Attachment JA-1.15 Solicitation Number FA5004-15-B-C006

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 1

PART 1 GENERAL

1.1 SCOPE: SECTION 26 05 10 – BASIC MATERIALS AND METHODS

A. This Section covers selection and installation basic electrical material and methods.

1.2 GENERAL

A. Provide all Work as shown on the Drawings and in these Specifications for a complete, safe, and functional installation. All Work shall comply with the latest edition of the National Electrical Code (NEC).

B. The Contractor is responsible for providing complete and operating systems in the facility. The intention of the Contract Documents is to include all labor and materials, equipment, and transportation necessary or reasonably inferable as being necessary for the execution of the work.

Where minor adjustments of the work are necessary for purposes of fabrication or installation of items, or resolution of conflicts between items within the intent of the Contract Documents, the Contractor shall make such adjustments at no added expense to the Government. Where such adjustments affect functional or aesthetic design of the work, they shall first be submitted to the Contracting Officer for review and approval.

C. Obtain and pay for all permits, plan reviews, and inspections required for the Work covered by this Division of the Specifications.

D. Unless otherwise noted, all materials shall be of new manufacture, and installed before expiration of their shelf life, if applicable.

E. Materials and equipment are to be those of major and reputable manufacturers with ability to render competent and thorough service through local and regional organizations capable of expeditiously providing service, parts, and assistance.

F. Materials of similar nature, style, function, purpose, and/or appearance shall be like products from the standard product line of the same manufacturer.

G. All products shall be listed and labeled by an approved national testing laboratory for their intended use and location in all cases where such products are listed and labeled. Where no product listed by an approved national testing laboratory for the application is available, provide certification of performance, function, and rating from an independent testing agency or laboratory approved by the Contracting Officer.

H. The omission of express reference to any parts, supplies, services, or facilities necessary for, or incidental to, a complete installation shall not be construed as a release from furnishing such items.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 2

I. Verification is required of all equipment sizes and locations prior to the ordering or installation of connection materials and disconnecting equipment to ensure that the power connections are of the proper size and type, and in the proper location. Verify all electrical loads (voltage, phase, full load amperes, number and point of connections, minimum circuit ampacity, etc.) for equipment furnished under all divisions of this specification, by reviewing respective shop drawings furnished under each division. Meet with each contractor and subcontractor furnishing equipment requiring electrical service and review electrical characteristics. Report any variances from electrical characteristics noted on the drawings with the Contracting Officer before proceeding with rough work. Obtain and review the equipment shop drawings to determine particular final connection requirements before rough-in begins for each equipment item.

J. All materials shall be installed in a neat, orderly, and secure fashion, as required by these specifications and commonly recognized standards of good workmanship, for which the Contracting Officer’s judgment shall be final. The norms for execution of the work shall be in conformity with NEC Chapter 3 and the National Electrical Contractors’ Association “National Electrical Installation Standards”.

K. Electrical equipment shall be installed in spaces that are accessible and in a manner that allows for maintenance and replacement. Entries into spaces shall allow for the passage of equipment.

1.3 SUBMITTALS

A. Prior to the purchase of any materials or equipment, the Contractor shall submit for acceptance data completely describing all items intended for use in the work. This data shall include the manufacturer and identifying number or nomenclature; the manufacturer's published data as to size, capacity, power requirements and dimensions, shop drawings; and such other information as necessary to properly describe each item. Catalog cuts fulfilling these requirements will be considered appropriate for this application. Such "commodity" items need not be submitted if they are being provided exactly as specified, and are so certified in the Index section of the submittal.

1.4 DRAWINGS

A. Unless otherwise indicated, drawing symbols conform to the applicable standards of ANSI. The Drawings (or Contract Drawings) rely heavily upon symbolic representation of the features shown, and represent exact details only so far as indicated.

1. The Drawings are diagrammatic and are not intended to show exact details.

2. Dimensions scaled from the Drawings may vary due to tracing tolerances, printing distortion, field conditions, field changes, and other factors. For these reasons, it shall be the Contractor's responsibility to field verify dimensions that pertain to his work. The Contractor shall make minor relocations where necessary to resolve conflicts or present a uniform appearance. The Drawings show exact location of electrical features only where specifically dimensioned.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 3

3. The Electrical Contractor shall review the Contract Documents of the other trades on the Project, and shall coordinate the installation of electrical features with the Work of all other trades.

4. Provide fixtures, devices, equipment, conduit, conductors, and accessories indicated on the Drawings unless it is specifically indicated that the fixture, device, equipment, conduit, conductor, or accessory is existing.

