ANNEX_A-D_-_MECHANICAL_Part1.pdf
PDF 2 MB Posted
- Attached to
- Multiple Award Construction Contract (MACC) Italy Federal contract opportunity
- Solicitation number
- FA568219RA001
About this file
This notice is a draft pre-solicitation for a Multiple Award Construction Contract to provide design-build construction services in Italy. The contract will have a one year base period and four option years, with a minimum guarantee of $2,500 and a maximum total value of $96 million across all awards.
Work will primarily take place at Aviano Air Base and include grading, utilities, painting, roofing, building renovation, new construction, electrical, HVAC, refrigeration, fire suppression, fuel, power, communications, asbestos abatement and other site work. The contract will have indefinite delivery indefinite quantity task orders between $2,500 and $7 million.
Interested parties should submit any comments on the draft sections or attachments by April 19. The solicitation is expected to be released on federalbusinessopportunities.gov in May 2019. The North American Industry Classification code is 236220. Responses to this notice will be published with any revisions to the acquisition strategy.
ANNEX A-D MECHANICAL PART 1
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENOVATE/EXPAND FAC. 939 ASHE 18-1025
FINAL (100% design) DESIGN ANALYSIS
ANNEX A-Bs-Cs-Ds
MECHANICAL CALCULATION
# ANNEX
A Mechanical Works: Energy Calculation and building performance index
B Mechanical Works: Room Ventilation and Heating and Cooling Load
B1 Mechanical Works: Ducts Pressure Loss Calculation
C Mechanical Works: Domestic Water – Fixtures Count
C1 Mechanical Works: Domestic Hot Water Storage Capacity
C1A Mechanical Works: Domestic Hot Water Storage Capacity (NavFac design Manual)
C2 Mechanical Works: Domestic Cold-Water System
C3 Mechanical Works: Domestic Hot Water System
C4 Mechanical Works: Domestic Hot Water Return
C5 Mechanical Works: Water Hammer Calculation
D1 Mechanical Works: Heating System Calculation – Heat Pump Circuit
D2 Mechanical Works: Heating System Calculation – Secondary Circuit
D3 Mechanical Works: Heating System Calculation – Boiler Circuit
D4 Mechanical Works: Cooling System Calculation – Heat Pump Circuit
D5 Mechanical Works: Cooling System Calculation – Secondary Circuit
D6 Mechanical Works: Boiler Room Expansion Tanks Calculation
D7 Mechanical Works: Natural Gas Line Pressure Drop Calculation
D8 Mechanical Works: Boiler chimney Calculation
RENOVATE/EXPAND FAC. 939 ASHE 18-1025
DESIGN ANALYSIS FINAL (100% design)
THIS PAGE LEFT INTENTIONNALLY BLANK
ANNEX A
ENERGY CALCULATION AND BUILDING PERFORMANCE INDEX
15/02/2019 09:21:19 AERMEC MC Impianti 11300 Pagina 1
Indicatori di prestazione energetica di fabbricato Bldg #939
Dati generali Ambito di intervento Ristrutturazione importante di primo livello
Procedura Nazionale - D.Lgs. 19 agosto 2005, n. 192, e successive modificazioni.
Zona climatica E Gradi giorno 2.417 Volume lordo m³ 3.669,00
Riscaldamento Edificio di progetto Edificio di riferimento Durata della stagione (UNI/TS 11300-1:2014) 01/10 - 26/04 30/09 - 27/04 Durata della stagione (D.P.R. 412/1993) 15/10 - 15/04 15/10 - 15/04 Superficie disperdente m² 2.355,22 Superficie utile m² 743,86 Rapporto S/V 1/m 0,6419 Rapporto Superficie trasparente / Superficie utile 0,073 Fabbisogno di energia termica per riscaldamento kWh 53.775,004 60.146,242 EPH,nd kWh/(m²·a) 72,292 80,857 EPH,nd,limite (2019/21) kWh/(m²·a) 71,521 Qualità involucro Media Fabbisogno di energia primaria per riscaldamento kWh 44.090,508 50.224,633 Superficie calpestabile del volume riscaldato m² 743,860 EPH,nren kWh/(m²·a) 59,273 67,519 EPH,ren kWh/(m²·a) 60,259 75,474 EPH,tot kWh/(m²·a) 119,531 142,992 Rendimento del sottosistema di emissione, ηe 0,9428 Rendimento del sottosistema di regolazione, ηrg 0,9951 Rendimento del sottosistema di distribuzione, ηd 0,9152 Efficienza dei sottosistemi di utilizzazione, ηu 0,810 Efficienza media stagionale impianto riscaldamento ηh 1,4561 1,3196 Verifica efficienza media stagionale Positiva Copertura FER % 50,4125
Raffrescamento Edificio di progetto Edificio di riferimento Durata della stagione (UNI/TS 11300-1:2014) 20/05 - 06/09 19/05 - 06/09 Fabbisogno di energia termica per raffrescamento kWh 9.688,600 9.749,620 Superficie utile m² 743,86 EPC,nd kWh/(m²·a) 13,025 13,107 Verifica Positiva Asol,est/ Asup,utile kWh/m² 0,0193 YIE W/m²K 0,0200 Qualità involucro Alta Fabbisogno di energia primaria per raffrescamento kWh 28.170,223 34.450,273 Superficie calpestabile del volume raffrescato m² 743,860 EPC,nren kWh/(m²·a) 37,870 46,313 EPC,ren kWh/(m²·a) 13,093 14,208 EPC,tot kWh/(m²·a) 50,963 60,520 Efficienza media stagionale impianto raffrescamento ηc 0,1824 0,1593 Verifica efficienza media stagionale Positiva Copertura FER % 25,6912
Acqua calda sanitaria Edificio di progetto Edificio di riferimento Superficie utile m² 743,86 Fabbisogno di energia termica per acs kWh 3.889,369 3.889,369 Fabbisogno di energia primaria per acs kWh 2.265,067 3.887,621 EPW,nren kWh/(m²·a) 3,045 5,226 EPW,ren kWh/(m²·a) 5,808 6,049 EPW,tot kWh/(m²·a) 8,854 11,275
15/02/2019 09:21:19 AERMEC MC Impianti 11300 Pagina 2
Efficienza media stagionale impianto acs ηw 1,2994 0,7696 Verifica efficienza media stagionale Positiva Copertura FER % 65,6067
Ventilazione Edificio di progetto Edificio di riferimento Fabbisogno di energia termica per ventilazione kWh 46.572,000 44.437,047 Superficie utile m² 743,86 EPV,nren kWh/(m²·a) 62,609 59,738 EPV,ren kWh/(m²·a) 20,668 17,915 EPV,tot kWh/(m²·a) 83,276 77,654
Globale Edificio di progetto Edificio di riferimento EPgl,nren kWh/(m²·a) 162,796 178,796 EPgl,nren,rif,standard kWh/(m²·a) 181,775 Verifica Positiva Classe energetica A1 EPgl,ren kWh/(m²·a) 99,828 113,645 EPgl,tot kWh/(m²·a) 262,625 292,442 Coefficiente medio globale di scambio termico, H’T 0,29 0,55 Verifica H’T Positiva Asol,est/Asup,utile 0,0193 0,0400 Verifica Asol,est/Asup,utile Positiva Emissioni di CO2 KgCO2/(m²·a) 41,146 Copertura FER % 38,0117
Consumi Fabbisogno di energia elettrica da rete per ausiliari riscaldamento kWhe 1.657,780
