ASHE_13-1013_F3N042_5034A001_ATTACHMENT_2_REV.pdf
PDF 2 MB Posted
- Attached to
- PREFABRICATED CONCRETE AND HARDWARE MATERIALS
- Solicitation number
- FA5682-15-Q-5129
About this file
ATTACHMENT 2 REV
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
435TH AIR GROUND OPERATIONS WING (USAFE)
435TH AIR EXPEDITIONARY WING (AFAFRICA)
RAMSTEIN AIR BASE GERMANY
Bernd Walter/Jürgen Lösch, 435 CTS - ATTACHMENT 2 REV 13 JULY 15 Page 1
MEMORANDUM FOR 435 CTS/CEP
FROM: 435 CTS/CEP, GERMANY 13. July 2015
SUBJECT: REPAIR STORM WATER RUN-OFF SYSTEM, AVIANO, ASHE 13-1013
Specifications for constructions materials (Concrete Goods):
1. Prefabricated concrete water channel 1072 each
Size: 50 x 50 x 10 cm
2. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
Prefabricated concrete control pit with the INTERIOR dimensions of 80 x 80 x 80 cm. Wall thickness: at least 10 cm. Concrete C28/35– UNI EN 206. With sloping base slab and concrete cover with cast iron grate D400 with frame. Incl. manhole pipe connector DN/OD 250 (for heavy-duty PP sewer pipe SN 10), manhole pipe connector DN/OD 350 (Rauvia PE connecting piece ID 300).
Height: Measurement from center pipe to bottom of control pit (Hc):
Height pipe connector DN/OD 350: Hc1 = 26 cm Height Pipe connector DN/OD 250: Hc2 = 26 cm
(NCP – 1)
Connection to concrete chamber DN/OD 250 (PP sewer pipe)
Rauvia PE connecting piece ID 300
LEFT
ATTACHMENT 2 REV
Department of the Air Force Page: 2 of 19 435th Air Ground Operations Wing (USAFE) ASHE 13-1013
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 2
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 27 cm
3. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however with 4 connection pieces as shown below.
(NCP – 2)
Rauvia PE connecting piece ID 300 Hc = 29cm
Rauvia PE connecting piece ID 300, Hc = 28 cm
Rauvia PE connecting piece ID 400, Hc = 32.5 cm
H c1
H c2
Department of the Air Force Page: 3 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 3
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc =43.5 cm
Connection to concrete chamber DN/OD 200 (heavy-duty PP sewer pipe), Hc = 53 cm
4. Precast Concrete Control Pit 80 x 80 x 80 cm 2 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 3, NCP – 4)
5. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 5)
Rauvia PE connecting piece ID 400, Hc = 43.5 cm
Rauvia PE connecting piece ID 400, Hc = 30 cm
Rauvia PE connectingpiece ID 400, Hc = 30 cm
Rauvia PE connecting piece ID 400, Hc = 30 cm
Department of the Air Force Page: 4 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 4
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 51 cm
6. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 6)
7. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 7)
8. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 8)
Rauvia PE connecting piece ID 400, Hc = 30 cm
Rauvia PE connecting piece ID 400, Hc = 30 cm
Rauvia PE connecting piece ID 300, Hc = 23 cm
Rauvia PE connecting piece ID 400, Hc = 29cm Rauvia PE connecting piece
ID 300, Hc = 23 cm
Rauvia PE connecting piece ID 400, Hc = 32 cm
Rauvia PE connecting piece ID 400, Hc = 53 cm
Department of the Air Force Page: 5 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 5
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 63 cm
9. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 9)
10. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 10)
11. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 2 connection pieces as shown below.
(NCP – 11)
Rauvia PE connecting piece ID 500, Hc = 43 cm
Rauvia PE connecting piece ID 400, Hc = 38 cm
Rauvia PE connecting piece ID 300, Hc = 37 cm
Rauvia PE connecting piece ID 500, Hc = 42 cm
Rauvia PE connecting piece ID 500, Hc = 41 cm
Rauvia PE connecting piece ID 600, Hc = 45 cm
ID 300, Hc = 45 cm
Department of the Air Force Page: 6 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 6
12. Precast Concrete Control Pit 80 x 80 x 80 cm 4 each
As descrided in Item 15, however w/ 2 connection pieces as shown below.
