00
1 028 (VR #295) 3/26/2014 Removal of ASCII communication requirements Information Only
1 029 (VR #289) 3/17/2014 Removal of JCI remote control of breakers Information Only
1 030 (VR #NA) VOID Exclusion of non-standard options for UPS 2000-1.00
1 031 (VR #299) 5/7/2014 Reduction of Workstation UPS backup time Information Only
1 032 (VR #287) 3/17/2014 Exclusion of factory wiring for electrical metering communications Information Only
1 033 (VR #294) 3/26/2014 Timestamps of historical data to be displayed in 1.0 vs 0.1 second increments Information Only
1 034 (VR #288) 3/17/2014 Veris Sub-metering to be Modbus vs Bacnet 8001-1.00
1 035 (VR #297) 5/7/2014 GE Waveform Technical Sample Sizes Modified Information Only
1 2724 (VA #2757) 1/14/2014 Revisions to Steam Meter Design 11001-1.00
1 2732 (VR #2758) 1/14/2014 Revisions to NG Meter Design 11001-2.00
1 5835 (VR #5129) 11/6/2014 ENC – Domestic Water Meters Information Only
1 6228 1/13/2015 ENC – Chilled Water Meter Clarification (adds Meter) Information Only
1 6457 2/25/2015 CAMPUS WIDE – Line Size Reduction For AUMS Steam Meters Information Only
1 6515 3/4/2015 Div 25 – AUMS Domestic Water Meter List Clarification Information Only
1 6612 3/13/2015 ENC - Div 25 - #300 Flange Coordination Information Only
1 6880 4/1/2015 IBN - Div 25 – Steam Meter 05-STM-1 Minimum Flow (Approved) Information Only
1 6879 4/24/2015 VA Wide Server Data Storage (Answered) Information Only
1 7647 7/14/2015 08-CWFM-1 Pipe / Meter Sizing Mismatch 11001-1.00
1 7273 6/9/2015 Confirmation of RAID Hard Drive Storage Information Only
1 7274 6/2/2015 Location of Fieldserver Integrator 8001-1.00
1 8451 n/a Confirmation that Data Reporting to AUMS Corporate Data Center will utilize Information Only the information coordinated with Schneider Electric to match existing data.
1 JSI-91 7/7/14 Removal of the Solar PV meters from monitoring scope. See Title Pg – Rev6
1 10049 4/24/2017 CON-Div25-26-Veris Meter for Panel 10-NLS4 8001-1.50
Creation 1 7/8/2015 MJS
RFI 8451 & JSI-91 1/6/2016 MJS
2 Dates/#s 1/22/2015 MJS
Field 15 As-Built 10/27/2017 SM
AUMS – RFI Index
INTERNET
CONNECTION &
FIREWALL
(Provided by VA)
CON BUILDING
3429-0001
Drawing Title
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 1/14/2014
REFERENCE DRAWING
AUMS Network Layout
JT 10/27/2017
2000-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
PSN BUILDING
PVN BUILDING
AUMS Data Server
CBN BUILDING
Control Center:
11/2/17 at 8:35 AM
Filename: 2000-1.00.vsd Last Modified:
ENC BUILDING
Control Center: LS-203 (06-SV-F3-01)
Workstation #1
SWITCHGEAR AND
ELECTRICAL METERS
WATER
METER
GAS
METER
WM GM
STEAM
METER
SM
BacNet
TYPICAL PER BUILDING
SWITCH
ATS
SWITCH
RMP
(RTU#)
REMOTE
MONITORING
PANEL
EM
Modbus/RTU
SUBSTATION EM
FIBER IN
FIBER OUT
LEGEND
Fiber (N/A)
Protocol: Wiring
Ethernet (8/24)
Modbus RTU (4/18)
FIBER OUT
FIBER IN
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Workstation Field Devices:
Monitor 1 P2412H Dell Professional P2412H - LED monitor - 24"
Printer 1 M551n HP LaserJet Enterprise M551n - printer - color - l
Workstation 1 MS-OFFICE Microsoft Office Suite
1 Optiplex3040 Dell Desktop Computer
1 Symantec Endpoi Symanted Endpoint Virus Protection
2 Viewnode GE Viewpoint Software to monitor Wafeforms
1 Viewpoint GE Viewpoint Software to monitor Wafeforms
AUMS Server Field Devices:
AUMS Server 1 MS-NIE8500-0 NAE-8500 Server
1 Symantec Endpoi Symanted Endpoint Virus Protection
AUMS Server 1 MS-15KUPG-0 15K UPGRADE NX85/LCS85
MOD
HUB
Fieldserver 1
See Drawing:
‘ELEC-1’ for details and BOM
BACnet (3/22)
NAE
AUMS NETWORK RISER DIAGRAM
RFI-7274 4 Field Server 7/14/2015 MJS
Field 15 As-Built 10/27/2017 SM
IBN BUILDING
IBS BUILDING
DAT NORTH
BUILDING
DAT SOUTH
BUILDING
RES BUILDING
CBC BUILDING
CBS BUILDING
PVS BUILDING
Berg Submittals 3 Veris Mtrs moved from Modbus 4/23/2015 MJS
3429-0001
Drawing Title
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Steam Meter Wiring
JT 10/27/2017
4000-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
10/31/17 at 11:20 AM
Filename: 4000-1.00.vsd Last Modified:
H
N
T4
Shield
D-100 Series Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
4-20 mA +
Onicon 2600 Series Meter
Loop Pwr +
Loop Pwr -4-20 mA -
TERMINATE SHIELD AT
D-100. LEAVE SHIELD
UN-TERMINATED AT
THE METER
RJ45CAT5EREFER TO 11000-XXX FOR
TELECOM TERMINATION
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
STEAM - Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Steam Meter 1 F-26xx Onicon Steam Meter
Approved For Contstruction 2 12/30/2014 ED
20/2 – Shielded: AlphaWire
M5365 Or equal.
