1) Are we to reuse the existing support structure for the new cooling tower?

Response - Yes.

2) Item #0003 and #0004 are worded exactly the same on the bid form. Please explain the difference in these two items.

Response – Each of these line items represents one month of service.

3) The condenser water filter schedule is based on a granular media type, but the spec (23 65 00,2.7.6.1) talks about centrifugal action separators. What type of separator is required?

Response – The condenser water solids removal system shall be as indicated on the schedule shown on drawing sheet M-601. An addendum will be issued to remove all of section 2.7.6.1 of specification section 23 65 00.