Fabbisogno di energia elettrica da rete per ausiliari raffrescamento kWhe 762,554
Fabbisogno di energia elettrica da rete per ausiliari acs kWhe 0,000 Fabbisogno di energia elettrica da rete per ausiliari ventilazione kWhe 23.883,076
Riscaldamento Energia elettrica da rete kWh 19.574,365 Raffrescamento Energia elettrica da rete kWh 13.683,713 Acqua calda sanitaria Energia elettrica da rete kWh 1.161,572
Dati climatici mensili
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
Temperatura media giornaliera dell'aria esterna [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78
Irradiazione solare diffusa [W/m2] 24,31 37,04 53,24 76,39 99,54 107,64 104,17 84,49 64,81 43,98 25,46 21,99
Irradiazione solare diretta [W/m2] 32,41 52,08 79,86 91,44 137,73 159,72 152,78 137,73 109,95 45,14 26,62 26,62
Irradiazione solare su superficie orizzontale [W/m2] 56,71 89,12 133,10 167,82 237,27 267,36 256,94 222,22 174,77 89,12 52,08 48,61
Irradiazione solare su superficie verticale, S [W/m2] 116,46 131,69 133,97 111,05 120,95 121,05 122,36 131,08 150,59 107,36 90,49 107,57
Irradiazione solare su superficie verticale, SE [W/m2] 89,78 108,97 125,76 121,79 146,18 151,71 151,32 152,36 151,39 93,16 71,63 81,93
Irradiazione solare su superficie verticale, E [W/m2] 48,63 71,09 98,90 115,02 156,46 173,01 167,79 151,57 127,26 67,13 42,38 42,23
Irradiazione solare su superficie verticale, NE [W/m2] 20,08 35,29 59,31 85,07 127,43 147,69 140,03 113,52 80,44 39,14 20,37 17,12
Irradiazione solare su superficie verticale, N [W/m2] 17,88 27,49 39,99 59,11 94,44 115,35 106,40 76,15 50,27 30,96 18,00 15,91
Irradiazione solare su superficie verticale, NO [W/m2] 20,08 35,29 59,31 85,07 127,43 147,69 140,03 113,52 80,44 39,14 20,37 17,12
Irradiazione solare su superficie verticale, O [W/m2] 48,63 71,09 98,90 115,02 156,46 173,01 167,79 151,57 127,26 67,13 42,38 42,23
Irradiazione solare su superficie verticale, SO [W/m2] 89,78 108,97 125,76 121,79 146,18 151,71 151,32 152,36 151,39 93,16 71,63 81,93
Pressione parziale del vapore d'acqua nell'aria esterna [Pa] 553 630 774 925 1378 1645 1888 1930 1480 1200 932 651
Umidità relativa dell'aria esterna [%] 78,50 78,20 73,29 65,65 67,32 64,27 68,18 75,41 74,15 81,87 87,07 81,36
FABBISOGNO DI ENERGIA TERMICA UTILE
Zona: Existing bldg #939
Fabbisogno di riscaldamento
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
Flusso termico per trasmissione con l'ambiente esterno
Qd [MJ] 10865,48 8779,50 7369,24 5229,97 1280,95 -860,45 -1672,77 -889,13 1472,97 5146,65 7014,85 9780,44
Flusso termico per trasmissione con il terreno
Qg [MJ] 8531,43 6893,54 5786,22 4106,50 1005,79 -675,61 -1313,44 -698,13 1156,56 4041,08 5507,96 7679,47
Flusso termico per trasmissione con ambienti non climatizzati
Qu [MJ] 657,21 531,04 445,74 316,34 77,48 -52,05 -101,18 -53,78 89,09 311,30 424,30 591,58
Flusso termico per trasmissione con zone climatizzate a temperatura diversa
Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico per ventilazione Qve [MJ] 17524,88 14160,41 11885,80 8435,39 2066,04 -1387,81 -2698,00 -1434,08 2375,75 8301,01 11314,21 15774,82
Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)
Qr,op [MJ] 637,62 576,27 675,94 730,39 717,78 750,10 739,23 640,67 607,72 546,24 506,07 607,51
Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)
Qr,w [MJ] 21,13 19,10 22,40 24,21 23,79 24,86 24,50 21,24 20,14 18,11 16,77 20,14
Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)
Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico prodotto da sorgenti di calore interne
Qint [MJ] 7711,06 6964,83 7711,06 7462,32 7711,06 7462,32 7711,06 7711,06 7462,32 7711,06 7462,32 7711,06
Flusso termico prodotto da sorgenti di calore interne (da U)
Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Apporti solari su componenti opachi Qsol,op [MJ] 446,20 620,87 1015,90 1168,76 1758,73 1905,66 1899,03 1663,52 1294,92 606,59 390,00 386,69
Apporti solari su componenti trasparenti Qsol,w [MJ] 1161,35 1445,99 2143,31 2316,93 3318,28 3523,03 3516,11 3179,86 2620,23 1379,57 969,57 1042,04
Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Rapporto apporti/dispersioni γ 0,23 0,28 0,39 0,55 3,23 -2,68 -1,62 -2,67 2,28 0,51 0,35 0,26
Fattore di utilizzazione degli apporti termici ηgn 1,00 1,00 1,00 0,98 0,31 -0,37 -0,62 -0,37 0,44 0,99 1,00 1,00
Fabbisogno di energia termica utile Qnd [MJ] 28921,80 21934,90 15356,47 8087,45 5,02 0,00 0,00 0,00 31,33 8795,35 15981,68 25318,54
Fabbisogno di raffrescamento
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
Flusso termico per trasmissione con l'ambiente esterno
Qd [MJ] 13879,49 11501,83 10383,24 8146,75 4294,96 2056,33 1341,23 2124,87 4389,75 8160,66 9931,63 12794,45
Flusso termico per trasmissione con il terreno
Qg [MJ] 10897,98 9031,08 8152,78 6396,71 3372,34 1614,60 1053,12 1668,42 3446,77 6407,64 7798,18 10046,02
Flusso termico per trasmissione con ambienti non climatizzati
Qu [MJ] 839,52 695,70 628,04 492,77 259,79 124,38 81,13 128,53 265,52 493,61 600,73 773,89
Flusso termico per trasmissione con zone climatizzate a temperatura diversa
Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico per ventilazione Qve [MJ] 15003,98 12433,69 11224,48 8806,78 4642,93 2222,93 1449,90 2297,03 4745,40 8821,82 10736,27 13831,03
Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)
Qr,op [MJ] 637,62 638,01 675,94 754,74 717,78 775,11 739,23 640,67 627,98 546,24 522,93 607,51
Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)
Qr,w [MJ] 21,13 21,15 22,40 25,02 23,79 25,69 24,50 21,24 20,81 18,11 17,33 20,14
Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)
Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico prodotto da sorgenti di calore interne
Qint [MJ] 7711,06 6964,83 7711,06 7462,32 7711,06 7462,32 7711,06 7711,06 7462,32 7711,06 7462,32 7711,06
Flusso termico prodotto da sorgenti di calore interne (da U)
Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Apporti solari su componenti opachi Qsol,op [MJ] 446,20 620,87 1015,90 1223,59 1758,73 1905,66 1899,03 1663,52 1294,92 674,95 390,00 386,69
