This notice is a draft pre-solicitation for a Multiple Award Construction Contract to provide design-build construction services in Italy. The contract will have a one year base period and four option years, with a minimum guarantee of $2,500 and a maximum total value of $96 million across all awards.

Work will primarily take place at Aviano Air Base and include grading, utilities, painting, roofing, building renovation, new construction, electrical, HVAC, refrigeration, fire suppression, fuel, power, communications, asbestos abatement and other site work. The contract will have indefinite delivery indefinite quantity task orders between $2,500 and $7 million.

Interested parties should submit any comments on the draft sections or attachments by April 19. The solicitation is expected to be released on federalbusinessopportunities.gov in May 2019. The North American Industry Classification code is 236220. Responses to this notice will be published with any revisions to the acquisition strategy.

ANNEX A-D MECHANICAL PART 1

View the file

Other files for this federal contract opportunity

Other files attached to Multiple Award Construction Contract (MACC) Italy, newest first.
File Type Posted
Attachment 1 Section L REV 03.pdf PDF
Solicitation_Amendment_FA568219RA0010004_SF_30.pdf PDF
JA6P70~1.PDF PDF
ATTACH~3.PDF PDF
ATTACH~2.PDF PDF
Solicitation_Amendment_FA568219RA0010002_SF_30.pdf PDF
Attachment_1_Section_L_REV_02.pdf PDF
Attachment_9_Questions_and_Answers.docx DOCX document
ATTACH~3.DOC DOC document
ANNEX_S_-_STRUCTURAL_Part11.pdf PDF
ANNEX_E_-_ELECTRICAL_Part5.pdf PDF
ANNEX_E_-_ELECTRICAL_Part10.pdf PDF
ANNEX_S_-_STRUCTURAL_Part8.pdf PDF
ANNEX_E_-_ELECTRICAL_Part8.pdf PDF
ANNEX_S_-_STRUCTURAL_Part1.pdf PDF
ANNEX_E_-_ELECTRICAL_Part2.pdf PDF
ANNEX_E_-_ELECTRICAL_Part4.pdf PDF
Attachment_10_ASHE_18-1025_TS__Part6_Part5_Part2.pdf PDF
Attachment_10_ASHE_18-1025_TS__(Seed_project)_Part3.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part10_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part1_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part17.pdf PDF
Attachment_13_Physical_Data.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part6.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part7.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part2_Part5.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part7.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part4.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_Project)__Part1.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part5.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part15_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part13_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part15_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part1_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part2_Part2.pdf PDF
Attachment_10_ASHE_18-1025_TS__(Seed_project)_Part5.pdf PDF
Solicitation_-_FA568219RA001.pdf PDF
Attachment_3_CEN_-MACC_SOW_v3.pdf PDF
Attachment_2_Section_M.pdf PDF
Attachment_8_Client_Authorization_Letter.pdf PDF
Attachment_9_Questions_and_Answers.pdf PDF
Questions_and_Answers_draft_RFP_FA568219RA0001_May_03_2019.pdf PDF
Questions_and_Answers_draft_RFP_FA568219RA0001_May_02_2019.pdf PDF
(draft)_Attachment_6_Experience_Overview_Sheet.pdf PDF
(draft)_Attachment_9_Client_Authorization_Letter.pdf PDF
(draft)_Attachment_1_Section_L__20_March.pdf PDF
(draft)_Attachment_3_General_Requirements_and_Provisions.pdf PDF
(draft)_Attachment_10_Questions_and_Answers.pdf PDF
(draft)_Attachment_7_Experience_Information_Sheet.pdf PDF
Show all 50

Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RENOVATE/EXPAND FAC. 939 ASHE 18-1025

FINAL (100% design) DESIGN ANALYSIS

ANNEX A-Bs-Cs-Ds

MECHANICAL CALCULATION

# ANNEX

A Mechanical Works: Energy Calculation and building performance index

B Mechanical Works: Room Ventilation and Heating and Cooling Load

B1 Mechanical Works: Ducts Pressure Loss Calculation

C Mechanical Works: Domestic Water – Fixtures Count

C1 Mechanical Works: Domestic Hot Water Storage Capacity

C1A Mechanical Works: Domestic Hot Water Storage Capacity (NavFac design Manual)

C2 Mechanical Works: Domestic Cold-Water System

C3 Mechanical Works: Domestic Hot Water System

C4 Mechanical Works: Domestic Hot Water Return

C5 Mechanical Works: Water Hammer Calculation

D1 Mechanical Works: Heating System Calculation – Heat Pump Circuit

D2 Mechanical Works: Heating System Calculation – Secondary Circuit

D3 Mechanical Works: Heating System Calculation – Boiler Circuit

D4 Mechanical Works: Cooling System Calculation – Heat Pump Circuit

D5 Mechanical Works: Cooling System Calculation – Secondary Circuit

D6 Mechanical Works: Boiler Room Expansion Tanks Calculation

D7 Mechanical Works: Natural Gas Line Pressure Drop Calculation

D8 Mechanical Works: Boiler chimney Calculation

RENOVATE/EXPAND FAC. 939 ASHE 18-1025

DESIGN ANALYSIS FINAL (100% design)

THIS PAGE LEFT INTENTIONNALLY BLANK

ANNEX A

ENERGY CALCULATION AND BUILDING PERFORMANCE INDEX

15/02/2019 09:21:19 AERMEC MC Impianti 11300 Pagina 1

Indicatori di prestazione energetica di fabbricato Bldg #939

Dati generali Ambito di intervento Ristrutturazione importante di primo livello

Procedura Nazionale - D.Lgs. 19 agosto 2005, n. 192, e successive modificazioni.

Zona climatica E Gradi giorno 2.417 Volume lordo m³ 3.669,00

Riscaldamento Edificio di progetto Edificio di riferimento Durata della stagione (UNI/TS 11300-1:2014) 01/10 - 26/04 30/09 - 27/04 Durata della stagione (D.P.R. 412/1993) 15/10 - 15/04 15/10 - 15/04 Superficie disperdente m² 2.355,22 Superficie utile m² 743,86 Rapporto S/V 1/m 0,6419 Rapporto Superficie trasparente / Superficie utile 0,073 Fabbisogno di energia termica per riscaldamento kWh 53.775,004 60.146,242 EPH,nd kWh/(m²·a) 72,292 80,857 EPH,nd,limite (2019/21) kWh/(m²·a) 71,521 Qualità involucro Media Fabbisogno di energia primaria per riscaldamento kWh 44.090,508 50.224,633 Superficie calpestabile del volume riscaldato m² 743,860 EPH,nren kWh/(m²·a) 59,273 67,519 EPH,ren kWh/(m²·a) 60,259 75,474 EPH,tot kWh/(m²·a) 119,531 142,992 Rendimento del sottosistema di emissione, ηe 0,9428 Rendimento del sottosistema di regolazione, ηrg 0,9951 Rendimento del sottosistema di distribuzione, ηd 0,9152 Efficienza dei sottosistemi di utilizzazione, ηu 0,810 Efficienza media stagionale impianto riscaldamento ηh 1,4561 1,3196 Verifica efficienza media stagionale Positiva Copertura FER % 50,4125

