Operating and Maintenance Manual OMM 1130
Group: Chiller
Part Number: OMM 1130
Effective: October 2011
Supercedes: New
Water-Cooled Scroll Compressor Chillers WGZ030DW to WGZ200DW, Packaged Water-Cooled Chiller
WGZ030DA to WGZ200DA, Chiller with Remote Condenser
30 to 200 Tons, 105 to 700 kW
R-410a
50-60 Hertz
Software Version WGZDU0102F
2 OMM 1130
Table of Contents
Introduction General Description Nomenclature Water Pressure Drop Operating Limits Components
Unit Configuration Field Wiring Diagrams Control Panel Layout Motor Protection Module
Start-Up and Shutdown Sequence of Operation
Start-up/Compressor Staging MicroTech II Controller
Controller Software Version General Description Expansion I/O Controller Setpoints Automatic Adjusted Limits Dynamic Defaults
Events & Alarms Unit Stop Alarms Limit Events
Controller Operation EXV Control
Using the Controller Menu Screens Menu Descriptions
BAS Interface Parameter Details
Optional Controls Phase/Voltage Monitor (Optional) Hot Gas Bypass (Optional)
System Maintenance General Electrical Terminals Compressor Lubrication Sightglass and Moisture Indicator Crankcase Heaters Maintenance Schedule
System Service Troubleshooting Chart
Warranty Statement
Products manufactured in an ISO Certified facility
©2011 McQuay International. Illustrations and data cover the McQuay International product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the
LONMARK logo are managed, granted and used by LONMARK International under a license granted by Echelon Corporation;
Compliant Scroll from Copeland Corporation; Modbus from Schneider Electric;, MicroTech II, Open Choices from McQuay
International.
Cover Picture: WGZ130C with full-paint option
OMM 1130 3
Introduction
General Description McQuay Type WGZ water chillers are designed for indoor installations and are available with water-cooled condensers (Model DW), or arranged for use with remote air-cooled or evaporative condensers (Model DA).
Each water-cooled unit is completely assembled and factory wired before evacuation, charging and testing.
They consist of hermetic scroll compressors, brazed-plate evaporator, water-cooled condenser (WGZ-DW), and complete refrigerant piping.
Units manufactured for use with remote condensers (Models WGZ-DA) have all refrigerant specialties factory-mounted and connection points for refrigerant discharge and liquid lines.
Liquid line components that are included are manual liquid line shutoff valves, charging valves, filter-driers, liquid line solenoid valves, sight glass/moisture indicators, and thermal expansion valves. Other features include compressor crankcase heaters, and a MicroTech II microprocessor controller.
The electrical control center includes all equipment protection and operating controls necessary for dependable automatic operation.
NOTE: This manual contains information on the chiller unit control software operating with various refrigerants as follows:
R-410A, used with the current “D” vintage of the WGZ chiller.
R-134a, used with only with Model TGZ Templifiers. The operating manual devoted exclusively to Templifiers is OMM TGZ-1.
BOOT & BIOS
BOOT Version: 3.0F BIOS Version 3.56
Manuals: Information in unit initial installation and routine maintenance is contained in Installation and Maintenance Manual IM 1131.
Nomenclature W G Z 100 - D W
Water Pressure Drop Water flow rates should be maintained as closely as possible to job design values. The vessel flow rates must fall between the minimum and maximum values shown on the appropriate evaporator and condenser curves.
Measure the water pressure drop through the vessels at field-installed pressure taps and check the flow rate using the following tables. Do not include valves or strainers in these readings.
The evaporator flow rates and pressure drops shown on the following page are for full load design purposes.
The maximum flow rate and pressure drop are based on a 6-degree temperature drop. Avoid higher flow rates with resulting lower temperature drops to prevent potential control problems resulting from very small control bands and limited start up/shut off temperature changes.
The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16-degrees.
Water-Cooled
Global Design
Scroll Compressor Nominal Capacity (Tons)
W = Water-Cooled Cond.
