23 07 00-1 03/07/12
SECTION 23 07 00
THERMAL INSULATION FOR MECHANICAL SYSTEMS
PART 1 GENERAL
1.1 REFERENCES
1.1.1 The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only. Unless other wise noted, the latest published version and/or revision shall be used.
1.1.1.1 AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
a. ASHRAE 90.1 - IP Energy Standard for Buildings Except Low-Rise Residential
Buildings, I-P Edition
b. ASHRAE 90.2 Energy Efficient Design of Low-Rise Residential Buildings
1.1.1.2 ASTM INTERNATIONAL (ASTM)
a. ASTM A 167 Standard Specification for Stainless and Heat-Resisting
Chromium-Nickel Steel Plate, Sheet, and Strip
b. ASTM A 240 Standard Specification for Chromium and Chromium-Nickel
Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
c. ASTM A 580 Standard Specification for Stainless Steel Wire
d. ASTM B 209 Standard Specification for Aluminum and Aluminum-Alloy
Sheet and Plate
e. ASTM C 1136 Standard Specification for Flexible, Low Permeance Vapor
Retarders for Thermal Insulation
f. ASTM C 195 Standard Specification for Mineral Fiber Thermal Insulating
Cement
g. ASTM C 449 Standard Specification for Mineral Fiber Hydraulic-Setting
Thermal Insulating and Finishing Cement
h. ASTM C 547 Standard Specification for Mineral Fiber Pipe Insulation
i. ASTM C 553 Standard Specification for Mineral Fiber Blanket Thermal
Insulation for Commercial and Industrial Applications
j. ASTM C 592 Standard Specification for Mineral Fiber Blanket Insulation and
Blanket-Type Pipe Insulation (Metal-Mesh Covered) (Industrial
Type)
k. ASTM C 612 Mineral Fiber Block and Board Thermal Insulation
l. ASTM C 647 Properties and Tests of Mastics and Coating Finishes for Thermal
Insulation
23 07 00-2 03/07/12
m. ASTM C 920 Standard Specification for Elastomeric Joint Sealants
n. ASTM C 921 Standard Practice for Determining the Properties of Jacketing
Materials for Thermal Insulation
o. ASTM D 774 Bursting Strength of Paper
p. ASTM D 882 Tensile Properties of Thin Plastic Sheeting
q. ASTM E 2231 Specimen Preparation and Mounting of Pipe and Duct Insulation
Materials to Assess Surface Burning Characteristics
r. ASTM E 84 Standard Test Method for Surface Burning Characteristics of
Building Materials
s. ASTM E 96 Standard Test Methods for Water Vapor Transmission of
Materials
1.1.1.3 MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
a. MSS SP-69 Standard for Pipe Hangers and Supports - Selection and
Application
1.1.1.4 MIDWEST INSULATION CONTRACTORS ASSOCIATION (MICA)
a. MICA Insulation Stds National Commercial & Industrial Insulation Standards
1.1.1.5 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
a. NFPA 255 Standard Method of Test of Surface Burning Characteristics of
Building Materials
1.1.1.6 U.S. DEPARTMENT OF DEFENSE (DOD)
a. MIL-A-3316 Adhesives, Fire-Resistant, Thermal Insulation
1.1.1.7 UNDERWRITERS LABORATORIES (UL)
a. UL 723 Standard for Test for Surface Burning Characteristics of Building
Materials
1.2 SYSTEM DESCRIPTION
1.2.1 Field-applied insulation and accessories on mechanical systems shall be as specified herein;
factory-applied insulation is specified under the piping, duct or equipment to be insulated. Field applied insulation materials required for use on Government-furnished items as listed in the
SPECIAL CONTRACT REQUIREMENTS shall be furnished and installed by the Contractor.
1.3 GENERAL QUALITY CONTROL
1.3.1 Industry Standards
1.3.1.1 Provide insulation systems in accordance with the approved MICA National Insulation
Standards plates as supplemented by this specification.
23 07 00-3 03/07/12
1.3.2 Standard Products
1.3.2.1 Provide field-applied insulation for heating, ventilating, and cooling (HVAC) air distribution systems and piping systems which are located within, on, under, and adjacent to buildings; and for plumbing systems. Materials shall be the standard products of manufacturers regularly engaged in the manufacture of such products and shall essentially duplicate items that have been in satisfactory use for at least 2 years prior to bid opening.