Field 15 As-Built 10/27/2017 SM
STEAM METER WIRING DETAIL
3 Addition of Wire P/N 10/30/2015 MJS
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Hot Water BTU Meter Wiring
JT 10/27/2017
4001-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
10/31/17 at 2:17 PM
Filename: 4001-1.00.vsd Last Modified:
H
N
T3
BTUS-T
Sig
Ref
Sig
Ref
Shld
Red
Blk
T4
Shield
Freq +
SYSTEM-10 Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
BTUR-T
Red
Blk
Freq -
T5
4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Onicon 3100 Series Meter
9 4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Shield
Freq +
Freq -
S
H
N
TERMINATE SHIELD AT D-100. LEAVE
SHIELD UN-TERMINATED AT THE METER
RJ45CAT5E
REFER TO 11000-XXX FOR
TELECOM TERMINATION
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
HW - Field Devices:
Water Meter 1 F-31xx Onicon Mag Meter
1 System-10 BTU Meter and Comm
Approved For Contstruction 2 12/30/2014 ED
20/6 – Shielded: AlphaWire
M5365 Or equal.
Field 15 As-Built 10/27/2017 SM
HOT WATER BTU METER WIRING DETAIL
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Solar Water BTU Meter Wiring
JT 10/27/2017
4002-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
10/31/17 at 2:17 PM
Filename: 4002-1.00.vsd Last Modified:
H
N
T3
BTUS-T
Sig
Ref
Sig
Ref
Shld
Red
Blk
T4
Shield
Freq +
SYSTEM-10 Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
BTUR-T
Red
Blk
Freq -
T5
4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Onicon 3100 Series Meter
9 4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Shield
Freq +
Freq -
S
H
N
TERMINATE SHIELD AT D-100. LEAVE
SHIELD UN-TERMINATED AT THE METER
RJ45CAT5E
REFER TO 11000-XXX FOR
TELECOM TERMINATION
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
SOLAR HW - Field Devices:
Water Meter 1 F-31xx Onicon Mag Meter
1 System-10 BTU Meter and Comm
3 Addition of Wire P/N 10/30/2015 MJS
20/6 – Shielded: AlphaWire
M5365 Or equal.
Mfgr IOM 4 Supply/Return Temp Terminals 3/23/2016 MJS
Field 15 As-Built 10/27/2017 SM
SOLAR WATER BTU METER WIRING DETAIL
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Snowmelt Water BTU Meter Wiring
JT 10/27/2017
4003-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
10/31/17 at 2:17 PM
Filename: 4003-1.00.vsd Last Modified:
H
N
T3
BTUS-T
Sig
Ref
Sig
Ref
Shld
Red
Blk
T4
Shield
Freq +
SYSTEM-10 Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
BTUR-T
Red
Blk
Freq -
T5
4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Onicon 3100 Series Meter
9 4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Shield
Freq +
Freq -
S
H
N
TERMINATE SHIELD AT D-100. LEAVE
SHIELD UN-TERMINATED AT THE METER
RJ45CAT5E
REFER TO 11000-XXX FOR
TELECOM TERMINATION
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
SNMLT HW - Field Devices:
Water Meter 1 F-31xx Onicon Mag Meter
1 System-10 BTU Meter and Comm
Approved For Contstruction 2 12/30/2014 ED
20/6 – Shielded: AlphaWire
M5365 Or equal.
Field 15 As-Built 10/27/2017 SM
SNOWMELT WATER BTU METER WIRING DETAIL
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Condensate BTU Meter Wiring
JT 10/27/2017
4004-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Filename: 4004-1.00.vsd Last Modified:
H
N
T3
BTUS-T
Sig
Ref
Sig
Ref
Shld
Red
Blk
T4
Shield
Freq +
SYSTEM-10 Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
BTUR-T
Red
Blk
Freq -
T5
4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Onicon 3100 Series Meter
9 4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Shield
Freq +
Freq -
S
H
N
TERMINATE SHIELD AT D-100. LEAVE
SHIELD UN-TERMINATED AT THE METER
RJ45CAT5E
REFER TO 11000-XXX FOR
TELECOM TERMINATION
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
CONDENSATE - Field Devices:
Water Meter 1 F-31xx Onicon Mag Meter
1 System-10 BTU Meter and Comm
Approved For Contstruction 2 12/30/2014 ED
20/6 – Shielded: AlphaWire
M5365 Or equal.
Field 15 As-Built 10/27/2017 SM
CONDENSATE BTU METER WIRING DETAIL
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Chilled Water BTU Meter Wiring
JT 10/27/2017
5000-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
10/31/17 at 2:17 PM
Filename: 5000-1.00.vsd Last Modified:
H
N
T3
BTUS-T
Sig
Ref
Sig
Ref
Shld
Red
Blk
T4
Shield
Freq +
SYSTEM-10 Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
BTUR-T
Red
Blk
Freq -
T5
4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
9 4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Shield
Freq +
Freq -
S
H
N
TERMINATE SHIELD AT D-100. LEAVE
SHIELD UN-TERMINATED AT THE METER
RJ45CAT5E
REFER TO 11000-XXX FOR
TELECOM TERMINATION
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
CHW - Field Devices:
Water Meter 1 F-31xx Onicon Mag Meter
1 System-10 BTU Meter and Comm
Approved For Contstruction 2 12/30/2014 ED
20/6 – Shielded: AlphaWire
M5365 Or equal.
CHILLED WATER BTU METER WIRING DETAIL
Onicon 3100 Series Meter
Field 15 As-Built 10/27/2017 SMField 15 As-Built 10/27/2017 SM
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Chilled Water Meter Wiring
JT 10/27/2017
5001-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Filename: 5001-1.00.vsd Last Modified:
H
N
T4
Shield
Freq +
D-100 Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
Freq -
T5
4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
9 4-20 mA +
AI Common
(B) Scaled +
(B) Scaled -
Freq +
Freq -
H
N
TERMINATE SHIELD AT D-100. LEAVE
SHIELD UN-TERMINATED AT THE METER
RJ45CAT5E
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
CHW - Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
Approved For Contstruction 2 12/30/2014 ED
20/6 – Shielded:
AlphaWire M5365 Or equal.
