Q and A for FA860123Q0141.pdf

PDF 300 KB Posted

Attached to
AFIT Studio Soundproofing Federal contract opportunity
Solicitation number
FA860123Q0141
Issued by
Department of the Air Force Materiel Command Lifecycle Management Center Wright Patterson Air Force Base

About this file

This document provides responses to questions regarding solicitation number FA860123Q0141 from the Department of the Air Force Materiel Command Lifecycle Management Center for soundproofing studios at Wright Patterson Air Force Base. The responses include dimensions and square footage for six studios ranging in size from 100 to 195 square feet. Diagrams and pictures are attached. Ceiling tiles in the entire 30 by 43 foot area need to be replaced with soundproof padding. Desks and shelves need to be removed from each room. Metal doors require sealing around edges and bottoms to improve soundproofing.

View the file

Other files for this federal contract opportunity

Other files attached to AFIT Studio Soundproofing, newest first.
File Type Posted
Room 6.jpg JPG image
Room 5.jpg JPG image
Room 3B.jpg JPG image
Room 2B.jpg JPG image
Room 1.jpg JPG image
Hallway Facing room 3.jpg JPG image
Hallway 2.jpg JPG image
2. Solicitation - FA860123Q0141.pdf PDF
Room 4.jpg JPG image
Room 5B.jpg JPG image
Hallway.jpg JPG image
Small Studio Drawing with Measurements.png PNG image
Room 3.jpg JPG image
Room 2.jpg JPG image
Solicitation - FA860123Q0141.pdf PDF
2. Solicitation - FA860123Q0141.pdf PDF
3. Reps_and_Certs.pdf PDF
1. Soundproofing Statement of Work.pdf PDF
Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

BUSINESS AND ENTERPRISE SYSTEMS DIRECTORATE

WRIGHT PATTERSON AIR FORCE BASE, OHIO

23 August 2023

FROM: AFLCMC/PZIBA

1940 Allbrook Drive, Room 109 Wright-Patterson AFB OH 45433

SUBJECT: Response to Inquiries Regarding FA8601-23-Q-0141

QUESTIONS

Question 1: Please provide Square Footage for 6 studios.

ANSWER: Please see attached diagram.Whole area is about 30ft x 43ft Room 6: 9'4"W x 12'8"L Room 5: 8'9"W x 17'6"L Room 4: 8'9"W x 11'10"L Room 3: 8'9"W x 14'6"L Room 2: 11'2"W x 8'9"L Room 1: 10'3"W x 10'L

Question 2: What are the wall sizes and hallway sizes?

ANSWER: Please see attached diagram.

Question 3: Are there pictures available?

ANSWER: Yes, pictures attached.

Question 4: What are existing conditions that must be considered for the installation (if any) Ceiling sizes for pad replacements?

ANSWER: Ceiling tiles need to be replaced with sound proof padding. The entire foot print of the area needs to have ceiling tiles replaced. 30ft x 43ft area

Question 5: How much furniture is to be removed in each studio?

ANSWER: Desk and shelves in each room. See pictures.

Question 6: What are the existing doors that require sound seals? (Wood, Metal)

ANSWER: Metal doors. Need to be sealed around edges and bottom.

Jessica K. Wade

Contracting Officer

AFLCMC/PZIBA

2023-08-23T10:30:31-0400
WADE.JESSICA.K.1548551834

File details come from the government source that posted it. Updated .