This Scope of Work document outlines fire safety testing, inspection, and monitoring services required by two healthcare facilities in Cumberland, Maryland: Sheppard Pratt of Cumberland and Thomas B. Finan Center. The procurement solicits bids for a fixed two-year contract term covering baseline inspections, diagnostic testing, and system monitoring performed during normal business hours (Monday-Friday, 7:00 AM to 5:00 PM). Sheppard Pratt of Cumberland requires annual fire alarm system inspections covering one main control panel, two NAC panels, 88 initiating and supervisory devices, and 79 notification and output devices; quarterly water-based sprinkler system testing of three wet systems; and 24/7 central station monitoring of one fire alarm system with cellular dialer maintenance. Thomas B. Finan Center requires more extensive services including annual fire alarm inspections of one main 640 control panel, nine NAC panels, two annunciator panels, 327 initiating and supervisory devices, and 438 notification and output devices with annual elevator recall testing; quarterly testing of eight wet sprinkler systems; semi-annual commercial kitchen hood suppression system inspections; annual portable fire extinguisher tagging and inspection; and 24/7 central station monitoring of one fire alarm system.
The vendor is responsible solely for determining system functionality at the time of performance, with standard contract pricing excluding routine maintenance, repairs, parts replacements, and compliance design analyses. Vendors must itemize suggested improvements in accordance with NFPA Guidelines and report findings accordingly. The facility maintains primary responsibility for system readiness, providing unobstructed access to all devices, maintaining active system engagement, coordinating pre-test notifications with local fire departments and monitoring providers, scheduling third-party inspections and elevator service coordination, providing up-to-date as-built system drawings, supplying stable 120VAC power with two active phone lines on RJ31X jacks adjacent to control panels, ensuring adequate external drainage capacity for sprinkler testing discharge, maintaining heated sprinkler valve enclosures above 40 degrees Fahrenheit, and managing routine maintenance of dry pipe low-point drum drips. Areas that are locked, concealed, or present safety hazards such as unfloored or poorly lit attics are excluded from inspection scope.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Scope of Work: Fire Safety Test, Inspection and Monitoring
TECHNICAL SPECIFICATIONS FOR TEST, INSPECTION, AND MONITORING CONTRACT
PROCUREMENT
This document details the operational duties, technical testing specifications, and facility requirements necessary to maintain the fire protection and safety systems at the specified locations. It serves as a simplified, vendor-neutral framework for soliciting future service contracts.
Procurement Requirement: The facility is explicitly soliciting bids for a fixed two (2) year contract term covering all baseline inspections, diagnostic testing, and system monitoring outlined below.
1. Covered Locations & General Service Terms
Location A: Sheppard Pratt of Cumberland
10100 Country Club Road, Cumberland, MD 21502
Location B: Thomas B Finan Center
10102 Country Club Road, Cumberland, MD 21502
Service Hours: All routine inspections and testing must be performed during normal business hours:
Monday through Friday, 7:00 AM to 5:00 PM.
2. Technical Scope of Work by Facility
Facility 1: Sheppard Pratt of Cumberland
The vendor is required to perform recurring inspection, testing, and monitoring for the following equipment inventory:
Fire Alarm System & Devices (Annual Inspection and Test)
Control Equipment: (1) Main Control Panel, (2) NAC Panels.
Initiating & Supervisory Devices: (12) Duct Detectors, (17) Manual Pull Stations, (6) Heat Detectors,
(47) Smoke Detectors, (3) Flow Switches, (6) Tamper Switches.
Notification & Output Devices: (37) Audio/Visual Devices, (36) Strobes, (6) Door Holders.
Water-Based Sprinkler Systems (Quarterly Inspection and Test)
Systems Covered: (3) Wet Sprinkler Systems.
Required Tests: Functional testing of Flow Switches, Inspector's Tests, Tamper Switches, and Main Drain
Tests.
System Monitoring
Central Station Monitoring: 24/7 monitoring of (1) Fire Alarm System.
Cellular Communications: Operational maintenance and cellular monitoring of (1) existing Cellular Dialer.