B. All existing equipment left remaining shall be maintained in service. When encountered in work, whether shown on the drawings or not, protect, brace and support existing items. If existing active electrical services are encountered that require relocation in order to execute general, electrical or mechanical work, relocate services as required and as directed without additional cost to the Government. Any equipment, which is not specifically indicated for removal or is not shown or noted, shall remain in service.

1.5 AS-BUILT DRAWINGS

A. The Electrical Contractor shall at all times keep a current set of Contract Drawings on the Project site. This set shall be kept in good condition, and shall be neatly and accurately marked to show the as-built condition of the electrical installation. Of particular importance are the precise locations of concealed features such as conductors, raceways, and junction boxes.

B. The field-marked set of drawings described in (A.) shall be made available to the Contracting Officer or their authorized representative for spot-checking at every inspection.

C. Upon completion of the Project, the field-marked set of Drawings described in (A.) shall be forwarded to the Contracting Officer, along with any supplementary drawings, sketches, notes, or other materials necessary to completely describe the as-built condition of the electrical installation.

1.6 REPAIR OF EXISTING FEATURES

A. Where existing or previously completed building surfaces or other features must be cut, penetrated, or otherwise altered for the installation of electrical features, such work shall be carefully laid out and performed, and any subsequent patching or repairs that it necessitates shall be performed by skilled mechanics of the trades involved. All cutting and patching shall be done with materials similar in appearance, function and rating to those in the existing construction. The patch shall not be noticeable and the contractor shall take such steps as painting any wall disturbed from corner to corner, top to bottom.

1.7 REMOVAL OF EXISTING ELECTRICAL FEATURES

A. Where connected to or serving fixtures or equipment being removed, or incidental to the required removal of walls, ceilings, or other features, existing electrical features shall be removed as follows:

1. All abandoned wiring shall be removed back to its source of supply.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 4

2. Exposed items shall be removed in their entirety.

a. All abandoned exposed conduit, including all abandoned conduit above accessible ceiling finishes shall be removed back to the source of supply, or back to the connection to a still active branch. Cap and properly close all openings in remaining conduits, boxes, and enclosures.

3. Concealed items such as raceways and boxes may be abandoned in place if they are completely concealed by the new construction and all conductors are removed or cut back so as to not be re-connectable to any source of power. Provide blank device plates or blank covers in all unused outlet boxes.

a. Conduits concealed in areas not accessible or that are not being made accessible shall be removed into areas of non-accessibility. Patch to match existing, openings in walls, ceilings, or floors left or created as a result of conduit removal.

b. Conduits that are being removed and that extend below slab on grade shall be ground flush with the top of the slab, plugged with concrete, and the slab patched to match existing.

4. Where other electrical items are fed through, supported by or attached to a removed item, re-route raceways and/or cut back building surfaces as necessary to rejoin raceways, provide new conductors as necessary, and patch and finish all damaged construction to match surrounding surfaces.

5. Salvage or disposal of removed items shall be as noted on the Drawings and/or as directed by the Contracting Officer.

1.8 VAPOR BARRIER PENETRATIONS

A. Penetrations of the building vapor barrier caused by the electrical installation shall be minimized, and where they do occur they shall be sealed.

1.9 FIRESTOPPING

A. Where electrical raceways or other features penetrate fire-rated building surfaces, they shall be securely sealed to the surrounding surface with barrier caulk. Acceptable manufacturers include, but are not limited to, 3M Fire Barrier Caulk No. CP25, Fire Barrier Putty No. 303, or equal.

1.10 PROTECTION AND CLEANING

A. All electrical equipment shall, during the entire duration of construction work, be protected against water, dust, debris, overspray or any other contamination, whether environmental in origin or as a result of construction work.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 5

B. All construction dust, debris, overspray, scrap and surplus materials, etc. resulting from this work shall be cleared away, leaving the installation in completely clean condition.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 6

PART 2 PRODUCTS

1.11 IDENTIFICATION

A. Nameplates: Three-layer plastic, 0.125 inch thick, white with black center core unless noted otherwise, with matte finish and square corners. Minimum size shall be ¾ inch by 2 inches;

minimum lettering shall be 1/4 inch. Unless otherwise noted, all labels shall be nameplates as specified herein.

B. Wire and Cable Markers: Cloth markers, wrap on type or tubing type.

C. Receptacle Plate Labels: Clear adhesive Mylar or plastic type, minimum 3/16 inches size with black letters by a Kroy or other electronic label maker.

