4b_Appendix_A2_Annual_IM_Check_List.pdf

PDF 173 KB Posted

Attached to
Inspection, Maintenance, and Repair Services of Water Supply Control Systems Bldg No. 832, 858 and 1043 at Camp Zama, Japan
Solicitation number
Fa520919Q004A
Issued by

About this file

PWS-Appendix A2

View the file

Other files

File Type Posted
4a_Appendix_A1_Qtly_IM_Check_List.pdf PDF
1_Attach_4_Notice_to_Offeror.pdf PDF
4e_Appendix_D.pdf PDF
4d_Appendix_C_Requr_parts_List.pdf PDF
3_Attach_1_Pricing_Schedule.pdf PDF
5_Business_w_US_Government.pdf PDF
4_Attach_2_PWS.pdf PDF
4c_Appendix_B_Equipment_List.pdf PDF
1a_Gate_Pass_Req.pdf PDF
2_Combined_Synopsis_19Q004A.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix A2: Annual Inspection and Maintenance Check List for Water Supply System

Appendix A2-1

Check List for Maintenance Inspection of Water Supply System:

Inspection and Maintenance Class Annually Attendant/Observer

Date Person in Charge

Name of Company

Bldg 1043: Main Control Panel

No. Inspection and Maintenance Item Judging Standard Remarks Pass or Failure

3-1

Changeover of Water Source System

① Changeover of Water Source System

Water source system can be changed to WATER WORKS, TOGETHER and WELL

WATER.

3-2

Indication in Trouble

① Control Host Trouble

Indication Host Trouble

[CPU TROUBLE] LED turns on.

Alarm buzzer sounds.

To return to AUTO mode when in REMOTE mode or in TEST mode.

When reset, [CPU TROUBLE] LED turns off and alarm stops.

② Irregular Communication among Host

[Irregular Communication] alarm is indicated on screen.

To reset automatically when connected.

Appendix A2-2

Bldg 1043: Main Control Panel

Maintenance Items Judging Standard Remark Pass or Failure

3-2

③ Communication Cut to Water Supply Facility (Degeneracy Operation)

Water Supply Facility Monitoring Panel [CPU TROUBLE] LED turns on and buzzer sounds.

To become degeneracy operation cut away from Water Supply Facility.

To rest automatically when connected.

④ Communication Cut to Area 1000 Facility Monitoring Panel (Degeneracy Operation)

Area 1000 Facility Monitoring Panel [CPU TROUBLE] LED turns on and buzzer

To become degeneracy operation, cut away from Area 1000 Facility.

To reset automatically when connected.

⑤ Communication Cut to Area 830 Facility Monitoring Panel (Degeneracy Operation)

Area 830 Facility Monitoring Panel [CPU TROUBLE] LED turns on and buzzer

To become degeneracy operation, cut away from Area 830 Facility.

To rest automatically when connected.

3-3

Power Cut

① Operation of

UPS

When power cut, to changeover to battery drive at the same time.

Alarm buzzer sounds.

To reset automatically when power is supplied.

Appendix A2-3

Bldg 1043: Water Supply Facility Monitoring Panel and its internal Equipment

3-4

Indication in Trouble ―

① Area Controller Trouble

[CPU TROUBLE] LED turns on.

Buzzer sounds.

Other monitoring panels return to AUTO mode when in REMOTE mode or in TEST mode.

When reset, [CPU TROUBLE] LED turns off and buzzer stops.

3-5

Power Cut

① Operation of UPS

When power cut, to changeover to battery drive at the same time.

Power light turns on.

Buzzer sounds.

To reset automatically when power is supplied.

3-6

Motor Valve Operation Confirmation

① Timer Motor Valve TMT Motor Valve TMT opens and closes according to operation.

3-7

Pump Operation Sequence Following operations are carried out in good order.

① Water Supply Pump T1, T2 & T3

Pump time-lag actuation confirmation.

Degeneracy operation (inside Area cut away) confirmation.

Appendix A2-4

Bldg 1043: Water Supply Facility Monitoring Panel and Its Internal Equipment

3-8

Set-up of Water Level Meter TLE 1.

① Water Level Meter TLE 1

To output alarm according to water level of Water Level Meter TLE 1.

Indication of Main Control Panel should change.

Water level confirmation. Figures in ( ) are initial values.