CHILLED WATER METER WIRING DETAIL
Onicon 3100 Series Meter
Field 15 As-Built 10/27/2017 SM
REFER TO 11000-XXX FOR
TELECOM TERMINATION
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 10/27/2017
REFERENCE DRAWING
Natural Gas Meter Wiring
JT 10/27/2017
8000-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
10/31/17 at 11:37 AM
Filename: 8000-1.00.vsd Last Modified:
H
N
T4
Shield
D-100 Series Enclosure
120V
POWER FEED BY DIV-26
PANEL _______
CIRCUIT ______
4-20 mA +
Onicon 5200 Series Meter
4-20 mA -
TERMINATE SHIELD AT
D-100. LEAVE SHIELD
UN-TERMINATED AT
THE METER
RJ45CAT5EREFER TO 11000-XXX FOR
TELECOM TERMINATION
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
NG - Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Nat Gas Meter 1 F52xx Onicon Nat Gas Meter
24 VDC +
24 VDC -
T5
SCALED +
SCALED -
T4
T5
RED
BLACK
SHIELD
BLUE
BROWN
WHITE
ORANGE
Approved For Contstruction 2 12/30/2014 ED
20/6 – Shielded: AlphaWire
M5365 Or equal.
NOTE:
ENC located XCEL NG meter being provided by XCEL.
Field 15 As-Built 10/27/2017 SM
NATURAL GAS METER WIRING DETAIL
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/11/14
REFERENCE DRAWING
AUMS Electrical Meters
SM 10/27/2017
8001-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
GE Meters
“PQMII” Supplied with gear per Div 26
Low Voltage Switchgear and ATS Switches
DIAGRAM IS SCHEMATIC. DOES NOT
REPRESENT ALL NETWORK TIE INS REQUIRED.
Port1
Port2
Veris Meter
“E50H2” Meters
Supplied with gear per
Div 26
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Field Devices:
Fieldserver 1 FS-8704-03 Driver, Modbus TCP/IP
1 FS-8704-06 Driver, BACnet/IP
1 FS-8790-30 FS-X35 Upgrade to 5,000 points
1 FS-B3510-05 FieldServer Serial/Ethernet Multiport
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
HIGH LEVEL OVERVIEW
THESE METERS AND EQUIPMENT TYPICAL PER BUILDING
To SCADA system
(All work by others)
* Modbus RTU wiring is Belden 9841: 24AWG/2 shielded.
** Modbus/TCP & Bacnet/IP is: CAT6 (RJ45 connection)
*** Gateway Panels are shown on individual building risers with a BOM on those pages.
10/31/17 at 3:17 PM
Filename: 8001-1.00.vsd Last Modified:
JSI064R1 7 Addition of Mains 2/16/2016 MJS
Modbus/RTU
Gateway
Modbus/TCP**
FIELDSERVER
AUMS Data Server Integration (By Johnson Controls)
Modbus/TCP ** BACnet/IP
THIS EQUIPMENT LOCATED IN CBN DATA CENTER
120 VAC
Power
24 VAC
Power 120 VAC
Power
BACnet MS/TP
See DDC Network
Riser Diagrams for BAS
Tie In Locations
Medium Voltage Switchgear
“PQMII” Supplied with gear per Div 26
Port1
Port2
To SCADA system
(All work by others)
GE Meters
MultiNet Gateway
120 VAC
Power L
N
G com
PQMII / GATEWAY SPECIFIC WIRING DETAILS
Network Switches
Typical PQMII Meter On
Trunk
(c
Note 1
NOTE: 120 Ω, 1/4 watt terminating resistor and 1 Nf.
Note 1
Ground once per trunk at gateway only
To IT Closet
Network Switch
Last PQMII Meter On
Trunk
(c
VERIS SPECIFIC WIRING DETAILS
Typical Veris Meter
S (+
Ref FAN410 for grounding information.
Next Veris Device
Previous JCI Bacnet Device
(c o m
(S
NAEs (also used to bring in DDC information)
Network Switches
BACnet IP
Shield
Wire
Anixter Cable # CBL-22/3-FC-PVC (Non Plenum Applications)
Anixter Cable # CBL-22/3-FC-PLN (Plenum Applications)
Anixter Cable# _____ (600V Applications)
Mounted in Data Center –
Wall TBD
THIS EQUIPMENT LOCATED IN ENC
06-
ELEC-3
XCEL Provided “LMR-1”
Pulse Meters
Use same wiring type as all DDC ‘BI’
22/2
JCI Boiler Panel.
22/2
06-
ELEC-4
BLK
WHT
BLU
600V Wiring Where Required.
Next JCI Bacnet Device
BLK
WHT
BLU
(c o m
ORG
YEL
NOTE: EOL resistors still required at last device, even if it is a Veris.