Apporti solari su componenti trasparenti Qsol,w [MJ] 1161,35 1445,99 2143,31 2405,30 3318,28 3523,03 3516,11 3179,86 2620,23 1509,75 969,57 1042,04
Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Tempo di attivazione t [gg] 0 0 0 0 22 30 31 31 17 0 0 0
Totale guadagni Qgn [MJ] 0,00 0,00 0,00 0,00 7827,28 10985,35 11227,17 10890,92 5713,44 0,00 0,00 0,00
Totale dispersioni Qht [MJ] 0,00 0,00 0,00 0,00 8198,79 4913,37 2790,07 5217,23 6914,08 0,00 0,00 0,00
Rapporto apporti/dispersioni γ 0,00 0,00 0,00 0,00 1,08 1,32 2,24 1,25 1,47 0,00 0,00 0,00
Fattore di utilizzazione delle dispersioni ηls 0,00 0,00 0,00 0,00 0,90 1,00 1,00 1,00 0,81 0,00 0,00 0,00
Fabbisogno di energia termica utile Qnd [MJ] 0,00 0,00 0,00 0,00 474,60 6072,47 8437,09 5674,21 122,72 0,00 0,00 0,00
Fabbisogno per acqua calda sanitaria
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Tempo di attivazione t [gg] 31 28 31 30 31 30 31 31 30 31 30 31 365
Volume di acqua richiesto Vw [litri] 2935 2651 2935 2840 2935 2840 2935 2935 2840 2935 2840 2935 34558
Fabbisogno di energia termica Qw [kWh] 93 84 93 90 93 90 93 93 90 93 90 93 1100
FABBISOGNO DI ENERGIA TERMICA UTILE
Zona: New building #939
Fabbisogno di riscaldamento
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
Flusso termico per trasmissione con l'ambiente esterno
Qd [MJ] 8221,05 6642,75 5575,72 3957,10 969,19 -651,03 -1265,65 -672,74 1114,48 3894,06 5307,58 7400,08
Flusso termico per trasmissione con il terreno
Qg [MJ] 3923,76 3170,47 2661,19 1888,66 462,58 -310,73 -604,07 -321,08 531,92 1858,57 2533,21 3531,93
Flusso termico per trasmissione con ambienti non climatizzati
Qu [MJ] 382,36 308,96 259,33 184,05 45,08 -30,28 -58,87 -31,29 51,84 181,11 246,86 344,18
Flusso termico per trasmissione con zone climatizzate a temperatura diversa
Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico per ventilazione Qve [MJ] 12664,76 10233,35 8589,55 6096,03 1493,07 -1002,94 -1949,78 -1036,37 1716,89 5998,92 8176,48 11400,04
Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)
Qr,op [MJ] 466,78 421,87 494,84 534,70 525,46 549,13 541,17 469,02 444,90 399,89 370,48 444,74
Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)
Qr,w [MJ] 16,15 14,60 17,12 18,50 18,18 19,00 18,72 16,23 15,39 13,84 12,82 15,39
Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)
Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico prodotto da sorgenti di calore interne
Qint [MJ] 5002,07 4518,00 5002,07 4840,72 5002,07 4840,72 5002,07 5002,07 4840,72 5002,07 4840,72 5002,07
Flusso termico prodotto da sorgenti di calore interne (da U)
Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Apporti solari su componenti opachi Qsol,op [MJ] 383,20 503,16 779,85 872,05 1294,25 1397,14 1393,65 1231,22 972,82 484,36 326,09 336,19
Apporti solari su componenti trasparenti Qsol,w [MJ] 1054,42 1253,01 1700,01 1728,86 2308,58 2396,76 2415,74 2296,09 2026,76 1137,52 847,77 952,21
Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Rapporto apporti/dispersioni γ 0,24 0,28 0,40 0,56 3,29 -2,56 -1,57 -2,60 2,37 0,52 0,35 0,26
Fattore di utilizzazione degli apporti termici ηgn 1,00 1,00 1,00 0,99 0,30 -0,39 -0,64 -0,38 0,42 0,99 1,00 1,00
Fabbisogno di energia termica utile Qnd [MJ] 19236,38 14520,13 10132,58 5326,76 1,27 0,07 0,00 0,15 10,02 5781,38 10639,68 16847,07
Fabbisogno di raffrescamento
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
Flusso termico per trasmissione con l'ambiente esterno
Qd [MJ] 10501,50 8702,52 7856,17 6164,00 3249,65 1555,86 1014,80 1607,72 3321,38 6174,52 7514,47 9680,54
Flusso termico per trasmissione con il terreno
Qg [MJ] 5012,18 4153,56 3749,61 2941,97 1551,00 742,58 484,35 767,34 1585,23 2946,99 3586,52 4620,35
Flusso termico per trasmissione con ambienti non climatizzati
Qu [MJ] 488,43 404,76 365,39 286,69 151,14 72,36 47,20 74,78 154,48 287,18 349,50 450,24
Flusso termico per trasmissione con zone climatizzate a temperatura diversa
Qa [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico per ventilazione Qve [MJ] 10842,91 8985,44 8111,58 6364,39 3355,30 1606,44 1047,80 1659,99 3429,35 6375,26 7758,77 9995,26
Extra flusso termico per radiazione infrarossa verso la volta celeste (opachi)
Qr,op [MJ] 466,78 467,07 494,84 552,52 525,46 567,44 541,17 469,02 459,72 399,89 382,83 444,74
Extra flusso termico per radiazione infrarossa verso la volta celeste (trasparenti)
Qr,w [MJ] 16,15 16,16 17,12 19,12 18,18 19,63 18,72 16,23 15,91 13,84 13,25 15,39
Extra flusso termico per radiazione infrarossa verso la volta celeste (da U)
Qr,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Flusso termico prodotto da sorgenti di calore interne
Qint [MJ] 5002,07 4518,00 5002,07 4840,72 5002,07 4840,72 5002,07 5002,07 4840,72 5002,07 4840,72 5002,07
Flusso termico prodotto da sorgenti di calore interne (da U)
Qint,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Apporti solari su componenti opachi Qsol,op [MJ] 383,20 503,16 779,85 908,69 1294,25 1397,14 1393,65 1231,22 972,82 535,26 326,09 336,19
Apporti solari su componenti trasparenti Qsol,w [MJ] 1054,42 1253,01 1700,01 1759,10 2308,58 2396,76 2415,74 2296,09 2026,76 1226,35 847,77 952,21
Apporti solari da U Qsol,u [MJ] 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00 0,00
Tempo di attivazione t [gg] 0 0 0 0 22 30 31 31 18 0 0 0
Totale guadagni Qgn [MJ] 0,00 0,00 0,00 0,00 5188,21 7237,47 7417,81 7298,16 4120,49 0,00 0,00 0,00
Totale dispersioni Qht [MJ] 0,00 0,00 0,00 0,00 5362,67 3167,17 1760,39 3363,85 4795,95 0,00 0,00 0,00
Rapporto apporti/dispersioni γ 0,00 0,00 0,00 0,00 1,22 1,23 2,10 1,18 1,80 0,00 0,00 0,00
Fattore di utilizzazione delle dispersioni ηls 0,00 0,00 0,00 0,00 0,91 1,00 1,00 1,00 0,84 0,00 0,00 0,00
Fabbisogno di energia termica utile Qnd [MJ] 0,00 0,00 0,00 0,00 325,87 4070,30 5657,42 3934,65 109,63 0,00 0,00 0,00
Fabbisogno per acqua calda sanitaria
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Tempo di attivazione t [gg] 31 28 31 30 31 30 31 31 30 31 30 31 365
Volume di acqua richiesto Vw [litri] 7440 6720 7440 7200 7440 7200 7440 7440 7200 7440 7200 7440 87600
Fabbisogno di energia termica Qw [kWh] 237 214 237 229 237 229 237 237 229 237 229 237 2789