Indication Max. Value (3.0m)

Water Level HWL (2.5m) Alarm Output

Water Level MWL 1 (1.4m)

Water Level MWL 2 (1.3m)

Water Level MWL 3 (1.0m) Backup Alarm Output

Water Level MWL 4 (0.9m)

Water Level LWL (0.7m) Alarm Output

Indication Min. Value (0.0m)

Set-up of Water Level Meter TLE2

① Water Level Meter TLE 1

To output alarm according to water level of Water Level Meter TLE2.

Indication on Main Control Panel should change.

Water level confirmation. Figures in ( ) are initial values.

Indication Max. Value (3.0m)

Water Level HWL (2.5m) Alarm Output

Water Level MWL 1 (1.4m)

Appendix A2-5

Bldg 1043: Water Supply Facility Monitoring Panel and Its Internal Equipment

3-8 ① Water Level Meter TLE 1

Water Level MWL 2 (1.3m)

Water Level MWL 3 (1.0m) Backup Alarm Output

Water Level MWL 4 (0.9m)

Water Level LWL (0.7m) Alarm Output

Indication Min. Value (0.0m)

3-9

Set-up of Electromagnetic Flow Meter Water Flow volume values of Water Flow Meter TSM are properly indicated.

① Water Flow Meter TSM

To confirm flow volume.

Flow volume 10.0 m3/min

Flow volume 5.0 m3/min

Flow volume 0.0 m3/min

Appendix A2-6

Bldg 858: Facility Monitoring Panel and its internal Equipment

3-10 Indication in Trouble

① Area Controller Trouble [CPU TROUBLE] LED turns on.

Buzzer sounds.

Other monitoring panels return to AUTO mode when in REMOTE mode or in TEST mode.

When reset, [CPU TROUBLE] LED turns off and buzzer stops.

3-11 Power Cut

① Operation of UPS When power cut, to changeover to battery drive at the same time.

Power light flashes.

Buzzer sounds.

To reset automatically when power is supplied.

3-12 Confirmation of Motor Valve Operation Set to MANUAL mode by Area 1000 Monitoring Panel. After inspection, reset to AUTO mode.

① Motor Valve SM 1 Motor Valve SM 1 opens and closes according to operation.

② Motor Valve SM 2 Motor Valve SM 2 opens and closes according to operation.

③ Motor Valve SF 1 Motor Valve SF 1 opens and closes according to operation.

④ Motor Valve SF 2

Motor Valve SF 2 opens and closes according to operation.

⑤ Motor Valve SLM

Motor Valve SLM opens and closes according to operation.

Appendix A2-7

3-13 Pump Operation Sequence Following operation is carried out in good order.

① Water Distribution Pump S1, S2 Confirmation of pump time-lag actuation.

Confirmation of degeneracy operation (inside Area cut away).

② Emergency Pump S3, S4 Confirmation of pump time-lag actuation.

3-14 Set-up of Water Level Meter SLE 1 To output alarm according to water level of Water Level Meter SLE 1.

① Water Level Meter SLE 1

Indication of Main Control Panel should change.

Water level confirmation. Figures in ( ) are initial values.

Indication Max. Value (6.0m)

Water Level HWL (5.5m) Alarm Output

Water Level MWL 1 (5.0m)

Water Level MWL 2 (4.7m)

Water Level MWL 3 (4.6m)

Water Level MWL 4 (3.7m)

Water Level MWL 5 (2.0m)

Water Level MWL 6 (1.5m) Backup Alarm Output

Water Level LWL (1.2m) Alarm Output

Indication Min. Value (0.0m)

Appendix A2-8

3-14 ② Water Level Meter SLE 2 To output alarm according to water level of Water Level Meter SLE 1.

Indication of Main Control Panel should change.

Water level confirmation. Figures in ( ) are initial values.

Indication Max. Value (6.0m)

Water Level HWL (5.5m) Alarm Output

Water Level MWL 1 (5.0m)

Water Level MWL 2 (4.7m)

Water Level MWL 3 (4.6m)

Water Level MWL 4 (3.7m)

Water Level MWL 5 (2.0m)

Water Level MWL 6 (1.5m) Backup Alarm Output

Water Level LWL (1.2m) Alarm Output

3-15 Set-up of Electromagnetic Flow Meter Water Flow volume values of Water Flow Meter SCM are properly indicated.