(NCP – 12, NCP – 13, NCP – 19, NPC – 20)
13. Precast Concrete Control Pit 80 x 80 x 100 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below INTERIOR height: 100 cm.
(NCP – 14)
14. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 1 connection piece as shown below.
(NCP – 15)
Rauvia PE connecting piece ID 600, Hc = 41 cm
Rauvia PE connecting piece ID 600, Hc = 42 cm
Rauvia PE connecting piece ID 600, Hc = 42 cm
Rauvia PE connecting piece ID 600, Hc = 57 cm
Rauvia PE connecting piece ID 400, Hc = 30 cm
ID 300, Hc = 42 cm
Department of the Air Force Page: 7 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 7
15. Precast Concrete Control Pit 80 x 80 x 100 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
INTERIOR height: 100 cm.
(NCP – 16)
16. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 2 connection pieces as shown below.
(NCP – 17)
17. Precast Concrete Control Pit 80 x 80 x 100 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
INTERIOR height: 100 cm.
(NCP – 18)
Rauvia PE connecting piece ID 600, Hc = 42 cm
Rauvia PE connecting piece ID 600, Hc = 42 cm
Rauvia PE connecting piece ID 600, Hc = 41 cm
ID 300, Hc = 76 cm piece ID 300, Hc = 22 cm
Rauvia PE connecting piece ID 600, Hc = 42 cm
Rauvia PE connecting piece ID 300, Hc = 65 cm piece ID 300, Hc = 23 cm
Department of the Air Force Page: 8 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 8
Connection to concrete chamber DN/OD 250 (PP sewer pipe)
Connection to concrete chamber DN/OD 250 (PP sewer pipe)
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 43 cm
18. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 21A)
19. Precast Concrete Control Pit 80 x 80 x 80 cm 3 each
As descrided in Item 15, however w/ 2 connection pieces as shown below.
(NCP – 23, NCP – 33, NCP – 34)
20. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 27)
Rauvia PE connecting piece ID 300, Hc = 25 cm
Rauvia PE connecting piece ID 500, Hc = 35 cm
Rauvia PE connecting piece ID 500, Hc = 34 cm
Rauvia PE connecting piece ID 300, Hc = 26 cm
ID 300, Hc = 25 cm
Department of the Air Force Page: 9 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 9
21. Precast Concrete Control Pit 80 x 80 x 100 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
INTERIOR height: 100 cm.
(NCP – 28)
22. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 2 connection pieces at the right side.
(NCP – 29)
23. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 30)
Rauvia PE connecting piece ID 400, Hc = 29 cm
Rauvia PE connecting piece ID 400, Hc = 68 cm
Rauvia PE connecting piece ID 300, Hc = 50 cm
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 17 cm
Rauvia PE connecting piece ID 300, Hc = 20 cm
RIGHT
piece ID 300, Hc = 25 cm
Rauvia PE connecting piece ID 300, Hc = 26 cm piece ID 300, Hc = 26 cm
Department of the Air Force Page: 10 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 10
24. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 31)
25. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 4 connection pieces as shown below.
(NCP – 32)
26. Precast Concrete Control Pit 80 x 80 x 80 cm 1 each
As descrided in Item 15, however w/ 3 connection pieces as shown below.
(NCP – 35)
Rauvia PE connecting piece ID 400, Hc = 31 cm
Rauvia PE connecting piece ID 300, Hc = 27 cm
Rauvia PE connecting piece ID 500, Hc = 35 cm
Rauvia PE connecting piece ID 300, Hc = 27 cm
Rauvia PE connecting piece ID 500, Hc = 35 cm
Rauvia PE connecting piece ID 600, Hc = 41 cm
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 60 cm
Rauvia PE connecting piece ID 300, Hc = 25 cm piece ID 300, Hc = 26 cm
Department of the Air Force Page: 11 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 11
27. Pit Extentions for Control Pit 80 x 80 cm 184 each
Pit Extentions made of concrete C28/35– UNI EN 206.
Dimension: 80 x 80, h = 20 cm
28. Pit Extentions for Control Pit 80 x 80 cm 1 each
Pit Extentions as descrided in Item 40, however dimension: 80 x 80, h = 100 cm, incl manhole pipe connector DN/OD 465 (Rauvia PE connecting piece ID 400). Hc = 47 cm.
