FHPS Northern High School Structured Cabling RFP APP B.xlsx
XLSX spreadsheet 61 KB Posted
- Attached to
- Northern High School Structured Cabling RFP
- Solicitation number
- RFP FHP 270000000321 1
- Issued by
- Kent County, Michigan
About this file
This file is Appendix B of a Request for Proposals (RFP) issued by Forest Hills Public Schools for structured cabling work at Northern High School. The RFP requires vendors to submit responses in Microsoft Excel format including four mandatory forms: a Vendor Questionnaire, Technical Specifications, Device Inventory, and Cost sheets. The project involves comprehensive cabling infrastructure installation and includes 389 total data drops across various configurations (single, dual, triple, quad, and octuple drop locations), with 199 new single drops for general data, 196 blue drops, 3 yellow security camera drops, and specialized installations for wireless access points (black), Centigex alarm systems (white), and PA systems (purple). The scope also encompasses demolition of approximately 998 old cable runs, installation of 10 network closets with associated cabinets, and provision of backbone cabling with fiber optics for future use. Additionally, the project requires vendors to identify existing Category 5 or 5e security camera runs for replacement and existing wireless access point installations with single cable runs as potential change orders.
The cost structure includes a base bid total for Northern High School and a separate add/alternate option for Category 6A cabling, with vendors required to provide performance and payment bond percentages applicable to alternates. Unit pricing is requested for various components including structured cabling labor, raceway installation, data cables at multiple locations, patch panels, patch cords in various lengths, backbone cabling, cable tray, network closet components, and removal/demolition services. Vendors must also provide hourly rates for system-certified technicians for normal hours, after-hours, and Sunday/holiday work, along with trip charge information or travel time policies. All proposed cabling systems must include a certified 15-year performance guarantee, materials must be new and current production, and proposals must confirm compliance with federal bans on prohibited Chinese manufacturer components. The file does not identify any set-asides, incumbent contractors, specific response or award dates, or contract term information.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contents
Electronic Copy Must be submitted in Microsoft Excel format See section 1.7 of the RFP For Sumission Instructions
| Instructions: The RFP forms section contains the following documents that MUST to submitted with your RFP response. |
| REQUIRED FORMS: |
| The following forms MUST be submitted as a part of your RFP Response |
| Contents: |
| Vendor Questionnaire |
| Technical Specifications |
| Device Inventory |
| Cost |
Your bid response must include a completed copy of each form above, in the order listed above. An electronic copy of these forms in a Microsoft Excel (.xlsx) format must also be submitted. See RFP for Proposal Submission Instructions. Failure to submit each of the above forms may be cause for rejection of the bid response.
&"Lato,Bold"&10FOREST HILLS PUBLIC SCHOOLS
NORTHERN HIGH SCHOOL STRUCTURED CABLING RFP
&K04+000APPENDIX B
&"Lato,Italic"&9Prepared by: Plante Moran &"Lato,Italic"&9&A | Page &P
Vendor Questionnaire
| Vendor Questionnaire |
| General |
| Company name |
| Company address |
| Contact name |
| Phone |
| SPIN Number |
| Services provided by your firm: |
| Primary |
| Secondary |
| Business structure (corporation, partnership, sole proprietor, other) |
| Number of years in business as the company named above: |
| Geographical area of operations for your firm: |
| Work force: |
| Administrative |
| Field |
| Other |
| Total |
| Companies largest single contract: |
| Annual gross revenue for last three (3) years: |
| 2025 |
| 2024 |
| 2023 |
| Bonding limits |
| Single project |
| Aggregate project |
| Contact who can verify limits |
| Insurance limits (attach a certificate as well) |
| Bonding company for performance bond |
| Include letter from performance bond company |
| References |
| Reference 1 |
| Organization name |
| Contact name |
| Contact phone |
| Contact email |
| Project description |
| Dates |
| Reference 2 |
| Organization name |
| Contact name |
| Contact phone |
