This is a Sources Sought notice issued by the 766th Enterprise Sourcing Squadron (766 ESS) for market research purposes to identify potential sources for a Waste Accumulation Point to be provided to the 15AMXS. The notice is for information and planning purposes only and does not constitute a solicitation; however, responses will assist the Government in identifying capable sources and determining appropriate acquisition strategies.

The requirement is for one complete prefabricated, weatherproof steel building unit engineered to withstand minimum 120 mph wind loads. The structure must measure between 26-28 feet in width and a maximum of 10 feet in depth, with two internal partitions creating three separate rooms. All walls and partitions must be constructed with 2-hour fire-rated materials and include full insulation. The building requires two double doors and one single man door (or alternatively, three double doors), each opening to the outside and rated as hurricane-proof equivalent to 120 mph winds, with steel access ramps of minimum 54-inch width for each door. The flooring must be standard galvanized steel grating with a built-in 6-inch deep spill containment sump featuring a dedicated drain port with cap. All interior electrical components, including explosion-proof lighting in each of the three rooms, must meet explosion-proof specifications. Additional required systems include a climate control system with explosion-proof exhaust fan, an exterior-mounted NEMA-rated load center box, a static grounding system with rod and internal lugs, and an integrated dry chemical fire suppression system. An example photograph of a similar structure is provided as reference.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sources Sought: Hazardous Material Building

1. PURPOSE

The 766th Enterprise Sourcing Squadron (766 ESS) is conducting market research to identify potential sources capable of providing the 15AMXS with a Waste Accumulation Point. This RFI is issued solely for information and planning purposes **it does not constitute a solicitation**. Responses to this RFI will assist the Government in identifying capable sources and determining appropriate acquisition strategies.

2. REQUIREMENT OVERVIEW

Structure Overview One (1) complete prefabricated, weatherproof steel building unit engineered for high wind resistance, capable of withstanding minimum 120 mph wind loads.

Dimensions & Layout

• Exterior Dimensions: Minimum 26 ft. to Maximum 28 ft. Width; Maximum 10 ft.

Depth.

• Internal Layout:

o Features two (2) internal partitions creating three (3) separate and distinct rooms.

o Each wall and partition shall be constructed with 2-Hour Fire-Rated.

o Includes full insulation for the walls, floor, and ceiling.

Doors and Access

• All doors must be Hurricane-Proof (equivalent to the 120 mph wind rating).

• Door Configuration:

o Includes two (2) double doors and one (1) single man door or three (3) double doors.

o Each door shall open to the outside.

• Ramps: Steel access ramps with a minimum width of 54 inches are required for each door.

Spill Containment & Flooring

• Flooring: Constructed using standard galvanized steel grating.

• Containment: Features a built-in, 6-inch deep spill containment sump.

• Drainage: The sump includes a dedicated drain port equipped with a cap.

Climate & Electrical Systems

• Electrical: All interior electrical components must be explosion-proof.

• Lighting: Explosion-proof interior lighting is required in each of the three rooms.

• Climate Control: Includes a climate control system utilizing an explosion-proof exhaust fan (forced air).

• Power & Grounding: Equipped with an exterior-mounted NEMA-rated load center box and a static grounding system (including rod and internal lugs).

Additional Features

Fire Suppression: Equipped with an integrated Dry Chemical Fire Suppression System.