Facility 2: Thomas B Finan Center
The vendor is required to perform recurring inspection, testing, and monitoring for the following equipment inventory:
Fire Alarm System & Devices (Annual Inspection and Test)
Control Equipment: (1) Main 640 Control Panel, (9) NAC Panels, (2) Annunciator Panels.
Initiating & Supervisory Devices: (24) Duct Detectors, (76) Manual Pull Stations, (13) Heat Detectors,
(220) Smoke Detectors, (14) Tamper Switches.
Notification & Output Devices: (116) Strobe Devices, (245) Chime/Strobe Devices, (1) Bell Device, (76)
Door Holders.
Specialized Testing: Annual Elevator Recall testing.
Water-Based Sprinkler Systems (Quarterly Inspection and Test)
Systems Covered: (8) Wet Sprinkler Systems.
Required Tests: Functional testing of Flow Switches, Inspector's Tests, Tamper Switches, and Main Drain
Tests.
Commercial Kitchen Suppression (Semi-Annual Inspection and Test)
Systems Covered: (1) Kitchen Hood System tested on a semi-annual basis.
Portable Fire Extinguishers (Annual Inspection and Test)
Required Services: Annual tagging and basic inspection of all facility fire extinguishers.
Note: Deeper maintenance—such as recharging, parts replacement, and hydrostatic testing—should be dynamically completed during the annual walkthrough as needed.
System Monitoring (and Test)
Central Station Monitoring: 24/7 monitoring of (1) Fire Alarm System.
3. General Vendor Obligations & Limitations
Functional Limits: Testing and inspection services are designed solely to determine system functionality at the time of performance. Standard contract pricing excludes routine maintenance, systemic repairs, part replacements, or compliance design analyses.
Reporting: Vendor must itemize suggested improvements noticed during testing in accordance with
National Fire Protection Association (NFPA) Guidelines.
Excluded Areas: Areas that are locked, concealed, or deemed safety hazards (such as unfloored, poorly lit, or unsafe attics) are explicitly excluded from inspection.
4. Hospital Operational Responsibilities
To ensure the vendor can successfully execute these duties, the facility assumes the following operational responsibilities:
System Readiness & Access: Provide unobstructed, safe physical access to all programmatic devices wired to the main panels. Maintain the system in an active, engaged state.
Pre-Test Coordination: Prior to any live test, notify the local fire department, alarm monitoring provider, and all building tenants/occupants.
Third-Party Coordination: Schedule and coordinate the simultaneous presence of the Elevator Servicing
Company and a 3rd Party Inspector during the Annual Fire Alarm Inspection to successfully execute the
Elevator Recall tests (required for the Thomas B Finan Center). Co-facilitate access with door or mechanical contractors if roll-down doors or smoke dampers require resetting.
Documentation: Provide the service vendor with up-to-date "as-built" system drawings (including post-installation modifications).
Infrastructure Provisions:
Provide stable 120VAC power and (2) active phone lines on standard RJ31X jacks directly adjacent to the control panels for communication link-up.
Provide sufficient and accessible external drainage capacity to handle the full water discharge generated during quarterly sprinkler flow testing.
Maintain heated enclosures (above 40°F) for all sprinkler valve areas.
Manage weekly/monthly routine draining of dry pipe low-point drum drips to prevent system freeze damage.
| Scope of Work: Fire Safety Test, Inspection and Monitoring |
| 1. Covered Locations & General Service Terms |
| 2. Technical Scope of Work by Facility |
| Facility 1: Sheppard Pratt of Cumberland |
| Fire Alarm System & Devices (Annual Inspection and Test) |
| Water-Based Sprinkler Systems (Quarterly Inspection and Test) |
| System Monitoring |
| Facility 2: Thomas B Finan Center |
| Fire Alarm System & Devices (Annual Inspection and Test) |
| Water-Based Sprinkler Systems (Quarterly Inspection and Test) |
| Commercial Kitchen Suppression (Semi-Annual Inspection and Test) |
| Portable Fire Extinguishers (Annual Inspection and Test) |
| System Monitoring (and Test) |
| 3. General Vendor Obligations & Limitations |
| 4. Hospital Operational Responsibilities |