Questions and Answers
FA700018T0074
19 July 2018
Q1: Are all specifications equally important?
A1: All products quoted must meet the Government's specifications listed in the solicitation.
Q2: The government's requirement for a minimum 300 G extraction/spin rate would require a 24" rebar reinforced concrete foundation. Does this exist?
A2: The foundation and concrete pad is adequate for this type of equipment.
Q3: What results are achieved with communications between the washer and dryer?
A3: The communication between the washer and dryer allows the staff to operate the equipment thru the internet so that they do not have to be on-site to turn the equipment on or off.
Q4: Does this solicitation replace existing equipment?
A4: There is no existing equipment that needs to removed or replaced.
Q5: Are there photos of where the units are to be installed?
A5: There are no photos available to distribute with this solicitation.
Q6: Please explain the statement in RFQ, "must hook-up to Automated Clean Supply".
A6: The statement “must hook-up to automated clean supply” is not referenced in the solicitation.
Q7: Please clarify the requirements for the vent opening on the dryer (12” round).
A7: There is a 12" duct and outlet into the tunnel. These dimensions were built in the room based on upsizing from a 10" outlet at the unit. The solicitation has been amended on the vent size to reflect “10” vent opening or a size that is compatible with a 12” duct and outlet”.
Q8: Please clarify the requirements for the 12” aluminum wall cap.
A8: The vent and louver are provided/installed by the Government. This information was provided in the solicitation to describe the exisiting venting.