1.12 RACEWAYS

A. Minimum size for all raceways shall be 1/2 inch diameter.

B. Raceways shall be of types and characteristics recognized by the NEC.

C. Materials:

1. Rigid Steel Conduit shall be hot-dip galvanized, Schedule 40 Dimensions with smooth interior; Allied Tube & Conduit, J & L, Triangle, Western Tube & Conduit, Youngstown, or equal.

a. Rigid Steel Conduit shall be made up with threaded fittings only.

2. Flexible Metal Conduit ("flex") shall be Greenfield type, made of interlocking galvanized steel armor with steel or malleable iron fittings with insulated throat. Acceptable manufacturers include, but are not limited to the following: Alflex, American Metal, Carol Cable Co., Electri-flex, National Electric, RACO, Rome, Thomas & Betts, Triangle, or equal.

3. Liquid-tight Flexible Metal Conduit ("sealtite" flex or "LT flex") shall have a flexible galvanized steel spiral core with a flexible outer jacket of PVC, resistant to water, oil, grease, corrosive agents, and abrasion with steel or malleable iron fittings with insulated throat. Acceptable manufacturers include, but are not limited to the following: Carol, Anaconda, or equal.

a. Exterior or other extreme temperature applications of Liquid Flexible Metal Conduit shall have temperature rating of minus 67 degrees F to plus 220 degrees F, Liquatite “ATLA”, or equal.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 7

1.13 WIRES AND CABLES

A. All wire and cable shall conform to the latest Specifications of the NEC and/or the ICEA and shall be the products of American Insulated Wire, BICC General, Carol Cable, Excel Wire & Cable, Okonite, Southwire, Superior Essex, or equal.

B. Conductors:

1. All conductors shall be copper, except as otherwise noted. Conductors No. 10 AWG and smaller shall be solid or stranded. Conductors No. 8 AWG or larger shall be stranded.

C. Insulation Types:

1. Branch circuit conductors will consist of conductors run in conduit and raceways.

a. Branch circuit conductors in raceways shall be 600 volt insulated, and unless otherwise noted on the drawings, shall have the following insulation types:

1) Heated indoor spaces - THHN/THWN or XHHW.

2) In conduit, outdoors or other cold locations (such as attics) - XHHW.

2. Nylon-jacketed conductors such as types THHN or THWN shall not be used in any location subjected to ambient temperatures below 32 degrees F.

1.14 OUTLET BOXES

A. Boxes shall be deep-type (2-1/8 inch nominal) unless space limitations or drawing notes require shallower boxes.

1. Fixture outlet boxes for use with concealed raceway systems shall be 4 inch octagonal or square, galvanized sheet Steel.

2. Boxes for wall-mounted devices with concealed raceways shall be galvanized sheet Steel, 4 inches square for up to two devices, and solid ganged boxes for more than two devices.

1.15 WIRING DEVICES AND PLATES

A. Plates:

1. Cover plates for devices in recessed boxes shall be made of satin-finished 430 stainless steel. Cover plates for devices in surface-mounted boxes shall be of pressed or machined metal construction, specifically designed to suit the boxes.

B. Terminals:

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 8

1. Wiring devices shall have binding-screw type terminals only. Terminals using spring pressure to secure the wire and make electrical contact are not permitted.

C. Manufacturers:

1. Among the acceptable wiring devices and plates are the products of Arrow-Hart, Bryant, Hubbell, Leviton, Pass & Seymour. Alternate brand request or substitution request required.

1.16 MAGNETIC STARTERS

A. Unless otherwise noted, magnetic starters shall be:

1. Full-voltage non-reversing starting, with resettable integral solid state, ambient insensitive motor overload protection with Trip Class 20 protection.

2. Of the correct voltage rating for the system on which they are installed, with NEMA size and number of poles as shown on the drawings.

3. Housed in the NEMA enclosure appropriate for the location in which they are installed.

4. With hand-off-automatic switch for motors with automatic control, on-off switch for motors with manual control, red and green LED type pilot lights, and overload reset button in front cover.

5. With 120-volt coil and fused control circuit, control power to be derived from a separate control transformer in each starter enclosure.

6. With provisions for field-installation of at least two auxiliary control contacts, both normally-open and normally-closed types.

B. Combination magnetic starter/disconnects, also referred to in these Documents as "Combination Mags", shall each consist of a fusible disconnect switch and a magnetic starter as specified above, in a common enclosure with front-mounted operator handle for the disconnect.

C. Where starter types other than Full-Voltage Non-Reversing (FVNR) are called for on the Drawings, they shall be provided complete with all features specified for FVNR starters.

D. Among the acceptable motor starters are the products of Square D, Eaton, or equal.

1.17 DISCONNECT SWITCHES

A. Unless otherwise noted, disconnect switches shall have the following features:

1. The proper NEMA enclosure to suit the location, or as noted on the Drawings. The proper voltage rating to suit the circuit voltage.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 9

2. Quick-make/quick-break mechanisms with visible blades (when the cover is open), to disconnect all ungrounded conductors.

3. Switch handle positions shall be marked to indicate the ON and OFF conditions, and the handles shall be pad-lockable in the OFF position. Covers shall be interlocked with the handles to prevent cover opening while switch is ON, and a means shall be provided to permit qualified personnel to defeat this feature.

4. Disconnects shall be fusible, heavy-duty switches, unless otherwise noted. Where disconnects are not readily accessible, they shall be of the non-fusible type, and fusible protection for the circuit shall be provided in an accessible location.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 10

5. Motor disconnects shall be sized according to their standard, not maximum, ratings.

6. Where separate control voltages are supplied to motor controllers, the disconnect switch shall simultaneously disconnect the control circuit(s) with the power circuit(s).

B. Among the acceptable disconnects are the products of Square D, Eason, or equal.

1.18 GROUNDING

A. All metal raceways, enclosures, other electrical equipment and non-electrical equipment such as tanks and dispenser platforms that may pick up harmful potentials from the electrical system, shall be securely bonded and grounded as required by the NEC and the Drawings.

B. All grounding conductors and bonding jumpers shall be copper, sized according to the NEC or as noted on the Drawings.

PART 3 EXECUTION

2.1 IDENTIFICATION OF ELECTRICAL EQUIPMENT

A. Panelboards, disconnect switches, push-buttons, selector switches, motor starter switches, distribution panels or switchboards, switches and circuit breakers therein, and the like shall be labeled with laminated plastic labels.

1. Degrease and clean surfaces to receive nameplates.

2. Install nameplates parallel to equipment lines.

3. Labels shall be secured with pop rivets. Adhesive attachment is not acceptable, except for labels on receptacle plates or nameplates mounted on unheated indoor surfaces with foam tape.

4. Secure nameplate to inside face of recessed panelboard doors in finished areas.

B. Terminals on strips shall be numbered with indelible markings on special strips designed for the purpose, and a diagram or typed directory shall be provided in the terminal enclosure to identify the origin, function, and destination of each conductor in the enclosure.

C. Indelibly mark the outside cover of each junction box with the breaker number and panel identity of the source of power to each circuit within the box.

D. All conductors in pull or junction boxes or other enclosures shall be permanently and legibly tagged or labeled with panel and circuit numbers or other data, which clearly identifies their origin, function, and destination. Labeling shall be hand written or other appropriate representation. Exception: Conductors in a pull or junction box which contains only an individual branch circuit or a single multi-wire branch circuit whose conductors are terminated on a multi-pole breaker or contiguous breakers need not be tagged or labeled.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 11

E. All receptacle plates shall be labeled with the panel and circuit number for the branch circuit that supplies the receptacle.

F. Where more than one nominal voltage system exists in a building, each ungrounded conductor of a multiwire branch circuit, where accessible, shall be identified by phase and system. Install a label on each branch circuit panelboard: “This building contains two wiring systems: 480/277 V Brown, Orange, Yellow, Grey. 208/120 V Black, Red, Blue, White.

2.2 RACEWAYS

A. All conductors shall be installed in metal raceways, or as otherwise noted on the Drawings and/or specified herein.

B. Feeder and Branch Raceways - Rigid Steel Conduit (RSC).

C. All raceways, exposed and concealed, shall be run square with the building lines.

D. The final connection to any motor or other rotating or vibrating equipment, or equipment, which may require position adjustment after installation, shall be made through a slack section of flexible liquid-tight metal conduit 18 inches to 36 inches long.

E. Structural members shall not be cut, drilled, or notched for raceways or other electrical features unless specifically accepted by the Contracting Officer.

F. All raceways running from a warm area to a cold area shall be securely sealed inside the warm end with ductseal, a silicone compound not harmful to the wire insulation, or equivalent. Use sealoff fittings at panels if the feeder conduit enters the top of the panel and is run so as to expose it to different temperatures, such as through attic spaces.

G. Maintain a minimum 6 inch clearance between conduit and piping. Maintain 12 inch clearance between conduit and heat sources such as flues, steam pipes, heating pipes, and heating appliances.

H. Raceways shall be installed in switchboards, panelboards, gutters, pull boxes and the like from the back of the enclosure closest to the mounting surface, to the front in a manner that will not obstruct the future installation of raceways.

I. Raceways shall be physically and electrically continuous from enclosure to enclosure. Electrical continuity for all conduits shall be assured by inclusion of an NEC-sized grounding conductor.

