FA670320Q0019

Firestation Outside Plant

Questions and Answers

1. Is the pathway from COM closet to COM closet existing?

Answer: There is a new path from the new fire station Comm closet to the MH. From the MH into the Comm closet at base ops there is a path, but the exact path is not known and would have to be verified by the contractor. There is existing cable running from the manhole into the Comm closet in Base Ops already.

2. Are all ducts and manholes in pathway existing?

Answer: Yes

3. What type of MM Fiber does is require OM1, OM2, OM3, OM4?

Answer: OM2 for MM

4. I would like to know the allowance for the linear footage for the project?

Answer: 94 CS estimates a cable distance at 500 – 650 (max) feet. After contract award the awardee will verify all distance measurements.

5. Since the building is receiving new fiber cabling vs replacing cabling, does the customer have a preference between OM1, OM2, OM3 and OM4 Multimode fiber?

Answer: OM2 for MM

6. Is the Site Survey Report an item for the contractor or was that inadvertently left in this document?

Answer: The site survey report is to be submitted by the awardee. After contract award the awardee shall verify all requirements and measurements and provide the Site Survey Report to 94 CS within five (5) business days after conducting the survey.