1.3.3 Surface Burning Characteristics
1.3.3.1 Unless otherwise specified, insulation shall have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84. Flame spread, and smoke developed indexes, shall be determined by ASTM E 84, NFPA 255 or UL
723. Insulation shall be tested in the same density and installed thickness as the material to be used in the actual construction. Test specimens shall be prepared and mounted according to
ASTM E 2231. Insulation materials located exterior to the building perimeter are not required to be fire rated.
1.3.4 Identification of Materials
1.3.4.1 Packages or standard containers of insulation, jacket material, cements, adhesives, and coatings delivered for use, and samples required for approval shall have manufacturer's stamp or label attached giving the name of the manufacturer and brand, and a description of the material.
1.4 SUBMITTALS
1.4.1 Government approval may be required on any of the following items. Items requiring submittals will be listed on the AF Form 66. Provide copies of all submittals per the requirements in Section
01 33 00, Submittal Procedures, or as listed on the AF Form 66:
1.4.1.1 SD-02 Shop Drawings
MICA Plates
Pipe Insulation Systems and Associated Accessories
Equipment Insulation Systems and Associated Accessories
After approval of materials and prior to applying insulation, submit a booklet containing completed MICA Insulation Stds plates detailing each insulating system for each pipe, duct, or equipment insulating system.
a. The MICA plates shall detail the materials to be installed the specific insulation application.
Submit all MICA plates required showing the entire insulating system, including plates required to show insulation penetrations, vessel bottom and top heads, legs, and skirt insulation as applicable. The MICA plates shall present all variations of insulation systems including locations, materials, vaporproofing, jackets and insulation accessories.
b. If the Contractor elects to submit detailed drawings instead of edited MICA Plates, the detail drawings shall be technically equivalent to the edited MICA Plate submittal.
1.4.1.2 SD-03 Product Data
a. Pipe Insulation Systems
23 07 00-4 03/07/12
b. Equipment Insulation Systems
(1) A complete list of materials, including manufacturer's descriptive technical literature, performance data, catalog cuts, and installation instructions. The product number, k-value, thickness and furnished accessories including adhesives, sealants and jackets for each mechanical system requiring insulation shall be included. The product data must be copywrited, have an identifying or publication number, and shall have been published prior to the issuance date of this solicitation. Materials furnished under this section of the specification shall be submitted together in a booklet and in conjunction with the MICA plates booklet (SD-02). Annotate the product data to indicate which MICA plate is applicable.
1.5 STORAGE
1.5.1 Materials shall be delivered in the manufacturer's unopened containers. Materials delivered and placed in storage shall be provided with protection from weather, humidity, dirt, dust and other contaminants. The Contracting Officer may reject insulation material and supplies that become dirty, dusty, wet, or contaminated by some other means.
PART 2 PRODUCTS
2.1 GENERAL MATERIALS
Insulation material shall conform to Table 1. Insulation thickness shall be as listed in Table 2.
Insulation exterior shall be cleanable, grease resistant, non-flaking and non-peeling. Materials shall be compatible and shall not contribute to corrosion, soften, or otherwise attack surfaces to which applied in either wet or dry state. Materials to be used on stainless steel surfaces shall meet ASTM
C 795 requirements. Materials shall conform to the following:
2.1.1 Adhesives
2.1.1.1 Acoustical Lining Insulation Adhesive
a. Adhesive shall be a nonflammable, fire-resistant adhesive conforming to ASTM C 916, Type I.
2.1.1.2 Mineral Fiber Insulation Cement
a. Cement shall be in accordance with ASTM C 195.
2.1.1.3 Lagging Adhesive
a. Lagging is the material used for thermal insulation, especially around a cylindrical object. This may include the insulation as well as the cloth/material covering the insulation. Lagging adhesives shall be nonflammable and fire-resistant and shall have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with
ASTM E 84. Adhesive shall be MIL-A-3316, Class 1, pigmented white or red and be suitable for bonding fibrous glass cloth to faced and unfaced fibrous glass insulation board; for bonding cotton brattice cloth to faced and unfaced fibrous glass insulation board; for sealing edges of and bonding glass tape to joints of fibrous glass board; for bonding lagging cloth to thermal insulation; or Class 2 for attaching fibrous glass insulation to metal surfaces. Lagging adhesives shall be applied in strict accordance with the manufacturer's recommendations for
23 07 00-5 03/07/12 pipe and duct insulation.
