Text version
RFI-BOD Form
| RFI Comments Form |
| Name/description |
| Solicitation FA660619RA001 Design Build - Upgrade Energy Management System - Westover AFB | |
| Request |
| Comment Classification Code: | Status |
| 1 - Unclassified | 1 - Closed |
| 2 - SBU | 2 - Working |
| 3 - Classified | 3 - Pending |
Comment Classification Code RFI Government Response Response Date Disp. Codes KEE Follow Up Follow Up Date VA Response Date VA Responses
| 9.1 Indicates Facility record drawings are available for review at the BCE office? Some reference PDFs have been provided, will CAD drawing be available post award. | CAD drawings will be made available where possible, but not all facilities have BMS drawings in CAD. | 6/19/19 | 1 |
| Will the new server need to be rack mounted? Please provide minimum requirements for new N4 Server. | Server to be rack mounted - minimum requirements per SOW section 3.6.2 | 6/19/19 | 1 |
| Please extend the bid date allowing 2 weeks from RFI responses | Proposal due date has been extended until 11 July 2019 at 2:00PM EST | 6/19/19 | 1 |
| Please confirm that all Jace controllers that are not already N4 are to be upgraded to a Jace-8000 controller, including the existing Jace's running AX | Confirmed | 6/19/19 | 1 |
| Please confirm number of Jace's and versions is as follows: R2 = 32, AX = 18, N4 = 4. | Confirmed | 6/19/19 | 1 |
| What communication cards/interfaces do the existing electric and gas meters have? | no information available - assume no physical connectivity | 6/20/19 | 1 |
| Please provide voltage and amperage sizes required for the new electric meters | Building 1100- 200 amp main switch 3 phase 4 pole with 125 amp fuse 120/208 volt. |
Building 1204- 400 amp main switch 3 phase 4 pole 120/208 volt.
Building 1301- 225 amp main switch 3 phase 4 pole 480/277 volt.
Building 1408- 400 amp main switch 3 phase 4 pole 120/208 volt.
Building 1502- 200 amp main switch 3 phase 4 pole 120/208 volt.
Building 1510- 800 amp main switch 3 phase 4 pole 120/208 volt.
Building 1520- 100 amp main switch 3 phase 4 pole 120/208 volt.
Building 1530- 200 amp main switch 3 phase 4 pole 120/208 volt.
Building 1800- 200 amp main switch 3 phase 4 pole 120/208 volt.
Building 2235- 1000 amp main switch 3 phase 4 pole 120/208 volt.
Building 2400- 400 amp main switch 3 phase 4 pole 120/208 volt.
Building 2450- 800 amp main switch 3 phase 4 pole 120/208 volt.
Building 2452- 300 amp main switch 3 phase 4 pole 120/208 volt.
Building 5100- 800 amp main switch 3 phase 4 pole 120/208 volt.
Building 5305- 400 amp main switch 3 phase 4 pole 120/208 volt.
Building 5315- 200 amp main switch 3 phase 4 pole 120/208 volt.
Building 5325- 200 amp main switch 3 phase 4 pole 120/208 volt.
Building 5375- 600 amp main switch 3 phase 4 pole 120/208 volt.
Building 6640- 1600 amp main switch 3 phase 4 pole 120/208 volt.
Building 7000- 3000 amp main switch 3 phase 4 pole 480/277 volt.
Building 1610(7091)- 600 amp main switch 3 phase 4 pole 480/277 volt.