Raffrescamento Edificio di progetto Edificio di riferimento Durata della stagione (UNI/TS 11300-1:2014) 20/05 - 06/09 19/05 - 06/09 Fabbisogno di energia termica per raffrescamento kWh 9.688,600 9.749,620 Superficie utile m² 743,86 EPC,nd kWh/(m²·a) 13,025 13,107 Verifica Positiva Asol,est/ Asup,utile kWh/m² 0,0193 YIE W/m²K 0,0200 Qualità involucro Alta Fabbisogno di energia primaria per raffrescamento kWh 28.170,223 34.450,273 Superficie calpestabile del volume raffrescato m² 743,860 EPC,nren kWh/(m²·a) 37,870 46,313 EPC,ren kWh/(m²·a) 13,093 14,208 EPC,tot kWh/(m²·a) 50,963 60,520 Efficienza media stagionale impianto raffrescamento ηc 0,1824 0,1593 Verifica efficienza media stagionale Positiva Copertura FER % 25,6912

Acqua calda sanitaria Edificio di progetto Edificio di riferimento Superficie utile m² 743,86 Fabbisogno di energia termica per acs kWh 3.889,369 3.889,369 Fabbisogno di energia primaria per acs kWh 2.265,067 3.887,621 EPW,nren kWh/(m²·a) 3,045 5,226 EPW,ren kWh/(m²·a) 5,808 6,049 EPW,tot kWh/(m²·a) 8,854 11,275

15/02/2019 09:21:19 AERMEC MC Impianti 11300 Pagina 2

Efficienza media stagionale impianto acs ηw 1,2994 0,7696 Verifica efficienza media stagionale Positiva Copertura FER % 65,6067

Ventilazione Edificio di progetto Edificio di riferimento Fabbisogno di energia termica per ventilazione kWh 46.572,000 44.437,047 Superficie utile m² 743,86 EPV,nren kWh/(m²·a) 62,609 59,738 EPV,ren kWh/(m²·a) 20,668 17,915 EPV,tot kWh/(m²·a) 83,276 77,654

Globale Edificio di progetto Edificio di riferimento EPgl,nren kWh/(m²·a) 162,796 178,796 EPgl,nren,rif,standard kWh/(m²·a) 181,775 Verifica Positiva Classe energetica A1 EPgl,ren kWh/(m²·a) 99,828 113,645 EPgl,tot kWh/(m²·a) 262,625 292,442 Coefficiente medio globale di scambio termico, H’T 0,29 0,55 Verifica H’T Positiva Asol,est/Asup,utile 0,0193 0,0400 Verifica Asol,est/Asup,utile Positiva Emissioni di CO2 KgCO2/(m²·a) 41,146 Copertura FER % 38,0117

Consumi Fabbisogno di energia elettrica da rete per ausiliari riscaldamento kWhe 1.657,780

Fabbisogno di energia elettrica da rete per ausiliari raffrescamento kWhe 762,554

Fabbisogno di energia elettrica da rete per ausiliari acs kWhe 0,000 Fabbisogno di energia elettrica da rete per ausiliari ventilazione kWhe 23.883,076

Riscaldamento Energia elettrica da rete kWh 19.574,365 Raffrescamento Energia elettrica da rete kWh 13.683,713 Acqua calda sanitaria Energia elettrica da rete kWh 1.161,572

Dati climatici mensili

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC

Temperatura media giornaliera dell'aria esterna [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78

Irradiazione solare diffusa [W/m2] 24,31 37,04 53,24 76,39 99,54 107,64 104,17 84,49 64,81 43,98 25,46 21,99

Irradiazione solare diretta [W/m2] 32,41 52,08 79,86 91,44 137,73 159,72 152,78 137,73 109,95 45,14 26,62 26,62

Irradiazione solare su superficie orizzontale [W/m2] 56,71 89,12 133,10 167,82 237,27 267,36 256,94 222,22 174,77 89,12 52,08 48,61

Irradiazione solare su superficie verticale, S [W/m2] 116,46 131,69 133,97 111,05 120,95 121,05 122,36 131,08 150,59 107,36 90,49 107,57

Irradiazione solare su superficie verticale, SE [W/m2] 89,78 108,97 125,76 121,79 146,18 151,71 151,32 152,36 151,39 93,16 71,63 81,93

Irradiazione solare su superficie verticale, E [W/m2] 48,63 71,09 98,90 115,02 156,46 173,01 167,79 151,57 127,26 67,13 42,38 42,23

Irradiazione solare su superficie verticale, NE [W/m2] 20,08 35,29 59,31 85,07 127,43 147,69 140,03 113,52 80,44 39,14 20,37 17,12

Irradiazione solare su superficie verticale, N [W/m2] 17,88 27,49 39,99 59,11 94,44 115,35 106,40 76,15 50,27 30,96 18,00 15,91

Irradiazione solare su superficie verticale, NO [W/m2] 20,08 35,29 59,31 85,07 127,43 147,69 140,03 113,52 80,44 39,14 20,37 17,12

Irradiazione solare su superficie verticale, O [W/m2] 48,63 71,09 98,90 115,02 156,46 173,01 167,79 151,57 127,26 67,13 42,38 42,23

Irradiazione solare su superficie verticale, SO [W/m2] 89,78 108,97 125,76 121,79 146,18 151,71 151,32 152,36 151,39 93,16 71,63 81,93

Pressione parziale del vapore d'acqua nell'aria esterna [Pa] 553 630 774 925 1378 1645 1888 1930 1480 1200 932 651

Umidità relativa dell'aria esterna [%] 78,50 78,20 73,29 65,65 67,32 64,27 68,18 75,41 74,15 81,87 87,07 81,36

FABBISOGNO DI ENERGIA TERMICA UTILE

Zona: Existing bldg #939

Fabbisogno di riscaldamento

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC

Flusso termico per trasmissione con l'ambiente esterno

Qd [MJ] 10865,48 8779,50 7369,24 5229,97 1280,95 -860,45 -1672,77 -889,13 1472,97 5146,65 7014,85 9780,44

Flusso termico per trasmissione con il terreno

Qg [MJ] 8531,43 6893,54 5786,22 4106,50 1005,79 -675,61 -1313,44 -698,13 1156,56 4041,08 5507,96 7679,47

Flusso termico per trasmissione con ambienti non climatizzati

Qu [MJ] 657,21 531,04 445,74 316,34 77,48 -52,05 -101,18 -53,78 89,09 311,30 424,30 591,58

Flusso termico per trasmissione con zone climatizzate a temperatura diversa

Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico per ventilazione Qve [MJ] 17524,88 14160,41 11885,80 8435,39 2066,04 -1387,81 -2698,00 -1434,08 2375,75 8301,01 11314,21 15774,82

Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)

Qr,op [MJ] 637,62 576,27 675,94 730,39 717,78 750,10 739,23 640,67 607,72 546,24 506,07 607,51

Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)

Qr,w [MJ] 21,13 19,10 22,40 24,21 23,79 24,86 24,50 21,24 20,14 18,11 16,77 20,14

Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)

Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico prodotto da sorgenti di calore interne

Qint [MJ] 7711,06 6964,83 7711,06 7462,32 7711,06 7462,32 7711,06 7711,06 7462,32 7711,06 7462,32 7711,06

Flusso termico prodotto da sorgenti di calore interne (da U)

Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Apporti solari su componenti opachi Qsol,op [MJ] 446,20 620,87 1015,90 1168,76 1758,73 1905,66 1899,03 1663,52 1294,92 606,59 390,00 386,69

Apporti solari su componenti trasparenti Qsol,w [MJ] 1161,35 1445,99 2143,31 2316,93 3318,28 3523,03 3516,11 3179,86 2620,23 1379,57 969,57 1042,04

Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Rapporto apporti/dispersioni γ 0,23 0,28 0,39 0,55 3,23 -2,68 -1,62 -2,67 2,28 0,51 0,35 0,26

Fattore di utilizzazione degli apporti termici ηgn 1,00 1,00 1,00 0,98 0,31 -0,37 -0,62 -0,37 0,44 0,99 1,00 1,00

Fabbisogno di energia termica utile Qnd [MJ] 28921,80 21934,90 15356,47 8087,45 5,02 0,00 0,00 0,00 31,33 8795,35 15981,68 25318,54

Fabbisogno di raffrescamento

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC

Flusso termico per trasmissione con l'ambiente esterno

Qd [MJ] 13879,49 11501,83 10383,24 8146,75 4294,96 2056,33 1341,23 2124,87 4389,75 8160,66 9931,63 12794,45

Flusso termico per trasmissione con il terreno

Qg [MJ] 10897,98 9031,08 8152,78 6396,71 3372,34 1614,60 1053,12 1668,42 3446,77 6407,64 7798,18 10046,02

Flusso termico per trasmissione con ambienti non climatizzati

Qu [MJ] 839,52 695,70 628,04 492,77 259,79 124,38 81,13 128,53 265,52 493,61 600,73 773,89

Flusso termico per trasmissione con zone climatizzate a temperatura diversa

Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico per ventilazione Qve [MJ] 15003,98 12433,69 11224,48 8806,78 4642,93 2222,93 1449,90 2297,03 4745,40 8821,82 10736,27 13831,03

Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)

Qr,op [MJ] 637,62 638,01 675,94 754,74 717,78 775,11 739,23 640,67 627,98 546,24 522,93 607,51

Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)

Qr,w [MJ] 21,13 21,15 22,40 25,02 23,79 25,69 24,50 21,24 20,81 18,11 17,33 20,14

Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)

Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico prodotto da sorgenti di calore interne

Qint [MJ] 7711,06 6964,83 7711,06 7462,32 7711,06 7462,32 7711,06 7711,06 7462,32 7711,06 7462,32 7711,06

Flusso termico prodotto da sorgenti di calore interne (da U)

Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Apporti solari su componenti opachi Qsol,op [MJ] 446,20 620,87 1015,90 1223,59 1758,73 1905,66 1899,03 1663,52 1294,92 674,95 390,00 386,69

Apporti solari su componenti trasparenti Qsol,w [MJ] 1161,35 1445,99 2143,31 2405,30 3318,28 3523,03 3516,11 3179,86 2620,23 1509,75 969,57 1042,04

Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Tempo di attivazione t [gg] 0 0 0 0 22 30 31 31 17 0 0 0

Totale guadagni Qgn [MJ] 0,00 0,00 0,00 0,00 7827,28 10985,35 11227,17 10890,92 5713,44 0,00 0,00 0,00

Totale dispersioni Qht [MJ] 0,00 0,00 0,00 0,00 8198,79 4913,37 2790,07 5217,23 6914,08 0,00 0,00 0,00

Rapporto apporti/dispersioni γ 0,00 0,00 0,00 0,00 1,08 1,32 2,24 1,25 1,47 0,00 0,00 0,00

Fattore di utilizzazione delle dispersioni ηls 0,00 0,00 0,00 0,00 0,90 1,00 1,00 1,00 0,81 0,00 0,00 0,00

Fabbisogno di energia termica utile Qnd [MJ] 0,00 0,00 0,00 0,00 474,60 6072,47 8437,09 5674,21 122,72 0,00 0,00 0,00

Fabbisogno per acqua calda sanitaria

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Tempo di attivazione t [gg] 31 28 31 30 31 30 31 31 30 31 30 31 365

Volume di acqua richiesto Vw [litri] 2935 2651 2935 2840 2935 2840 2935 2935 2840 2935 2840 2935 34558

Fabbisogno di energia termica Qw [kWh] 93 84 93 90 93 90 93 93 90 93 90 93 1100

FABBISOGNO DI ENERGIA TERMICA UTILE

Zona: New building #939

Fabbisogno di riscaldamento

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC

Flusso termico per trasmissione con l'ambiente esterno

Qd [MJ] 8221,05 6642,75 5575,72 3957,10 969,19 -651,03 -1265,65 -672,74 1114,48 3894,06 5307,58 7400,08

Flusso termico per trasmissione con il terreno

Qg [MJ] 3923,76 3170,47 2661,19 1888,66 462,58 -310,73 -604,07 -321,08 531,92 1858,57 2533,21 3531,93

Flusso termico per trasmissione con ambienti non climatizzati

Qu [MJ] 382,36 308,96 259,33 184,05 45,08 -30,28 -58,87 -31,29 51,84 181,11 246,86 344,18

Flusso termico per trasmissione con zone climatizzate a temperatura diversa

Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico per ventilazione Qve [MJ] 12664,76 10233,35 8589,55 6096,03 1493,07 -1002,94 -1949,78 -1036,37 1716,89 5998,92 8176,48 11400,04

Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)

Qr,op [MJ] 466,78 421,87 494,84 534,70 525,46 549,13 541,17 469,02 444,90 399,89 370,48 444,74

Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)

Qr,w [MJ] 16,15 14,60 17,12 18,50 18,18 19,00 18,72 16,23 15,39 13,84 12,82 15,39

Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)

Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico prodotto da sorgenti di calore interne

Qint [MJ] 5002,07 4518,00 5002,07 4840,72 5002,07 4840,72 5002,07 5002,07 4840,72 5002,07 4840,72 5002,07

Flusso termico prodotto da sorgenti di calore interne (da U)

Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Apporti solari su componenti opachi Qsol,op [MJ] 383,20 503,16 779,85 872,05 1294,25 1397,14 1393,65 1231,22 972,82 484,36 326,09 336,19

Apporti solari su componenti trasparenti Qsol,w [MJ] 1054,42 1253,01 1700,01 1728,86 2308,58 2396,76 2415,74 2296,09 2026,76 1137,52 847,77 952,21

Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Rapporto apporti/dispersioni γ 0,24 0,28 0,40 0,56 3,29 -2,56 -1,57 -2,60 2,37 0,52 0,35 0,26

Fattore di utilizzazione degli apporti termici ηgn 1,00 1,00 1,00 0,99 0,30 -0,39 -0,64 -0,38 0,42 0,99 1,00 1,00

Fabbisogno di energia termica utile Qnd [MJ] 19236,38 14520,13 10132,58 5326,76 1,27 0,07 0,00 0,15 10,02 5781,38 10639,68 16847,07

Fabbisogno di raffrescamento

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC

Flusso termico per trasmissione con l'ambiente esterno

Qd [MJ] 10501,50 8702,52 7856,17 6164,00 3249,65 1555,86 1014,80 1607,72 3321,38 6174,52 7514,47 9680,54

Flusso termico per trasmissione con il terreno

Qg [MJ] 5012,18 4153,56 3749,61 2941,97 1551,00 742,58 484,35 767,34 1585,23 2946,99 3586,52 4620,35

Flusso termico per trasmissione con ambienti non climatizzati

Qu [MJ] 488,43 404,76 365,39 286,69 151,14 72,36 47,20 74,78 154,48 287,18 349,50 450,24

Flusso termico per trasmissione con zone climatizzate a temperatura diversa

Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico per ventilazione Qve [MJ] 10842,91 8985,44 8111,58 6364,39 3355,30 1606,44 1047,80 1659,99 3429,35 6375,26 7758,77 9995,26

Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)

Qr,op [MJ] 466,78 467,07 494,84 552,52 525,46 567,44 541,17 469,02 459,72 399,89 382,83 444,74

Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)

Qr,w [MJ] 16,15 16,16 17,12 19,12 18,18 19,63 18,72 16,23 15,91 13,84 13,25 15,39

Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)

Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Flusso termico prodotto da sorgenti di calore interne

Qint [MJ] 5002,07 4518,00 5002,07 4840,72 5002,07 4840,72 5002,07 5002,07 4840,72 5002,07 4840,72 5002,07

Flusso termico prodotto da sorgenti di calore interne (da U)

Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Apporti solari su componenti opachi Qsol,op [MJ] 383,20 503,16 779,85 908,69 1294,25 1397,14 1393,65 1231,22 972,82 535,26 326,09 336,19

Apporti solari su componenti trasparenti Qsol,w [MJ] 1054,42 1253,01 1700,01 1759,10 2308,58 2396,76 2415,74 2296,09 2026,76 1226,35 847,77 952,21

Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00

Tempo di attivazione t [gg] 0 0 0 0 22 30 31 31 18 0 0 0

Totale guadagni Qgn [MJ] 0,00 0,00 0,00 0,00 5188,21 7237,47 7417,81 7298,16 4120,49 0,00 0,00 0,00

Totale dispersioni Qht [MJ] 0,00 0,00 0,00 0,00 5362,67 3167,17 1760,39 3363,85 4795,95 0,00 0,00 0,00

Rapporto apporti/dispersioni γ 0,00 0,00 0,00 0,00 1,22 1,23 2,10 1,18 1,80 0,00 0,00 0,00

Fattore di utilizzazione delle dispersioni ηls 0,00 0,00 0,00 0,00 0,91 1,00 1,00 1,00 0,84 0,00 0,00 0,00

Fabbisogno di energia termica utile Qnd [MJ] 0,00 0,00 0,00 0,00 325,87 4070,30 5657,42 3934,65 109,63 0,00 0,00 0,00

Fabbisogno per acqua calda sanitaria

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Tempo di attivazione t [gg] 31 28 31 30 31 30 31 31 30 31 30 31 365

Volume di acqua richiesto Vw [litri] 7440 6720 7440 7200 7440 7200 7440 7440 7200 7440 7200 7440 87600

Fabbisogno di energia termica Qw [kWh] 237 214 237 229 237 229 237 237 229 237 229 237 2789

FABBISOGNO DI IMPIANTO: ACQUA CALDA SANITARIA

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Fabbisogno di energia termica QW [kWh] 93 84 93 90 93 90 93 93 90 93 90 93 1100

Rendimento di erogazione ηer - - - - - - - - - - - -

Perdite di erogazione Ql,er [kWh] - - - - - - - - - - - - -

Rendimento di distribuzione ηd - - - - - - - - - - - -

Perdite di distribuzione Ql,d [kWh] - - - - - - - - - - - - -

Perdite recuperate da distribuzione Qlrh,d [kWh] - - - - - - - - - - - - -

Fabbisogno di energia elettrica per ausiliari distribuzione

Eaux,d [kWh] - - - - - - - - - - - - -

Energia termica recuperata da ausiliari distribuzione

Qaux,rh,d [kWh] - - - - - - - - - - - - -

Rendimento del serbatoio di accumulo ηs - - - - - - - - - - - -

Perdite del serbatoio di accumulo Ql,s [kWh] - - - - - - - - - - - - -

Perdite recuperate da serbatoio di accumulo Qlrh,s [kWh] - - - - - - - - - - - - -

Perdite per distribuzione primaria Ql,dp [kWh] - - - - - - - - - - - - -

Perdite recuperate da distribuzione primaria Qlrh,dp [kWh] - - - - - - - - - - - - -

Fabbisogno di energia elettrica per ausiliari distribuzione primaria

Qaux,d [kWh] - - - - - - - - - - - - -

Energia termica recuperata da ausiliari distribuzione primaria

Qaux,rh,d [kWh] - - - - - - - - - - - - -

Fabbisogno di energia termica in entrata [kWh] 93 84 93 90 93 90 93 93 90 93 90 93 1100

Centralizzato

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Fabbisogno di energia termica QW [kWh] 330 298 330 320 330 320 330 330 320 330 320 330 3889

Rendimento di erogazione ηer 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Perdite di erogazione Ql,er [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Rendimento di distribuzione ηd 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93

Perdite di distribuzione Ql,d [kWh] 26 24 26 26 26 26 26 26 26 26 26 26 311

Perdite recuperate da distribuzione Qlrh,d [kWh] 24 21 24 12 0 0 0 0 0 13 23 24 140

Fabbisogno di energia elettrica per ausiliari distribuzione

Eaux,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia termica recuperata da ausiliari distribuzione

Qaux,rh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Rendimento del serbatoio di accumulo ηs 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85

Perdite del serbatoio di accumulo Ql,s [kWh] 62 56 62 60 62 60 62 62 60 62 60 62 736

Perdite recuperate da serbatoio di accumulo Qlrh,s [kWh] 50 45 50 24 0 0 0 0 0 27 48 50 295

Perdite per distribuzione primaria Ql,dp [kWh] - - - - - - - - - - - - -

Perdite recuperate da distribuzione primaria Qlrh,dp [kWh] - - - - - - - - - - - - -

Fabbisogno di energia elettrica per ausiliari distribuzione primaria

Qaux,d [kWh] - - - - - - - - - - - - -

Energia termica recuperata da ausiliari distribuzione primaria

Qaux,rh,d [kWh] - - - - - - - - - - - - -

Fabbisogno di energia termica in entrata [kWh] 419 379 419 406 419 406 419 419 406 419 406 419 4936

Generatore: PDC

Energia termica richiesta al sottosistema Qgn,out [kWh] 419 379 419 406 419 406 419 419 406 419 406 419 4936

Energia termica fornita dal sottosistema Q'gn,out [kWh] 419 379 419 406 419 406 419 419 406 419 406 419 4936

Fabbisogno di energia elettrica degli ausiliari

Egn,aux [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia in ingresso Qgn,in [kWh] 151 131 130 112 96 81 79 84 95 114 124 146 1344

Fabbisogno di energia elettrica degli ausiliari circuito generatore

Eaux,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia primaria non rinnovabile Qp,nren [kWh] 295 255 253 218 188 158 154 164 185 223 242 285 2620

Energia primaria rinnovabile Qp,ren [kWh] 268 248 289 294 323 325 340 335 311 305 282 273 3593

Energia primaria totale Qp,tot [kWh] 563 503 543 512 511 483 494 499 496 528 524 558 6213

Generatore: Condensing Boiler

Energia termica richiesta al sottosistema Qgn,out [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia termica fornita dal sottosistema Q'gn,out [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Rendimento termico ηgn 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Perdite totali Q'gn,l,t [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia elettrica degli ausiliari

Egn,aux [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia per la combustione Qgn,in [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia primaria non rinnovabile Qp,nren [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia primaria rinnovabile Qp,ren [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia primaria totale Qp,tot [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

FABBISOGNO DI IMPIANTO: RISCALDAMENTO

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Fabbisogno di energia termica QH [kWh] - - - - - - - - - - - - -

Perdite recuperate dal sistema di acqua calda sanitaria

Qlrh,W [kWh] - - - - - - - - - - - - -

Fabbisogno ideale di energia termica utile Q'H [kWh] 3145 2141 943 -58 0 0 0 0 0 64 1276 2630 10141

