This document is an attachment that provides salient specifications for a Camus DRNH3500-MSI Dynaforce Hydronic Heating Boiler with a 3,500,000 BTU input and 3,307,000 BTU output. The boiler is fully condensing with a stainless steel heat exchanger, 5:1 turndown ratio, and up to 99% thermal efficiency. It utilizes BACNet communication protocol and is factory fire tested.
The related federal contract opportunity is a solicitation from the Department of the Air Force Special Operations Command for the B4606 Boiler Replacement. Attachments include provisions and clauses, salient characteristics, brand name justification, and a Q&A combo. The solicitation number is FA485524Q0010, and responses are due by 12:00PM Mountain Time on 13 May 2024.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - Provisions and Clauses.pdf | ||
| Attachment 3 - Brand Name Justification - CO SIGNED.pdf | ||
| Attachment 4 - Combo.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building 4606 Boiler – Salient Specifications
• Camus DRNH3500-MSI Dynaforce Hydronic Heating Boiler
• 3,500,000 BTU Input
• 3,307,000 BTU Output
• CSD-1 Rated
• BACNet Communication Protocol
• Heat exchanger shall be a fully condensing vertical cylindrical counter-flow water tube design with 439 grade tubes and 316L grade headers of stainless steel construction and all welded design with constant allowable system return temperatures of 40F.
• Fine-tuned combustion premix providing homogeneous air and gas combustion mix to a radial burner incorporating a knitted stainless steel wrap ensuring stable light off and efficient clean combustion.
• Boiler shall operate up to 99% thermal efficiency
• 5:1 gas input turn down ratio with sustained efficient combustion characteristics throughout entire modulating range.
• The boiler is fully factory fire tested to obtain optimum combustion characteristics and to establish certified gas input rates.
• System safety and operating devices and controls are fully configured, calibrated and factory tested.