Operating and Maintenance Manual OMM 1130

Group: Chiller

Part Number: OMM 1130

Effective: October 2011

Supercedes: New

Water-Cooled Scroll Compressor Chillers WGZ030DW to WGZ200DW, Packaged Water-Cooled Chiller

WGZ030DA to WGZ200DA, Chiller with Remote Condenser

30 to 200 Tons, 105 to 700 kW

R-410a

50-60 Hertz

Software Version WGZDU0102F

2 OMM 1130

Table of Contents

Introduction General Description Nomenclature Water Pressure Drop Operating Limits Components

Unit Configuration Field Wiring Diagrams Control Panel Layout Motor Protection Module

Start-Up and Shutdown Sequence of Operation

Start-up/Compressor Staging MicroTech II Controller

Controller Software Version General Description Expansion I/O Controller Setpoints Automatic Adjusted Limits Dynamic Defaults

Events & Alarms Unit Stop Alarms Limit Events

Controller Operation EXV Control

Using the Controller Menu Screens Menu Descriptions

BAS Interface Parameter Details

Optional Controls Phase/Voltage Monitor (Optional) Hot Gas Bypass (Optional)

System Maintenance General Electrical Terminals Compressor Lubrication Sightglass and Moisture Indicator Crankcase Heaters Maintenance Schedule

System Service Troubleshooting Chart

Warranty Statement

Products manufactured in an ISO Certified facility

©2011 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the

LONMARK logo are managed, granted and used by LONMARK International under a license granted by Echelon Corporation;

Compliant Scroll from Copeland Corporation; Modbus from Schneider Electric;, MicroTech II, Open Choices from McQuay

International.

Cover Picture: WGZ130C with full-paint option

OMM 1130 3

Introduction

General Description McQuay Type WGZ water chillers are designed for indoor installations and are available with water-cooled condensers (Model DW), or arranged for use with remote air-cooled or evaporative condensers (Model DA).

Each water-cooled unit is completely assembled and factory wired before evacuation, charging and testing.

They consist of hermetic scroll compressors, brazed-plate evaporator, water-cooled condenser (WGZ-DW), and complete refrigerant piping.

Units manufactured for use with remote condensers (Models WGZ-DA) have all refrigerant specialties factory-mounted and connection points for refrigerant discharge and liquid lines.

Liquid line components that are included are manual liquid line shutoff valves, charging valves, filter-driers, liquid line solenoid valves, sight glass/moisture indicators, and thermal expansion valves. Other features include compressor crankcase heaters, and a MicroTech II microprocessor controller.

The electrical control center includes all equipment protection and operating controls necessary for dependable automatic operation.

NOTE: This manual contains information on the chiller unit control software operating with various refrigerants as follows:

R-410A, used with the current “D” vintage of the WGZ chiller.

R-134a, used with only with Model TGZ Templifiers. The operating manual devoted exclusively to Templifiers is OMM TGZ-1.

BOOT & BIOS

BOOT Version: 3.0F BIOS Version 3.56

Manuals: Information in unit initial installation and routine maintenance is contained in Installation and Maintenance Manual IM 1131.

Nomenclature W G Z 100 - D W

Water Pressure Drop Water flow rates should be maintained as closely as possible to job design values. The vessel flow rates must fall between the minimum and maximum values shown on the appropriate evaporator and condenser curves.

Measure the water pressure drop through the vessels at field-installed pressure taps and check the flow rate using the following tables. Do not include valves or strainers in these readings.

The evaporator flow rates and pressure drops shown on the following page are for full load design purposes.

The maximum flow rate and pressure drop are based on a 6-degree temperature drop. Avoid higher flow rates with resulting lower temperature drops to prevent potential control problems resulting from very small control bands and limited start up/shut off temperature changes.

The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16-degrees.

Water-Cooled

Global Design

Scroll Compressor Nominal Capacity (Tons)

W = Water-Cooled Cond.

A = Unit Less Cond.