A = Unit Less Cond.
Design Vintage
| Introduction |
| General Description |
| BOOT & BIOS |
| Nomenclature |
| Water Pressure Drop |
| Operating Limits |
| Components |
| Unit Configuration |
| Field Wiring Diagrams |
| Control Panel Layout |
| Motor Protection Module |
| Start-Up and Shutdown |
| Pre Start-up |
| Start-up |
| Weekend or Temporary Shutdown |
| Start-up after Temporary Shutdown |
| Extended Shutdown |
| Start-up after Extended Shutdown |
| Low Ambient Start |
| Fan High Ambient Rapid Start |
| Sequence of Operation |
| Compressor Heaters |
| Start-up/Compressor Staging |
| Manual Compressor Disable Logic |
| Automatic Pumpdown |
| Manual Pumpdown |
| Chilled Water and Condenser Water Pumps |
| Cooling Tower Control |
| Condenser Fan Control |
| ICE |
| MicroTech II Controller |
| Controller Software Version |
| General Description |
| Operator Friendly |
| Staging |
| Equipment Protection |
| Unit Enable Selection |
| Unit Mode Selection |
| Keypad/Display |
| Inputs/Outputs |
| Expansion I/O Controller |
| Digital Outputs |
| Analog Inputs |
| Setpoints |
| Automatic Adjusted Limits |
| Dynamic Defaults |
| Refrigerant Dependent Defaults |
| Number of Fans Dependent Defaults |
| Events & Alarms |
| Unit Stop Alarms |
| Evaporator Flow Loss |
| Condenser Flow Loss (Note: WaterCooled = On & TGZ units Only) |
| Low Evaporator Pressure |
| High Condenser Pressure |
| Mechanical High Pressure/Motor Protect |
| Phase Voltage Protection |
| Ground Fault Protection |
| Low OAT Restart Fault |
| Evaporator Water Freeze Protect |
| Leaving Evaporator Water Temperature Sensor Fault |
| Leaving Condenser Water Temperature Sensor Fault |
| Suction Temperature Sensor Fault |
| Evaporator Pressure Sensor Fault |
| Condenser Pressure Sensor Fault |
| Condenser Entering or Outdoor Air Temperature Sensor Fault |
| Evaporator Water Freeze Protect |
| No Pressure Change at Start |
| EXB Comm Failure on CP1 |
| Alarm Log |
| Active Alarms |
| Clearing Alarms |
| Limit Events |
| Low Evaporator Pressure - Hold |
| Low Evaporator Pressure - Unload |
| High Condenser Pressure - Unload |
| Failed Pumpdown |
| Condenser Freeze Event |
| Condenser Freeze Event (Water Cooled = Y Only) |
| Suction Temperature Sensor Fail |
| Entering Evaporator Water Temperature Sensor Fail (TGZ unit only) |
| Liquid Line Temperature Sensor Fail (TGZ unit only) |
| Low Source Water Temperature (TGZ unit in ‘heat’ mode only) |
| EXB Comm Failure on CP1 (TGZ unit only) |
| Event Log |
| Controller Operation |
| Calculations |
| Leaving Water Temperature (LWT) Reset |
| Reset Type = NONE |
| Reset Type = 4-20 mA |
| Reset Type = Return (only for TGZ unit, Refrig = R134a) |
| Active LWT Set Point |
| LWT Error |
| LWT Slope |
| Pull Down Rate |
| Evaporator Saturated Temperature |
| Condenser Saturated Temperature |
| Evaporator Approach |
| Suction Superheat |
| Pumpdown Pressure |
| Unit Enable |
| Unit Mode |
| Unit Test Mode |
| Circuit Available |
| Power Up Start Delay |
| Ice Mode Start Delay |
| Low Ambient Lockout |
| Unit State |
| Evaporator Water Pump State Control (Evap State) |
| Pump Selection |