2.1.2 Contact Adhesive
2.1.2.1 Adhesives may be any of, but not limited to, the neoprane based, rubber based, or elastomeric type that have a maximum flame spread index of 25 and a maximum smoke developed index of
50 when tested in accordance with ASTM E 84. The adhesive shall not adversely affect, initially or in service, the insulation to which it is applied, nor shall it cause any corrosive effect on metal to which it is applied. Any solvent dispersing medium or volatile component of the adhesive shall have no objectionable odor and shall not contain any benzene or carbon tetrachloride. The dried adhesive shall not emit nauseous, irritating, or toxic volatile matters or aerosols when the adhesive is heated to any temperature up to 212 degrees F. The dried adhesive shall be nonflammable and fire resistant. Natural cross-ventilation, local (mechanical) pickup, and/or general area (mechanical) ventilation shall be used to prevent an accumulation of solvent vapors, keeping in mind the ventilation pattern must remove any heavier-than-air solvent vapors from lower levels of the workspaces. Gloves and spectacle-type safety glasses are recommended in accordance with safe installation practices.
2.1.3 Caulking
2.1.3.1 ASTM C 920, Type S, Grade NS, Class 25, Use A.
2.1.4 Corner Angles
2.1.4.1 Nominal 0.016 inch aluminum 1 by 1 inch with factory applied kraft backing. Aluminum shall be ASTM B 209M( ASTM B 209), Alloy 3003, 3105, or 5005.
2.1.5 Finishing Cement
2.1.5.1 ASTM C 449: Mineral fiber hydraulic-setting thermal insulating and finishing cement. All cements that may come in contact with Austenitic stainless steel must comply with ASTM C
795.
2.1.6 Fibrous Glass Cloth and Glass Tape
2.1.6.1 Fibrous glass cloth, with 20X20 maximum mesh size, and glass tape shall have maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84. Tape shall be 4 inch wide rolls. Class 3 tape shall be 4.5 ounces/square yard.
2.1.7 Staples
2.1.7.1 Outward clinching type monel.
2.1.8 Jackets
2.1.8.1 Aluminum Jackets
a. Aluminum jackets shall be corrugated, embossed or smooth sheet, 0.016 inch nominal thickness; ASTM B 209M( ASTM B 209), Temper H14, Temper H16, Alloy 3003, 5005, or
3105. Corrugated aluminum jacket shall not be used outdoors. Aluminum jacket securing bands shall be Type 304 stainless steel, 0.015 inch thick, 1/2 inch wide for pipe under 12 inch
23 07 00-6 03/07/12 diameter and 3/4 inch wide for pipe over 12 inch and larger diameter. Aluminum jacket circumferential seam bands shall be 2 by 0.016 inch aluminum matching jacket material.
Bands for insulation below ground shall be 3/4 by 0.020 inch thick stainless steel, or fiberglass reinforced tape. The jacket may, at the option of the Contractor, be provided with a factory fabricated Pittsburg or "Z" type longitudinal joint. When the "Z" joint is used, the bands at the circumferential joints shall be designed by the manufacturer to seal the joints and hold the jacket in place.
2.1.8.2 Polyvinyl Chloride (PVC) Jackets
a. Polyvinyl chloride (PVC) jacket and fitting covers shall have high impact strength, UV resistant rating or treatment and moderate chemical resistance with minimum thickness 0.030 inch.
2.1.8.3 Vapor Barrier/Weatherproofing Jacket
a. Vapor barrier/weatherproofing jacket shall be laminated self-adhesive, greater than 3 plys standard grade, silver, white, black and embossed or greater than 8 ply 2.9 mils adhesive; with
0.0000 permeability when tested per ASTM E 96; heavy duty, white or natural; and UV resistant.
2.1.9 Vapor Retarder Required
ASTM C 921, Type I, minimum puncture resistance 50 Beach units on all surfaces except concealed ductwork, where a minimum puncture resistance of 25 Beach units is acceptable.
Minimum tensile strength, 35 pounds/inch width. ASTM C 921, Type II, minimum puncture resistance 25 Beach units, tensile strength minimum 20 pounds/inch width. Jackets used on insulation exposed in finished areas shall have white finish suitable for painting without sizing.