FABBISOGNO DI IMPIANTO: ACQUA CALDA SANITARIA
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Fabbisogno di energia termica QW [kWh] 93 84 93 90 93 90 93 93 90 93 90 93 1100
Rendimento di erogazione ηer - - - - - - - - - - - -
Perdite di erogazione Ql,er [kWh] - - - - - - - - - - - - -
Rendimento di distribuzione ηd - - - - - - - - - - - -
Perdite di distribuzione Ql,d [kWh] - - - - - - - - - - - - -
Perdite recuperate da distribuzione Qlrh,d [kWh] - - - - - - - - - - - - -
Fabbisogno di energia elettrica per ausiliari distribuzione
Eaux,d [kWh] - - - - - - - - - - - - -
Energia termica recuperata da ausiliari distribuzione
Qaux,rh,d [kWh] - - - - - - - - - - - - -
Rendimento del serbatoio di accumulo ηs - - - - - - - - - - - -
Perdite del serbatoio di accumulo Ql,s [kWh] - - - - - - - - - - - - -
Perdite recuperate da serbatoio di accumulo Qlrh,s [kWh] - - - - - - - - - - - - -
Perdite per distribuzione primaria Ql,dp [kWh] - - - - - - - - - - - - -
Perdite recuperate da distribuzione primaria Qlrh,dp [kWh] - - - - - - - - - - - - -
Fabbisogno di energia elettrica per ausiliari distribuzione primaria
Qaux,d [kWh] - - - - - - - - - - - - -
Energia termica recuperata da ausiliari distribuzione primaria
Qaux,rh,d [kWh] - - - - - - - - - - - - -
Fabbisogno di energia termica in entrata [kWh] 93 84 93 90 93 90 93 93 90 93 90 93 1100
Centralizzato
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Fabbisogno di energia termica QW [kWh] 330 298 330 320 330 320 330 330 320 330 320 330 3889
Rendimento di erogazione ηer 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00
Perdite di erogazione Ql,er [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Rendimento di distribuzione ηd 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93 0,93
Perdite di distribuzione Ql,d [kWh] 26 24 26 26 26 26 26 26 26 26 26 26 311
Perdite recuperate da distribuzione Qlrh,d [kWh] 24 21 24 12 0 0 0 0 0 13 23 24 140
Fabbisogno di energia elettrica per ausiliari distribuzione
Eaux,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia termica recuperata da ausiliari distribuzione
Qaux,rh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Rendimento del serbatoio di accumulo ηs 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85
Perdite del serbatoio di accumulo Ql,s [kWh] 62 56 62 60 62 60 62 62 60 62 60 62 736
Perdite recuperate da serbatoio di accumulo Qlrh,s [kWh] 50 45 50 24 0 0 0 0 0 27 48 50 295
Perdite per distribuzione primaria Ql,dp [kWh] - - - - - - - - - - - - -
Perdite recuperate da distribuzione primaria Qlrh,dp [kWh] - - - - - - - - - - - - -
Fabbisogno di energia elettrica per ausiliari distribuzione primaria
Qaux,d [kWh] - - - - - - - - - - - - -
Energia termica recuperata da ausiliari distribuzione primaria
Qaux,rh,d [kWh] - - - - - - - - - - - - -
Fabbisogno di energia termica in entrata [kWh] 419 379 419 406 419 406 419 419 406 419 406 419 4936
Generatore: PDC
Energia termica richiesta al sottosistema Qgn,out [kWh] 419 379 419 406 419 406 419 419 406 419 406 419 4936
Energia termica fornita dal sottosistema Q'gn,out [kWh] 419 379 419 406 419 406 419 419 406 419 406 419 4936
Fabbisogno di energia elettrica degli ausiliari
Egn,aux [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia in ingresso Qgn,in [kWh] 151 131 130 112 96 81 79 84 95 114 124 146 1344
Fabbisogno di energia elettrica degli ausiliari circuito generatore
Eaux,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia primaria non rinnovabile Qp,nren [kWh] 295 255 253 218 188 158 154 164 185 223 242 285 2620
Energia primaria rinnovabile Qp,ren [kWh] 268 248 289 294 323 325 340 335 311 305 282 273 3593
Energia primaria totale Qp,tot [kWh] 563 503 543 512 511 483 494 499 496 528 524 558 6213
Generatore: Condensing Boiler
Energia termica richiesta al sottosistema Qgn,out [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia termica fornita dal sottosistema Q'gn,out [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Rendimento termico ηgn 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00
Perdite totali Q'gn,l,t [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia elettrica degli ausiliari
Egn,aux [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia per la combustione Qgn,in [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia primaria non rinnovabile Qp,nren [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia primaria rinnovabile Qp,ren [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia primaria totale Qp,tot [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
FABBISOGNO DI IMPIANTO: RISCALDAMENTO
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Fabbisogno di energia termica QH [kWh] - - - - - - - - - - - - -
Perdite recuperate dal sistema di acqua calda sanitaria
Qlrh,W [kWh] - - - - - - - - - - - - -
Fabbisogno ideale di energia termica utile Q'H [kWh] 3145 2141 943 -58 0 0 0 0 0 64 1276 2630 10141
Rendimento di emissione ηe 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00
Perdite di emissione Ql,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia elettrica per ausiliari emissione
Eaux,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia termica recuperata da ausiliari emissione
Qaux,rh,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Rendimento di regolazione ηrg 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00
Perdite di regolazione Ql,rg [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Rendimento di distribuzione ηd 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00
Perdite di distribuzione Ql,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite recuperate da distribuzione Qlrh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia elettrica per ausiliari distribuzione
Eaux,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia termica recuperata da ausiliari distribuzione
Qaux,rh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di accumulo Ql,s [kWh] 62 56 62 30 0 0 0 0 0 34 60 62 369
Perdite recuperate da accumulo Qlrh,s [kWh] 50 45 50 12 0 0 0 0 0 15 48 50 271
Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite recuperate da circuito primario Qlrh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia elettrica per ausiliari circuito primario
Eaux,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia termica recuperata da ausiliari distribuzione
Qaux,rh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia termica in entrata [kWh] 3157 2152 956 0 0 0 0 0 0 83 1288 2643 10279
Fabbisogno di energia termica QH [kWh] - -
Perdite recuperate dal sistema di acqua calda sanitaria
Qlrh,W [kWh] - -
Fabbisogno ideale di energia termica utile Q'H [kWh] 4930 3295 1331 0 0 0 0 0 0 83 1921 4103 15664
Rendimento di emissione ηe 0,96 0,96 0,96 0,00 0,00 0,00 0,00 0,00 0,00 0,96 0,96 0,96
Perdite di emissione Ql,e [kWh] 205 137 55 0 0 0 0 0 0 3 80 171 653
Fabbisogno di energia elettrica per ausiliari emissione
Eaux,e [kWh] 99 66 27 0 0 0 0 0 0 2 38 82 313
Energia termica recuperata da ausiliari emissione
Qaux,rh,e [kWh] 99 66 27 0 0 0 0 0 0 2 38 82 313
Rendimento di regolazione ηrg 1,00 1,00 1,00 0,00 0,00 0,00 0,00 0,00 0,00 1,00 1,00 1,00
Perdite di regolazione Ql,rg [kWh] 25 17 7 0 0 0 0 0 0 0 10 21 80
Rendimento di distribuzione ηd 0,99 0,99 0,99 0,00 0,00 0,00 0,00 0,00 0,00 0,99 0,99 0,99
Perdite di distribuzione Ql,d [kWh] 39 26 11 0 0 0 0 0 0 1 15 33 125
Perdite recuperate da distribuzione Qlrh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia elettrica per ausiliari distribuzione
Eaux,d [kWh] 205 137 55 0 0 0 0 0 0 3 80 170 650
Energia termica recuperata da ausiliari distribuzione
Qaux,rh,d [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di accumulo Ql,s [kWh] 62 56 62 30 0 0 0 0 0 34 60 62 369
Perdite recuperate da accumulo Qlrh,s [kWh] 50 45 50 12 0 0 0 0 0 15 48 50 271
Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite recuperate da circuito primario Qlrh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia elettrica per ausiliari circuito primario
Eaux,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia termica recuperata da ausiliari distribuzione
Qaux,rh,dp [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia termica in entrata [kWh] 5114 3421 1390 18 0 0 0 0 0 105 2000 4258 16307
Generatore: PDC
Energia termica richiesta al sottosistema Qgn,out [kWh] 13780 10423 7268 1862 0 0 0 0 0 2037 7595 12059 55024
Energia termica fornita dal sottosistema Q'gn,out [kWh] 10196 9210 7268 1862 0 0 0 0 0 2037 7595 11211 49378
Fabbisogno di energia elettrica degli ausiliari
Egn,aux [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia in ingresso Qgn,in [kWh] 3716 3229 2308 546 0 0 0 0 0 583 2348 3956 16686
Fabbisogno di energia elettrica degli ausiliari circuito generatore
Eaux,dp [kWh] 113 120 147 70 0 0 0 0 0 80 142 138 809
Energia primaria non rinnovabile Qp,nren [kWh] 7246 6296 4501 1065 0 0 0 0 0 1137 4578 7714 32537
Energia primaria rinnovabile Qp,ren [kWh] 6480 5981 4960 1316 0 0 0 0 0 1454 5247 7255 32693
Energia primaria totale Qp,tot [kWh] 13726 12277 9460 2381 0 0 0 0 0 2590 9826 14969 65230
Generatore: Condensing Boiler
Energia termica richiesta al sottosistema Qgn,out [kWh] 3584 1214 0 0 0 0 0 0 0 0 0 848 5645
Energia termica fornita dal sottosistema Q'gn,out [kWh] 3584 1214 0 0 0 0 0 0 0 0 0 848 5645
Rendimento termico ηgn 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00
Perdite totali Q'gn,l,t [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Fabbisogno di energia elettrica degli ausiliari
Egn,aux [kWh] 7 2 0 0 0 0 0 0 0 0 0 2 11
Fabbisogno di energia per la combustione Qgn,in [kWh] 3584 1214 0 0 0 0 0 0 0 0 0 848 5645
Energia primaria non rinnovabile Qp,nren [kWh] 6989 2367 0 0 0 0 0 0 0 0 0 1654 11009
Energia primaria rinnovabile Qp,ren [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia primaria totale Qp,tot [kWh] 8673 2937 0 0 0 0 0 0 0 0 0 2052 13662
FABBISOGNO DI IMPIANTO: RAFFRESCAMENTO
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Fabbisogno ideale di energia termica utile QC [kWh] 0 0 0 0 1638 2304 2746 2214 1380 0 0 0 10283
Perdite di emissione Ql,e [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di regolazione Ql,rg [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di distribuzione in tubazioni acqua refrigerata
Ql,dw [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite recuperate da distribuzione acqua Qlrh,dw [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di distribuzione in canali Ql,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite recuperate da distribuzione aria Qlrh,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di accumulo Ql,s [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 -5 -12 -12 -12 -2 0 0 0 -44
Perdite recuperate da circuito primario Qlrh,cp [kWh] 0 0 0 0 -5 -12 -12 -12 -2 0 0 0 -44
Fabbisogno ideale di energia termica utile QC [kWh] 0 0 0 0 2813 3881 4609 3768 2417 0 0 0 17489
Perdite di emissione Ql,e [kWh] 0 0 0 0 57 79 94 77 49 0 0 0 357
Perdite di regolazione Ql,rg [kWh] 0 0 0 0 59 81 96 78 50 0 0 0 364
Perdite di distribuzione in tubazioni acqua refrigerata
Ql,dw [kWh] 0 0 0 0 60 82 98 80 51 0 0 0 372
Perdite recuperate da distribuzione acqua Qlrh,dw [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di distribuzione in canali Ql,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite recuperate da distribuzione aria Qlrh,da [kWh] 0 0 0 0 0 0 0 0 0 0 0 0 0
Perdite di accumulo Ql,s [kWh] 0 0 0 0 6 16 17 17 3 0 0 0 59
Perdite di circuito primario Ql,dp [kWh] 0 0 0 0 6 14 14 14 3 0 0 0 51
Perdite recuperate da circuito primario Qlrh,cp [kWh] 0 0 0 0 5 13 14 14 3 0 0 0 48
Trattamento dell'aria
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Umidità specifica x [g/kg] 3,41 3,89 4,79 5,73 8,58 10,26 11,81 12,08 9,22 7,45 5,77 4,02
Entalpia dell'aria esterna Ht [kJ/kg] 10,51 13,64 19,85 26,59 39,70 47,68 52,94 52,28 40,93 31,56 22,53 13,86
Fabbisogno specifico orario medio Qv,m,h [kJ/kg] 0,00 0,00 0,00 0,00 0,00 6,37 13,54 12,64 0,00 0,00 0,00 0,00
Fabbisogno di energia per trattamento aria Qv [kWh] 0 0 0 0 0 5376 11801 11021 0 0 0 0 28198
Generatore
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Energia termica richiesta al generatore Qgn,out [kWh] 0 0 0 0 2996 9516 16715 15043 2572 0 0 0 46842
