130 Ton Chiller - QandA.pdf
PDF 93 KB Posted
- Attached to
- FA485524Q0009 - 130 Ton Chiller
- Solicitation number
- FA485524Q0009CLB
About this file
This document contains Questions and Answers related to a 130 Ton Chiller being procured by the Department of the Air Force Special Operations Command under Solicitation Number FA485524Q0009.
The key details are:
- The unit will be ground-mounted with a maximum ambient temperature of 100°F, requiring R454B refrigerant.
- This procurement is for the delivery and startup of the chiller unit only, with installation under a separate contract.
- The contract includes a pre-start inspection and startup services, but not installation.
- The total quantity is one (1) 130 Ton Air Cooled Chiller package unit for Building 355.
- The solicitation number is FA485524Q0009-130 Ton Chiller.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
130 Ton Chiller
Questions & Answers
1. What will the highest ambient temperature be? The reason being is that you are asking for 454B refrigerant which is ok if the ambient does not go over 110 F, but if it does go over this we recommend using 513 refrigerant.
The ambient temperature would be no more than 100 F, requested refrigerant is R454B due to R134A being phased out.
2. Is this unit going to be ground of roof mounted?
This unit will be placed on the ground, see attached pictures of current unit.
3. Are there any photographs of where this unit is going to be located?
Yes, picture attached.
4. Is this strictly for delivery of the unit with Start Up and Pre Inspection with Installation conducted under a different contract?
This purchase is for delivery and start-up.
5. Is installation required as part of this solicitation?
No, installation is not part of solicitation.
File details come from the government source that posted it. Updated .