Fuel Tank Specifications (Rev. 10-29-26).pdf
PDF 95 KB Posted
- Solicitation number
- 645-DOTRFB-3184-2027
- Issued by
- Clinton County, Iowa
About this file
This is a Fuel Tank Specifications document issued by Iowa DOT for procurement of fuel storage systems for the Elkader and Missouri Valley maintenance garages, with bid responses due November 3, 2026. The Iowa DOT seeks new, double-wall fuel tanks that meet specific operational and safety standards. Tank specifications include two emergency vents, a pressure vacuum vent, integrated fuel gauges for volume measurement, and full operability upon delivery. Each tank must be paired with a 30-gallon-per-minute pump featuring a high-volume meter, 17–20 foot hose, high-volume automatic nozzle with shut-off capability, and high-volume filter head assembly. The requested tank sizes will be specified within the formal bid opportunity and may vary by site location. Iowa DOT will assume responsibility for registering delivered tanks with the Iowa State Fire Marshal and submitting all required Aboveground Storage Tank Plan Review Application forms to the Department of Inspections, Appeals, and Licensing.
The specifications require that all tanks be delivered clean and free of foreign material including rust, sediment, water, and residue from previous contents. No pricing terms, set-asides, incumbent information, or funding sources are detailed in the specifications document itself. These commercial-grade fuel storage systems represent standard equipment procurement for state maintenance facility operations, with compliance and registration responsibilities assigned to Iowa DOT upon delivery.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1464603-event.pdf | ||
| RFB 3184 Amendment 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fuel Tank Specifications – Oct. 2026
• Tanks must be new – not pre-owned or used.
• Double wall tanks should be clean when delivered. This means the tank is free from foreign material such as rust, sediment, water, and traces of products previously held by the tank.
• Tanks will need 2 emergency vents and a pressure vacuum vent.
• Tanks must have fuel gauges to properly measure & maintain gallons.
• Tanks must be fully operable upon delivery.
• 30 gal/minute pump w/high volume meter, 17-20 ft. hose, high volume automatic nozzle w/shut off and high-volume filter head & assembly to work w/30 gal/minute pump.
• Requested tank size(s) will be specified within the bid opportunity and may vary by site.
• Iowa DOT will be responsible for registering the delivered tank in their name with the Iowa State Fire Marshal. Iowa DOT will also be required to submit an Aboveground Storage Tank Plan Review Application form with the Iowa Department of Inspections, Appeals, and Licensing (DIAL).