Questions

1. Can existing conduit be used?

2. Will disposal tickets be required?

3. Will as-builts be required?

4. Will the fixtures need to be explosion proof?

5. Building 4414: Is the large cockpit and chairs going to be moved for installation of lights?

6. Building 2505: Are you adding 90 minute timers to lights in workout room with mirror?

7. Will the summary of work include the specific work to be done on each facility in case we missed some information in the site visit

8. We were talking about 2x2 LED's in the Racquet Ball court because of the amount of lost lumen in a 2x2 fluorescent. The cost for LED's and fluorescent are substantially different. Can you clarify what option you are looking for in the Racquet Ball court?

9. Do you have plans or drawings or will the switch and sensor placements be at our discretion?

10. what do the numbers next to the Facility numbers in parenthesis represent? Are these counts for the number of lamps being replaced or number of fixtures?

11. Are there any specifications on the type of T5HO lamp or the type of occupancy sensors that is required to be installed?

12. Under the summary of work “Provide all necessary electrical to control high-bay fixtures, to replace existing breaker switching.” Does this mean you are looking for all new wiring and electrical service for the light fixtures or would it be possible to get a more detailed explanation of this comment?

ANSWERS

1. Existing conduit can be used.

2. Disposal tickets are required.

3. No as- built drawings

4. No explosion proof fixtures.

5. Government will moved cockpit and chairs in building 4414.

6. 90 minute timer in workout room in building 2505.

7. N/A

8. 2 x 2LED’s Sport High Impact Fixture.

9. No plans or drawings/ Sensors are mounted on side of light fixture as brief in building 2711.

10. Parenthesis Number represents Category Code for DD Form 1354 Checklist.

11. Current fixtures are Metalux High bay 6 lamps Industrial Fluorescent Luminaries/ 120/277V, 351 Watts with wire guard, Sensors are Hubbell HMHB21U.

12. New wiring and electrical service for light fixtures.