(S h ld
(S h ld
BLU
BACnet/IP
AUMS ELECTRICAL
JSI064R1 7 Veris MS/TP Wire Colors 3/22/2016 MJS
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/26/14
REFERENCE DRAWING
CON Electrical Meter Wiring
JT 10/27/2017
8001-1.50
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Filename: 8001-1.50.vsd Last Modified:
Service Level
01-NHS1
01-NHS3
01-NHS5
01-NHS7
See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet
MS/TP Meters
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 CON 01-NHS1 Service Level CS-239 (01-SV-B2-E1) 1 5031
2 CON 01-NHS3 Service Level CS-205 (12-SV-A7-01) 11 7566
3 CON 01-NHS5 Service Level CS-175 (01-SV-C19-E5) 4 5778
4 CON 01-NHS7 Service Level CS-143 (01-SV-C29-E7) 6 6292
5 CON 01-LSH2 Service Level CS-215 (12-SV-A4-03) 1 5038
6 CON 01-LSH4 Service Level CS-189 (01-SV-C14-E4) 3 5523
7 CON 01-LSH6 Service Level CS-161 (01-SV-C24-E6) 5 6040
8 CON 01-LSH8 Service Level CS-135 (01-SV-C34-E8) 13 8089
9 CON 01-CHS2 Service Level CS-215 (12-SV-A4-03) 1 5039
10 CON 01-CHS4 Service Level CS-189 (01-SV-C14-E4) 3 5524
11 CON 01-CHS6 Service Level CS-161 (01-SV-C24-E6) 5 6032
12 CON 01-CHS8 Service Level CS-135 (01-SV-C34-E8) 13 8090
VERIS METER DETAILED INFO
01-LSH2
01-LSH4
01-LSH6
01-LSH8
01-CHS2
01-CHS4
01-CHS6
01-CHS8
Solar PV Meters No longer in scope6
JSI-91 2 Removal of Solar PV Monitoring 1/6/2016 MJS
CON BUILDING RISER
Solar PV Meters No longer in scope6
RFI-10049 3 Removal of 01-NLS4 5/2/2017 MJS
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/26/14
REFERENCE DRAWING
RES Electrical Meter Wiring
JT 10/27/2017
8001-2.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
02-ATS-LS1 (Mod Addr: 6)
02-ATS-SB1 (Mod Addr: 14)
02-ATS-EQ1 (Mod Addr: 8)
02-ATS-EQ2 (Mod Addr: 10)
02-ATS-EQ3 (Mod Addr: 12)
Gateway Panel (16W x 20H x 6.5"D)
(~20 lbs)
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Field Devices:
EOL 2 EOL-RSTR EOL BACnet Resistor
Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
Modbus RTU
10/31/17 at 2:17 PM
Filename: 8001-2.00.vsd Last Modified:
Berg Submittals 3 Veris Mtrs moved from Modbus 7/14/2015 MJS
Penthouse
Lower Levels
EOL
02-NHP1 Feed
02-NHP2 Feed
02-NH31 Feed
02-NH21 Feed
02-NLDP1 Feed
02-NLDP2 Feed
02-NH11 Feed
02-NHS1 Feed
02-CLDP1 Feed
02-CLDP2 Feed
02-NDCP (Mod Addr: 3)
02-EMDCP (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 RES 02-NHP1 Penthouse BP-107 (02-PH-D3-E1) 23 10650
2 RES 02-NHP2 Penthouse BP-109 (02-PH-F3-E1) 19 9616
3 RES 02-NH11 Level 1 B1-106 (02-01-B2-E1) 15 865021
4 RES 02-NH21 Level 2 B2-104 (02-02-B2-E1) 16 8856
5 RES 02-NH31 Level 3 B3-118 902-03-G2-E2) 17 9241
6 RES 02-NHS1 Service Level BS-159 (02-SV-G2-E1) 14 8483
7 RES 02-NLDP1 Penthouse BP-107 (02-PH-D3-E1) 23 10649
8 RES 02-NLDP2 Penthouse BP-109 (02-PH-F3-E1) 19 9617
9 RES 02-CLDP-1 Penthouse BP-107 (02-PH-D3-E1) 23 10651
10 RES 02-CLDP-2 Penthouse BP-107 (02-PH-D3-E1) 23 10652
RES BUILDING RISER
Switch
Fiber Network
Modbus/IP
VERIS METER DETAILED INFO
See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet
MS/TP Meters
See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet
MS/TP Meters
4 Addition of Modbus Addressing 3/25/2016 MJS
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 3/1/14
REFERENCE DRAWING
DAT - North (A) Electrical Meter Wiring
JT 10/27/2017
8001-3.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
03-NDCP3 (Mod Addr: 3)
03-ATS-CR3 (Mod Addr: 14)
03-ATS-EQ3 (Mod Addr: 16)
03-ATS-EQ4 (Mod Addr: 18)
03-ATS-EQ5 (Mod Addr: 20)
03-ATS-EQ6 (Mod Addr: 24)
03-ATS-EQ8 (Mod Addr: 22)
Elec Gateway Panel (16W x 20H x 6.5"D)
(~20 lbs)
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Steam Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Steam Meter 1 F-26xx Onicon Steam Meter
CHW Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
Field Devices:
EOL 2 EOL-RSTR EOL BACnet Resistor
Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
10/31/17 at 2:14 PM
Filename: 8001-3.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
03-NHS5
03-NH15
03-NH25
03-NH35
03-NHP5
03-NLP5
03-NLP6
03-NLP7
Penthouse
Lower Levels
03-ATS-LS2 (Mod Addr: 12)
03-EMDCP2 (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 DAT 03-NHS5 Service Level FS-126 (03-SV-F1-E1) 25 11317
2 DAT 03-NH15 Level 1 F1-334A (03-01-F1-E2) 26 11557
3 DAT 03-NH25 Level 2 F2-262 (03-02-F1-E2) 85 26656
4 DAT 03-NH35 Level 3 F3-286 (03-03-F1-E2) 29 12212
5 DAT 03-NHP5 Penthouse FP-103 (03-PH-C4-E2) 33 13205
6 DAT 03-NLP5 Penthouse FP-103 (03-PH-C4-E2) 33 13204
7 DAT 03-NLP6 Penthouse FP-103 (03-PH-C4-E2) 33 13206
8 DAT 03-NLP7 Penthouse FP-103 (03-PH-C4-E2) 33 13207
Removal of Solar PV Monitoring6
Note:
• Original labels match contract ‘one-lines’
• Alternate Labels match the floorplan layout (and actual equip naming), and are matched as best as possible by JCI without any given documentation.