Based on the application, insulation materials that require factory applied jackets are mineral fiber, cellular glass, polyisocyanurate, and phenolic foam. Insulation materials that do not require jacketing are flexible elastomerics. All non-metallic jackets shall have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM
E 84.
2.1.9.1 White Vapor Retarder All Service Jacket (ASJ)
a. Standard reinforced fire retardant jacket for use on hot/cold pipes, ducts, or equipment. Vapor retarder jackets used on insulation exposed in finished areas shall have white finish suitable for painting without sizing.
2.1.9.2 Vapor Retarder/Vapor Barrier Mastic Coatings
a. The vapor barrier shall be self adhesive (minimum 2 mils adhesive, 3 mils embossed) greater than 3 plys standard grade, silver, white, black and embossed white jacket for use on hot/cold pipes. Less than 0.02 permeability when tested per ASTM E 96. Meeting UL 723 or ASTM E
84 flame and smoke requirements; UV resistant.
b. The vapor retarder coating shall be fire and water resistant and appropriately selected for either outdoor or indoor service. Color shall be white. The water vapor permeance of the compound shall be determined according to procedure B of ASTM E 96 utilizing apparatus described in
ASTM E 96. The coating shall be a nonflammable, fire resistant type. All other application and service properties shall be in accordance with ASTM C 647.
2.1.9.3 Laminated Film Vapor Retarder
23 07 00-7 03/07/12
a. ASTM C 1136, Type I, maximum moisture vapor transmission 0.02 perms, minimum puncture resistance 50 Beach units on all surfaces except concealed ductwork, where Type II, maximum moisture vapor transmission 0.02 perms, a minimum puncture resistance of 25 Beach units is acceptable. Vapor retarder shall have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84.
2.1.9.4 Polyvinylidene Chloride (PVDC) Film Vapor Retarder
a. The PVDC film vapor retarder shall have a maximum moisture vapor transmission of 0.02 perms, minimum puncture resistance of 150 Beach units, a minimum tensile strength in any direction of 30 lb/inch when tested per ASTM D 882, and a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84.
2.1.9.5 Polyvinylidene Chloride Vapor Retarder Adhesive Tape
a. Requirements must meet the same as specified for Laminated Film Vapor Retarder above.
2.1.9.6 Vapor Barrier
a. The vapor barrier shall be greater than 3 ply self adhesive laminate -white vapor barrier jacket-superior performance (less than 0.0000 permeability when tested per ASTM E 96. Vapor barrier shall meet UL 723 or ASTM E 84 25 flame and 50 smoke requirements; and UV resistant. Minimum burst strength 185 psi per ASTM D 774. Tensile strength 68 lb/inch width
(PSTC-1000). Tape shall be as specified for laminated film vapor barrier above.
2.1.10 Vapor Retarder Not Required
2.1.10.1 ASTM C 921, Type II, Class D, minimum puncture resistance 50 Beach units on all surfaces except ductwork, where Type IV, maximum moisture vapor transmission 0.10, a minimum puncture resistance of 25 Beach units is acceptable. Jacket shall have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with
ASTM E 84.
2.1.11 Wire
2.1.11.1 Soft annealed ASTM A 580 Type 302, 304 or 316 stainless steel, 16 or 18 gauge.
2.1.12 Insulation Bands
2.1.12.1 Insulation bands shall be 1/2 inch wide; 26 gauge stainless steel.
2.1.13 Sealants
2.1.13.1 Sealants shall be chosen from the butyl polymer type, the styrene-butadiene rubber type, or the butyl type of sealants. Sealants shall have a maximum moisture vapor transmission of 0.02 perms, and a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84.
2.2 PIPE INSULATION SYSTEMS
The Contractor shall comply with EPA requirements in accordance with Section 01 62 35
Recycled/Recovered Materials. Pipe insulation materials shall be limited to those listed herein and file:///E:/Formatted%20by%20Monica/01%2062%2035.doc
23 07 00-8 03/07/12 shall meet the following requirements:
2.2.1 Aboveground Hot Pipeline (60 deg. F and above)
2.2.1.1 Insulation for outdoor, indoor, exposed or concealed applications shall meet the following requirements. Supply the insulation with manufacturer's recommended factory-applied jacket/vapor barrier.
a. Mineral Fiber: ASTM C 547, Types I, II or III, supply the insulation with manufacturer's recommended factory-applied jacket.
b. Calcium Silicate: ASTM C 533, Type I indoor only, or outdoors above 250 degrees F pipe temperature. Supply insulation with the manufacturer's recommended factory-applied jacket/vapor barrier.
