This notice is a draft request for proposal for a multiple award construction contract for design-build construction services in Italy. The scope of work includes projects involving various trades such as grading, water and sewer lines, painting, roofing, building renovation, new construction, electrical work, structural work, HVAC, fire suppression systems, fuel systems, generators, communication systems, and abatement services. The contract will have a one year base period and four option years, with a minimum of $2,500 guaranteed per award and a total maximum of $96 million across all awards. The minimum task order value is $2,500 and maximum is $7 million. Comments on the draft attachments are due by April 19, 2019. The solicitation will be issued through beta.SAM.gov and no paper copies will be provided. Offerors must be SAM registered to be eligible for award.
Attachment 10 ASHE 18-1025 Technical Specifications (Seed Project ) Part 6 Part 4
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 Helvar | Data is subject to change without notice. www.helvar.com
BACnet Gateway (435) The 435 BACnet Gateway provides a simple interface to a Helvar router system and allows lighting system data to appear in a BACnet Building energy Management System.
IP network
Helvar router(s)
435 BACnet Gateway
BACnet/IP network
The BACnet Gateway allows a BMS to control and monitor the lighting system as well as obtain device status and group power consumption information.
BACnet/IP clients can easily connect with the gateway via a TCP/IP network.
Available Router to BACnet/IP Communication
Helvar router
Group or DALI device
Group scene
Group consumption
Group direct level
Router fail
Device missing
Lamp fail
BACnet point instance
AV – Analogue value (read and write)
AI – Analogue input (read only)
AO – Analogue output (write only)
BI – Binary inputs (read only)
BI – Binary inputs (read only)
BI – Binary inputs (read only)
Key Features
• Operates as BACnet server
• Helvar workgroup discovery tool
• Helvar router selector
• Automatic Helvar point identification
• BACnet/IP compatible
• Automatic BACnet instance labelling
• COV (change of value) BACnet feature
• Browser programming interface
Device Limits
• Single workgroup
• 20 routers
• 300 groups
• 2000 BACnet/IP points
2Helvar 435 BACnet Gateway: Datasheet Doc. D007496, issue 2, 2016-10-26
Technical Data
Connections Connection type: 1 × 10/100 Mb/s for TCP/IP Default IP address: 10.254.0.100 Default subnet mask: 255.0.0.0 Power input: 9 VDC – 40 VDC Power consumption: 300 mA @12 VDC
150 mA @ 24 VDC
Mechanical data Dimensions: 78 mm × 108 × 32 mm
(excl. brackets) 102 mm × 108 × 32 mm (incl. brackets)
Weight: 330 g per unit (excl. DIN rail clips) 410 g shipped (incl. DIN rail clips)
Operating and storage conditions Operating temperature: 0 °C to +70 °C Storage temperature: 0 °C to +70 °C Relative humidity: Max. 90 %, noncondensing
Conformity and standards EMC emission: EN 55032 Class A EMC immunity EN 55024 Environment: Complies WEEE and RoHS directives.
Compatibility Helvar router firmware: v5.2 and above
Web browsers: Firefox (recommended), Chrome, Internet Explorer
Dimensions (mm) and connections
.5
⌀ 4
⌀ 7
Reset button
Power LED Ready LED
AMR1-24
power supply unit
–VE
Ethernet
Not used
Not used
Order code
LAN
activity LED
+VE
435+AMR1 PSU: BACnet Gateway with 24 VDC 1A PSU.
DIGIDIM Mini Input Unit (444)
Mini Input Unit
A Mini Input Unit used with a four-gang mains switch in a single-gang back box.
The Mini Input Unit is a DALI-compatible interface, designed to allow customer specified switches, sensors, time clocks or other on/off control devices to be incorporated into a DIGIDIM lighting control system.
The Mini Input Unit is a small, prewired, encapsulated printed circuit board and is suitable for inclusion into all standard size back boxes together with a suitable mains-rated switch.
Key Features
• Preconfigured with touch dimmer inputs for two groups.
• Fits into all standard size back boxes and architrave style back boxes.
• Touch dimming with a momentary push switch.