Design Vintage

Introduction
General Description
BOOT & BIOS
Nomenclature
Water Pressure Drop
Operating Limits
Components
Unit Configuration
Field Wiring Diagrams
Control Panel Layout
Motor Protection Module
Start-Up and Shutdown
Pre Start-up
Start-up
Weekend or Temporary Shutdown
Start-up after Temporary Shutdown
Extended Shutdown
Start-up after Extended Shutdown
Low Ambient Start
Fan High Ambient Rapid Start
Sequence of Operation
Compressor Heaters
Start-up/Compressor Staging
Manual Compressor Disable Logic
Automatic Pumpdown
Manual Pumpdown
Chilled Water and Condenser Water Pumps
Cooling Tower Control
Condenser Fan Control
ICE
MicroTech II Controller
Controller Software Version
General Description
Operator Friendly
Staging
Equipment Protection
Unit Enable Selection
Unit Mode Selection
Keypad/Display
Inputs/Outputs
Expansion I/O Controller
Digital Outputs
Analog Inputs
Setpoints
Automatic Adjusted Limits
Dynamic Defaults
Refrigerant Dependent Defaults
Number of Fans Dependent Defaults
Events & Alarms
Unit Stop Alarms
Evaporator Flow Loss
Condenser Flow Loss (Note: WaterCooled = On & TGZ units Only)
Low Evaporator Pressure
High Condenser Pressure
Mechanical High Pressure/Motor Protect
Phase Voltage Protection
Ground Fault Protection
Low OAT Restart Fault
Evaporator Water Freeze Protect
Leaving Evaporator Water Temperature Sensor Fault
Leaving Condenser Water Temperature Sensor Fault
Suction Temperature Sensor Fault
Evaporator Pressure Sensor Fault
Condenser Pressure Sensor Fault
Condenser Entering or Outdoor Air Temperature Sensor Fault
Evaporator Water Freeze Protect
No Pressure Change at Start
EXB Comm Failure on CP1
Alarm Log
Active Alarms
Clearing Alarms
Limit Events
Low Evaporator Pressure - Hold
Low Evaporator Pressure - Unload
High Condenser Pressure - Unload
Failed Pumpdown
Condenser Freeze Event
Condenser Freeze Event (Water Cooled = Y Only)
Suction Temperature Sensor Fail
Entering Evaporator Water Temperature Sensor Fail (TGZ unit only)
Liquid Line Temperature Sensor Fail (TGZ unit only)
Low Source Water Temperature (TGZ unit in ‘heat’ mode only)
EXB Comm Failure on CP1 (TGZ unit only)
Event Log
Controller Operation
Calculations
Leaving Water Temperature (LWT) Reset
Reset Type = NONE
Reset Type = 4-20 mA
Reset Type = Return (only for TGZ unit, Refrig = R134a)
Active LWT Set Point
LWT Error
LWT Slope
Pull Down Rate
Evaporator Saturated Temperature
Condenser Saturated Temperature
Evaporator Approach
Suction Superheat
Pumpdown Pressure
Unit Enable
Unit Mode
Unit Test Mode
Circuit Available
Power Up Start Delay
Ice Mode Start Delay
Low Ambient Lockout
Unit State
Evaporator Water Pump State Control (Evap State)
Pump Selection
Primary/Standby Pump Staging
Auto Control
Evaporator Water Flow Loss
Condenser Fans – Air Cooled
Fantrol
Fan Stages
Normal Operation – Staging Up
Normal Operation – Staging Down
Forced Fan Stage at Start
Condenser Pump and Tower Control – Water Cooled
Condenser Water Pump State Control (Cond State)
Pump Selection
Primary/Standby Pump Staging
Auto Control
Condenser Water Flow Loss
Tower Fans
Cooling Tower Bypass Valve
Initial Valve Position
Valve Set Point Mode
Valve Stage Mode
Cooling Tower Fan VFD
Compressor Start/Stop Timing
Stage Up Now
Stage Down Now
Compressor Sequencing
Low Ambient Start (WaterCooled = NO)
Low Ambient Start Procedure
Circuit Capacity Overrides
Low Evaporator Pressure
High Condenser Pressure – Unload Logic
Unit Capacity Overrides
Demand Limit
Network Limit
Maximum LWT Rate
Low Ambient Lockout (Water Cooled = NO Only)
Manual Compressor Control
Normal Circuit Shutdown
Pump Down Procedure
Rapid Circuit Shutdown
Liquid Line Solenoid
Hot Gas Bypass Solenoid
EXV Control
EXV Control Range
Manual EXV Control
Maximum EXV Operating Pressure
Using the Controller
Getting Started
Navigating Through the Menus
MENU Key
ENTER Key
Menu Screens
Menu Descriptions
Screen Definitions – MENU
Top level menu:
ALARM menu:
VIEW menu:
VIEW UNIT menu:
SET menu:
Screen Definitions – VIEW
View Unit Status
View Unit Tempertures
View Circuit
View Refrigerant
Water Cooled = Y Only or
TGZ Unit (R134a)
Water Cooled = Y Only or
TGZ Unit (R134a)
Water Cooled = N Only
Screen Definitions – ALARM
Screen Definitions – EVENT LOG
Screen Definitions – SET
Set Unit Setpoints
WGZ Units Only TGZ Units Only (R134a)
Water-Cooled = ON Water-Cooled = OFF
TGZ Units (R134a)
TGZ Units (Refrig = R134a)
WGZ Unit (R22,R407C,R410A) TGZ Unit (Refrig = 134a)
WGZ Unit (R22,R407C,R410A) TGZ Unit (Refrig = 134a)
TGZ Unit in Cooling Mode . TGZ Unit in Heat Mode.
TGZ Unit Heat Mode.
Set Compressor Setpoints
Set Air-Cooled Condenser Fans
Set Cooling Tower Control
Initial Valve Position
Operation After Start
TEST
Editing Review
Alarms
Security
BAS Interface
Protocols Supported
BACnet®
LONworks®
Modbus®
Available Parameters
Parameter Details
Units of Measure
Chiller Mode
LON Chiller Run Mode
Unit Identification
Compressor Select
Timeclock Setting
Network Defaults
Other Digital Output Parameters
Optional Controls
Phase/Voltage Monitor (Optional)
Hot Gas Bypass (Optional)
System Maintenance
General
Electrical Terminals
Compressor Lubrication
Sightglass and Moisture Indicator
Crankcase Heaters
Maintenance Schedule
System Service
Filter-Driers
Liquid Line Solenoid Valve
Thermostatic Expansion Valve
Water-cooled Condenser
Evaporator
Troubleshooting Chart

Warranty Statement