Rendimento di emissione ηe 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00

Perdite di emissione Ql,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia elettrica per ausiliari emissione

Eaux,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia termica recuperata da ausiliari emissione

Qaux,rh,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Rendimento di regolazione ηrg 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00

Perdite di regolazione Ql,rg [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Rendimento di distribuzione ηd 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00

Perdite di distribuzione Ql,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite recuperate da distribuzione Qlrh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia elettrica per ausiliari distribuzione

Eaux,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia termica recuperata da ausiliari distribuzione

Qaux,rh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di accumulo Ql,s [kWh] 62 56 62 30 0 0 0 0 0 34 60 62 369

Perdite recuperate da accumulo Qlrh,s [kWh] 50 45 50 12 0 0 0 0 0 15 48 50 271

Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite recuperate da circuito primario Qlrh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia elettrica per ausiliari circuito primario

Eaux,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia termica recuperata da ausiliari distribuzione

Qaux,rh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia termica in entrata [kWh] 3157 2152 956 0 0 0 0 0 0 83 1288 2643 10279

Fabbisogno di energia termica QH [kWh] - -

Perdite recuperate dal sistema di acqua calda sanitaria

Qlrh,W [kWh] - -

Fabbisogno ideale di energia termica utile Q'H [kWh] 4930 3295 1331 0 0 0 0 0 0 83 1921 4103 15664

Rendimento di emissione ηe 0,96 0,96 0,96 0,00 0,00 0,00 0,00 0,00 0,00 0,96 0,96 0,96

Perdite di emissione Ql,e [kWh] 205 137 55 0 0 0 0 0 0 3 80 171 653

Fabbisogno di energia elettrica per ausiliari emissione

Eaux,e [kWh] 99 66 27 0 0 0 0 0 0 2 38 82 313

Energia termica recuperata da ausiliari emissione

Qaux,rh,e [kWh] 99 66 27 0 0 0 0 0 0 2 38 82 313

Rendimento di regolazione ηrg 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00

Perdite di regolazione Ql,rg [kWh] 25 17 7 0 0 0 0 0 0 0 10 21 80

Rendimento di distribuzione ηd 0,99 0,99 0,99 0,00 0,00 0,00 0,00 0,00 0,00 0,99 0,99 0,99

Perdite di distribuzione Ql,d [kWh] 39 26 11 0 0 0 0 0 0 1 15 33 125

Perdite recuperate da distribuzione Qlrh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia elettrica per ausiliari distribuzione

Eaux,d [kWh] 205 137 55 0 0 0 0 0 0 3 80 170 650

Energia termica recuperata da ausiliari distribuzione

Qaux,rh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di accumulo Ql,s [kWh] 62 56 62 30 0 0 0 0 0 34 60 62 369

Perdite recuperate da accumulo Qlrh,s [kWh] 50 45 50 12 0 0 0 0 0 15 48 50 271

Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite recuperate da circuito primario Qlrh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia elettrica per ausiliari circuito primario

Eaux,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia termica recuperata da ausiliari distribuzione

Qaux,rh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia termica in entrata [kWh] 5114 3421 1390 18 0 0 0 0 0 105 2000 4258 16307

Generatore: PDC

Energia termica richiesta al sottosistema Qgn,out [kWh] 13780 10423 7268 1862 0 0 0 0 0 2037 7595 12059 55024

Energia termica fornita dal sottosistema Q'gn,out [kWh] 10196 9210 7268 1862 0 0 0 0 0 2037 7595 11211 49378

Fabbisogno di energia elettrica degli ausiliari

Egn,aux [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia in ingresso Qgn,in [kWh] 3716 3229 2308 546 0 0 0 0 0 583 2348 3956 16686

Fabbisogno di energia elettrica degli ausiliari circuito generatore

Eaux,dp [kWh] 113 120 147 70 0 0 0 0 0 80 142 138 809

Energia primaria non rinnovabile Qp,nren [kWh] 7246 6296 4501 1065 0 0 0 0 0 1137 4578 7714 32537

Energia primaria rinnovabile Qp,ren [kWh] 6480 5981 4960 1316 0 0 0 0 0 1454 5247 7255 32693

Energia primaria totale Qp,tot [kWh] 13726 12277 9460 2381 0 0 0 0 0 2590 9826 14969 65230

Generatore: Condensing Boiler

Energia termica richiesta al sottosistema Qgn,out [kWh] 3584 1214 0 0 0 0 0 0 0 0 0 848 5645

Energia termica fornita dal sottosistema Q'gn,out [kWh] 3584 1214 0 0 0 0 0 0 0 0 0 848 5645

Rendimento termico ηgn 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00

Perdite totali Q'gn,l,t [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Fabbisogno di energia elettrica degli ausiliari

Egn,aux [kWh] 7 2 0 0 0 0 0 0 0 0 0 2 11

Fabbisogno di energia per la combustione Qgn,in [kWh] 3584 1214 0 0 0 0 0 0 0 0 0 848 5645

Energia primaria non rinnovabile Qp,nren [kWh] 6989 2367 0 0 0 0 0 0 0 0 0 1654 11009

Energia primaria rinnovabile Qp,ren [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia primaria totale Qp,tot [kWh] 8673 2937 0 0 0 0 0 0 0 0 0 2052 13662

FABBISOGNO DI IMPIANTO: RAFFRESCAMENTO

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Fabbisogno ideale di energia termica utile QC [kWh] 0 0 0 0 1638 2304 2746 2214 1380 0 0 0 10283

Perdite di emissione Ql,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di regolazione Ql,rg [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di distribuzione in tubazioni acqua refrigerata

Ql,dw [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite recuperate da distribuzione acqua Qlrh,dw [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di distribuzione in canali Ql,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite recuperate da distribuzione aria Qlrh,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di accumulo Ql,s [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 -5 -12 -12 -12 -2 0 0 0 -44

Perdite recuperate da circuito primario Qlrh,cp [kWh] 0 0 0 0 -5 -12 -12 -12 -2 0 0 0 -44

Fabbisogno ideale di energia termica utile QC [kWh] 0 0 0 0 2813 3881 4609 3768 2417 0 0 0 17489

Perdite di emissione Ql,e [kWh] 0 0 0 0 57 79 94 77 49 0 0 0 357

Perdite di regolazione Ql,rg [kWh] 0 0 0 0 59 81 96 78 50 0 0 0 364

Perdite di distribuzione in tubazioni acqua refrigerata

Ql,dw [kWh] 0 0 0 0 60 82 98 80 51 0 0 0 372

Perdite recuperate da distribuzione acqua Qlrh,dw [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di distribuzione in canali Ql,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite recuperate da distribuzione aria Qlrh,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0

Perdite di accumulo Ql,s [kWh] 0 0 0 0 6 16 17 17 3 0 0 0 59

Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 6 14 14 14 3 0 0 0 51

Perdite recuperate da circuito primario Qlrh,cp [kWh] 0 0 0 0 5 13 14 14 3 0 0 0 48

Trattamento dell'aria

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Umidità specifica x [g/kg] 3,41 3,89 4,79 5,73 8,58 10,26 11,81 12,08 9,22 7,45 5,77 4,02

Entalpia dell'aria esterna Ht [kJ/kg] 10,51 13,64 19,85 26,59 39,70 47,68 52,94 52,28 40,93 31,56 22,53 13,86