| Primary/Standby Pump Staging |
| Auto Control |
| Evaporator Water Flow Loss |
| Condenser Fans – Air Cooled |
| Fantrol |
| Fan Stages |
| Normal Operation – Staging Up |
| Normal Operation – Staging Down |
| Forced Fan Stage at Start |
| Condenser Pump and Tower Control – Water Cooled |
| Condenser Water Pump State Control (Cond State) |
| Pump Selection |
| Primary/Standby Pump Staging |
| Auto Control |
| Condenser Water Flow Loss |
| Tower Fans |
| Cooling Tower Bypass Valve |
| Initial Valve Position |
| Valve Set Point Mode |
| Valve Stage Mode |
| Cooling Tower Fan VFD |
| Compressor Start/Stop Timing |
| Stage Up Now |
| Stage Down Now |
| Compressor Sequencing |
| Low Ambient Start (WaterCooled = NO) |
| Low Ambient Start Procedure |
| Circuit Capacity Overrides |
| Low Evaporator Pressure |
| High Condenser Pressure – Unload Logic |
| Unit Capacity Overrides |
| Demand Limit |
| Network Limit |
| Maximum LWT Rate |
| Low Ambient Lockout (Water Cooled = NO Only) |
| Manual Compressor Control |
| Normal Circuit Shutdown |
| Pump Down Procedure |
| Rapid Circuit Shutdown |
| Liquid Line Solenoid |
| Hot Gas Bypass Solenoid |
| EXV Control |
| EXV Control Range |
| Manual EXV Control |
| Maximum EXV Operating Pressure |
| Using the Controller |
| Getting Started |
| Navigating Through the Menus |
| MENU Key |
| ENTER Key |
| Menu Screens |
| Menu Descriptions |
| Screen Definitions – MENU |
| Top level menu: |
| ALARM menu: |
| VIEW menu: |
| VIEW UNIT menu: |
| SET menu: |
| Screen Definitions – VIEW |
| View Unit Status |
| View Unit Tempertures |
| View Circuit |
| View Refrigerant |
| Water Cooled = Y Only or |
| TGZ Unit (R134a) |
| Water Cooled = Y Only or |
| TGZ Unit (R134a) |
| Water Cooled = N Only |
| Screen Definitions – ALARM |
| Screen Definitions – EVENT LOG |
| Screen Definitions – SET |
| Set Unit Setpoints |
| WGZ Units Only TGZ Units Only (R134a) |
| Water-Cooled = ON Water-Cooled = OFF |
| TGZ Units (R134a) |
| TGZ Units (Refrig = R134a) |
| WGZ Unit (R22,R407C,R410A) TGZ Unit (Refrig = 134a) |
| WGZ Unit (R22,R407C,R410A) TGZ Unit (Refrig = 134a) |
| TGZ Unit in Cooling Mode . TGZ Unit in Heat Mode. |
| TGZ Unit Heat Mode. |
| Set Compressor Setpoints |
| Set Air-Cooled Condenser Fans |
| Set Cooling Tower Control |
| Initial Valve Position |
| Operation After Start |
| TEST |
| Editing Review |
| Alarms |
| Security |
| BAS Interface |
| Protocols Supported |
| BACnet® |
| LONworks® |
| Modbus® |
| Available Parameters |
| Parameter Details |
| Units of Measure |
| Chiller Mode |
| LON Chiller Run Mode |
| Unit Identification |
| Compressor Select |
| Timeclock Setting |
| Network Defaults |
| Other Digital Output Parameters |
| Optional Controls |
| Phase/Voltage Monitor (Optional) |
| Hot Gas Bypass (Optional) |
| System Maintenance |
| General |
| Electrical Terminals |
| Compressor Lubrication |
| Sightglass and Moisture Indicator |
| Crankcase Heaters |
| Maintenance Schedule |
| System Service |
| Filter-Driers |
| Liquid Line Solenoid Valve |
| Thermostatic Expansion Valve |
| Water-cooled Condenser |
| Evaporator |
| Troubleshooting Chart |
Warranty Statement