DAT - NORTH (A) BUILDING RISER
VERIS METER DETAILED INFO
See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet
MS/TP Meters
Switch
Fiber Network
Modbus/IP
See DDC NAE Risers (number in spreadsheet) for Integration of Veris BACnet
MS/TP Meters
7 Addition of Modbus Addressing 3/25/2016 MJS
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/28/14
REFERENCE DRAWING
DAT - South (B) Electrical Meter Wiring
JT 10/27/2017
8001-4.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
03-ATS-EQ1 (Mod Addr: 30)
03-ATS-EQ2 (Mod Addr: 32)
03-ATS-EQ7 (Mod Addr: 34)
03-ATS-LS1 (Mod Addr: 36)
03-ATS-CR1 (Mod Addr: 26)
03-NLP3
03-NLP4
03-ATS-CR2 (Mod Addr: 28)
03-NLP1
03-NLP2
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Steam Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Steam Meter 1 F-26xx Onicon Steam Meter
CHW Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
NG - Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Nat Gas Meter 1 F26xx Onicon Nat Gas Meter
10/31/17 at 11:56 AM
Filename: 8001-4.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
Penthouse
Lower Levels
03-NHP1
03-NHP3
03-NH33
03-NHS3
03-NH23
03-NH13
03-NH31
03-NHS1
03-NH21
03-NH11
03-NDCP1 (Mod Addr: 3)
03-NDCP2 (Mod Addr: 5)
03-EMDCP1 (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 DAT 03-NLP4 Penthouse PH-A7-E3 43 15762
2 DAT 03-NHS3 Service Level SV-D4-01 25 11174
3 DAT 03-NH13 Level 1 01-B8-E5 27 11710
4 DAT 03-NH11 Level 1 01-D10-E7 27 11838
5 DAT 03-NH21 Level 2 02-D10-E7 28 11956
6 DAT 03-NH23 Level 2 02-C4-04 28 11955
7 DAT 03-NH31 Level 3 03-D10-E6 30 12471
8 DAT 03-NH33 Level3 03-B8-E6 30 12468
9 DAT 03-NHP1 Penthouse PH-A7-E3 43 15759
10 DAT 03-NHP3 Penthouse PH-A7-E3 43 15764
11 DAT 03-NLP1 Penthouse PH-A7-E3 43 15760
12 DAT 03-NLP2 Penthouse PH-A7-E3 43 15761
13 DAT 03-NLP3 Penthouse PH-A7-E3 43 15763
**FUTURE (No Wire/No graphic)
Removal of Solar PV Monitoring6
DAT - SOUTH (B) BUILDING RISER
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
VERIS METER DETAILED INFO
Switch
Fiber Network
Modbus/IP
Note:
• Original labels match contract ‘one-lines’
• Alternate Labels match the floorplan layout (and actual equip naming), and are matched as best as possible by JCI without any given documentation.
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 3/1/14
REFERENCE DRAWING
IBS Electrical Meter Wiring
JT 10/27/2017
8001-5.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Switch
04-ATS-EQ1 (Mod Addr: 10)
04-ATS-EQ2 (Mod Addr: 12)
04-ATS-LS1 (Mod Addr: 6)
04-ATS-CR1 (Mod Addr: 8)
04-NHP1
04-NHS1
04-NLP1
04-NLP2
04-NH12
04-NH22
Fiber Network
Elec Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Steam Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Steam Meter 1 F-26xx Onicon Steam Meter
CHW Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
NG - Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Nat Gas Meter 1 F26xx Onicon Nat Gas Meter
Modbus/IP
10/31/17 at 1:48 PM
Filename: 8001-5.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
Penthouse
Lower Levels
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters. See Detailed Information chart.
04-NH31
04-EQHK
04-EQLK SEC.1
04-NDCP (Mod Addr: 3)
04-EMDCP (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 IBS 04-NHP1 Penthouse HP-107 (04-PH-D1-E2) 53 18327
2 IBS 04-NHS1 Service Level HS-147 (04-SV-F3-E1) 47 16804
3 IBS 04-NLP1 Penthouse HP-107 (04-PH-D1-E2) 53 18325
4 IBS 04-NLP2 Penthouse HP-107 (04-PH-D1-E2) 53 18326
5 IBS 04-NH12 Level 1 H1-132 (04-01-F3-E2) 48 17086
6 IBS 04-NH22 Level 2 H2-329 (04-02-G2-02) 49 17453
7 IBS 04-NH31 Level 3 H3-215 (04-03-C3-E1) 50 17715
8 IBS 04-EQLK SEC.1 Service Level HS-100 (04-SV-A1-03) 47 16925
9 IBS 04-EQHK Service Level HS-100 (04-SV-A1-03) 47 16924
Removal of Solar PV Monitoring6
IBS BUILDING RISER
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters. See Detailed Information chart.
