Fire Suppression System specs.doc

DOC document 31 KB Posted

Attached to
Fire Suppression System
Solicitation number
RFQ - 17D - 11070800000000000005
Issued by
Kennebec County, Maine

About this file

This specifications document outlines requirements for a dry chemical fire suppression system to be installed at Maine Department of Transportation Fleet Services in Augusta, Maine. The system is required for a COL-MET truck and equipment paint booth (model TSC 1813-40 PSB) with dimensions of 19 feet wide by 15 feet 2 inches tall by 40 feet 6 inches long. The paint booth includes a paint mixing room (PMR-0810) measuring approximately 8 feet by 8 feet by 10 feet, equipped with two personnel access doors, exhaust systems, and thirty-two four-tube fluorescent light fixtures. The facility also includes a Titan Heat and Cure Air Make-Up Unit (Model TA-220 LG VRH-H.O.T) with a 2,500,000 BTU LP gas direct-fired burner and 15 horsepower fan motor capable of producing 160-degree hot air for paint curing. The installed system must comply with all applicable Federal, State, local, and OSHA regulations and be inspected and certified by the local regulating authority.

Bid proposals must include all shipping, delivery, and installation costs to the Maine DOT Fleet Services location at 105 Capitol Street, Augusta, Maine 04333. Bidders are required to include an external fire alarm system with all materials, temperature detectors, alarms, installation, testing, test gases, and certification, along with a designated warranty period per Maine State requirements. Bids will be evaluated based on price, warranty, manufacturer performance data, delivery schedule, parts availability, and other appropriate factors. Maine DOT reserves the right to pre-inspect equipment before delivery, and upon delivery, all necessary documentation including invoices, layout diagrams, drawings, and maintenance and inspection schedules must accompany the unit. Vendors must submit all questions regarding the request for quote through the designated Question and Answer link on the Solicitation Details View page.

View the file

Other files

File Type Posted
Solicitation_terms.doc DOC document
LakeSmart Firewise Brochure[1].pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE SUPPRESSION SYSTEM

Specifications

The following specifications are intended to describe an area where a dry chemical fire suppression system is required to be installed. The completed system must meet all applicable Federal, State, local and OSHA regulations. The system must be well designed, tested for reliable performance, inspected and certified by the local regulating authority.

1. COL-MET TRUCK and EQUIPMENT PAINT BOOTH

1. COL-MET truck and equipment, modified down-flow, pressurized paint and bake booth, model TSC 1813-40 PSB. With paint mixing room and a Titan Heat and Cure, Air Make-Up Unit attached.

2. Dimensions and Accessories of Paint Booth

2.1 Out-side dimensions 19ft. wide x 15ft. 2” tall x 40ft 6” long.

2.2 Inside dimensions 18ft x 13 ft. x 40 ft. long.

2.3 Two 24” Vaneaxial exhaust fans with intake air and exhaust pipes.

2.4 Thirty two (32) four (4) ft. UL listed four tube fluorescent light fixtures.

2.5 Three bi-folding product doors 16ft. wide x 1ft high (approximate)

3. Paint Mixing Room (PMR-0810)

3.1 Dimensions are 8ft x 8ft x 10ft (approximate).

3.2 Two personnel access doors 30in. wide x 7ft. tall (approximate).

3.3 One open light fixture.

3.4 Exhaust stack 12in diameter x 15ft. high.

3.5 One 12in.exhaust fan with a 1-1/4hp.motor to provide exhaust at 1700 scfm.

4. TITAN HEAT AND CURE AIR MAKE-UP UNIT

4.1 Titan Outdoor Vertical Air Make-up Unit Model TA-220 LG VRH-H.O.T with Bake Mode.

4.2 AMU has a LP Gas Direct-Fired 2,500,000 BTU burner with a 15 hp.fan motor.

4.3 AMU is capable of 160° hot air for paint curing.

4.4 AMU will replace exhausted paint booth air at normal requirements.

4.5 AMU requires 460V, 3ph, 3 wire and 60Hz power source.

5. GENERAL INFORMATION:

5.1 Engineer drawings, manufacturer brochures and related information will be issued upon request to bidding vendors.

5.2 All bid proposals will include shipping, delivery and installation costs at:

Maine DOT Fleet Services, 105 Capitol St. Augusta, Maine 04333.

5.3 Maine DOT reserves the right to pre-inspect the equipment before delivery.

5.4 Upon delivery of unit all necessary paper work such as invoices, lay-out diagrams, drawings and maintenance and/or inspection schedules shall accompany unit

5.7 Be it known that these specifications are a minimum and

that bids will be valuated based on price, warranty, manufacturer’s performance data, delivery schedule, parts availability and other items deemed appropriate.

You bid must include an external fire alarm system along with all materials, temperature detectors, alarms, installation, testing, test gases, and certification, plus a designated warranty period per State of Maine’s requirement.

If you have a question regarding this RFQ, you must submit your questions thru the Question and Answer link on the Solicitation Details View page. Your answer will appear there as well. It is the vendor’s responsibility to log in to view all questions and answers posted there. Questions and Answers obtained any other way will not be valid for this RFQ.

REV. 6/11 ESB

File details come from the government source that posted it. Updated .