• Can be used with momentary or latching switches.
• Fully programmable using DIGIDIM Toolbox software.
2Doc. D005322, issue 4, 2017-08-09
Helvar 444 Mini Input Unit: Datasheet
Technical Data
Connections Inputs: 4 inputs (active low)
COM Input Ground Overload protection: ± 7 V Short-circuit current: 0.5 mA maximum Debounce period: 50 ms Voltage-free switched inputs:
5 V nominal with switch open, must be less than 0.3 V with switch closed.
Isolation: No isolation from DALI network:
switches must provide user protection.
Cable requirements DALI: DALI Ribbon cable terminated with
1.2 mm ferrules.
Cable length 170 mm
Caution: Do not increase the length of the wires. This can cause interference problems.
Power DALI supply output: None (Use external DALI power supply.)
DALI consumption: 10 mA
Mechanical data Dimensions: Encapsulated printed circuit board Weight: 10 g IP code: IP20 Mounting: For installation in a suitably enclosed location only.
Operating conditions Ambient temperature: 0 °C to +40 °C Relative humidity: Max. 90 %, noncondensing Storage temperature: −10 °C to +70 °C
Conformity and standards EMC emission: EN 55015 EMC immunity: EN 61547
Safety: EN 61347-2-11 Environment: Complies with WEEE and RoHS directives.
BROWN
RED
ORANGE
YELLOW
GREEN
BLUE
VIOLET
COM
IP1
IP2
IP3
IP4
DA+
DA–
Default Functions
Dimensions (mm)
• Common Brown
• 1 Scene 1 Recall/Store Red
• 2 Scene 2 Recall/Store Orange
• 3 Scene 3 Recall/Store Yellow
• 4 Touch Last level Green
• DALI (+) Blue
• DALI (–) Violet
Multisensor with linked PIR (312)
PIR Automatic ON/OFF Sequence ON scene Default: scene 16 (last level set by user) INTERMEDIATE scene Default: scene 14 OFF scene Default: scene 15
Constant Light Coverage with restrictor
Presence Detection Coverage
No presence detected for 20 min
Intermediate scene activated after 20 min
20 min (default setting) 20 s (default setting)
Pr es en ce d et ec te d
Lights on
Lights off
OFF scene (Scene 15)
ON scene (Scene 16)
INTERMEDIATE
scene (Scene 14)
85°
2.8 m
5.1 m
Constant Light Coverage without restrictor
100°
2.8 m
0.8 m
6.6 m
4.7 m
40°
2 m
2.8 m
The Multisensor is a compact unit containing sensors to provide energy-saving functions when used in a DALI system. It contains:
• A light sensor
• A passive infrared (PIR) movement detector
• An infrared receiver (for remote control)
The unit is push-fitted into a ceiling or luminaire housing.
The light sensor measures the ambient-light level in the room. The PIR detector enables the system to detect when the room is occupied. Helvar infrared remote control can be used to set the required light levels and to carry out basic system programming.
Key Features
• Presence detection default time-out of 20 minutes.
• Programmable constant light control for energy efficiency.
• Complete control using the hand-held remote.
• A local switch can be fitted to provide ON/OFF and a manual dimming function.
• The multisensor’s programmable functions are set by five DIL switches at the back of the unit.
• These DIL switch settings can be overridden remotely by Helvar’s Toolbox or Designer software – no need for access to the Multisensor after installation.
• The coverage restrictor (provided) can be fitted to the Multisensor for more precise constant-light coverage.
Additional Functions
• The remote control handset can program most functions. Toolbox and Designer give full system access.
• Multiple linked PIR sensors connected in one system can communicate with each other and switch off the loads when all sensors are nondetecting.
• The automatic ON/OFF sequence of the presence detection system has three programmable steps (on, intermediate, off). Users can define how the loads react to the automatic presence detection commands from the Multisensor.
2Doc. D005152, issue 6, 2017-05-17
Helvar 312 Multisensor with linked PIR: Datasheet
Technical Data
Connections DALI: Removable connector block Wire size: 0.5 mm² – 1.5 mm² solid or stranded Local control: 2 wires Cable rating: All cables must be mains rated.