(for NCP – 8)
29. Pit Extentions for Control Pit 80 x 80 cm 1 each
Pit Extentions as descrided in Item 40, however dimension: 80 x 80, h = 100 cm, incl 2 manhole pipe connector DN/OD 580 (Rauvia PE connecting piece ID 500) and DN/OD 465 (Rauvia PE connecting piece ID 400). Hc = 36 cm.
(for NCP – 11)
Rauvia PE connecting piece ID 400, Hc = 47 cm
Rauvia PE connecting piece ID 500, Hc = 36 cm piece ID 400, Hc = 36 cm
Department of the Air Force Page: 12 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 12
30. Pit Extentions for Control Pit 80 x 80 cm 3 each
Pit Extentions as descrided in Item 40, however dimension:
80 x 80, h = 40 cm, incl. manhole pipe connector DN/OD 250 (for heavy-duty PP sewer pipe SN 10). Hc = 20 cm.
(for NCP – 15, NCP – 34, NCP – 35)
31. Pit Extentions for Control Pit 80 x 80 cm 2 each
Pit Extentions as descrided in Item 40, however dimension:
80 x 80, h = 40 cm, incl. manhole pipe connector DN/OD 250 (for heavy-duty PP sewer pipe SN 10). Hc = 27 cm.
(for NCP – 19, NCP – 20)
Rauvia PE connecting piece ID 500, Hc = 36 cm
Rauvia PE connecting piece ID 400, Hc = 36 cm
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 20 cm
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc = 27 cm
Department of the Air Force Page: 13 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 13
32. Precast Concrete Control Pit 120 x 120 x 100 cm 1 each
Prefabricated concrete control pit with the INTERIOR dimensions of 120 x 120 x h = 100 cm. Wall thickness: at least 10 cm. Concrete C28/35– UNI EN 206. With sloping base slab, 2 manhole pipe connectors ID 600 and ID 800 (all Rauvia PE connecting pieces) and concrete cover with cast iron grate D400 and frame.
(NCP – 21)
Rauvia PE connecting piece ID 600, Hc = 42 cm
Rauvia PE connecting piece DN/OD 800, Hc = 45 cm
H c 10
Department of the Air Force Page: 14 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 14
33. Precast Concrete Control Pit 120 x 120 x 120 cm 1 each
As descrided in Item 45, however w/ 2 connection pieces (Rauvia) As shon below. INTERIOR height: 120 cm.
(NCP – 22)
34. Precast Concrete Control Pit 120 x 120 x 120 cm 1 each
As descrided in Item 45, however w/ 3 connection pieces as shown below.
INTERIOR height: 120 cm.
(NCP – 24)
35. Precast Concrete Control Pit 120 x 120 x 120 cm 1 each
As descrided in Item 45, however w/ 3 connection pieces as shown below.
INTERIOR height: 120 cm.
(NCP – 25)
Rauvia PE connecting piece OD 800, Hc = 46 cm
Rauvia PE connecting piece OD 800, Hc = 45 cm
Rauvia PE connecting piece ID 500, Hc = 75 cm
Rauvia PE connecting piece OD 800, Hc = 75 cm
Rauvia PE connecting piece OD 800, Hc = 45 cm
Rauvia PE connecting piece ID 400, Hc = 43 cm
Rauvia PE connecting piece OD 800, Hc = 45 cm
OD 800, Hc = 44 cm
Department of the Air Force Page: 15 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 15
36. Precast Concrete Control Pit 120 x 120 x 120 cm 1 each
As descrided in Item 45, however w/ 2 connection pieces as shown below.
INTERIOR height: 120 cm.
(NCP – 26)
37. Precast Concrete Control Pit 140 x 140 x 140 cm 1 each
As descrided in Item 45, however w/ INTERIOR dimension:
140 x 140 x h= 140 cm. Incl. 3 connection pieces as shown below.
(NCP – 36)
38. Precast Concrete Control Pit 140 x 140 x 160 cm 1 each
As descrided in Item 45, however w/ 2 connection pieces as shown below.
INTERIOR height: 160 cm.