2.3 EQUIPMENT INSULATION SYSTEMS
2.3.1 Insulate equipment and accessories as specified in Tables 4 and 5. In outside locations, provide insulation 1/2 inch thicker than specified. Increase the specified insulation thickness for equipment where necessary to equal the thickness of angles or other structural members to make a smooth, exterior surface.
PART 3 EXECUTION
3.1 APPLICATION – GENERAL
Insulation shall only be applied to unheated and uncooled piping and equipment. Flexible elastomeric cellular insulation shall not be compressed at joists, studs, columns, ducts, hangers, etc.
The insulation shall not pull apart after a one hour period; any insulation found to pull apart after one hour, shall be replaced.
3.1.1 Installation
3.1.1.1 Except as otherwise specified, material shall be installed in accordance with the manufacturer's written instructions. Insulation materials shall not be applied until tests specified in other sections of this specification are completed. Material such as rust, scale, dirt and moisture shall be removed from surfaces to receive insulation. Insulation shall be kept clean and dry.
Insulation shall not be removed from its shipping containers until the day it is ready to use and shall be returned to like containers or equally protected from dirt and moisture at the end of each workday. Insulation that becomes dirty shall be thoroughly cleaned prior to use. If insulation becomes wet or if cleaning does not restore the surfaces to like new condition, the insulation will be rejected, and shall be immediately removed from the jobsite. Joints shall be staggered on multi layer insulation. Mineral fiber thermal insulating cement shall be mixed with demineralized water when used on stainless steel surfaces. Insulation, jacketing and accessories shall be installed in accordance with MICA Insulation Stds plates except where modified herein or on the drawings.
3.1.2 Firestopping
3.1.2.1 Where pipes and ducts pass through fire walls, fire partitions, above grade floors, and fire rated
23 07 00-9 03/07/12 chase walls, the penetration shall be sealed with fire stopping materials as specified in Section
07 84 00 Firestopping.
3.1.3 Painting and Finishing
3.1.3.1 Painting shall be as specified in Section 09 90 00 Paints and Coatings.
3.1.4 Installation of Flexible Elastomeric Cellular Insulation
3.1.4.1 Flexible elastomeric cellular insulation shall be installed with seams and joints sealed with rubberized contact adhesive. Flexible elastomeric cellular insulation shall not be used on surfaces greater than 200 degrees F. Seams shall be staggered when applying multiple layers of insulation. Insulation exposed to weather and not shown to have jacketing shall be protected with two coats of UV resistant finish or PVC or metal jacketing as recommended by the manufacturer after the adhesive is dry and cured. A brush coating of adhesive shall be applied to both butt ends to be joined and to both slit surfaces to be sealed. The adhesive shall be allowed to set until dry to touch but tacky under slight pressure before joining the surfaces.
Insulation seals at seams and joints shall not be capable of being pulled apart one hour after application. Insulation that can be pulled apart one hour after installation shall be replaced.
3.1.5 Welding
3.1.5.1 No welding shall be done on piping, duct or equipment without written approval of the
Contracting Officer. The capacitor discharge welding process may be used for securing metal fasteners to duct.
3.1.6 Pipes/Ducts/Equipment which Require Insulation
3.1.6.1 Insulation is required on all pipes, ducts, or equipment, except for omitted items, as specified.
3.2 PIPE INSULATION SYSTEMS INSTALLATION
Install pipe insulation systems in accordance with the approved MICA Insulation Stds plates as supplemented by the manufacturer's published installation instructions.
3.2.1 Pipe Insulation
3.2.1.1 General
Pipe insulation shall be installed on aboveground hot and cold pipeline systems as specified below to form a continuous thermal retarder/barrier, including straight runs, fittings and appurtenances unless specified otherwise. Installation shall be with full length units of insulation and using a single cut piece to complete a run. Cut pieces or scraps abutting each other shall not be used. Pipe insulation shall be omitted on the following:
a. Pipe used solely for fire protection.
b. Chromium plated pipe to plumbing fixtures. However, fixtures for use by the physically handicapped shall have the hot water supply and drain, including the trap, insulated where exposed.
c. Sanitary drain lines.
file:///E:/Formatted%20by%20Monica/07%2084%2000.doc file:///E:/Formatted%20by%20Monica/09%2090%2000.doc
23 07 00-10 03/07/12
d. Air chambers.
e. Adjacent insulation.
f. ASME stamps.
g. Access plates of fan housings.
h. Cleanouts or handholes.