Maximum length: 50 m
Power DALI supply input: 13 V to 22.5 V DALI consumption: 15 mA
Sensors Light sensor: For constant-light functions Presence detector: PIR: Passive infrared presence detector Infrared receiver: For remote control commands
Remote control functions Infrared remote control:
Constant-light level Group creation and adjustment Scene store and recall
Mechanical data Mounting hole diameter:
52 mm (mounting surface
0.5 mm – 2 mm);
55 mm (mounting surface > 2 mm)
Bezel diameter: 65 mm Recommended clearance depth:
80 mm (without cable cover);
100 mm (with cable cover, incl. 50 mm for cabling)
Material (casing): UL94V-0 nylon Finish/Colour: Matt / White RAL 9003 Weight: 48 g without cable cover;
54 g with cable cover IP code: IP30
Operating conditions Ambient temperature: 0 °C to +50 °C Relative humidity: Max. 90 %, noncondensing Storage temperature: –10 °C to +70 °C
Conformity and standards EMC emission: EN 55015 EMC immunity: EN 61547 Safety: EN 61347-2-11 Environment: Complies with WEEE and RoHS directives.
Dimensions (mm)
Installation: mounting hole ø52 mm0.5 mm – 2 mm ø55 mm
> 2 mm
Ø 65 Ø 65
26.4
51.4
Ø20
Ø5 Ø5
SC DA–DA+
O
FF
Local control
Connections
Installation: Surface back box SBB-C (Order separately)
DA–
DA+
The 329 DALI External Light Sensor, when used in conjunction with a Helvar Lighting Router based controls system, can provide energy savings by adjusting light levels based on the available daylight.
Mount the 329 outdoors to monitor the level of daylight. For instance, bright sunlight will raise the overall light level in the rooms of a building. The sensor will detect this, and the system will reduce the energy levels supplied to the lamps.
If the day then becomes overcast, the system will respond to the lower levels of ambient light by increasing the energy provided to the lamps. By profiling the building (measuring the daylight contribution per room), the system can be used to maintain an approximate constant light level, and thereby reduce energy use.
The 329 is for mounting outdoors. The unit head assembly is waterproof when correctly installed and mounted vertically, and can tolerate a wide range of operating temperatures and conditions.
Key Features
• Open loop light control
• Light range of 1 lx – 100 000 lx
• Simple mounting
• Easy connection to Helvar router system
Incident Light (lx)
Light Level Output Value
Equivalent To
≤ 1 0 Darkness
2 11
5 26
10 38 Twilight
20 49
50 65
100 76 Dark day
200 87
500 102
1000 114 Overcast day
2000 125
5000 140
10 000 152 Full daylight
20 000 163
50 000 178
100 000 190 Bright sunlight 85º 85º
Light Sensing Angle Vertical plane: Unrestricted viewing angle of 170°.
Horizontal plane: 360° viewing angle.
1 10 100 1000 10 000 100 000
Incident light (lx)
Li gh t l ev el o ut pu t
Light Level Output The external light sensor is calibrated to provide a scaled light level output of 0 to 200 covering the full range of daylight. The sensitivity of the external light sensor is factory-set, and no adjustment is required.
Installation Notes
• The unit is intended for wall mounting.
• Isolate the mains supply before installation.
• Cabling must be 230 VAC mains rated.
• Do not mount sensor in direct line of artificial light sources, e.g. lamps, uplighters.
• The unit must be mounted vertically, i.e. with the clear
Sensor Head Cover pointing upwards. Any convenient surface may be used as long as the sensor element has a reasonably unrestricted view of the sky.
• To avoid the possible risk of lightning strikes, never install the external light sensor at the highest point on a building.
DALI External Light Sensor (329)
2Doc. D005508, issue 3, 2017-05-18
Helvar 329 Dali External Light Sensor: Datasheet
Technical Data
Fixing Centre Locations (mm)
Dimensions (mm)
81 93
Ø 5
Ø 5
Connections DALI Wire size: 1.0 mm² – 2.5 mm²
2-core solid, flexible or stranded Max. length: 300 m @ 2.5 mm² (part of DALI subnet)
Connector type: Screw terminals:
N: DALI+
L0: DALI–
L1: No connection
Cable rating: All cables must be mains rated.