| Building 8840- 225 amp main switch 3 phase 4 pole 120/208 volt this main switch serves 8844 and 8845 | 6/19/19 | 1 | |||
| Please see attached meter Info spreadsheet and fill out meter information for each gas and electric meter included in this project. | Please refer to SOW 3.6.5.2 for table of meters - if cell contains 'Y' response is Yes, if cell empty response is No - and assume no physical connecivity to EMCS | 6/20/19 | 1 | ||
| Please see attached Jace Info spreadsheet and fill out Jace information for each Jace included in this project. | Done | 6/19/19 | 1 | ||
| Confirm as discussed at the site visit - wireless controls are acceptable for both the hotel HVAC Controls and the hw boiler controls | Wireless controls are acceptable for HVAC key card controls in B2200/B2201 - boiler controls in B5100 should not be wireless | 6/19/19 | 1 | ||
| Please confirm that new boiler HW controls are integrated to new emcs. | Assuming the question is for boiler controls in B5100, confirm they are to be integrated into new EMCS JACE to be installed in that building | 6/19/19 | 1 | ||
| Please provide type and spec for key cards used currently in the hotel rooms. | CARD KEY SWITCH WITH BACKLIT CARD KEY SLOT, 120V INPUT, 30 SECOND EGRESS TIME DELAY, IVORY COLOR, WATTSTOPPER HS-150 SERIES OR APPROVED EQUAL. | 6/19/19 | 1 | ||
| Please provide any Manufactures boiler data and maintainece records - bldg 5100 | Cleaver-Brooks Model CBI200-150LE Serial L-106594 (#1) |
Cleaver-Brooks Model CBI200-150LE Serial L-106595 (#2)
| maintenance records available during design phase | 6/19/19 | 1 | |||
| Please confirm no permits are required for this project. | Confirmed | 6/20/19 | 1 | ||
| Please provide sign in sheet from the site visit. | Contracting will provide | 6/19/19 | 1 | ||
| Please confirm integration and calibration scope and reporting requirements for the electric and gas meters. | Please refer to SOW 3.6.5.1 for description of requirements | 6/19/19 | 1 | ||
| Commissioning Agent - We assume this to be the manufactures rep, for the N4 system. Please Confirm. | Confirmed | 6/19/19 | 1 | ||
| Cyber Commissioning - will this process allow remote programming of the N4 system. | No | 6/19/19 | 1 | ||
| Please confirm no new Gas meters are included in this project | Confirmed | 6/19/19 | 1 | ||
| Provide details for existing HVAC controls (seimans?) in the hotel rooms to be upgraded | Siemens HVAC Products Model SSA61U (typical) | 6/21/19 | 1 | ||
| Re Section 3.9.2.4.5 please strike reference to Gas Meters | For expediency, propose leaving in - paragraph states "proposed to be incorporated" so if not proposing to incorporate, point is moot | 6/19/19 | 1 | ||
| Re Section 3.9.2.5.1 please strike reference to HVAC Demo | For expediency, propose leaving in - paragraph states "Drawings may consist of" so since demolition is not required, point is moot | 6/19/19 | 1 | ||
| Spec Preparations - please confirm specs sections to be provided per Att. 1. Please complete the attached form Table of Docs | Confirmed - spec sections per SOW Attachment 1 | 6/19/19 | 1 | ||
| Design Requirements - please confirm the design deliverables we anticipate a site plan to include typical diagramattical controls details for each Jace in tabular form. Please complete the attached form Table of Docs | Controls details PDF drawings have been provided as available - no additional drawing details are available | 6/19/19 | 1 | ||
| Cybersecurity - please confirm reporting and scope for this consultant. Since the N4 software is off the shelf we anticipate working within the capabilities of this software. We would anticipate a single cyber security review of the software and installations, not the Cybersecurity Design Five Steps described in 3.9.1.6. | We anticipate the same, but cannot guarantee this | 6/19/19 | 1 |
Page &P of &N &F
SAMPLE Security Operations Jace
| JACE Name | SecurityOperations |
| JACE Location | Security Operations 2510 |
| Niagara Version | R2.301.532 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N.A. |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N.A. |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N.A. |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N.A. |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N.A. |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N.A. |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | 30 |
| What are the Lonworks Device Types on each network? | 27 Honeywell Excel 10 VAV controllers, 2 Honeywell Excel 15C, 1 Trane Chiller |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | The 27 Honeywell Excel 10 VAV controllers are controlling VAV boxes, 1 Honeywell Excel 15C is controlling AHU-1, 1 Honeywell Excel 15C is controlling the HW Plant, 1 integration to the Trane chiller |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N.A. |
| What type of equipment is each N2 Device controlling and/or monitoring? | N.A. |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N.A. |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N.A. |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N.A. |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N.A. |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N.A. |
| What type of equipment is each device controlling and/or monitoring? | N.A. |
| JACE Name | Chapel |
| JACE Location | Building 1100 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Conference Center |
| JACE Location | Building 1204 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Hazardous Storage |
