Questions and Answers from Site visit held on Cannon AFB on 6 August 2015 for RFQ FA4855-15-T-0071

***The site visiti lasted for 1 ½ hours, there were eight (8) potential vendors and four (4)*** ***government representative in attendance. ***

Question #1 – What are the Sizes of the three (3) airrators?

Answer- Horse Power =5

Voltage= 460
Phase= 3

Question #2- What is the depth of the Wells?

Answer- 12 Feet

Question #3- Can the Bowl assemble be an “or equal item”?

Answer- YES

Question #4- What is the amount of pressure?

Answer- 500 GPM

120 PSI

Question #5- Does the roof come off?

Answer- YES

Question #6- What does the Pressure Transmitter need to be?

Answer-110 PSI

Question #7- What is the length of the Pumps?

Answer- 12.6 Feet

Question #8- Will the current filter be intergrated into the new system?

Answer- YES

Question #9- Can the nema inclosure have one(1) disconnect that is equal to 200 amps rather than have two(2) that are each 100 amps?

Answer- YES

Question #10- Are we going to be replacing the transformer and the “110”?

Answer- No, just move them Higher****

Question #11- Will we have to put in a new electrical panel?

Answer- YES

Question #12- What is the size of the platform that the system sits on?

Answer- 139 inches by 80 inches