VERIS METER DETAILED INFO
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/15/14
REFERENCE DRAWING
IBN Electrical Meter Wiring
JT 10/27/2017
8001-6.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Steam Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Steam Meter 1 F-26xx Onicon Steam Meter
CHW Field Devices:
Comm Module 1 BACnet IP D100 Onicon BACnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
10/31/17 at 1:48 PM
Filename: 8001-6.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
Switch
05-ATS-EQ1 (Mod Addr: 10)
05-ATS-EQ2 (Mod Addr: 12)
05-ATS-LS1 (Mod Addr: 6)
05-ATS-CR1 (Mod Addr: 8)
05-NHP1
05-NLP1
05-NLP2
Fiber Network
Elec Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
Modbus/IP
Penthouse
Lower Levels
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
05-NHS1
05-NH12
05-NH22
05-NH31
05-NDCP (Mod Addr: 3)
05-EMDCP (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 IBN 05-NHP1 Penthouse KP-107 (05-PH-D1-E2) 62 20632
2 IBN 05-NHS1 Service Level KS-111 (05-SV-C3-E2) 55 18852
3 IBN 05-NLP1 Penthouse KP-107 (05-PH-D1-E2) 62 20630
4 IBN 05-NLP2 Penthouse KP-107 (05-PH-D1-E2) 62 20631
5 IBN 05-NH31 Level 3 K3-219 (05-03-C3-E1) 58 19632
6 IBN 05-NH22 Level 2 K2-241 (05-02-F3-E2) 57 19505
7 IBN 05-NH12 Level 1 K1-145 (05-01-F3-E1) 56 19244
Removal of Solar PV Monitoring6
Modbus/RTU
IBN BUILDING RISER
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
VERIS METER DETAILED INFO
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/15/14
REFERENCE DRAWING
ENC Electrical Meter Wiring
JT 10/27/2017
8001-7.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
06-ATS-EQ4 (Mod Addr: 8)
06-ATS-CH4 (Mod Addr: 16)
06-ATS-CH2 (Mod Addr: 12)
06-ATS-CH3 (Mod Addr: 14)
06-ATS-CR (Mod Addr: 26)
06-ATS-EQ1 (Mod Addr: 2)
06-ATS-CH1 (Mod Addr: 10)
06-ATS-LS1 (Mod Addr: 18)
06-ATS-GEN (Mod Addr: 20)
Switch
Fiber Network
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
CHW Field Devices:
Comm Module 1 Bacnet IP D100 Onicon Bacnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
Elec Gateway Panel 2 Multinet4 GE Seriel to Ethernet Converter
2 PA0000001FH0 EXP PANEL 6X162X20 W/5
Workstation 1 See Riser Diagram
10/31/17 at 1:50 PM
Filename: 8001-7.00.vsd Last Modified:
Elec Gateway Panel #1 (North)
(16W x 20H x 6.5"D)
(~30 lbs)
Elec Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
06-NHDP12
06-NHDP11
06-CL11
Level 1
Service Level
06-CLS1
06-EMDCP3 (Mod Addr: 15)
06-NDCP4 (Mod Addr: 5)
06-EMDCP1 (Mod Addr: 11)
06-NDCPP1 (Mod Addr: 3)
06-EMDCP2 (Mod Addr: 13)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 ENC 06-NHDP11 Level 1 11-F2-E17 63 21010
2 ENC 06-NHDP12 Level 1 11-F2-E17 63 21011
3 ENC 06-CL11 Level 1 11-F2-E17 63 21009
4 ENC 06-CLS1 Service Level SV-F2-E1 63 20909
GEN BUS-A (Mod Addr: 6)
GEN BUS-B (Mod Addr: 7) Near Col 4.5/G
(level 1)
7 Modbus Addressing 3/25/2016 MJS
As-Built routing shown here.
06-ATS-EQ2 (Mod Addr: 4)
06-ATS-EQ3 (Mod Addr: 6)
06-NDCP3 (Mod Addr: 5)
06-NDCP2 (Mod Addr: 3)
06-EMDCP4 (Mod Addr: 17)
Entry Meter
(Provided by XCEL Energy)
ENC BUILDING RISER
As-Built routing shown here.
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
See DDC NAE Risers for Integration of Veris BACnet
MS/TP MetersVERIS METER DETAILED INFO
Modbus/IP
Modbus/IP
As-Built 6 Routing of Modbus Trunks 1/6/2016 MJS
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/22/14
REFERENCE DRAWING
CBN Electrical Meter Wiring
JT 10/27/2017
8001-8.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
08-ATS-LS1 (Mod Addr: 6)
08-ATS-CR1 (Mod Addr: 8)
08-ATS-CR2 (Mod Addr: 12)
08-ATS-EQ1 (Mod Addr: 10)
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
AUMS Data Server
1 See Network Riser for BOM
10/31/17 at 1:54 PM
Filename: 8001-8.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
Switch
08-NHP1
08-NLP1
08-NLP2
Fiber Network
Elec Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
Modbus/IP
Penthouse
Lower Levels
08-NH11
08-NH21
08-NH31
08-CLP1
08-CLP2
08-CLP4
08-CH11
08-CH21
08-CH31
08-NDCP (Mod Addr: 3)
08-EMDCP (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 CBN 08-NHP1 Penthouse GP-107 (08-PH-E3-E1) 74 23701
2 CBN 08-NH11 Level 1 G1-317 (08-01-D2-E1) 69 22569
3 CBN 08-NH21 Level 2 G2-311 (08-02-D2-E1) 70 22690
4 CBN 08-NH31 Level 3 G3-313 (08-03-D2-E1) 71 23075
5 CBN 08-NLP1 Penthouse GP-107 (08-PH-E3-E1) 74 23702
6 CBN 08-NLP2 Penthouse GP-107 (08-PH-E3-E1) 74 23703
7 CBN 08-CH11 Level 1 G1-317 (08-01-D2-E1) 69 22571
8 CBN 08-CH21 Level 2 G2-311 (08-02-D2-E1) 70 22691
9 CBN 08-CH31 Level 3 G3-313 (08-03-D2-E1) 71 23076
10 CBN 08-CLP1 Penthouse GP-107A (08-PH-E4-E1) 74 23697
11 CBN 08-CLP2 Penthouse GP-107A (08-PH-E4-E1) 74 23699
12 CBN 08-CLP4 Penthouse GP-107A (08-PH-E4-E1) 74 23698
Removal of Solar PV Monitoring6
CBN BUILDING RISER
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
VERIS METER DETAILED INFO
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/24/14
REFERENCE DRAWING
CBC Electrical Meter Wiring
JT 10/27/2017
8001-9.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
10/31/17 at 1:54 PM
Filename: 8001-9.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
