questions_and_response.docx
DOCX document 13 KB Posted
- Attached to
- Three Phase AC Power Source
- Solicitation number
- FA500419QA0390001
View the file
Other files
| File | Type | Posted |
|---|---|---|
| HAF_Call_18-03_CMBRE_Power.pdf | ||
| J&A_Three_Phase_AC_Power_Source.pdf | ||
| Solicitation_-_FA500419QA0390001.pdf | ||
| Solicitation_-_FA500419QA0390001.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. Is the 115 Vac voltage referenced ‘line-to-neutral’ or ‘line-to-line’? –
Output power is configured as 115/200Vac, 400hz, 3-phase power. The output voltage is 115Vl-n (line-to-neutral) per phase and 200Vl-l (line-to-line) Phase-to-Phase. Maximum current phase is 16Arms/phase continuously with a short term overload to 20Arms/phase.
2. It also states: “Needs to be able to be plugged in to 110V or 220V”. Is this also 3-phase power? If so, are the voltages referenced ‘line-to-neutral’ or ‘line-to-line’? –
Input power for this system is configured for a 208Vac (referenced line-to-line), 3-phase Delta, 47-63Hz, with a range of +/-10%.