Fabbisogno specifico orario medio Qv,m,h [kJ/kg] 0,00 0,00 0,00 0,00 0,00 6,37 13,54 12,64 0,00 0,00 0,00 0,00

Fabbisogno di energia per trattamento aria Qv [kWh] 0 0 0 0 0 5376 11801 11021 0 0 0 0 28198

Generatore

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Energia termica richiesta al generatore Qgn,out [kWh] 0 0 0 0 2996 9516 16715 15043 2572 0 0 0 46842

Fattore di carico medio della macchina frigorifera

Fk 0,00 0,00 0,00 0,00 0,11 0,14 0,24 0,22 0,19 0,00 0,00 0,00

EER al fattore di carico medio 0,00 0,00 0,00 0,00 2,76 3,02 3,60 3,49 3,36 0,00 0,00 0,00

Coefficiente di prestazione ηmm 0,00 0,00 0,00 0,00 2,58 2,56 2,94 2,95 3,19 0,00 0,00 0,00

Fabbisogno di energia in ingresso Qgn,in [kWh] 0 0 0 0 1159 3724 5691 5092 806 0 0 0 16473

Energia primaria non rinnovabile Qp,nren [kWh] 0 0 0 0 2261 7261 11098 9930 1572 0 0 0 32122

Energia primaria rinnovabile Qp,ren [kWh] 0 0 0 0 545 1750 2675 2393 379 0 0 0 7742

Energia primaria totale Qp,tot [kWh] 0 0 0 0 2806 9011 13773 12324 1951 0 0 0 39864

ENERGIA PRIMARIA

Energia primaria rinnovabile

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Riscaldamento H 10244 8381 6335 1690 0 0 0 0 0 1820 6552 9802 44824

Raffrescamento C 0 0 0 0 781 2239 3275 2913 532 0 0 0 9739

Acqua calda sanitaria W 342 314 360 362 384 371 383 381 369 368 344 345 4321

Ventilazione V 1160 1082 1291 1402 1501 1317 1299 1292 1403 1307 1152 1167 15374

Illuminazione L 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia primaria non rinnovabile

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Riscaldamento H 14567 8713 4272 887 0 0 0 0 0 1109 4797 9747 44091

Raffrescamento C 0 0 0 0 1685 6168 10030 9029 1258 0 0 0 28170

Acqua calda sanitaria W 285 239 219 161 131 128 132 141 137 190 228 274 2265

Ventilazione V 4490 3930 4010 3318 3238 3630 3979 4005 3316 3952 4238 4466 46572

Illuminazione L 0 0 0 0 0 0 0 0 0 0 0 0 0

Energia primaria totale

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Riscaldamento H 24811 17093 10607 2577 0 0 0 0 0 2929 11348 19548 88915

Raffrescamento C 0 0 0 0 2466 8407 13305 11942 1790 0 0 0 37910

Acqua calda sanitaria W 627 553 579 523 515 499 515 522 505 558 572 619 6586

Ventilazione V 5651 5012 5301 4720 4738 4947 5278 5298 4719 5259 5390 5633 61946

Illuminazione L 0 0 0 0 0 0 0 0 0 0 0 0 0

Quota rinnobabile

GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale

Riscaldamento H % 50,41

Raffrescamento C % 25,69

Acqua calda sanitaria W % 65,61

Ventilazione V % 24,82

Illuminazione L % 0,00

ANNEX B

ROOM VENTILATION AND HEATING AND COOLING LOAD

People outdoor air rate

People outdoor air rate

People outdoor air rate

People outdoor air rate

People outdoor air rate

People outdoor air rate

People outdoor air rate M in e xh au st

M in e xh au st

M in e xh au st

M in e xh au st

M in e xh au st

Ashrae 62.1

Ashrae 62.1

Area UNI 10339

UNI EN

13779

Ashrae

62.1 UNI 10339

UNI EN

13779

Ashrae

62.1

Ashrae

62.1

Ashrae

62.1 ASS5 ASS5

m2 m m2 pers/m2

n. n. l/(s*pers) (l/s*m2) l/(s*pers) l/(s*pers) l/s l/s l/s l/s l/s*m2 l/s*unit l/s n. l/s l/s

1 entry G 8,80 3,00 26,40 0 0,0 0 0 0 0 0 0,0 0 0 0

2 office G 41,02 2,60 106,65 0,05 2,1 5 2,50 0,3 11 10 17,4 55 50 55

3 office G 25,72 2,60 66,87 0,05 1,3 3 2,50 0,3 11 10 10,9 33 30 33

4 office G 33,05 2,60 85,93 0,05 1,7 5 2,50 0,3 11 10 14,0 55 50 55

5 office G 17,53 2,60 45,58 0,05 0,9 1 2,50 0,3 11 10 7,5 11 10 11

6 AHU room G 12,63 2,60 32,84

7 office G 16,10 2,60 41,86 0,05 0,8 1 2,50 0,3 11 10 6,8 11 10 11

8 vault G 23,05 2,64 60,85 0,05 1,2 2 3,80 0,3 11 10 11,3 22 20 25 22

9 office G 14,63 2,60 38,04 0,05 0,7 1 2,50 0,3 11 10 6,2 11 10 11

10 armory G 5,51 2,64 14,55 0,05 0,3 0 0,00 0 0 0 0,0 0 0 0

11 reception G 22,14 2,60 57,56 0,3 6,6 2 2,50 0,3 11 10 23,2 22 20 22

12 boiler room G 17,88 3,00 53,64 0 0,0 0 0 0 0 0 0,0 0 0 0

13 office G 23,91 2,60 62,17 0,05 1,2 3 2,50 0,3 11 10 10,2 33 30 33

14 WC G 5,88 2,60 15,29 0 0,0 1 0 0 0 0 0,0 0 0 0 10,0 42,5 50

15 WC G 5,90 2,60 15,34 0 0,0 1 0 0 0 0 0,0 0 0 0 10,0 42,6 50

16 comm. room G 11,23 2,60 29,20 0 0,0 0 0,00 0 0 0 0,0 0 0 10 0,0 0,0

17 office G 39,21 2,60 101,95 0,05 2,0 5 2,50 0,3 11 11 16,7 55 55 55

18 conference room G 69,70 2,60 181,22 0,5 34,9 35 2,50 0,3 5,5 11 108,0 192,5 385 195 195

19 Electrical room G 4,62 2,60 12,01

20 corridor G 83,19 2,60 216,29 0,05 4,2 2 2,50 0,3 0 0 35,4 0 0 20 58

21 sprinkler room G 14,56 2,70 39,31

22 corridor G 10,24 2,40 24,58 0,05 0,5 2 2,5 0,3 0 0 4,4 0 0 0

23 corridor G 20,89 2,70 56,40 0,05 1,0 2 2,5 0,3 0 0 8,9 0 0 45

24 corridor G 21,21 2,70 57,27 0,05 1,1 2 2,5 0,3 0 0 9,0 0 0 20

25 locker room G 45,87 2,70 123,85 0 0,0 0 0,0 0 0 0 0,0 0 0 80 2,5 114,7 4,0 137,6 138

25.1 restroom and showers G 23,31 2,70 62,94 0 0,0 0 0,0 0 0 0 0 0 0 35,0 35,0 8,0 139,9 140

26 breaking area G 56,76 2,70 153,25 0,5 28,4 10 2,5 0,6 10 10 105,0 100 100 105 1,5 85,1 85

