DEPARTMENT OF THE AIR FORCE
OKLAHOMA CITY AIR LOGISTICS COMPLEX (OC-ALC)
TINKER AIR FORCE BASE OKLAHOMA
Salient Characteristics 76 MXSG is requesting the purchase of the following Energy Recovery Ventilators (ERV, 2 ea), Tagged as ERV-1 & ERV-2:
Tag: ERV-1 (Qty: 1)
• Unit Overview o Product Data: Energy Recovery Ventilator o Model Number: Greenheck Model ERV-20 or Equivalent o Mounting option: Indoor Unit o Approximate weight (lbs): 900 o 1 Inch Fiberglass Insulation
• Unit Electrical:
o Voltage/Phases/Hz: 460/3/60 o UL Listed o Factory Wired Non-Fused Disconnect Switch o Single Point Power
• Exhaust Air Discharge: Standard
• Supply (Outdoor) Air o Air flow (cfm): 1722 o External Static Pressure (in. w.c.): 1 o Intake location: End o Discharge location: End o OA Design Conditions: Summer- 97degF (db), Winter
7degF (db)
• Exhaust Air o Air flow (cfm): 1800 o External Static Pressure (in. w.c.): .5 o Intake location: End o Discharge location: End
• Filters: 2" MERV 8
• Options o Dirty Filter Sensor o Hinged Access o BACnet MSTP Network Protocol o Monitoring Interface o Duct Flanges o Frost Control-Timed Exhaust o Outdoor Air Damper-Insulated Low Leakage o Fan VFDs-Multispeed o Wheel/Rotation Sensor
• Unit Overview o Product Data: Energy Recovery Ventilator o Model Number: Greenheck Model ERV-10 or Equivalent o Mounting option: Indoor Unit o Approximate weight (lbs): 300 o 1 Inch Fiberglass Insulation
• Unit Electrical:
o Voltage/Phases/Hz: 208/1/60 o UL Listed o Factory Wired Non-Fused Disconnect Switch o Single Point Power
• Exhaust Air Discharge: Standard
• Supply (Outdoor) Air o Air flow (cfm): 844 o External Static Pressure (in. w.c.): .8 o Intake location: End o Discharge location: End o OA Design Conditions: Summer- 97degF (db), Winter
7degF (db)
• Exhaust Air o Air flow (cfm): 900 o External Static Pressure (in. w.c.): .5 o Intake location: End o Discharge location: End
• Filters: 2" MERV 8
• Options o Dirty Filter Sensor o Hinged Access o BACnet MSTP Network Protocol o Monitoring Interface o Duct Flanges o Frost Control-Timed Exhaust o Outdoor Air Damper-Insulated Low Leakage o Speed Control-Motor Potentiometer o Wheel/Rotation Sensor
Tag: ERV-2 (Qty: 1)