① Water Flow Meter SCM To confirm flow volume.

Flow Volume 10.0 m3/min

Flow Volume 5.0 m3/min

Flow Volume 0.0 m3/min

Appendix A2-9

Maintenance Items Judging Standard Remark Pass or Failure

3-16 Set-up of Pressure Gauge Water Flow volume values of Water Flow Meter SCM are properly indicated.

① Water Flow Meter SCM To confirm Pressure

Pressure 1.0 Mpa

Pressure 0.5 Mpa

Pressure 0.0 Mpa

Appendix A2-10

Bldg 832: Facility Monitoring Panel and its internal Equipment

3-17 Indication in Trouble

① Area Controller Trouble [CPU TROUBLE] LED turns on.

Other monitoring panels return to AUTO mode when in REMOTE mode or in TEST mode.

When reset, [CPU TROUBLE] LED turns off and buzzer stops.

3-18 Power Cut

① Operation of UPS When power cut, to changeover to battery drive at the same time.

Power light flashes.

Buzzer sounds.

To reset automatically when power is supplied.

3-19 Set to MANUAL mode by Area 830 Monitoring Panel. After inspection, reset to AUTO mode.

① Motor Valve MM 1

Motor Valve MM 1 opens and closes according to operation.

② Motor Valve MM 2

Motor Valve MM 2 opens and closes according to operation.

③ Motor Valve MF 1

Motor Valve MF 1 opens and closes according to operation.

④ Motor Valve MF 2 Motor Valve MF 2 opens and closes according to operation.

Appendix A2-11

Maintenance Items Judging Standard Remark Pass or Failure

3-20

Pump Operation Sequence Following operation is carried out in good order.

① Water Distribution Pump M1, M2

Confirmation of pump time-lag actuation.

Confirmation of degeneracy operation (inside Area cut away).

② Water Distribution Pump M3, M4 Confirmation of pump time-lag actuation.

3-21

Set-up of Water Level Meter To output alarm according to water level of Water Level Meter MLE 1.

① Water Level Meter MLE 1

Indication of Main Control Panel should change.

Water level confirmation. Figures in ( ) are initial values.

Indication Max. Value (12.0m)

Water Level HWL (11.0m) Alarm Output

Water Level MWL 1 (10.9m)

Water Level MWL 2 ( 7.5m)

Water Level MWL 3 ( 4.0m)) Backup Alarm Output

Water Level LWL ( 2.3m) Alarm Output

Appendix A2-12

Maintenance Items Judging Standard Remark Pass or Failure

3-21

Set-up of Water Level Meter To output alarm according to water level of Water Level Meter MLE 2.

① Water Level Meter MLE 2

Indication of Main Control Panel should change.

Water level confirmation. Figures in ( ) are initial values.

Indication Max. Value (12.0m)

Water Level HWL (11.0m) Alarm Output

Water Level MWL 1 (10.9m)

Water Level MWL 2 ( 7.5m)

Water Level MWL 3 ( 4.0m) Backup Alarm Output

Water Level LWL ( 2.3m) Alarm Output

Indication Min. Value (0.0m)

3-22

Set-up of Electromagnetic Flow Meter Water Flow volume values of Water Flow Meter MAM are properly indicated.

① Flow Meter

MAM

To confirm flow volume.

Flow Volume 10.0 m3/min

Flow Volume 5.0 m3/min

Flow Volume 0.0 m3/min

Appendix A2-13

Maintenance Items Judging Standard Remark Pass or Failure

3-22 Set-up of Electromagnetic Flow Meter Water Flow volume values of Water Flow Meter MBM are properly indicated.

② Water Flow Meter

MBM

To confirm flow volume.

Flow Volume 10.0 m3/min

Flow Volume 5.0 m3/min

Flow Volume 0.0 m3/min 3-23 Set-up of Pressure Gauge Water Flow volume values of Water Flow Meter MAM are properly indicated.

① Pressure Gauge MAP

To confirm Pressure.

Pressure 1.0 Mpa

Pressure 0.5 Mpa

Pressure 0.0 Mpa

Set-up of Pressure Gauge Water Flow volume values of Water Flow Meter MBM are properly indicated.

② Pressure Gauge MBP

To confirm Pressure.

Pressure 1.0 Mpa

Pressure 0.5 Mpa

Pressure 0.0 Mpa