27 bedroom G 14,33 2,70 38,69 0,1 1,4 2 2,5 0,3 11 10 7,9 22 20 30

27.1 wc G 4,23 2,70 11,42 0 0,0 0 0,0 0 0 0 0 0 0 25,0 25,0 8,0 25,4 25

28 bedroom G 15,60 2,70 42,12 0,1 1,6 2 2,5 0,3 11 10 8,6 22 20 30

29 bedroom G 14,36 2,70 38,77 0,1 1,4 1 2,5 0,3 11 10 7,9 11 10 30

29.1 wc G 4,16 2,70 11,23 0 0,0 0 0,0 0 0 0 0 0 0 25,0 25,0 8,0 25,0 25

30 bedroom G 15,37 2,70 41,50 0,1 1,5 2 2,5 0,3 11 10 8,5 22 20 30

31 laundry G 8,94 2,70 24,14 0,1 0,9 2 2,5 0,6 0 0 7,6 0 0 20

32 kitchen G 14,25 2,70 38,48 0,2 2,9 4 3,8 0,6 19,4 0 0 40 1,5 21,4

34 AHU room G 14,25 2,70 38,48

35 Electrical room G 10,90 2,70 29,43 0 0 0

36 female locker room G 15,17 2,70 40,96 0 0,0 0 0,0 0 0 0 0,0 0 0 0 2,5 37,9 8,0 91,0 69

37 janitory G 1,95 2,70 5,27 0 0,0 0 0,0 0 0 0 0 0 0 5,0 9,8 10

98,3 96 454,7 677,5 840 966 354 867

In the FC heating and cooling coil calculation the contribute for the outside air is not considered

In the room #36 for the locker has been taken #4 volume ari change. For the bathroom #8 air volume change

ROOM VENTILATION AND HEATING AND COOLING LOAD

O cc u p an t d en si ty

A sh ra e

.1

P er so n p er

A sh ra e

.1

P er so n d es ig n

D es ig n

O A s u p p ly

D es ig n

E xh au st

Lo ca l c o d e

U se d es ti n at io n

Fl o o r

A re a

H ei gh t

V o lu m e

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 1

Dati Generali Progetto

Descrizione progetto Renovation/expand Fac. 939 Ambito di intervento Ristrutturazione importante di primo livello

Metodologia di calcolo Metodo di calcolo da rilievo sull’edificio Procedura di calcolo Nazionale - D.Lgs. 19 agosto 2005, n. 192, e successive modificazioni.

Edificio pubblico No Classificazione edificio E.2 - Edifici adibiti a uffici e assimilabili

Dati Climatici

Provincia Pordenone Comune Aviano

Zona climatica E Gradi giorno 2.417 Altezza sul livello del mare [m] 159 Temperatura esterna di progetto invernale [°C] -5,00 Temperatura esterna media annuale [°C] 12,60

Fattore di correzione fg1 1,45 Fattore di correzione fg2 0,30 Fattore di correzione Gw 1,00

Fattori di correzione per esposizione:

Nord 1,20 Nord – Est 1,20 Est 1,15 Sud – Est 1,10 Sud 1,00 Sud – Ovest 1,05 Ovest 1,10 Nord – Ovest 1,15

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 2

Risultati per Ambiente

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #02

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 41,02 Volume netto [m³] 106,65

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D SE OP MUR_01 Existing ext. wall 0,241 16,41 -5,00 1,10 4,3503 108,76

D SE OP MUR_01B Old column on the existing ext. wall 0,280 1,97 -5,00 1,10 0,6068 15,17

D SE OP MUR_01A New column on the existing ext. wall 0,286 3,28 -5,00 1,10 1,0319 25,80

D SE TR FIN_01 Window 1.93x1.56 1,613 6,02 -5,00 1,10 10,6813 267,03 D NE OP MUR_01 Existing ext. wall 0,241 16,52 -5,00 1,20 4,7776 119,44 D OR(C) OP SOL_01 Existing roof 0,194 41,02 -5,00 1,00 7,9579 198,95 D SE PT PT_1 Window Thermal bridge 0,035 13,96 -5,00 1,10 0,5375 13,44 D SE PT PT_2 thermal bridge wall-roof 0,046 8,44 -5,00 1,10 0,4271 10,68

D SE PT PT_5 Thermal bridge - existing column on the wall 0,072 13,12 -5,00 1,10 1,0391 25,98

D SE PT PT-6

Thermal bridge - new column on the existing wall

0,028 6,56 -5,00 1,10 0,2020 5,05

Dispersioni per trasmissione [W] 790,28 Dispersioni per ventilazione [W] 293,71 Potenza di ripresa [W] 943,46 Carico termico totale [W] 2.027,46

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 3

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #03

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 25,72 Volume netto [m³] 66,87

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D NO OP MUR_01 Existing ext. wall 0,241 10,57 -5,00 1,15 2,9295 73,24

D NO OP MUR_01B Old column on the existing ext. wall 0,280 1,97 -5,00 1,15 0,6343 15,86

D NO OP MUR_01A New column on the existing ext. wall 0,286 1,64 -5,00 1,15 0,5394 13,48

D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58 D OR(C) OP SOL_01 Existing roof 0,194 25,72 -5,00 1,00 4,9897 124,74 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 5,24 -5,00 1,15 0,2772 6,93

D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 6,56 -5,00 1,15 0,5432 13,58

U OP MUR_03 Internal fire resistant wall (insulated) 0,282 16,42 5,00 1,00 2,7783 69,46

D NO PT PT-6

Thermal bridge - new column on the existing wall

0,028 3,28 -5,00 1,15 0,1056 2,64

Dispersioni per trasmissione [W] 466,54 Dispersioni per ventilazione [W] 184,16 Potenza di ripresa [W] 591,56 Carico termico totale [W] 1.242,26

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 4

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #04

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 33,05 Volume netto [m³] 85,93

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D SE OP MUR_01 Existing ext. wall 0,241 15,30 -5,00 1,10 4,0560 101,40

D SE OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,10 0,3018 7,55

D SE TR FIN_01 Window 1.93x1.56 1,613 6,02 -5,00 1,10 10,6813 267,03 D OR(C) OP SOL_01 Existing roof 0,194 33,05 -5,00 1,00 6,4117 160,29 D SE PT PT_1 Window Thermal bridge 0,035 13,96 -5,00 1,10 0,5375 13,44 D SE PT PT_2 thermal bridge wall-roof 0,046 8,44 -5,00 1,10 0,4271 10,68

D NE PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,20 0,2834 7,08

U OP MUR_03 Internal fire resistant wall (insulated) 0,282 13,43 10,00 1,00 1,5149 37,87

Dispersioni per trasmissione [W] 605,34 Dispersioni per ventilazione [W] 236,65 Potenza di ripresa [W] 760,15 Carico termico totale [W] 1.602,14

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 5

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #05

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 17,53 Volume netto [m³] 45,58

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D NO OP MUR_01 Existing ext. wall 0,241 7,72 -5,00 1,15 2,1396 53,49

D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89

D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58 D OR(C) OP SOL_01 Existing roof 0,194 17,53 -5,00 1,00 3,4008 85,02 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 3,57 -5,00 1,15 0,1889 4,72

D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79

Dispersioni per trasmissione [W] 304,52 Dispersioni per ventilazione [W] 125,53 Potenza di ripresa [W] 403,19 Carico termico totale [W] 833,24

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 6

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #07

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 16,10 Volume netto [m³] 41,86

