Fuel Tank SoN_12 December 2024.pdf

PDF 114 KB Posted

Attached to
Fuel Tank System
Solicitation number
FA570225QZ008
Issued by

About this file

This is a Statement of Need (SON) from the 379th EMXS detailing requirements for a 10,000-gallon capacity fuel tank. The document specifies the preferred brand/model as a 10,000 Gallon Fireguard Fuel Tank or equal, with key features including a built-in 240 volt, single phase, 50hz pump for dispensing, UL-2085 labeling and listing, compliance with NFPA 30-30A requirements, and double wall construction with 3" to 6" of lightweight thermal insulation for fire protection.

The technical specifications include detailed requirements for components such as emergency vents, monitoring wells, stack vents, high-level shut-off valves, clock gauges with alarms, safety features, dispensing equipment, and construction materials. Notable components include a UL Listed lockable dispensing box, FE Petro 3/4 Hp pump assembly, Hannay hose reel with 25' hose, and specialized coatings (Envirolastic 940 DTM and Chemline 4000 Epoxy). The tank must be constructed with 1/4" shell and 5/16" head steel thickness. Delivery is required to 379 EMXS UNIT 61217, APO, AE 09309-1217, with the point of contact to be provided after contract award.

View the file

Other files

File Type Posted
Sources Sought - Fuel Tank.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12 December 2024

Specifications/Item Listing (Commodity) Statement of Need (SON)

Fuel Tank

379th EMXS has a requirement for a fuel tank.

Description:

- Fuel tank 10,000 Gallon capacity

- Built in 240 volt, Single Phase, 50hz pump for dispensing

- UL-2085 labeled & listed

- UL-2085 passes requirements for NFPA 30-30A

- Double Wall Tank with 3” to 6” of lightweight thermal insulation for fire protection

- Plug-and-play system meaning, set in place, connect power, fill with fuel, and start dispensing the same day

Preferred Brand/Model Number – 10,000 Gallon Fireguard Fuel Tank or equal

Minimum Salient Characteristics or equal:

1 - 10,000 Gallon Fireguard Tank Mounted on Saddles 2 - 8'' 8 Oz Emergency Vent Male w/O-ring 1 - Monitoring Well w/ 2'' Cap 1 - 3'' Stack Vent (12' above grade) w/ 3'' Updraft Vent 1 - Morrison Bros. High Level Shut-off Valve with test mechanism & 3'' Ground Level Fill (Vertical Check Valve, Ball Valve, Fill Pipe w/ Diffuser, Fill Adapter, & Dust Cap) 1 - 2'' 918 Clock Gauge w/ Alarm & Standard Float for Accurate Fuel Level Reading 1 - Ladder with Safety Shield 1 - Total Control 682-15 Piston Meter with 10:1 Pulser 1 - UL Listed Lockable Dispensing Box Welded on Tank 3'6''x4'2''x6'6'', Cross Broken for Easy Drainage, 2'' Vent, 2'' Mushroom Cap, & 1/2'' Ball Valve 1 - FE Petro 3/4 Hp. Pump Assy w/Anti-Syphon Valve & Ball Valve 1 - 1'' Hannay Hose Reel with 25' 1'' Hose, Ball Stop, 1'' Nozzle, Breakaway and Swivel 1 - Electric Packages for Pumps and Switches 1 - Envirolastic 940 DTM Polyaspartic Urethane for High Performance Finish 1 - Chemline 4000 Epoxy Lining 1 - Tank Decal Kit 1 - Interstitial Leak Gauge 1 - ROM Door (Roll Up) 3'x6' 1 - Cim-Tek 1.5'' Filter Adapter and 1'' Filter 1 - 18'' Manway for easy inner tank accessibility 1 - UL 2085 Labeled & Listed

1 - STEEL THICKNESS 1/4'' SHELL & 5/16'' HEAD

1 - 1'' Replacement Fuel Filters (Qty. 6) 1 - Touch-up Paint 1 - Owner's Manual

Point of Contact: Provided after contract award.

Delivery Address: 379 EMXS UNIT 61217, APO, AE 09309-1217