09-ATS-LS1 (Mod Addr: 6)
09-ATS-CR1 (Mod Addr: 8)
09-ATS-EQ1 (Mod Addr: 10)
Switch
09-NHP1
09-NLP1
09-NLP2
Fiber Network
Elec Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
Modbus/IP
Penthouse
Lower Levels
09-NH11
09-NH21
09-NH31
09-CLP1
09-CLP4
09-CH11
09-CH21
09-CH31
09-NDCP (Mod Addr: 3)
09-EMDCP (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 CBC 09-NHP1 Penthouse EP-107 (09-PH-E2-E1) 81 25491
2 CBC 09-NH11 Level 1 E1-311 (09-01-D2-E1) 76 24356
3 CBC 09-NH21 Level 2 E2-309 (09-02-D2-E1) 77 24615
4 CBC 09-NH31 Level 3 E3-309 (09-03-C2-E1) 78 24872
5 CBC 09-NLP1 Penthouse EP-107 (09-PH-E2-E1) 81 25496
6 CBC 09-NLP2 Penthouse EP-107 (09-PH-E2-E1) 81 25492
7 CBC 09-CH11 Level 1 E1-311 (09-01-D2-E1) 76 24357
8 CBC 09-CH21 Level 2 E2-309 (09-02-D2-E1) 77 24616
9 CBC 09-CH31 Level 3 E3-309 (09-03-C2-E1) 78 24873
10 CBC 09-CLP1 Penthouse EP-105 (PH-C2-E1) 79 24985
11 CBC 09-CLP4 Penthouse EP-105 (PH-C2-E1) 79 24986
Removal of Solar PV Monitoring6
CBC BUILDING RISER
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
VERIS METER DETAILED INFO See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/25/14
REFERENCE DRAWING
CBS Electrical Meter Wiring
JT 10/27/2017
8001-10.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
10/31/17 at 1:55 PM
Filename: 8001-10.00.vsd Last Modified:
Switch
Fiber Network
Elec Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
Modbus/IP
Penthouse
Lower Levels
10-NDCP (Mod Addr: 1)
10-EMDCP (Mod Addr: 2)
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
CBS BUILDING RISER
Berg Submittals 3 MV meters added into scope 7/13/2015 MJS
4 Modbus Addressing 3/25/2016 MJS
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/25/14
REFERENCE DRAWING
PSN Electrical Meter Wiring
JT 10/27/2017
8001-11.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
CHW - Field Devices:
Comm Module 1 Bacnet IP D100 Onicon Bacnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
10/31/17 at 3:14 PM
Filename: 8001-11.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
11-ATS-LS1 (Mod Addr: 4)
11-ATS-CR1 (Mod Addr: 6)
11-ATS-EQ1 (Mod Addr: 8)
Switch
11-NHS1
11-NLS1
11-EQLS1
Fiber Network
Elec Gateway Panel (16W x 20H x 6.5"D)
(~30 lbs)
Modbus/IP
Level P0
11-CLS1
11-LSLS1
11-NDCP (Mod Addr: 3)
11-EMDCP (Mod Addr: 1)
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 PSN 11-NHS1 Level P0 P0-G3-01 82 25747
2 PSN 11-NLS1 Level P0 P0-G3-01 82 25748
3 PSN 11-EQLS1 Level P0 P0-G2-03 82 25745
4 PSN 11-CLS1 Level P0 P0-G2-01 82 25742
5 PSN 11-LSLS1 Level P0 P0-G2-03 82 25746
Removal of Solar PV Monitoring6
PSN BUILDING RISER
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
VERIS METER DETAILED INFO
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/25/14
REFERENCE DRAWING
PVN Electrical Meter Wiring
JT 10/27/2017
8001-12.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
12-NDCP (Mod Addr: 3)
12-EMDCP (Mod Addr: 1)
GATEWAY
PANEL
(16W x 20H x 6.5"D)
(~30 lbs)
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Elec Gateway Panel 1 Multinet4 GE Seriel to Ethernet Converter
1 PA0000001FH0 EXP PANEL 6X162X20 W/5
CHW - Field Devices:
Comm Module 1 Bacnet IP D100 Onicon Bacnet IP Comm Module
Water Meter 1 F-31xx Onicon Mag Meter
10/31/17 at 1:57 PM
Filename: 8001-12.00.vsd Last Modified:
JSI-91 6 Removal of Solar PV Monitoring 1/6/2016 MJS
12-ATS-LS1 (Mod Addr: 4)
12-ATS-EQ1 (Mod Addr: 8)
12-ATS-EQ2 (Mod Addr: 10)
12-ATS-CR1 (Mod Addr: 6)
PVN BUILDING RISER
Switch
Fiber Network Modbus/IP
E. DanielsG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 2/25/14
REFERENCE DRAWING
PVS Electrical Meter Wiring
JT 10/27/2017
8001-13.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
13-NH11
10/31/17 at 2:15 PM
Filename: 8001-13.00.vsd Last Modified:
Pending RFI 5 Addition of 5 PQMII 5/16/2016 MJS
Level P1
Switch
13-NDCP (Mod Addr: 3)
13-EMDCP (Mod Addr: 1)
Fiber Network GATEWAY
PANEL
(16W x 20H x 6.5"D)
(~30 lbs)
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
Elec Gateway Panel 2 Multinet4 GE Seriel to Ethernet Converter
2 PA0000001FH0 EXP PANEL 6X162X20 W/5
Modbus/IP
Sr. No. Building Equipment Level Room ID NAE# BACnet
1 PVS 13-NH11 Level P1 P1-A10-01 84 26260
South Mech Room:
South Mech Room
ATS-LS1 (Mod Addr: 4)
ATS-CR1 (Mod Addr: 6)
ATS-EQ1 (Mod Addr: 8)
ATS-EQ2 (Mod Addr: 10)
ATS-EQ3 (Mod Addr: 12)
North Mech
Room 5
GATEWAY
PANEL
(16W x 20H x 6.5"D)
(~30 lbs)
Modbus/IP
PVS BUILDING RISER
See DDC NAE Risers for Integration of Veris BACnet
MS/TP Meters
VERIS METER DETAILED INFO
Field Coordination 6 Addition of Multinet 7/18/2016 MJS
Matt StalkerG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
MJS 7/17/15
REFERENCE DRAWING
Domestic Water Meter
JT 10/27/2017
9000-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
BILL OF MATERIALS
Designation Qty Part Number Description / Manufacturer / Product Data Sheet
PANEL TYP PA0000004GC0 EXPANSION PANEL, 12x16x6.5. 5 POINT 24VAC ISTR TB, 40VA
To IT Closet
Reed Switch Transmitter
(RST)
// Domestic Water Meter
GENERAL NOTES:
• All 120V power is the responsibility of Div 26 to run, and of the Mechanical Contractors to Coordinate.