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D NO OP MUR_01 Existing ext. wall 0,241 7,08 -5,00 1,15 1,9622 49,06

D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89

D NO TR FIN_02 Window 0.87x1.56 1,650 2,70 -5,00 1,15 5,1232 128,08 D OR(C) OP SOL_01 Existing roof 0,194 16,10 -5,00 1,00 3,1234 78,09 D NO PT PT_1 Window Thermal bridge 0,035 9,72 -5,00 1,15 0,3912 9,78 D NO PT PT_2 thermal bridge wall-roof 0,046 3,28 -5,00 1,15 0,1735 4,34

D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79

Dispersioni per trasmissione [W] 284,02 Dispersioni per ventilazione [W] 115,28 Potenza di ripresa [W] 370,30 Carico termico totale [W] 769,60

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 7

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #08

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 23,05 Volume netto [m³] 60,85

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

U OP MUR_03 Internal fire resistant wall (insulated) 0,282 10,74 10,00 1,00 1,2115 30,29

D SE OP MUR_04 Concrete ext. wall vault 0,267 18,64 -5,00 1,10 5,4746 136,86

D SE OP MUR_01B Old column on the existing ext. wall 0,280 1,71 -5,00 1,10 0,5267 13,17

D OR(C) OP SOL_01 Existing roof 0,194 23,05 -5,00 1,00 4,4717 111,79

U OP MUR_05 Vault concrete wall 44cm thickness 1,200 8,09 10,00 1,00 3,8832 97,08

D SE PT PT_4 roof ridge Thermal bridge 0,003 7,14 -5,00 1,10 0,0236 0,59

D SE PT PT_5 Thermal bridge - existing column on the wall 0,072 6,56 -5,00 1,10 0,5196 12,99

Dispersioni per trasmissione [W] 402,77 Dispersioni per ventilazione [W] 167,58 Potenza di ripresa [W] 530,15 Carico termico totale [W] 1.100,50

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 8

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #09

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 14,63 Volume netto [m³] 38,04

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D NO OP MUR_01 Existing ext. wall 0,241 6,76 -5,00 1,15 1,8735 46,84 D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58

D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89

D OR(C) OP SOL_01 Existing roof 0,194 14,63 -5,00 1,00 2,8382 70,96 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 2,98 -5,00 1,15 0,1576 3,94

D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79

Dispersioni per trasmissione [W] 283,02 Dispersioni per ventilazione [W] 104,76 Potenza di ripresa [W] 336,49 Carico termico totale [W] 724,27

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 9

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #010

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 5,51 Volume netto [m³] 14,55

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D OR(C) OP SOL_01 Existing roof 0,194 5,51 -5,00 1,00 1,0689 26,72

U OP MUR_05 Vault concrete wall 44cm thickness 1,200 4,22 10,00 1,00 2,0256 50,64

Dispersioni per trasmissione [W] 77,36 Dispersioni per ventilazione [W] 40,07 Potenza di ripresa [W] 126,73 Carico termico totale [W] 244,16

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 10

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #011

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 22,14 Volume netto [m³] 57,56

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D NO OP MUR_01 Existing ext. wall 0,241 12,09 -5,00 1,15 3,3507 83,77 D NO TR FIN_02 Window 0.87x1.56 1,650 2,70 -5,00 1,15 5,1232 128,08 D OR(C) OP SOL_01 Existing roof 0,194 23,91 -5,00 1,00 4,6385 115,96 D NO PT PT_1 Window Thermal bridge 0,035 9,72 -5,00 1,15 0,3912 9,78 D NO PT PT_2 thermal bridge wall-roof 0,046 4,51 -5,00 1,15 0,2386 5,96

D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79

Dispersioni per trasmissione [W] 350,35 Dispersioni per ventilazione [W] 158,52 Potenza di ripresa [W] 509,22 Carico termico totale [W] 1.018,09

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 11

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #013

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 23,91 Volume netto [m³] 62,17

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D NO OP MUR_01 Existing ext. wall 0,241 11,98 -5,00 1,15 3,3203 83,01

D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89

D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58 D OR(C) OP SOL_01 Existing roof 0,194 23,91 -5,00 1,00 4,6385 115,96 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 4,87 -5,00 1,15 0,2576 6,44

D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79

Dispersioni per trasmissione [W] 366,70 Dispersioni per ventilazione [W] 171,22 Potenza di ripresa [W] 549,93 Carico termico totale [W] 1.087,84

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 12

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #014

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 5,88 Volume netto [m³] 15,29

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D SE OP MUR_01 Existing ext. wall 0,241 6,19 -5,00 1,10 1,6410 41,02

D SE OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,10 0,3018 7,55

D SE TR FIN_08 Window 0.66x1,56 1,551 1,03 -5,00 1,10 1,7573 43,93 D OR(C) OP SOL_01 Existing roof 0,194 5,88 -5,00 1,00 1,1407 28,52 D SE PT PT_1 Window Thermal bridge 0,035 6,40 -5,00 1,10 0,2464 6,16 D SE PT PT_2 thermal bridge wall-roof 0,046 2,50 -5,00 1,10 0,1265 3,16

D NE PT PT_5 Thermal bridge - existing column on the wall 0,072 6,56 -5,00 1,20 0,5668 14,17

U OP MUR_06 Internal fire resistant wall (insulated both side) 0,258 5,18 10,00 1,00 0,5346 13,36

Dispersioni per trasmissione [W] 157,88 Dispersioni per ventilazione [W] 42,11 Potenza di ripresa [W] 135,24 Carico termico totale [W] 335,23

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 13

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #015

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 5,90 Volume netto [m³] 15,34

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D OR(C) OP SOL_01 Existing roof 0,194 5,90 -5,00 1,00 1,1446 28,62

U OP MUR_03 Internal fire resistant wall (insulated) 0,282 7,11 10,00 1,00 0,8020 20,05

Dispersioni per trasmissione [W] 48,67 Dispersioni per ventilazione [W] 42,25 Potenza di ripresa [W] 135,70 Carico termico totale [W] 226,61

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 14

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #016

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 11,23 Volume netto [m³] 29,20

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D OR(C) OP SOL_01 Existing roof 0,194 11,23 -5,00 1,00 2,1786 54,47

U OP MUR_06 Internal fire resistant wall (insulated both side) 0,258 3,45 10,00 1,00 0,3560 8,90

Dispersioni per trasmissione [W] 63,37 Dispersioni per ventilazione [W] 80,42 Potenza di ripresa [W] 258,29 Carico termico totale [W] 402,07

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 15

Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #017

Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 39,21 Volume netto [m³] 101,95

Amb.

Conf. Esp. Tipo Codice Descrizione U [W/m²K]

[W/mK] Sup. [m²]

Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]

D NO OP MUR_01 Existing ext. wall 0,241 19,17 -5,00 1,15 5,3130 132,82

D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89

D NO TR FIN_01 Window 1.93x1.56 1,613 6,02 -5,00 1,15 11,1668 279,17 D OR(C) OP SOL_01 Existing roof 0,194 39,21 -5,00 1,00 7,6067 190,17 D NO PT PT_1 Window Thermal bridge 0,035 13,96 -5,00 1,15 0,5619 14,05 D NO PT PT_2 thermal bridge wall-roof 0,046 7,98 -5,00 1,15 0,4221 10,55

D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79

Dispersioni per trasmissione [W] 641,44 Dispersioni per ventilazione [W] 280,77 Potenza di ripresa [W] 901,83 Carico termico totale [W] 1.824,04

16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 16