3.2.1.2 Pipes Passing Through Walls, Roofs, and Floors
a. Pipe insulation shall be continuous through the sleeve.
b. An aluminum jacket or vapor barrier/weatherproofing - self adhesive jacket (minimum 2 mils adhesive, 3 mils embossed) less than 0.0000 permeability, greater than 3 ply standard grade, silver, white, black and embossed with factory applied moisture retarder shall be provided over the insulation wherever penetrations require sealing.
c. Where pipes penetrate interior walls, the aluminum jacket or vapor barrier/weatherproofing -self adhesive jacket (minimum 2 mils adhesive, 3 mils embossed) less than 0.0000 permeability, greater than 3 plys standard grade, silver, white, black and embossed shall extend
2 inches beyond either side of the wall and shall be secured on each end with a band.
d. Where penetrating floors, the aluminum jacket shall extend from a point below the backup material to a point 10 inches above the floor with one band at the floor and one not more than 1 inch from the end of the aluminum jacket.
e. Where penetrating waterproofed floors, the aluminum jacket shall extend from below the backup material to a point 2 inches above the flashing with a band 1 inch from the end of the aluminum jacket.
f. Where penetrating exterior walls, the aluminum jacket required for pipe exposed to weather shall continue through the sleeve to a point 2 inches beyond the interior surface of the wall.
g. Where penetrating roofs, pipe shall be insulated as required for interior service to a point flush with the top of the flashing and sealed with vapor retarder coating. The insulation for exterior application shall butt tightly to the top of flashing and interior insulation. The exterior aluminum jacket shall extend 2 inches down beyond the end of the insulation to form a counter flashing. The flashing and counter flashing shall be sealed underneath with caulking.
h. For hot water pipes supplying lavatories or other similar heated service that requires insulation, the insulation shall be terminated on the backside of the finished wall. The insulation termination shall be protected with two coats of vapor barrier coating with a minimum total thickness of 1/16 inch applied with glass tape embedded between coats (if applicable). The coating shall extend out onto the insulation 2 inches and shall seal the end of the insulation.
Glass tape seams shall overlap 1 inch. The annular space between the pipe and wall penetration shall be caulked with approved fire stop material. The pipe and wall penetration shall be covered with a properly sized (well fitting) escutcheon plate. The escutcheon plate shall overlap the wall penetration at least 3/8 inches.
i. For domestic cold water pipes supplying lavatories or other similar cooling service that requires insulation, the insulation shall be terminated on the finished side of the wall (i.e., insulation must cover the pipe throughout the wall penetration). The insulation shall be protected with two coats of vapor barrier coating with a minimum total thickness of 1/16 inch. The coating shall extend out onto the insulation 2 inches and shall seal the end of the insulation. The annular space between the outer surface of the pipe insulation and the wall penetration shall be caulked with an approved fire stop material having vapor retarder properties. The pipe and wall
23 07 00-11 03/07/12 penetration shall be covered with a properly sized (well fitting) escutcheon plate. The escutcheon plate shall overlap the wall penetration by at least 3/8 inches.
3.2.1.3 Pipes Passing Through Hangers
a. Insulation, whether hot or cold application, shall be continuous through hangers. All horizontal pipes 2 inches and smaller shall be supported on hangers with the addition of a Type 40 protection shield to protect the insulation in accordance with MSS SP-69. Whenever insulation shows signs of being compressed, or when the insulation or jacket shows visible signs of distortion at or near the support shield, insulation inserts as specified below for piping larger than 2 inches shall be installed, or factory insulated hangers (designed with a load bearing core) can be used.
b. Horizontal pipes larger than 2 inches at 60 degrees F and above shall be supported on hangers in accordance with MSS SP-69, and Section 22 00 00 Plumbing, General Purpose .
c. Horizontal pipes larger than 2 inches and below 60 degrees F shall be supported on hangers with the addition of a Type 40 protection shield in accordance with MSS SP-69. An insulation insert of cellular glass, calcium silicate (or perlite above 80 degrees F), or the necessary strength polyisocyanurate shall be installed above each shield. The insert shall cover not less than the bottom 180-degree arc of the pipe. Inserts shall be the same thickness as the insulation, and shall extend 2 inches on each end beyond the protection shield. When insulation inserts are required per the above, and the insulation thickness is less than 1 inch, wooden or cork dowels or blocks may be installed between the pipe and the shield to prevent the weight of the pipe from crushing the insulation, as an option to installing insulation inserts.
The insulation jacket shall be continuous over the wooden dowel, wooden block, or insulation insert.
d. Vertical pipes shall be supported with either Type 8 or Type 42 riser clamps with the addition of two Type 40 protection shields in accordance with MSS SP-69 covering the 360-degree arc of the insulation. An insulation insert of cellular glass or calcium silicate shall be installed between each shield and the pipe. The insert shall cover the 360-degree arc of the pipe. Inserts shall be the same thickness as the insulation, and shall extend 2 inches on each end beyond the protection shield. When insulation inserts are required per the above, and the insulation thickness is less than 1 inch, wooden or cork dowels or blocks may be installed between the pipe and the shield to prevent the hanger from crushing the insulation, as an option instead of installing insulation inserts. The insulation jacket shall be continuous over the wooden dowel, wooden block, or insulation insert. The vertical weight of the pipe shall be supported with hangers located in a horizontal section of the pipe. When the pipe riser is longer than 30 feet, the weight of the pipe shall be additionally supported with hangers in the vertical run of the pipe that are directly clamped to the pipe, penetrating the pipe insulation. These hangers shall be insulated and the insulation jacket sealed as indicated herein for anchors in a similar service.
e. Inserts shall be covered with a jacket material of the same appearance and quality as the adjoining pipe insulation jacket, shall overlap the adjoining pipe jacket 1-1/2 inches, and shall be sealed as required for the pipe jacket. The jacket material used to cover inserts in flexible elastomeric cellular insulation shall conform to ASTM C 1136, Type 1, and is allowed to be of a different material than the adjoining insulation material.
3.2.1.4 Flexible Elastomeric Cellular Pipe Insulation
a. Flexible elastomeric cellular pipe insulation shall be tubular form for pipe sizes 6 inches and less. Grade 1, Type II sheet insulation used on pipes larger than 6 inches shall not be stretched around the pipe. On pipes larger than 12 inches, the insulation shall be adhered directly to the file:///E:/Formatted%20by%20Monica/22%2000%2000.doc
23 07 00-12 03/07/12 pipe on the lower 1/3 of the pipe. Seams shall be staggered when applying multiple layers of insulation. Sweat fittings shall be insulated with miter-cut pieces the same size as on adjacent piping. Screwed fittings shall be insulated with sleeved fitting covers fabricated from miter-cut pieces and shall be overlapped and sealed to the adjacent pipe insulation.
3.2.1.5 Pipes in high abuse areas.
a. In high abuse areas such as janitor closets and traffic areas in equipment rooms, kitchens, and mechanical rooms, welded PVC, stainless steel, aluminum or flexible laminate cladding
(comprised of elastomeric, plastic or metal foil laminate) laminated self-adhesive (minimum 2 mils adhesive, 3 mils embossed) vapor barrier/weatherproofing jacket, - less than 0.0000 permeability; (greater than 3 ply, standard grade, silver, white, black and embossed) jackets shall be utilized. Pipe insulation to the 6 foot level shall be protected.
3.2.1.6 Pipe Insulation Material and Thickness
TABLE 1
Insulation Material For Piping (°F)
Service Material Spec. Type Class Vapor Retarder/
Vapor Barrier
Required
Heating Hot Mineral Fiber ASTM C 547 I 1 No
Water Supply &
Return
(Max 250°F)
23 07 00-13 03/07/12
TABLE 2
Piping Insulation Thickness (inch and °F)
Tube And Pipe Size (Inches)
Service Material <1 1-<1.5 1.5-<4 4-<8 >or = to 8
Heating Hot Water Mineral Fiber 1.5 1.5 2 2 2
Supply & Return, (Max.