Power supply DALI power supply: 13 V – 22 V DALI consumption: 10 mA
Sensor Sensor element: Photodiode matched to human eye response.
Light sensing angle: When mounted vertically:
• 85° from vertical
• Horizontal plane: 360°
Working light range: 1 lx – 100 000 lx Light level reading output: 0–200
Mounting Mounting angle: Vertical (clear sensor head at top) Mounting points: 2 × M4 (No. 8 woodscrew)
For fixing centres, see diagram.
Mechanical data Dimensions: 148 mm × 82 mm × 87 mm
Materials Base & mounting bracket: Black ABS Socket & sensor accessory: Black glass-filled nylon Sensor cover: Toughened acrylic (UV stable) Weight: 250 g IP code: IP65
Operating conditions Ambient temperature: –35 °C to +70 °C Relative humidity: Max. 90 %, noncondensing Storage temperature: –35 °C to +70 °C
Conformity and standards EMC emission: EN 55015 EMC immunity: EN 61547 Safety: EN 61347-2-11 Environment: Complies with WEEE and
RoHS directives.
2-Channel Blinds Controller (490)
DALI
Supply wiring
Load wiring
Connection details
The 2-Channel Blinds Controller is a DALI-compatible interface unit that allows control of blinds and curtains in a DIGIDIM lighting control system. The blinds controller is a DIN-rail mounted unit that provides two independent control channels, each with two single-pole, volt-free contacts for switching up to 550 W up/down or power direction motors from a DIGIDIM system.
The unit has a status LED, a physical selection switch and relay-state indicators. The status LED provides status and a fault indication. The physical selection switch is used to identify the device during system configuration. The relay-state indicator LEDs are illuminated when the respective relay is closed.
Note: This unit does not contain a DALI power supply.
Therefore, one must be present elsewhere in the system.
Key Features
• Up/Down mode operates in a ‘Break before Make’ manner to prevent motor damage.
• Relays are internally isolated permitting separate mains phases to be used for each control channel.
• All DALI functions are programmed with either DIGIDIM
Toolbox or Designer software.
• DIN-rail mounted and only 88 mm wide.
Installation Notes
• The blinds controller is for use with motors up to 550 W.
• The external mains supply to the unit must be protected. It is recommended that a 6 A MCB is used.
• All cabling must be 230 V mains rated.
2Doc. D007818, issue 5, 2018-01-04
Helvar 490 Blinds Controller: Datasheet
Technical Data
Relay load Motor load: 550 W max.
Connections DALI: Standard DIGIDIM removable terminal block 0.5 mm² – 1.5 mm² solid or stranded
Mains: Up to 4 mm² solid core or up to
2.5 mm² stranded Note: If equipment is used in an electrically noisy environment, the DALI cable should be screened and connected to the earth.
Power Mains supply: 220 VAC – 240 VAC, 50 Hz – 60 Hz DALI consumption: 2 mA
Mechanical data Dimensions: 88 mm × 90 mm × 58 mm Housing: DIN-rail case 88 mm wide Weight: 300 g Mounting: DIN rail (installation in switchgear/ controlgear cabinet) IP code: IP30 (IP00 at terminals)
Operating and storage conditions Ambient temperature: 0 °C to +40 °C Relative humidity: Max. 90 %, noncondensing Storage temperature: −10 °C to +70 °C
Conformity and standards Emission: EN 55015 Immunity: EN 61547 Safety: EN 61347-2-11 Isolation: 4 kV Environment: Complies with WEEE and RoHS directives.
Dimensions (mm)
DA+ DA– DA–DA+
DALI IN DALI OUT
L N
Channel 1 Channel 2
Up Down Up Down
UP
DOWNUP
DOWN
N
L
N
L
Connections
88 58
45 90
File details come from the government source that posted it. Updated .