Fattore di carico medio della macchina frigorifera
Fk 0,00 0,00 0,00 0,00 0,11 0,14 0,24 0,22 0,19 0,00 0,00 0,00
EER al fattore di carico medio 0,00 0,00 0,00 0,00 2,76 3,02 3,60 3,49 3,36 0,00 0,00 0,00
Coefficiente di prestazione ηmm 0,00 0,00 0,00 0,00 2,58 2,56 2,94 2,95 3,19 0,00 0,00 0,00
Fabbisogno di energia in ingresso Qgn,in [kWh] 0 0 0 0 1159 3724 5691 5092 806 0 0 0 16473
Energia primaria non rinnovabile Qp,nren [kWh] 0 0 0 0 2261 7261 11098 9930 1572 0 0 0 32122
Energia primaria rinnovabile Qp,ren [kWh] 0 0 0 0 545 1750 2675 2393 379 0 0 0 7742
Energia primaria totale Qp,tot [kWh] 0 0 0 0 2806 9011 13773 12324 1951 0 0 0 39864
ENERGIA PRIMARIA
Energia primaria rinnovabile
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Riscaldamento H 10244 8381 6335 1690 0 0 0 0 0 1820 6552 9802 44824
Raffrescamento C 0 0 0 0 781 2239 3275 2913 532 0 0 0 9739
Acqua calda sanitaria W 342 314 360 362 384 371 383 381 369 368 344 345 4321
Ventilazione V 1160 1082 1291 1402 1501 1317 1299 1292 1403 1307 1152 1167 15374
Illuminazione L 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia primaria non rinnovabile
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Riscaldamento H 14567 8713 4272 887 0 0 0 0 0 1109 4797 9747 44091
Raffrescamento C 0 0 0 0 1685 6168 10030 9029 1258 0 0 0 28170
Acqua calda sanitaria W 285 239 219 161 131 128 132 141 137 190 228 274 2265
Ventilazione V 4490 3930 4010 3318 3238 3630 3979 4005 3316 3952 4238 4466 46572
Illuminazione L 0 0 0 0 0 0 0 0 0 0 0 0 0
Energia primaria totale
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Riscaldamento H 24811 17093 10607 2577 0 0 0 0 0 2929 11348 19548 88915
Raffrescamento C 0 0 0 0 2466 8407 13305 11942 1790 0 0 0 37910
Acqua calda sanitaria W 627 553 579 523 515 499 515 522 505 558 572 619 6586
Ventilazione V 5651 5012 5301 4720 4738 4947 5278 5298 4719 5259 5390 5633 61946
Illuminazione L 0 0 0 0 0 0 0 0 0 0 0 0 0
Quota rinnobabile
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC Totale
Riscaldamento H % 50,41
Raffrescamento C % 25,69
Acqua calda sanitaria W % 65,61
Ventilazione V % 24,82
Illuminazione L % 0,00
ANNEX B
ROOM VENTILATION AND HEATING AND COOLING LOAD
People outdoor air rate
People outdoor air rate
People outdoor air rate
People outdoor air rate
People outdoor air rate
People outdoor air rate
People outdoor air rate M in e xh au st
M in e xh au st
M in e xh au st
M in e xh au st
M in e xh au st
Ashrae 62.1
Ashrae 62.1
Area UNI 10339
UNI EN
13779
Ashrae
62.1 UNI 10339
UNI EN
13779
Ashrae
62.1
Ashrae
62.1
Ashrae
62.1 ASS5 ASS5
m2 m m2 pers/m2
n. n. l/(s*pers) (l/s*m2) l/(s*pers) l/(s*pers) l/s l/s l/s l/s l/s*m2 l/s*unit l/s n. l/s l/s
1 entry G 8,80 3,00 26,40 0 0,0 0 0 0 0 0 0,0 0 0 0
2 office G 41,02 2,60 106,65 0,05 2,1 5 2,50 0,3 11 10 17,4 55 50 55
3 office G 25,72 2,60 66,87 0,05 1,3 3 2,50 0,3 11 10 10,9 33 30 33
4 office G 33,05 2,60 85,93 0,05 1,7 5 2,50 0,3 11 10 14,0 55 50 55
5 office G 17,53 2,60 45,58 0,05 0,9 1 2,50 0,3 11 10 7,5 11 10 11
6 AHU room G 12,63 2,60 32,84
7 office G 16,10 2,60 41,86 0,05 0,8 1 2,50 0,3 11 10 6,8 11 10 11
8 vault G 23,05 2,64 60,85 0,05 1,2 2 3,80 0,3 11 10 11,3 22 20 25 22
9 office G 14,63 2,60 38,04 0,05 0,7 1 2,50 0,3 11 10 6,2 11 10 11
10 armory G 5,51 2,64 14,55 0,05 0,3 0 0,00 0 0 0 0,0 0 0 0
11 reception G 22,14 2,60 57,56 0,3 6,6 2 2,50 0,3 11 10 23,2 22 20 22
12 boiler room G 17,88 3,00 53,64 0 0,0 0 0 0 0 0 0,0 0 0 0
13 office G 23,91 2,60 62,17 0,05 1,2 3 2,50 0,3 11 10 10,2 33 30 33
14 WC G 5,88 2,60 15,29 0 0,0 1 0 0 0 0 0,0 0 0 0 10,0 42,5 50
15 WC G 5,90 2,60 15,34 0 0,0 1 0 0 0 0 0,0 0 0 0 10,0 42,6 50
16 comm. room G 11,23 2,60 29,20 0 0,0 0 0,00 0 0 0 0,0 0 0 10 0,0 0,0
17 office G 39,21 2,60 101,95 0,05 2,0 5 2,50 0,3 11 11 16,7 55 55 55
18 conference room G 69,70 2,60 181,22 0,5 34,9 35 2,50 0,3 5,5 11 108,0 192,5 385 195 195
19 Electrical room G 4,62 2,60 12,01
20 corridor G 83,19 2,60 216,29 0,05 4,2 2 2,50 0,3 0 0 35,4 0 0 20 58
21 sprinkler room G 14,56 2,70 39,31
22 corridor G 10,24 2,40 24,58 0,05 0,5 2 2,5 0,3 0 0 4,4 0 0 0
23 corridor G 20,89 2,70 56,40 0,05 1,0 2 2,5 0,3 0 0 8,9 0 0 45
24 corridor G 21,21 2,70 57,27 0,05 1,1 2 2,5 0,3 0 0 9,0 0 0 20
25 locker room G 45,87 2,70 123,85 0 0,0 0 0,0 0 0 0 0,0 0 0 80 2,5 114,7 4,0 137,6 138
25.1 restroom and showers G 23,31 2,70 62,94 0 0,0 0 0,0 0 0 0 0 0 0 35,0 35,0 8,0 139,9 140
26 breaking area G 56,76 2,70 153,25 0,5 28,4 10 2,5 0,6 10 10 105,0 100 100 105 1,5 85,1 85
27 bedroom G 14,33 2,70 38,69 0,1 1,4 2 2,5 0,3 11 10 7,9 22 20 30
27.1 wc G 4,23 2,70 11,42 0 0,0 0 0,0 0 0 0 0 0 0 25,0 25,0 8,0 25,4 25
28 bedroom G 15,60 2,70 42,12 0,1 1,6 2 2,5 0,3 11 10 8,6 22 20 30
29 bedroom G 14,36 2,70 38,77 0,1 1,4 1 2,5 0,3 11 10 7,9 11 10 30
29.1 wc G 4,16 2,70 11,23 0 0,0 0 0,0 0 0 0 0 0 0 25,0 25,0 8,0 25,0 25
30 bedroom G 15,37 2,70 41,50 0,1 1,5 2 2,5 0,3 11 10 8,5 22 20 30
31 laundry G 8,94 2,70 24,14 0,1 0,9 2 2,5 0,6 0 0 7,6 0 0 20
32 kitchen G 14,25 2,70 38,48 0,2 2,9 4 3,8 0,6 19,4 0 0 40 1,5 21,4
34 AHU room G 14,25 2,70 38,48
35 Electrical room G 10,90 2,70 29,43 0 0 0
36 female locker room G 15,17 2,70 40,96 0 0,0 0 0,0 0 0 0 0,0 0 0 0 2,5 37,9 8,0 91,0 69
37 janitory G 1,95 2,70 5,27 0 0,0 0 0,0 0 0 0 0 0 0 5,0 9,8 10
98,3 96 454,7 677,5 840 966 354 867
In the FC heating and cooling coil calculation the contribute for the outside air is not considered
In the room #36 for the locker has been taken #4 volume ari change. For the bathroom #8 air volume change
ROOM VENTILATION AND HEATING AND COOLING LOAD
O cc u p an t d en si ty
A sh ra e
.1
P er so n p er
A sh ra e
.1
P er so n d es ig n
D es ig n
O A s u p p ly
D es ig n
E xh au st
Lo ca l c o d e
U se d es ti n at io n
Fl o o r
A re a
H ei gh t
V o lu m e
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 1
Dati Generali Progetto
Descrizione progetto Renovation/expand Fac. 939 Ambito di intervento Ristrutturazione importante di primo livello
Metodologia di calcolo Metodo di calcolo da rilievo sull’edificio Procedura di calcolo Nazionale - D.Lgs. 19 agosto 2005, n. 192, e successive modificazioni.