(NCP – 37)
Rauvia PE connecting piece OD 800, Hc = 45 cm
Rauvia PE connecting piece OD 930, Hc = 50 cm
Rauvia PE connecting piece ID 600, Hc = 46 cm
Rauvia PE connecting piece OD 930, Hc = 55 cm
Rauvia PE connecting piece OD 1200, Hc = 65 cm
Rauvia PE connecting piece OD 1200, Hc = 60 cm
Rauvia PE connecting piece OD 1200, Hc = 60 cm
ID 300, Hc = 140 cm
Department of the Air Force Page: 16 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 16
39. Precast Concrete Control Pit 140 x 140 x 140 cm 2 each
As descrided in Item 45, however w/ 2 connection pieces as shown below.
INTERIOR height: 140 cm.
(NCP – 38, NCP – 39)
40. Pit Extentions for Control Pit 120 x 120 cm 70 each
Pit Extentions made of concrete C28/35– UNI EN 206.
Dimensions: 120 x 120, h = 20 cm
41. Pit Extentions for Control Pit 120 x 120 x 60 cm 1 each
Pit Extentions as descrided in Item 53, however dimensions:
120 x 120, h = 60 cm, incl. manhole pipe connector DN/OD 465 (Rauvia PE connecting piece ID 400). Hc = 30 cm.
(for NCP – 21)
Rauvia PE connecting piece OD 1200, Hc = 68 cm
Rauvia PE connecting piece OD 1200, Hc = 67 cm
Rauvia PE connecting piece ID 400, Hc = 30 cm.
Department of the Air Force Page: 17 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 17
42. Pit Extentions for Control Pit 120 x 120 cm 4 each
Pit Extentions as descrided in Item 53, however dimensions:
120 x 120, h = 40 cm, incl. manhole pipe connector DN/OD 250 (for heavy-duty PP sewer pipe SN 10). Hc = 20 cm.
(for NCP – 22, NCP – 24, NCP 25, NCP – 26)
43. Pit Extentions for Control Pit 140 x 140 cm 1 each
Pit Extentions as descrided in Item 53, however dimensions:
140 x 140, h = 40 cm, incl. manhole pipe connector DN/OD 250 (for heavy-duty PP sewer pipe SN 10). Hc = 16 cm.
(for NCP – 36)
44. Pit Extentions for Control Pit 140 x 140 cm 4 each
Pit Extentions made of concrete C28/35– UNI EN 206.
Dimensions: 140 x 140, h = 20 cm (for NCP – 36, NCP – 39)
Connection to concrete chamber DN/OD 250 (PP sewer pipe), Hc =20 cm
DN/OD 250 (PP sewer pipe), Hc =16 cm
Department of the Air Force Page: 18 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 18
45. Pit Extentions for Control Pit 140 x 140 cm 6 each
Pit Extentions made of concrete C28/35– UNI EN 206.
Dimensions: 140 x 140, h = 40 cm (for NCP – 37, NCP – 38, NCP – 39)
46. Precast Concrete Control Pit 80 x 80 cm 2 each
Prefabricated concrete control pit with the INTERIOR dimensions of 80 x 80 cm, incl. extentions and Cover D400 as shown below. Wall thickness: at least 10 cm.
Height: see drawing. Concrete C28/35– UNI EN 206. With sloping base slab, 2 manhole pipe connectors ID 500 (all Rauvia PE connecting pieces) and concrete cover with cast iron grate D400 and frame.
(NCP – 40, NCP – 41)
Rauvia PE connecting piece ID 500, Hc = 34 cm
ID 500, Hc = 33 cm
Department of the Air Force Page: 19 of 19
435 CTS – CEP
Bernd Walter/Jürgen Lösch, 435 CTS- ATTACHMENT 2 REV 13 JULY 15 Page 19
47. Precast Concrete Catch Basin 50 x 50 x 80 cm 18 each
Prefabricated concrete catch basin as descrided in Item 2, however INTERIOR height = 80 cm. With concave gully grating and manhole pipe connector DN/OD 250 (for heavy-duty PP sewer pipe SN 10).
Class D400, Cast-iron inlet, incl. frame.
DN/OD 250 (PP sewer pipe), Hc = 16 cm
File details come from the government source that posted it. Updated .