| JACE Location | Building 1301 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Aeromedical |
| JACE Location | Building 1310 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | AE Training |
| JACE Location | Building 1408 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Recruiting |
| JACE Location | Building 1502 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | USO |
| JACE Location | Building 1510 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Reserve Fire |
| JACE Location | Building 1520 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Base Operations |
| JACE Location | Building 1610 |
| Niagara Version | AX 3.5.25 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 1 |
| How many BACnet Devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the BACnet Device Types on each network? | |
| What type of equipment is each BACnet Device controlling and/or monitoring? | |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 0 |
| How many lonworks devices on each network? | 0 |
| What are the Lonworks Device Types on each network? | N/A |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | N/A |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Base Gymnasium |
| JACE Location | Building 1700 |
| Niagara Version | AX 3.8.41 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 1 |
| How many BACnet Devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the BACnet Device Types on each network? | |
| What type of equipment is each BACnet Device controlling and/or monitoring? | |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 0 |
| How many lonworks devices on each network? | 0 |
| What are the Lonworks Device Types on each network? | N/A |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | N/A |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Base Finance |
| JACE Location | Building 1800 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Civilian Personnel |
| JACE Location | Building 1850 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Reserve Affairs |
| JACE Location | Building 1875 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Hotel |
| JACE Location | Building 2200 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Hotel |
| JACE Location | Building 2201 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Medical Training |
| JACE Location | Building 1700 |
| Niagara Version | AX 3.7.106 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 1 |
| How many BACnet Devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the BACnet Device Types on each network? | |
| What type of equipment is each BACnet Device controlling and/or monitoring? | |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 0 |
| How many lonworks devices on each network? | 0 |
| What are the Lonworks Device Types on each network? | N/A |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | N/A |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Contracting |
| JACE Location | Building 2400 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Emergency Management |
| JACE Location | Building 2416 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |
| What type of equipment is being controlled and/or monitored by the NDIO modules? | N/A |
| NRIO Network | |
| Does the Jace have a NRIO Network? | No |
| How many NRIO modules are connected to the Jace? | 0 |
| UI Count | 0 |
| AO Count | 0 |
| DI Count | 0 |
| What type of equipment is being controlled and/or monitored by the NRIO modules? | N/A |
| BACnet MS/TP Networks | |
| How Many BACnet MS/TP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| BACnet IP or Ethernet Networks | |
| How Many BACnet IP Networks are connected to the Jace? | 0 |
| How many BACnet Devices on each network? | 0 |
| What are the BACnet Device Types on each network? | N/A |
| What type of equipment is each BACnet Device controlling and/or monitoring? | N/A |
| Lonworks Networks | |
| How many lonworks networks are connected to the Jace? | 1 |
| How many lonworks devices on each network? | Refer to JACE and Device count table in the Satement of Work |
| What are the Lonworks Device Types on each network? | |
| What type of equipment is each Lonworks Device controlling and/or monitoring? | |
| JCI N2 Networks | |
| How many N2 networks are connected to the Jace? | 0 |
| How many N2 devices on each network? | 0 |
| What are the N2 Device Types on each network? | N/A |
| What type of equipment is each N2 Device controlling and/or monitoring? | N/A |
| Modbus RTU Networks | |
| How many Modbus RTU networks are connected to the Jace? | 0 |
| How many Modbus RTU devices on each network? | 0 |
| What are the Modbus RTU Device Types on each network? | N/A |
| What type of equipment is each Modbus RTU controlling and/or monitoring? | N/A |
| Modbus TCP Networks | |
| How many Modbus TCP networks are connected to the Jace? | 0 |
| How many Modbus TCP devices on each network? | 0 |
| What are the Modbus TCP Device Types on each network? | N/A |
| What type of equipment is each Modbus TCP controlling and/or monitoring? | N/A |
| 3rd Party or other Networks | |
| How many other 3rd party or other networks are connected to the Jace | 0 |
| How many devices on each network? | 0 |
| What are the device Types on each network? | N/A |
| What type of equipment is each device controlling and/or monitoring? | N/A |
| JACE Name | Civil Engineering |
| JACE Location | Building 2450 |
| Niagara Version | R2.301.529 |
| NDIO on Jace | |
| Does the Jace have a NDIO Network? | No |
| UI Count | 0 |
| AO Count | 0 |
| DO Count | 0 |