Edificio pubblico No Classificazione edificio E.2 - Edifici adibiti a uffici e assimilabili
Dati Climatici
Provincia Pordenone Comune Aviano
Zona climatica E Gradi giorno 2.417 Altezza sul livello del mare [m] 159 Temperatura esterna di progetto invernale [°C] -5,00 Temperatura esterna media annuale [°C] 12,60
Fattore di correzione fg1 1,45 Fattore di correzione fg2 0,30 Fattore di correzione Gw 1,00
Fattori di correzione per esposizione:
Nord 1,20 Nord – Est 1,20 Est 1,15 Sud – Est 1,10 Sud 1,00 Sud – Ovest 1,05 Ovest 1,10 Nord – Ovest 1,15
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 2
Risultati per Ambiente
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #02
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 41,02 Volume netto [m³] 106,65
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D SE OP MUR_01 Existing ext. wall 0,241 16,41 -5,00 1,10 4,3503 108,76
D SE OP MUR_01B Old column on the existing ext. wall 0,280 1,97 -5,00 1,10 0,6068 15,17
D SE OP MUR_01A New column on the existing ext. wall 0,286 3,28 -5,00 1,10 1,0319 25,80
D SE TR FIN_01 Window 1.93x1.56 1,613 6,02 -5,00 1,10 10,6813 267,03 D NE OP MUR_01 Existing ext. wall 0,241 16,52 -5,00 1,20 4,7776 119,44 D OR(C) OP SOL_01 Existing roof 0,194 41,02 -5,00 1,00 7,9579 198,95 D SE PT PT_1 Window Thermal bridge 0,035 13,96 -5,00 1,10 0,5375 13,44 D SE PT PT_2 thermal bridge wall-roof 0,046 8,44 -5,00 1,10 0,4271 10,68
D SE PT PT_5 Thermal bridge - existing column on the wall 0,072 13,12 -5,00 1,10 1,0391 25,98
D SE PT PT-6
Thermal bridge - new column on the existing wall
0,028 6,56 -5,00 1,10 0,2020 5,05
Dispersioni per trasmissione [W] 790,28 Dispersioni per ventilazione [W] 293,71 Potenza di ripresa [W] 943,46 Carico termico totale [W] 2.027,46
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 3
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #03
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 25,72 Volume netto [m³] 66,87
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D NO OP MUR_01 Existing ext. wall 0,241 10,57 -5,00 1,15 2,9295 73,24
D NO OP MUR_01B Old column on the existing ext. wall 0,280 1,97 -5,00 1,15 0,6343 15,86
D NO OP MUR_01A New column on the existing ext. wall 0,286 1,64 -5,00 1,15 0,5394 13,48
D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58 D OR(C) OP SOL_01 Existing roof 0,194 25,72 -5,00 1,00 4,9897 124,74 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 5,24 -5,00 1,15 0,2772 6,93
D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 6,56 -5,00 1,15 0,5432 13,58
U OP MUR_03 Internal fire resistant wall (insulated) 0,282 16,42 5,00 1,00 2,7783 69,46
D NO PT PT-6
Thermal bridge - new column on the existing wall
0,028 3,28 -5,00 1,15 0,1056 2,64
Dispersioni per trasmissione [W] 466,54 Dispersioni per ventilazione [W] 184,16 Potenza di ripresa [W] 591,56 Carico termico totale [W] 1.242,26
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 4
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #04
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 33,05 Volume netto [m³] 85,93
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D SE OP MUR_01 Existing ext. wall 0,241 15,30 -5,00 1,10 4,0560 101,40
D SE OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,10 0,3018 7,55
D SE TR FIN_01 Window 1.93x1.56 1,613 6,02 -5,00 1,10 10,6813 267,03 D OR(C) OP SOL_01 Existing roof 0,194 33,05 -5,00 1,00 6,4117 160,29 D SE PT PT_1 Window Thermal bridge 0,035 13,96 -5,00 1,10 0,5375 13,44 D SE PT PT_2 thermal bridge wall-roof 0,046 8,44 -5,00 1,10 0,4271 10,68
D NE PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,20 0,2834 7,08
U OP MUR_03 Internal fire resistant wall (insulated) 0,282 13,43 10,00 1,00 1,5149 37,87
Dispersioni per trasmissione [W] 605,34 Dispersioni per ventilazione [W] 236,65 Potenza di ripresa [W] 760,15 Carico termico totale [W] 1.602,14
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 5
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #05
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 17,53 Volume netto [m³] 45,58
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D NO OP MUR_01 Existing ext. wall 0,241 7,72 -5,00 1,15 2,1396 53,49
D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89
D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58 D OR(C) OP SOL_01 Existing roof 0,194 17,53 -5,00 1,00 3,4008 85,02 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 3,57 -5,00 1,15 0,1889 4,72
D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79
Dispersioni per trasmissione [W] 304,52 Dispersioni per ventilazione [W] 125,53 Potenza di ripresa [W] 403,19 Carico termico totale [W] 833,24
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 6
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #07
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 16,10 Volume netto [m³] 41,86
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D NO OP MUR_01 Existing ext. wall 0,241 7,08 -5,00 1,15 1,9622 49,06
D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89
D NO TR FIN_02 Window 0.87x1.56 1,650 2,70 -5,00 1,15 5,1232 128,08 D OR(C) OP SOL_01 Existing roof 0,194 16,10 -5,00 1,00 3,1234 78,09 D NO PT PT_1 Window Thermal bridge 0,035 9,72 -5,00 1,15 0,3912 9,78 D NO PT PT_2 thermal bridge wall-roof 0,046 3,28 -5,00 1,15 0,1735 4,34
D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79
Dispersioni per trasmissione [W] 284,02 Dispersioni per ventilazione [W] 115,28 Potenza di ripresa [W] 370,30 Carico termico totale [W] 769,60
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 7
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #08
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 23,05 Volume netto [m³] 60,85
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
U OP MUR_03 Internal fire resistant wall (insulated) 0,282 10,74 10,00 1,00 1,2115 30,29
D SE OP MUR_04 Concrete ext. wall vault 0,267 18,64 -5,00 1,10 5,4746 136,86
D SE OP MUR_01B Old column on the existing ext. wall 0,280 1,71 -5,00 1,10 0,5267 13,17
D OR(C) OP SOL_01 Existing roof 0,194 23,05 -5,00 1,00 4,4717 111,79
U OP MUR_05 Vault concrete wall 44cm thickness 1,200 8,09 10,00 1,00 3,8832 97,08
D SE PT PT_4 roof ridge Thermal bridge 0,003 7,14 -5,00 1,10 0,0236 0,59
D SE PT PT_5 Thermal bridge - existing column on the wall 0,072 6,56 -5,00 1,10 0,5196 12,99