All joints shall be made up wrench-tight and free of foreign materials. Threaded conduits shall enter enclosures by means of threaded hubs or double-locknut-and bushing connections. For conduits of one inch trade size and larger, bushings shall be of the insulated type.

J. Conduit joints shall be cut square, reamed smooth, and cleaned of burrs, cutting oil, cuttings, and other foreign materials prior to assembly. Ends shall be capped to prevent entrance of foreign materials during construction.

K. Bends, offsets, and saddles shall be made with factory elbows and fittings, or field-made with approved benders, to no less than NEC-required radii.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 12

2.3 WIRING AND CABLES

A. Branch circuit conductors shall be color-coded by factory pigmentation of the insulation. Larger conductors may be color-coded by wrapping the ends with colored tape in all enclosures, except that white and green conductors may never be phase-taped for any use other than neutral and ground, respectively. Color-coding for single conductors shall be consistent throughout the entire installation and shall be as follows:

SYSTEM VOLTAGE

Conductor 208Y/120 480Y/277

Phase A Black Brown Phase B Red Orange Phase C Blue Yellow Neutral White Gray Ground Green Green

B. Branch circuit conductors shall be No. 12 AWG copper, except for the following:

1. On 120-volt, 20 amp circuits over 70 feet (actual measured one-way distance) from panel to the last receptacle or middle of the lighting string (as appropriate), use No. 10 conductors for the entire circuit.

2. Where branch circuit conductor sizes are indicated on the drawings, they shall take precedence over the foregoing. Where field conditions dictate circuit routings that increase conductor lengths beyond what would be expected from the layout shown on the drawings, they shall be submitted to the Contracting Officer for acceptance.

C. All conductor connections shall be made up securely with solderless pressure connectors such as setscrew lugs, split-bolts, wirenuts, "wingnuts", or suitable crimp fittings. Live-spring connectors which cannot be tightened to a point where conductor deformation occurs (such as "Scotchloks") are not permitted. Each wirenut-type connector shall not contain more than four conductors, regardless of size.

D. Use compression type connectors for copper wire splices and taps, #6 AWG and larger. Utilize heat shrink tubing of the proper voltage rating for uninsulated conductors and connectors.

E. Thoroughly clean wires before installing lugs and connectors.

F. Make splices, taps, and terminations to carry full ampacity of conductors without perceptible temperature rise.

G. Terminate spare conductors with wire nuts.

H. Where stranded conductors are used, their ends shall be twisted and "tinned" with solder prior to connection, or else terminated with crimp-on connectors, set screw lugs, box lugs, or self-lifting pressure terminals.

REPAIR CH&PP COAL CAR SHAKER SECTION 26 05 10

EIELSON AFB, ALASKA BASIC MATERIALS AND METHODS

PROJECT NO.: FTQW 11-1005

Design Alaska, Inc. 26 05 10 - 13

I. Flexible cords shall be connected to equipment, fixtures, boxes, or other enclosures only by means of cord-grip bodies or other strain-relief fittings specifically designed for the purpose.

J. Where conductors or their connectors are to be connected to metal surfaces, the surface shall first be scraped free of any paint, oxide, or other non-conductive substances. Where there is a possibility of corrosion due to moisture or other cause, a conductive corrosion inhibitor shall be used between the conductor and the metal surface.

K. Conductors shall be pulled into raceways only by constant-tension pulling methods. Where necessary, wire-pulling lubricants of a type that is not harmful to conductor insulation and will not harden shall be used.

L. Completely and thoroughly swab raceway system before installing conductors.

M. Neatly train and lace wiring inside boxes, equipment, and panelboards.

2.4 MOTOR STARTER INSTALLATION

A. Provide overload setting correlated with full load current, NEMA code letter and service factor reflected on actual nameplate of each furnished motor.

B. After final connections are made, check and correct the rotation of all motors.

C. Provide engraved nameplates for all units clearly identifying the equipment served.

D. Do not mount starters on vibrating equipment. Fasten securely to supporting structure at walls and mounting stands.

E. Motor Data: Provide neatly typed label inside each motor starter enclosure door identifying motor served, nameplate horsepower, full load amperage, code letter, service factor, voltage/phase rating, and the final settings of overload devices.

2.5 DISCONNECT SWITCH INSTALLATION

A. Install disconnect switches in accessible locations within sight of the equipment they control for all equipment as indicated on the Drawings.

B. Install fuses in fusible disconnect switches.

C. Provide a label on inside door of each switch indicating UL fuse class and size for replacement.

END OF SECTION