Fan coils data sheet.pdf

PDF 364 KB Posted

Attached to
4520--Daikin Fan Coil and filter Purchase Federal contract opportunity
Solicitation number
36C26324Q1148
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23

About this file

This document is a Request for Quotes (RFQ) for a procurement of Brand Name Only Daikin Fan Coils and Filters for the VA Central Iowa Health Care System. The solicitation number is 36C26324Q1148, with a NAICS code of 238220 and a size standard of $19.0 million. The VA anticipates awarding a single fixed-price contract with delivery within 90 days after order. Quotes are due by 09/10/2024 at 12:00 PM Central Time and should be emailed to the Contracting Office. The solicitation includes FAR provisions 52.212-1, 52.212-2, 52.212-3, 52.212-4, and 52.212-5. Contact information for the Contract Specialist is provided. The Defense Priorities and Allocations System (DPAS) does not apply to this acquisition.

View the file

Other files for this federal contract opportunity

Other files attached to 4520--Daikin Fan Coil and filter Purchase, newest first.
File Type Posted
Solicitation 36C26324Q1148.pdf PDF
36C26324Q1148_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FC 001 Technical Data Sheet

A6LH1N VA Hospital - Vertical Fan 4 8/22/2024

Job Information Technical Data Sheet

Job Name VA Hospital - Vertical Fan Coils

Date 8/22/2024

Submitted By Dillan Dwyer

Software Version 11.42

Unit Tag FC 001

Unit Overview

Model Number Unit Size Voltage V/Hz/Phase

Air Flow

CFM

External Static Pressure ŝŶ,ЇK

Unit Configuration

FCVC102 02 115/60/1 200.0 0.10 Vertical

Unit

Model Number: FCVC102

Type: Fan Coil

Orientation: Vertical

Size: 02

Cabinet: Flat Cabinet

Approval None

Physical

Depth Width Height Shipping Weight

10.0 in 35.0 in 25.00 in 83 lb

Filters

Type (Quantity) Height x Width

1 in Throwaway MERV 13 Filter (1) 16 in x 8.75 in

Electrical

Voltage Fan Motor Amps Unit MCA Unit MROPD

115/60/1 V/Hz/Phase 3.5 A 4.4 A 15 A

A6LH1N VA Hospital - Vertical Fan 5 8/22/2024

Chilled Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity Connections

0.7 ϸ

270.3 ft/min

1/2 inch Nominal Sweat

(5/8 O.D.)

Performance

Capacity Air Temperature

Total Btu/hr

Sensible Btu/hr

Entering Leaving

Dry Bulb

OF

Wet Bulb

OF

Dry Bulb

OF

Wet Bulb

OF

6259 4885 80.0 67.0 57.7 57.1

Temperature

Entering Leaving

OF OF

Type

Fluid Flow rate gpm

Pressure Drop

Unit Handing

44.0 54.0 Water 1.3 0.63 Left Hand (Front of Face)

Hot Water Coil

Physical

Fins per Inch Number of Rows Coil Circuits Face Area Connections

12 4 4 0.7 ϸ 1/2 inch Nominal Sweat

(5/8 O.D.)

Performance

Total Capacity Btu/hr

Temperature

Air Fluid

Entering

OF

Leaving

OF

Entering

OF

Leaving

OF

16568 70.0 145.8 160.0 139.9

Fluid

Type Flow rate gpm

Pressure Drop

Unit Handing

Water 1.6 0.72 Left Hand (Front of Face)

Supply Fan

Fan

Fan Height Fan Width Quantity

6.30 in 6.26 in 1

Motor

Type Horsepower Quantity

0 to 10 VDC Modulating ECM 1/4 hp 1

A6LH1N VA Hospital - Vertical Fan 6 8/22/2024

Sound

Casing Radiated Sound Power (db)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

52 55 54 54 51 45 39

Options

General

Cabinet Style: Standard

Cabinet Coating: Premium

Cabinet Color: Antique Ivory

Cabinet Plenum Insulation: 1/4 inch Closed Cell

Cabinet Gauge: 18 Gauge

Sub-base Height: 3.5" Subbase

Leveling Legs: Leveling Legs

Return Air Location: Front

Disconnect Switch: Disconnect Switch

Control

Occ/Vacant Control Input: None

Filter Status: None

Fan Status: None

Condensate Overflow Protection: Condensate Overflow Switch

Warranty

Warranty: 4 year Extended component warranty (66 month from shipment or 60 month from installation)

AHRI Certification

Certified in accordance with the AHRI 440 Certification Program, which is based on AHRI Standard 440. Certified units may be found in the AHRI Directory at wwww.ahridirectory.org.

Notes

Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.

Total sound power level data based On units With 115/1/60 volt PSC motor at corresponding motor speed, 4 row coil, 1" throwaway filter, unit standard insulation, 0.0" external Static pressure And standard rated internal pressure losses.

http://www.ahridirectory.org/

A6LH1N VA Hospital - Vertical Fan 7 8/22/2024

Product Drawing Unit Tag: FC 001 Sales Office: Mechanical Sales, Inc.

13600 Industrial Park Blvd.

Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 11.42

Product: Project Name: VA Hospital - Vertical Fan

Sales Engineer:

Model: FCVC102 Aug. 22, 2024 Ver/Rev: Sheet: 1 of 1 Scale:

NTS

Tolerance: +/- 0.25"

Dwg Units: in

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

http://www.daikinapplied.com/

File details come from the government source that posted it. Updated .