| Contact email |
| Project description |
| Dates |
| Reference 3 |
| Organization name |
| Contact name |
| Contact phone |
| Contact email |
| Project description |
| Dates |
| Subcontractors |
| Do you intend to use subcontractors for this project? |
| If yes, indicate subcontractor name |
| If yes, indicate what role they will play |
| If yes, provide 3 references where you have worked with them on similar projects: |
| Personnel |
| # of crews |
| # of staff per crew |
| Composition of crew |
| Average experience of crew |
| Solution |
| Please indicate any assumptions you made in your proposal. |
| Are you comfortable with the outlined implementation schedule and the work hours? |
| Please confirm that you have included all required solution components for the quantities listed in this appendix and on the prints, and if your proposal does not include enough you will include these at no additional charge. |
| Please state the cabling manufacturer and model. |
| Do all proposed cabling systems include a certified 15-year performance guarantee? |
| State specifically what organizations are responsible for the certified 15-year warranty. |
| Please include a copy of the performance guarantee with your proposal. |
| Please confirm all proposed materials are new/current-production. |
| In light of the federal ban on technologies/ telecommunications equipment from various Chinese manufacturers, please confirm that your proposal contains no components from a prohibited manufacturer and is compliant with federal law. |
NORTHERN HIGH SCHOOL STRUCTURED CABLING RFP
&K04+000APPENDIX B
&"Lato,Italic"&9Prepared by: Plante Moran &"Lato,Italic"&9&A | Page &P
Technical Specifications
| Technical Specifications | ||
| This spreadsheet is to be used to provide detail on the equipment necessary to fulfill the requirements as requested in the RFP. Indicate in the right column what brand and model you are proposing, and whether you comply, take exception or exceed the required spec. If exceed or exception, please list what this exception is. | ||
| Item | Requirement | Vendor Response |
Model/Comply/Exceed/Exception
| Section 2 - Cabling | |
| Patch panels | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Port count per panel | 48 |
| Performance/Cable category | Category 6 |
| Port configuration | 8P8C |
| Port termination | 110 punch down |
| Mounting application | Rack-mounted (19") |
| Wire management (front) | One horizontal per patch panel |
| Wire management (rear) | One horizontal per patch panel |
| Wiring configuration | T568B |
| Standards & compliance | ANSI/TIA-568.2 |
UL-listed
| Horizontal cabling | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Performance/Cable category | Category 6 |
| Jacket insulation | CMP (plenum) rated |
| Pair count | 4-Pair |
| Wiring configuration | T568B |
| Gauge | 24 AWG solid copper conductors |
| Connectors | IDC, 110-type jack, UL-rated |
| Bundling | No more than 24 cords per bundle |
| Color | General: Blue |
Wireless: Black Centigex alarm system: White PA: Purple Video surveillance: Yellow Qualifications/Certifications ANSI/TIA-568.0
ANSI/TIA-568.2
NEC Certified CSA Certified UL LP-rated UL Standard 444 IEEE 802.3af/at/bt
| Device patch cords | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Performance/Cable category | Category 6 |
| Jacket insulation | CMP (plenum) rated |
| Pair count | 4-Pair |
| Wiring configuration | T568B |
| Gauge | 24 AWG solid copper conductors |
| Connectors | IDC, 110-type jack, UL-rated |
| Min. cable length | 6 ft |
| Color | General: Blue |
Wireless: Black PA: Purple Video surveillance: Red Qualifications/Certifications ANSI/TIA-568.0
ANSI/TIA-568.2
NEC Certified CSA Certified UL LP-rated UL Standard 444 IEEE 802.3af/at/bt
| Patch panel-to-equipment patch cords | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Performance/Cable category | Category 6 |
| Jacket insulation | CMP (plenum) rated |
| Pair count | 4-Pair |
| Wiring configuration | T568B |
| Gauge | 24-26 AWG solid copper conductors |
| Connectors | 8P8C (RJ45) |
| Min. cable length | 1 ft |
| Bundling | No more than 24 cords per bundle |
| Color | General: Blue |
Wireless: Black PA: Purple Video surveillance: Red Qualifications/Certifications ANSI/TIA-568.0
ANSI/TIA-568.2
NEC Certified CSA Certified UL LP-rated UL Standard 444 IEEE 802.3af/at/bt
| Backbone cabling- Provide for potential future use | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Fiber type | Single-mode inside plant - OS1a |
(TIA-492CAAC B-652.D, IEC 60793-2-50)
Connectors For 1-2 fibers: LC (ANSI/TIA-604-10) For 3+ fibers: MPO (ANSI/TIA-604-5)
| Buffer tube design | Tight buffer tube |
| Core diameter | 8.2 µm |
| Cladding diameter | 125 + 0.7 µm |
| Minimum bend radius | 25 mm when not subject to tensile load. |
| Strand count | 12 |
| Jacket | Armored OFNP (Plenum & dielectric) |
| Maximum attenuation | @ 1310nm: 0.5 dB/km |
@ 1383nm: 0.5 dB/km @ 1550nm: 0.5 dB/km Standards & compliance ANSI/TIA-492CAAC B652.D
ANSI/TIA-568.3
ANSI/TIA-604
All corresponding TIA FOCIS
ICEA S-83-596
IEC 60793-2-50
ISO/IEC 11801
| Fiber enclosure | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Rack units | Sized according to termination requirements |
| Bulkhead inserts/adapters | LC or MPO adapters, compatible with fiber type and connector |
| Covers | Front and rear with hinge |
| Cable management | Bend radius control and cable management for fiber patch cords, cable routing kit |
| Tray | Front and rear sliding tray |
| Standards & compliance | ANSI/TIA-548.3 |
All corresponding TIA FOCIS
ANSI/TIA-606
| Wall-mounted half cabinet | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Rack units | 26 |
| Rack mount spacing | 19" |
| Depth | 42" |
| Rack material | Steel |
| Door type | Front perforated steel, key-locking |
| Additional features | Ventilated side panels, top-mounted gland plate, rear and front vertical cable managers, levelers, reversible hinge, UPS bracket/mount |
| Floor-mounted cabinet - Provide for potential future use | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Rack units | 45 |
| Rack mount spacing | 19" |
| Depth | 42" |
| Rack material | Steel |
| Door type | Rear and front perforated steel, key-locking |
| Additional features | Ventilated side panels, top-mounted gland plate, rear and front vertical cable managers, levelers |
| Two-post open rack - Provide for potential future use | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Rack units | 45 |
| Rack mount spacing | 19" |
| Depth | 42" |
| Rack material | Extruded aluminum or steel |
| Door type | N/A |
| Additional features | Vertical cable management |
| Floor-mounted wall cabinet- Provide for potential future use | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Rack units | 40 |
| Rack mount spacing | 19" |
| Depth | 42" |
| Rack material | Steel |
| Door type | Front perforated steel, key-locking |
| Additional features | Ventilated side panels, top-mounted gland plate, rear and front vertical cable managers, levelers, reversible hinge, UPS bracket/mount |
| Power distribution unit- Provide for potential future use | |
| Manufacturer | Vendor to indicate manufacturer |
| Model name | Vendor to indicate model name and number |
| Form-factor | Rack-mounted (19") |
| Input voltage | 120V |
| Input plug type | NEMA 5-20P; NEMA L5-20P (with adapter to 5-20P) |
| # of outlets | 12 |
| Outlet types | NEMA 5-15/20R |
| Additional features | Remote management, digital ammeter |
&"Lato,Bold"&10FOREST HILLS PUBLIC SCHOOLS
NORTHERN HIGH SCHOOL STRUCTURED CABLING RFP
&K04+000APPENDIX B
&"Lato,Italic"&9Prepared by: Plante Moran &"Lato,Italic"&9&A | Page &P
Device Inventory
| Device Inventory | ||||
| NHS | Comments | Confirm total count on prints matches total in spreadsheet. If not, indicated variances | Confirm all Drops included in bid (Y/N/indicate variances): | |
| Cabling | ||||
| Cabling - New single drop | 199 | |||
| General data - blue | 196 | |||
| Security camera - yellow | 3 | |||
| Cabling - New dual drop location (2 drops per location) | 52 | |||
| General data - blue | 47 | |||
| Wireless access point - black | 5 | |||
| Cabling - New triple drop location (3 drops per location) - blue | 6 | |||
| Cabling - New quad drop location (4 drops per location) - blue | 13 | |||
| Cabling - New octuple drop location (8 drops per location) - blue | 2 | |||
| Total data drops | 389 | |||
| Demo | ||||
| Cabling | 998 | |||
| Old phone lines | 60 | |||
| Old AV (e.g., aux) | 60 | |||
| Network closets & cabinets | ||||
| # of network closets (including new) | 10 | |||
| Network cabinet uninstall/reinstall | 1 | |||
| Cables to be secured and reinstalled for construction phase: | ||||
| Single drops | 44 | |||
| Video surveillance - yellow | 41 | |||
| Centigex - white | 3 | |||
| Dual drops | 120 | |||
| General data (run in 2020) - blue | 3 | |||
| Wireless (2 drops per location) - black | 117 | |||
| Cables to be rerun and maintained (Temporary Media Center) | ||||
| Cabling - New single drop | 9 | |||
| General data - blue | 8 | |||
| Security camera - yellow | 1 | |||
| Other | ||||
| Permits | 12 |
| Notes: |
| 1. Demo counts are estimations. |
| 2. Drops for temporary media center layout are included in the Cabling counts. Cables to be rerun and maintained are for drops run new for temporary layout that will be rerun to their final locations. |
| 3. Cabling vendor to identify existing category 5 or 5e security camera runs to be replaced and added as change order. |
| 4. Cabling vendor to identify existing wireless access point installations with only one existing cable run to it. |
NORTHERN HIGH SCHOOL STRUCTURED CABLING RFP
&K04+000APPENDIX B
&"Lato,Italic"&9Prepared by: Plante Moran &"Lato,Italic"&9&A | Page &P
Cost
| Cost | |
| Base Bid | Total |
| Northern HS |
| Total Base Bid: |
| Performance / Payment bond (do not include in base bid total) |
| Performance / Payment bond % |
(to be used to adjust for any alternates/options selected):
| Add / Alternates | Total cost |
| Add Alternate 1 - Category 6A cabling | |
| Northern HS |
| Total Add/Alternate: |
| Performance / Payment bond (not included in A/A total): |
| Performance/ Payment bond % |
(to be used to adjust for any alternates/options selected):
| Unit pricing - Maximum potential annual price increase - FOR CHANGE ORDERS ONLY | ||
| (if needed due to product price increases; vendor must provide documentation showing product price increase) | Max % Increase | |
| 2026 (expect this to be at base unit costs listed below) | ||
| 2027 (expect this to be at base unit costs listed below) | ||
| 2028 | ||
| 2029 | ||
| <add rows as needed> | ||
| Unit costs (add/deduct cost must be the same) | Unit cost - | |
| Cat 6 | Unit cost - |
Cat 6A
| Structured cabling (includes labor) |
| V2000 raceway (ceiling to 16" AFF with install) |
| V4000 raceway (ceiling to 16" AFF with install) |
| Data cables - 1 per location (include 1 and 6 foot patch cords) |
| Data cables - 2 at same location (include 1 and 6 foot patch cords) |
| Data cables - 3 at same location (include 1 and 6 foot patch cords) |
| Data cables - 4 at same location (include 1 and 6 foot patch cords) |
| Data cables - 5 at same location (include 1 and 6 foot patch cords) |
| Data cables - 6 at same location (include 1 and 6 foot patch cords) |
| Move 1 data cable |
| Move 2 data cables at same location |
| Move 3 data cables at same location |
| Remove / reinstall 1 data cable |
| Remove / reinstall 2 data cables at same location |
| Remove / reinstall 3 data cables at same location |
| 24-port patch panel |
| 48-port patch panel |
| Patch cord - 1 foot |
| Patch cord - 3 foot |
| Patch cord - 6 foot |
| Patch cord - 10 foot |
| Backbone cabling |
| Backbone cabling (addl. 50') |
| Unit cost for coring / sleeving / firestopping |
| 1 foot cable tray |
| 3 feet cable tray |
| 6 feet cable tray |
| Network closet components (includes labor) |
| Rack-mounted power distribution unit (L5-30P input, w/ install) |
| Rack-mounted power distribution unit (5-20P input, w/ install) |
| Floor-mounted cabinet (w/ installation & removal of existing) |
| Two-post open rack (w/ installation & removal of existing) |
| Floor-mounted wall cabinet (w/ installation & removal of existing) |
| Wall-mounted half cabinet (w/ installation & removal of existing) |
| Removal, Demolition, Reinstallation (includes labor) |
| Cabling demo - hourly rate |
| Remove 1 classroom projector |
| Remove 1 wall-mounted display |
| Reinstall 1 existing wall-mounted display (or install 1 new wall-mounted display) |
| Remove 1 classroom audio system (incl. speakers & wiring) |
| Reinstall 1 classroom audio system (incl. speakers & wiring) |
| Remove 1 AV location at the top of teacher raceway & cover with blank faceplate |
| Remove surface mounted junction box |
| IDL demolition |
| MDL demolition |
| Additional Labor Rates |
| Hourly service rates for system-certified technicians: |
| Normal: |
| After hours: |
| Sunday / holiday: |
| Is there a trip charge? |
If so, what is the trip charge?
If no trip charge, is travel time charged?
If so, explain:
| Other |
| Add or remove 1 additional permit if phase is added or removed |
| <insert description> |
| <add rows as needed> |
&"Lato,Bold"&10FOREST HILLS PUBLIC SCHOOLS
NORTHERN HIGH SCHOOL STRUCTURED CABLING RFP
&K04+000APPENDIX B
&"Lato,Italic"&9Prepared by: Plante Moran &"Lato,Italic"&9&A | Page &P