• Mounting of all transmitters and controllers is by others.
WHT/BLK WHT/BLK
Wires with RST. If extension needed, use Belden 1032A (or equivalent) Not
Polarity Sensitive
ER-420
With Display
9 10
G
Ground
120V N
120V H
Output Power
This chart provided for Owner Reference Only. Meter Installers/startup team to input appropriate K-Factors.
BASC-20R
1 2A C
“Chassis”
Power
UI2UI1
Ethernet
X1
VAC
X1
L1 L2
VAC
120V by Div 26
Up to 4 inputs available on UI1-UI-4.
A C
Smartwire: 027200-10IMS
(18/3 AWG)
Recommendation to MC: Password
Protect ER-420 with “VADOM” as the password
Mechanical Responsibility:
Provide all domestic water meters, Reed Switches, ER-420, BASC-20R and applicable programming/settings/setup.
UI2
FOR SINGLE METER APPLICATIONS:
UI-1: As needed
FOR TRIPLE METER APPLICATIONS:
UI-1: DCW Meter
UI-2: DHW Meter
UI3: DHWR Meter Typical
A C
Transformer supplied by JCI in pre-built panel.
To ER-420 To ER-420
BAS PANEL CONTENTS
120V by Div 26
DOMESTIC & MAKEUP WATER METER WIRING DETAIL
Dom Water Submittals 2 All 8/8/2015 MJS
Scope Change 3 All 5/2/2016 MJS
Field 15 As-Built 10/27/2017 SM
10/31/17 at 2:19 PM
Filename: 9000-1.00.vsd Last Modified:
A. CamposG. SonjuS. Nixon
Johnson Controls, Inc.
10289 W. Centennial Rd.
Littleton, CO 80127
Phone: 303.973.5930
Fax: 303.979.6847
SM 12/2/16
REFERENCE DRAWING
Fuel Oil System
ACG 12/2/16
8002-1.00
Project Title
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Denver Replacement VA Medical Center
FUEL OIL SYSTEM – SEQUENCE OF OPERATION
GENERAL: THE FUEL OIL SYSTEM WILL OPERATE UNDER MANUFACTURER CONTROLS AND SAFETIES.
THE BAS WILL INTERFACE TO THE FUEL OIL SYSTEM CONTROL PANEL. THE FOLLOWING LIST OF
POINTS WILL BE OBTAINED THROUGH INTEGRATION.
GEN2FO-S
(By Others)
N C
480/3Ø
FP03-S
(w/Fuel Oil) (By Others)
06-FP-03
480/3Ø
FP04-S
(w/Fuel Oil) (By Others)
06-FP-04
480/3Ø
FP01-S
(w/Fuel Oil) (By Others)
06-FP-01
480/3Ø
FP02-S
(w/Fuel Oil) (By Others)
06-FP-02
FT1BoilSV-S
N O
FT1BoilRV-S
N O
FT2BoilSV-S
N O
FT2BoilRV-S
N O
FT3BoilSV-S
N O
FT3BoilRV-S
N O
FT4BoilSV-S
N O
FUEL OIL TO
BOILERS
480/3Ø
06-FP-22
06FP22-S
(w/Fuel Oil) (By Others)
480/3Ø
06-FP-21
06FP21-S
(w/Fuel Oil) (By Others)
480/3Ø
06-FP-23
06FP23-S
(w/Fuel Oil) (By Others)
480/3Ø
06-FP-24
06FP24-S
(w/Fuel Oil) (By Others)
FCL1-S
FCL1-A
(w/Fuel Oil)
FCL2-S
FCL2-A
(w/Fuel Oil)
FCL3-S
FCL3-A
(w/Fuel Oil)
FCL4-S
FCL4-A
(w/Fuel Oil)
DAYTNKS-P
(By Others)
BLRS-P
10/23/17 at 10:44 AM
Filename: 06-8002-1.00.vsd Last Modified:
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTES:
1. Points are provided with factory controls and shall be obtained through integration.
Field 9 Revised Construction Set 1/22/2016 SS
DT1LEAK-A
DT1LEVEL
(By Others)
DT2LEAK-A
DT2LEVEL
(By Others)
DT3LEAK-A
DT3LEVEL
(By Others)
DT3LEAK-A
DT3LEVEL
(By Others)
FT1LEAK-A
FT1LEVEL
(By Others)
FT2LEAK-A
FT2LEVEL
(By Others)
FT3LEAK-A
FT3LEVEL
(By Others)
FT4LEAK-A
FT4LEVEL
(By Others)
FP01-A
FP01FAULT
FP01HOAPOS
FP01Run-T (By Others)
FP01-A
FP01FAULT
FP01HOAPOS
FP01Run-T (w/Fuel Oil) (By Others)
FP03-A
FP03FAULT
FP03HOAPOS
FP03Run-T (By Others)
FP04-A
FP04FAULT
FP04HOAPOS
FP04Run-T (By Others)
06FP21-C
06FP21-A
06FP21FAULT
06FP21HOAPOS
06FP21Run-T (By Others)
06FP22-C
06FP22-A
06FP22FAULT
06FP22HOAPOS
06FP22Run-T (By Others)
06FP23-C
06FP23-A
06FP23FAULT
06FP23HOAPOS
06FP23Run-T (By Others)
06FP24-C
06FP24-A
06FP24FAULT
06FP24HOAPOS
06FP24Run-T (By Others)GENERATOR
PUMP
CONTROLLER
PNUEMERACTOR
PANEL
DAY TANK
CONTROLLER
MODBUS TCP/IP
MODBUS TCP/IP
MODBUS TCP/IP
MODBUS TCP/IP
MODBUS TCP/IP
MODBUS TCP/IP
MO…