Dispersioni per trasmissione [W] 402,77 Dispersioni per ventilazione [W] 167,58 Potenza di ripresa [W] 530,15 Carico termico totale [W] 1.100,50
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 8
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #09
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 14,63 Volume netto [m³] 38,04
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D NO OP MUR_01 Existing ext. wall 0,241 6,76 -5,00 1,15 1,8735 46,84 D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58
D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89
D OR(C) OP SOL_01 Existing roof 0,194 14,63 -5,00 1,00 2,8382 70,96 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 2,98 -5,00 1,15 0,1576 3,94
D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79
Dispersioni per trasmissione [W] 283,02 Dispersioni per ventilazione [W] 104,76 Potenza di ripresa [W] 336,49 Carico termico totale [W] 724,27
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 9
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #010
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 5,51 Volume netto [m³] 14,55
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D OR(C) OP SOL_01 Existing roof 0,194 5,51 -5,00 1,00 1,0689 26,72
U OP MUR_05 Vault concrete wall 44cm thickness 1,200 4,22 10,00 1,00 2,0256 50,64
Dispersioni per trasmissione [W] 77,36 Dispersioni per ventilazione [W] 40,07 Potenza di ripresa [W] 126,73 Carico termico totale [W] 244,16
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 10
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #011
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 22,14 Volume netto [m³] 57,56
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D NO OP MUR_01 Existing ext. wall 0,241 12,09 -5,00 1,15 3,3507 83,77 D NO TR FIN_02 Window 0.87x1.56 1,650 2,70 -5,00 1,15 5,1232 128,08 D OR(C) OP SOL_01 Existing roof 0,194 23,91 -5,00 1,00 4,6385 115,96 D NO PT PT_1 Window Thermal bridge 0,035 9,72 -5,00 1,15 0,3912 9,78 D NO PT PT_2 thermal bridge wall-roof 0,046 4,51 -5,00 1,15 0,2386 5,96
D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79
Dispersioni per trasmissione [W] 350,35 Dispersioni per ventilazione [W] 158,52 Potenza di ripresa [W] 509,22 Carico termico totale [W] 1.018,09
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 11
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #013
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 23,91 Volume netto [m³] 62,17
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D NO OP MUR_01 Existing ext. wall 0,241 11,98 -5,00 1,15 3,3203 83,01
D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89
D NO TR FIN_01 Window 1.93x1.56 1,613 3,01 -5,00 1,15 5,5834 139,58 D OR(C) OP SOL_01 Existing roof 0,194 23,91 -5,00 1,00 4,6385 115,96 D NO PT PT_1 Window Thermal bridge 0,035 6,98 -5,00 1,15 0,2809 7,02 D NO PT PT_2 thermal bridge wall-roof 0,046 4,87 -5,00 1,15 0,2576 6,44
D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79
Dispersioni per trasmissione [W] 366,70 Dispersioni per ventilazione [W] 171,22 Potenza di ripresa [W] 549,93 Carico termico totale [W] 1.087,84
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 12
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #014
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 5,88 Volume netto [m³] 15,29
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D SE OP MUR_01 Existing ext. wall 0,241 6,19 -5,00 1,10 1,6410 41,02
D SE OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,10 0,3018 7,55
D SE TR FIN_08 Window 0.66x1,56 1,551 1,03 -5,00 1,10 1,7573 43,93 D OR(C) OP SOL_01 Existing roof 0,194 5,88 -5,00 1,00 1,1407 28,52 D SE PT PT_1 Window Thermal bridge 0,035 6,40 -5,00 1,10 0,2464 6,16 D SE PT PT_2 thermal bridge wall-roof 0,046 2,50 -5,00 1,10 0,1265 3,16
D NE PT PT_5 Thermal bridge - existing column on the wall 0,072 6,56 -5,00 1,20 0,5668 14,17
U OP MUR_06 Internal fire resistant wall (insulated both side) 0,258 5,18 10,00 1,00 0,5346 13,36
Dispersioni per trasmissione [W] 157,88 Dispersioni per ventilazione [W] 42,11 Potenza di ripresa [W] 135,24 Carico termico totale [W] 335,23
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 13
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #015
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 5,90 Volume netto [m³] 15,34
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D OR(C) OP SOL_01 Existing roof 0,194 5,90 -5,00 1,00 1,1446 28,62
U OP MUR_03 Internal fire resistant wall (insulated) 0,282 7,11 10,00 1,00 0,8020 20,05
Dispersioni per trasmissione [W] 48,67 Dispersioni per ventilazione [W] 42,25 Potenza di ripresa [W] 135,70 Carico termico totale [W] 226,61
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 14
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #016
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 11,23 Volume netto [m³] 29,20
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D OR(C) OP SOL_01 Existing roof 0,194 11,23 -5,00 1,00 2,1786 54,47
U OP MUR_06 Internal fire resistant wall (insulated both side) 0,258 3,45 10,00 1,00 0,3560 8,90
Dispersioni per trasmissione [W] 63,37 Dispersioni per ventilazione [W] 80,42 Potenza di ripresa [W] 258,29 Carico termico totale [W] 402,07
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 15
Impianto Bldg #939 Zona Existing bldg #939 Ambiente room #017
Categoria di destinazione d’uso E.2 - Edifici adibiti a uffici e assimilabili Temperatura interna di progetto [°C] 20 Superficie utile [m²] 39,21 Volume netto [m³] 101,95
Amb.
Conf. Esp. Tipo Codice Descrizione U [W/m²K]
[W/mK] Sup. [m²]
Lungh. [m] Te [°C] ek Ht [W/K] Qt [W]
D NO OP MUR_01 Existing ext. wall 0,241 19,17 -5,00 1,15 5,3130 132,82
D NO OP MUR_01B Old column on the existing ext. wall 0,280 0,98 -5,00 1,15 0,3156 7,89
D NO TR FIN_01 Window 1.93x1.56 1,613 6,02 -5,00 1,15 11,1668 279,17 D OR(C) OP SOL_01 Existing roof 0,194 39,21 -5,00 1,00 7,6067 190,17 D NO PT PT_1 Window Thermal bridge 0,035 13,96 -5,00 1,15 0,5619 14,05 D NO PT PT_2 thermal bridge wall-roof 0,046 7,98 -5,00 1,15 0,4221 10,55
D NO PT PT_5 Thermal bridge - existing column on the wall 0,072 3,28 -5,00 1,15 0,2716 6,79
Dispersioni per trasmissione [W] 641,44 Dispersioni per ventilazione [W] 280,77 Potenza di ripresa [W] 901,83 Carico termico totale [W] 1.824,04
16/02/2018 11:37:54 AERMEC MC Impianti 11300 Pagina 16
Impianto Bldg #939 Zona Existing…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .