785asbestos.pdf

PDF 736 KB Posted

Attached to
QSEU 12-2002, Repair Infrared Heaters
Solicitation number
FA4830-13-B-0002
Issued by

About this file

BLDG 785 Asbestos Report

View the file

Other files

File Type Posted
Amendment_0001.pdf PDF
758_Asbestos.pdf PDF
01_57_20.00_ENVIRONMENTAL_PROTECTION_26_Mar_13_corrected.pdf PDF
01_00_00_GENERAL_REQUIREMENTS_9003_26_Mar_13correted.pdf PDF
Infrared_Heaters_Repair_Questions_(3).pdf PDF
02_41_00__DEMOLITION_AND_RECONSTRUCTION.pdf PDF
m-1.pdf PDF
23_11_23.00_10_GAS_PIPING_SYSTEMS.pdf PDF
Bidders_Checklist.doc DOC document
m-3.pdf PDF
e-3.pdf PDF
m-2.pdf PDF
SITE_VISIT_CONFERENCE_RESERVATION_FORM.docx DOCX document
Lobby_Activities_Form.pdf PDF
01_45_01_CONTRACTORS_QUALITY_CONTROL.pdf PDF
01_00_01_SPECIFIC_REQUIREMENTS__MAFB.pdf PDF
01_00_00_GENERAL_REQUIREMENTS.pdf PDF
e-2.pdf PDF
23_52_00_HEATING_BOILERS.pdf PDF
Title_Page TOC_ _COVER_SHT.pdf PDF
01_62_35_RECYCLED__RECOVERED_MATERIALS.pdf PDF
01_31_01_PROJECT_MANAGEMENT.pdf PDF
e-1.pdf PDF
m-5.pdf PDF
Architectural_electrical_Design_Analysis.docx DOCX document
23_07_00_THERMAL_INSULATION_FOR_MECHANICAL_SYSTEMS.pdf PDF
01_78_23_OPERATION_AND_MAINTENANCE_DATA.pdf PDF
01_35_29_SAFETY_AND_OCCUPATIONAL_HEALTH_REQUIREMENTS.pdf PDF
Contractor_Information.rtf RTF text file
IFB_solicitation.doc DOC document
m-7.pdf PDF
01_35_00_SPECIAL_PROVISIONS_FOR_WORKING_ON_OR_NEAR_THE_AIRFI.pdf PDF
X-1_VICINITY_MAP _INDEX_OF_DRAWINGS.pdf PDF
01_57_20.00_ENVIRONMENTAL_PROTECTION_.pdf PDF
m-4.pdf PDF
m-6.pdf PDF
Question_Form.docx DOCX document
AF_Form_66.xls XLS spreadsheet
01_78_00_TASK_ORDER_CLOSE_OUT_REQUIREMENTS.pdf PDF
23_54_16.00_10_HEATING_SYSTEM__GAS-FIRED_HEATERS.pdf PDF
01_33_00_SUBMITTAL_PROCEDURES.pdf PDF
01_55_01__SECURITY_REQUIREMENTS.pdf PDF
Wage_Determination.docx DOCX document
01_04_00_Unit_Price_Book_and_Software_Requirments.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Moody AFB, Selected Buildings Asbestos Inspection Report February 2010

4.15 Building MB 785 (Sheet Metal and Battery Shop)

Building MB 785 is a large building containing a variety of aircraft maintenance shops. The building was constructed by the U.S. military in 1966. Photograph available here.

A total of 54 samples were collected from 7 different material types in Building 785 during the inspection visit of 5 and 6 November 2009. Sampled materials included gypsum board and finishing compound, vinyl wall covering, vinyl cove molding and mastic, vinyl floor tiles and mastics, ceiling tiles, thermal system insulation, and duct insulation mastic. Table MB 785-1 provides a listing of the samples with their analytical results. Figures MB 785A-loc and MB 785B-loc show a floor plan of the building showing the sample locations.

Table MB 785-1 Suspect ACBM Samples in Building MB 785

Sample ID Sample Material Sample Location Analytical Result

MB-785-01-001 Gypsum board and finishing compound –

Type I

Room 42, behind W wall access door locking jamb above molding

NAD

MB-785-01-002 Gypsum board and finishing compound –

Type I

Room 32, behind door in SE corner, above cove molding

NAD

MB-785-01-003 Gypsum board Room 14, bottom of electrical panel on W wall

NAD

MB-785-01-004 Gypsum board w/vinyl wall covering – Type II

Room 31, N wall in area previously damaged

NAD

MB-785-01-005 Gypsum board w/vinyl wall covering – Type II

Room 30, W wall by access door locking jamb above molding

NAD

MB-785-02-001 2’ x 2’ ceiling tile w/fissures and pits –

Type I

Room 1, ceiling in alcove between rooms 13 and 4, by S wall

NAD

MB-785-02-002 2’ x 2’ ceiling tile w/fissures and pits –

Type I

Room 4, first floor, ceiling above east entry doors

NAD

MB-785-02-003 2’ x 4’ ceiling tile w/fissures and pits –

Type II

Room 32, first floor, ceiling above fixed bench, NW corner

NAD

MB-785-02-004 2’ x 4’ ceiling tile w/fissures and pits –

Type II

Room 1, ceiling in alcove between Rooms 13 and 4, by S wall

NAD

NAD=No asbestos detected

Sample ID Sample Material Sample Location Analytical Result

MB-785-02-005 2’ x 2’ ceiling tile, smooth– Type III

Room 44A, first floor, Ceiling by S wall, 6’ from W wall

NAD

MB-785-02-006 2’ x 2’ ceiling tile, smooth– Type III

Room 44A, first floor, ceiling by E wall, 6’ from S wall

NAD

MB-785-03-001 Beige 12” x 12” floor tile

– Type I

Floor at entry door alcove to Room 13

NAD

MB-785-03A-001 Black mastic for beige 12” x 12” floor tile

Floor at entry door alcove to Room 13

NAD

MB-785-03-002 Beige 12” x 12” floor tile

– Type I

Floor at N entry door to Room 4 in NW corner

NAD

MB-785-03B-002 Black mastic for beige 12” x 12” floor tile

Floor at N entry door to Room 4 in NW corner

NAD

MB-785-03-003 Green 12” x 12” floor tile – Type II

Room 19A, N end of hallway, floor at locking jamb of W access door

NAD

MB-785-03C-003 Clear mastic for green 12” x 12” floor tile

Room 19A, N end of hallway, floor at locking jamb of W access door

NAD

MB-785-03-004 Green 12” x 12” floor tile – Type II

Room 19A, floor at doorway to cleaning room, S end of hallway

NAD

MB-785-03D-004 Clear mastic for green 12” x 12” floor tile

Room 19A, floor at doorway to cleaning room, S end of hallway

NAD

MB-785-03-005 Scored 12” x 12” floor tile – Type III

Room 12, floor at access doorway on W wall

2% Chrysotile

MB-785-03E-005 Mastic for scored 12” x 12” floor tile

Room 12, floor at access doorway on W wall

5% Chrysotile

MB-785-03-006 Scored 12” x 12” floor tile w/carpet mastic pattern– Type III

Room 25, floor at access doorway on N wall

NAD

MB-785-03F-006 Black Mastic for scored 12” x 12” floor tile

Room 25, floor at access doorway on N wall

NAD

MB-785-03FF-006 Yellow Mastic for scored 12” x 12” floor tile

Room 25, floor at access doorway on N wall

NAD

MB-785-03-007 Beige 12” x 12” floor tile w/red streaks– Type IV

Room 41A, floor at S side of locker room entry doorway

NAD

MB-785-03G-007 Black Mastic for Beige 12” x 12” floor tile w/red streaks

Room 41A, first floor, S side of locker room entry doorway

NAD

MB-785-03-008 Beige 12” x 12” floor tile w/red streaks– Type IV

Room 41A, floor at S wall between lockers

NAD

MB-785-03H-008 Black Mastic for Beige 12” x 12” floor tile w/red streaks

Room 41A, floor at S wall between lockers

NAD

MB-785-03-009 Black 12” x 12” floor tile

– Type V

Room 40, floor at locking jamb of access door

NAD

MB-785-03I-009 Clear Mastic for Black 12” x 12” floor tile

Room 40, floor at locking jamb of access door

NAD

MB-785-03-010 Black 12” x 12” floor tile

– Type V

Room 19, floor in SW corner NAD

MB-785-03J-010 Clear Mastic for Black 12” x 12” floor tile

Room 19, floor in SW corner NAD

MB-785-03-011 Light Brown 12” x 12” floor tile – Type VI

Room 13A, floor under metal shelf unit, NE corner

NAD

MB-785-03K-011 Mastic for light brown 12” x 12” floor tile

Room 13A, floor under metal shelf unit, NE corner

NAD

MB-785-03-012 Light Brown 12” x 12” floor tile – Type VI

Room 13A, floor under S end of shelf unit

NAD

MB-785-03L-012 Mastic for light brown 12” x 12” floor tile

Room 13A, floor under S end of shelf unit

NAD

MB-785-03-013 Dark brown 9” x 9” floor tile

Room 42, Floor near W wall doorway locking jamb

NAD

MB- 785-03M-013 Mastic for Dark brown 9” x 9” floor tile

Room 42, Floor near W wall doorway locking jamb

NAD

MB-785-03-014 Dark brown 9” x 9” floor tile

Room 42, Floor at E wall doorway to Room 44

NAD

MB-785-03N-014 Mastic for Dark brown 9” x 9” floor tile

Room 42, Floor at E wall doorway to Room 44

NAD

MB-785-04-001 Brown cove molding Room 4, W wall by entrance to locker room

NAD

MB-785-04A-001 Mastic for brown cove molding

Room 4, W wall by entrance to locker room

NAD

MB-785-04-002 Brown cove molding, no mastic present

Room 10, by locking jamb side of entry door

NAD

MB-785-04-003 Brown cove molding, no mastic present

Room 44A, at hinge jamb of access door

NAD

MB-785-06-001 Hard, white, friable joint mud on pipe elbow

Mechanical Room B, first floor, from elbow of scrap pipe found in Mechanical Room B on floor

65% Chrysotile

MB-785-06-002 Hard, white, friable pipe joint mud on pipe fitting

Mechanical Room B, first floor, NE corner 9’ above floor, elbow on 2” and 3” pipe

NAD

MB-785-06-003 Fiberglass Lagging w/cover

Mechanical Room B, first floor, NE corner, 9’ above floor, lagging near sample 002

NAD

MB-785-06-004 Elbow – fiberglass and foil w/white duct tape wrap

Room 6, first floor, SE corner above drop ceiling

NAD

MB-785-06-005 Hard, white, friable pipe joint mud on pipe fitting

Room 4, first floor, above entry door to Room 5, above drop ceiling, from elbow at capped end

65% Chrysotile

MB-785-06-006 Hard, white, friable pipe joint mud on pipe fitting

Room 35, first floor, SW corner from elbow on wall, turning towards heater

65% Chrysotile

MB-785-06-007 Hard, white, friable pipe joint mud on pipe fitting

Room 35, first floor, along S wall, 9’ above floor, 30’ E of SW corner, from 4” condensate trap line

45% Chrysotile

MB-785-06-008 Hard, white, friable pipe joint mud on pipe fitting

Room 37, first floor, from valve fitting above heater in SE corner

45% Chrysotile

MB-785-06-009 Hard, white, friable pipe joint mud on pipe fitting

Room 25, first floor, approx.

center of ceiling area – piping above ceiling (T-fitting)

15% Chrysotile

MB-785-07-001 Black duct insulation mastic

Approx. center of Room 4 above drop ceiling, E side of duct above ceiling disperser vent

7% Chrysotile

MB-785-07-002 Black duct insulation mastic

Room 14, first floor, approx center of N wall, above drop ceiling, from duct terminus

8 % Chrysotile

NAD=No asbestos detected

Of the sampled materials in Building MB 785, the following contained asbestos:

• 12” x 12” floor tile, unknown color, and black mastic found in a maintenance space (Room 12). NESHAPS Classification: Category I Non-friable ACM assessed as being in damaged condition. The floor tile had been overlain with carpet and carpet mastic; it contains 2% chrysotile asbestos and the mastic contains 5% chrysotile asbestos.

Photograph available here.

• Thermal System Insulation on piping in various locations throughout MB 785; the pipe insulation is fiberglass lagging with hard, troweled-on pipe-joint insulation. NESHAPS Classification: Friable RACM, removal required prior to repair, renovation or demolition.

The pipe joint mud contains chrysotile (15%-65%) asbestos; it was assessed as being in damaged condition and it lacks protective covering. The pipe insulation is normally accessible only to maintenance personnel, as it is either above drop ceiling systems or suspended high above open-ceiling shops. This material should be labeled, maintained and monitored for deterioration. Photograph available here.

• Black Duct Insulation Mastic found on duct insulation above Rooms 4, 13, 15, and 16.

NESHAPS Classification: Category I Non-friable ACM found in good condition. This material contains 7% to 8% Chrysotile asbestos but is relatively inaccessible to building occupants. HVAC maintenance personnel should be cautioned to avoid any work practices which would sand, grind, abrade, or pulverize the mastic. Photograph available here.

Table MB 785-2 lists the ACBM at Building MB 785, and Figure MB 785-ACBM shows the location and areal extent of the material.

Table MB 785-2 ACBM at Building MB 785

Material Sample ID Condition Potential for Disturbance

Material Quantity

NESHAPS

Class

12” x 12” Unknown color floor tile and black FT mastic

MB-785-03-005 Damaged High ~300 SF Category I Non-friable

ACM

TSI, Pipe Joint Insulation w/fiberglass lagging

MB785-06-001,

005,006,007,008 and 009

Damaged Moderate >100 Fittings, >1000 Linear

Feet

RACM

Black Duct Insulation

Mastic

MB-785-07-001

and 002

Good Low 125 LF Category I Non-friable

ACM

SF = Square feet LF= Linear Feet

Figure MB 785A-loc

Figure MB 785B-loc

Figure MB 785-ACBM

Moody AFB, Selected Buildings February 2010 Asbestos Inspection Report

Moody Air Force Base Building 785

South Elevation

Sample ID: MB-785-03-005; Doorway into Room 12

Description: Unknown color 12” x 12” floor tile and black floor tile mastic

Sample ID: MB-785-06-001; Scrap on floor of Mechanical Room B

Description: TSI, Fiberglass pipe lagging and mudded pipe joint insulation in canvass wrap

Sample ID: MB-785-06-009; above ceiling in Room 25

Description: TSI, Fiberglass pipe lagging and mudded pipe joint insulation in canvass wrap

Sample ID: MB-785-07-001; Approximate center of Room 4, above drop ceiling at disperser

Description: Black duct insulation mastic on foil/fiberglass duct insulation

TABLE OF CONTENTS
TABLES
ACRONYMS AND ABBREVIATIONS
1.0 PURPOSE, SCOPE, AND LIMITATIONS
1.1 Purpose
1.2 Site Information
Table 1-1
1.3 Scope of Services
1.4 Refocusing the Scope of Services
1.5 Limitations
2.0 ASBESTOS BACKGROUND INFORMATION
3.0 ASBESTOS INSPECTION
3.1 Modification of AHERA Inspection Method
3.2 Previous Investigation Reports
3.3 Sampling of Suspect ACBM
3.4 Sample Numbering
3.5 Assumed ACBM
3.6 Room Nu
3.7 Recommendations
4.0 INSPECTION RESULTS – MOODY AIR FORCE BASE
4.1 Building MB 104 (Child Development Center)
Table MB 104-1
Table MB 104-2
4.2 Building MB 112 (Accounting and Finance
Table MB 112-1
4.3 Building MB 134 (Moody AFB Post Office)
Table MB 134-1
Table MB 134-2
4.4 Building MB 325 (Moody Inn Dormitory)
Table MB 325-1
Table MB 325-2
4.5 Building MB 571 (Dining Hall)
Table MB 571-1
Table MB 571-2
4.6 Building MB 574 (Air Conditioning Plant)
Table MB 574-1
Table MB 574-2
4.7 Building MB 617 (Security/Police)
Table MB 617-1
4.8 Building MB 717 (Paint Hangar)
Table MB 717-1
Table MB 717-2
4.9 Building MB 757 (Communications)
Table MB 757-1
Table MB 757-2
4.10 Building MB 768 (Painting Hanger/Storage)
Table MB 768-1
Table MB 768-2
4.11 Building MB 769 (Refueling Maintenance Shop)
Table MB 769-1
4.12 Building MB 770 (A10 AMU)
Table MB 770-1
4.13 Building MB 772 (A-10 Parts Store)
Table MB 772-1
4.14 Building MB 776 (CAMS Office)
Table MB 776-1
4.15 Building MB 785 (Sheet Metal and Battery Shop)
Table MB 785-1
Table MB 785-2
4.16 Building MB 788 (A10 Fuels System MX and MX Hangar)
Table MB 788-1
Table MB 788-2
4.17 Building MB 803 (COMM BIDDS Switching)
Table MB 803-1
4.18 Building MB 804 (Thrift Shop)
Table MB 804-1
Table MB 804-2
4.19 Building MB 841 (Base General Storage Facility)
Table MB 841-1
4.20 Building MB 901 (Moody Field Club)
Table MB 901-1
4.21 Building MB 907 (Equipment Rental/MWR Warehouse)
Table MB 907-1
Table MB 907-2
4.22 Building MB 908 (Airman’s Attic and Multi-purpose Storage Building)
Table MB 908-1
Table MB 908-2
4.23 Building MB 917 (Army COE)
Table MB 917-1
Table MB 917-2
4.24 Building MB 918 (Headquarters 23rd CES)
Table MB 918-1
Table MB 918-2
4.25 Building MB 921 (SABER Contractor)
Table MB 921-1
4.26 Building MB 932 (Supply, Contracting and 820thSFS)
Table MB 932-1
Table MB 932-2 ACBM at Building MB 932
4.27 Building MB 934 (Base Supply, Paint and HazMat Storage)
Table MB 934-1
Table MB 934-2
4.28 Building MB 976 (Motor Pool Special Purpose and Heavy Equipment VehicleMaintenance)
Table MB 976-1
4.29 Building MB 978 (CE Storage)
4.30 Building MB 979 (Honor Guard and CEH Warehouse)
Table MB 979-1
4.31 Building MB 980 (CE Material Control Office and Warehouse)
Table MB 980-1
Table MB 980-2
4.32 Building MB 1107 (Rocket Test Cell)
Table MB 1107-1
4.33 Building MB 1108 (Missile Assembly Shop)
Table MB 1108-1
Table MB 1108-2
4.34 Building MB 1111 (Munitions Maintenance Administration Building)
Table MB 1111-1
Table MB 1111-2
4.35 Building MB 1219 (PME Storage)
Table MB 1219-1
Table MB 1219-2
4.36 Building MB 1220 (Youth Center and CE Storage)
Table MB 1220-1
Table MB 1220-2
4.37 Building MB 1500 (820th Security Forces Group)
Table MB 1500-1
4.38 Building MB 1501 (Communications Receiver Building)
Table MB 1501-1
4.39 Building MB 1806 (Golf Course Clubhouse)
Table MB 1806-1
APPENDIX A FLOOR PLANS FOR INSPECTED BUILDINGS
Figure MB 104-loc 1
Figure MB 104-ACBM
Figure MB 112-loc
Figure MB 134-loc
Figure MB 134-ACBM
Figure MB 325A-loc
Figure MB 325B-loc
Figure MB 325A-ACBM
Figure MB 325B-ACBM
Figure MB 571-loc
Figure MB 571-ACBM
Figure MB 574-loc
Figure MB 574-ACBM
Figure MB 617-loc
Figure MB 717A-loc
Figure MB 717B-loc
Figure MB 717A-ACBM
Figure MB 717B-ACBM
Figure MB 757-loc
Figure MB 757-ACBM
Figure MB 768-loc
Figure MB 768-ACBM
Figure MB 769-loc
Figure MB 770-loc
Figure MB 772-loc
Figure MB 776-loc
Figure MB 785A-loc
Figure MB 785B-loc
Figure MB 785-ACBM
Figure MB 788-loc
Figure MB 788-ACBM
Figure MB 803-loc
Figure MB 804-loc
Figure MB 804-ACBM
Figure MB 841-loc
Figure MB 901-loc
Figure MB 907-loc
Figure MB 907-ACBM
Figure MB 908-loc
Figure MB 908-ACBM
Figure MB 917-loc
Figure MB 917-ACBM
Figure MB 918A-loc
Figure MB 918B-loc
Figure MB 918C-loc
Figure MB 918A-ACBM
Figure MB 918B-ACBM
Figure MB 918C-ACBM
Figure MB 921-loc
Figure MB 932A-loc
Figure MB 932B-loc
Figure MB 932C-loc
Figure MB 932D-loc
Figure MB 932A-ACBM
Figure MB 932B-ACBM
Figure MB 932C-ACBM
Figure MB 932D-ACBM
Figure MB 934-loc
Figure MB 934-ACBM
Figure MB 976-loc
Figure MB 978-loc
Figure MB 979-loc
Figure MB 980A-loc
Figure MB 980B-loc
Figure MB 980A-ACBM
Figure MB 980B-ACBM
Figure MB 1107-loc
Figure MB 1108-loc
Figure MB 1108-ACBM
Figure MB 1111-loc
Figure MB 1111-ACBM
Figure MB 1219-loc
Figure MB 1219-ACBM
Figure MB 1220-loc
Figure MB 1220-ACBM
Figure MB 1500-loc
Figure MB 1501-loc
Figure MB 1806-loc
APPENDIX B PHOTOGRAPHS OF ACBM
Moody Air Force Base Building 104
Moody Air Force Base Building 112
Moody Air Force Base Building 134
Moody Air Force Base Building 325
Moody Air Force Base Building 571
Moody Air Force Base Building 574
Moody Air Force Base Building 617
Moody Air Force Base Building 717
Moody Air Force Base Building 757
Moody Air Force Base Building 768
Moody Air Force Base Building 769
Moody Air Force Base Building 770
Moody Air Force Base Building 772
Moody Air Force Base Building 776
Moody Air Force Base Building 785
Moody Air Force Base Building 788
Moody Air Force Base Building 803
Moody Air Force Base Building 804
Moody Air Force Base Building 841
Moody Air Force Base Building 901
Moody Air Force Base Building 907
Moody Air Force Base Building 908
Moody Air Force Base Building 917
Moody Air Force Base Building 918
Moody Air Force Base Building 921
Moody Air Force Base Building 932
Moody Air Force Base Building 934
Moody Air Force Base Building 976
Moody Air Force Base Building 978
Moody Air Force Base Building 979
Moody Air Force Base Building 980
Moody Air Force Base Building 1107
Moody Air Force Base Building 1108
Moody Air Force Base Building 1111
Moody Air Force Base Building 1219
Moody Air Force Base Building 1220
Moody Air Force Base Building 1500
Moody Air Force Base Building 1501
Moody Air Force Base Building 1806

Figure MB 803-loc