Tate Concore Raised Floor Item Description

Specific Requirements

1. (1,000ea) 24” x 24”, Tate Concore CC1250-24

a. 1/8" Laminated HPL Tile, Factory Laminated with Integral Trim

b. Gray Starlite Tile Color/Pattern

c. Cementitious Core

d. Epoxy Painted Underside

e. Static Design Load: Min. 1250 lbs.

f. Safety Factor: Min 2, rolling loads 10 passes 1000 lbs.

g. Impact Load: 150 lbs. (Accordance with CISCA)

2. (36ea) 24” x 24”, Tate GrateAire-24”, Perforated Aluminum Airflow Panel

a. Min. 50% open area.

b. Static design load: Min. 1000 lbs.

c. Safety Factor: Min. 2, rolling loads 10 passes 1000 lbs.

d. Impact load: 100 lbs. (Accordance with CISCA)

3. (963ea) Galvanized bolted heavy duty Steel Stringer

a. 1-1/4” x ¾” Roll-formed

b. 4’ x 4’ grid pattern

4. (4525ea) Flathead Screw

a. ¼”-20 x 1-3/4”

5. (975ea) Field Pedestal including: nut, stud tubing steel head, and base plate for CC1250-24

a. Finish Floor Height is 18" with 2” total adjustment

b. Tate Type 2B pedestal only

6. (180ea) Perimeter Pedestal including: nut, stud tubing steel head, and base plate for CC1250-24

a. Finish Floor Height is 18" with 2” total adjustment

b. Tate Type 2B pedestal Only

7. (40ea) K10077 Koldlok air sealing grommet

8. (10ea) K3030 Koldlok air sealing grommet