250°F)
3.2.1.7 Installing Insulation for Straight Runs Hot and Cold Pipe
a. Insulation shall be applied to the pipe with joints tightly butted. All butted joints and ends shall be sealed with joint sealant and sealed with a vapor retarder coating, greater than 3 ply laminate jacket - less than 0.0000 perm adhesive tape or PVDC adhesive tape.
b. Longitudinal laps of the jacket material shall overlap not less than 1-1/2 inches. Butt strips 3 inches wide shall be provided for circumferential joints.
c. Laps and butt strips shall be secured with adhesive and stapled on 4 inch centers if not factory self-sealing. If staples are used, they shall be sealed per item "e." below. Note that staples are not required with cellular glass systems.
d. Factory self-sealing lap systems may be used when the ambient temperature is between 40 and
120 degrees F during installation. The lap system shall be installed in accordance with manufacturer's recommendations. Stapler shall be used only if specifically recommended by the manufacturer. Where gaps occur, the section shall be replaced or the gap repaired by applying adhesive under the lap and then stapling.
e. All Staples, including those used to repair factory self-seal lap systems, shall be coated with a vapor retarder coating or PVDC adhesive tape or greater than 3 ply laminate jacket - less than
0.0000 perm adhesive tape. All seams, except those on factory self-seal systems shall be coated with vapor retarder coating or PVDC adhesive tape or greater than 3 ply laminate jacket - less than 0.0000 perm adhesive tape.
f. Breaks and punctures in the jacket material shall be patched by wrapping a strip of jacket material around the pipe and securing it with adhesive, stapling, and coating with vapor retarder coating or PVDC adhesive tape or greater than 3 ply laminate jacket - less than 0.0000 perm adhesive tape. The patch shall extend not less than 1-1/2 inches past the break.
g. At penetrations such as thermometers, the voids in the insulation shall be filled and sealed with vapor retarder coating or PVDC adhesive tape or greater than 3 ply laminate jacket - less than
0.0000 perm adhesive tape or greater than 3 ply laminate jacket - less than 0.0000 perm adhesive tape.
h. Installation of flexible elastomeric cellular pipe insulation shall be by slitting the tubular sections and applying them onto the piping or tubing. Alternately, whenever possible slide un-slit sections over the open ends of piping or tubing. All seams and butt joints shall be secured and sealed with adhesive. When using self seal products only the butt joints shall be secured
23 07 00-14 03/07/12 with adhesive. Insulation shall be pushed on the pipe, never pulled. Stretching of insulation may result in open seams and joints. All edges shall be clean cut. Rough or jagged edges of the insulation shall not be permitted. Proper tools such as sharp knives shall be used. Grade 1, Type II sheet insulation when used on pipe larger than 6 inches shall not be stretched around the pipe. On pipes larger than 12 inches, adhere sheet insulation directly to the pipe on the lower 1/3 of the pipe.
3.2.1.8 Insulation for Fittings and Accessories
a. Pipe insulation shall be tightly butted to the insulation of the fittings and accessories. The butted joints and ends shall be sealed with joint sealant and sealed with a vapor retarder coating or PVDC adhesive tape or greater than 3 ply laminate jacket - less than 0.0000 perm adhesive tape.
b. Precut or preformed insulation shall be placed around all fittings and accessories and shall conform to MICA plates except as modified herein: 5 for anchors; 10, 11, and 13 for fittings;
14 for valves; and 17 for flanges and unions. Insulation shall be the same insulation as the pipe insulation, including same density, thickness, and thermal conductivity. Where precut/preformed is unavailable, rigid preformed pipe insulation sections may be segmented into the shape required. Insulation of the same thickness and conductivity as the adjoining pipe insulation shall be used. If nesting size insulation is used, the insulation shall be overlapped 2 inches or one pipe diameter. Elbows insulated using segments shall conform to MICA Tables
12.20 "Mitered Insulation Elbow'.
c. Upon completion of insulation installation on flanges, unions, valves, anchors, fittings and accessories, terminations, seams, joints and insulation not protected by factory vapor retarder jackets or PVC fitting covers shall be protected with PVDC or greater than 3 ply laminate jacket - less than 0.0000 perm adhesive tape or two coats of vapor retarder coating with a minimum total thickness of 1/16 inch, applied with glass tape embedded between coats. Tape seams shall overlap 1 inch. The coating shall extend out onto the adjoining pipe insulation 2 inches. Fabricated insulation with a factory vapor retarder jacket shall be protected with either greater than 3 ply laminate jacket - less than 0.0000 perm adhesive tape, standard grade, silver, white, black and embossed or PVDC adhesive tape or two coats of vapor retarder coating with a minimum thickness of 1/16 inch and with a 2 inch wide glass tape embedded between coats.
Where fitting insulation butts to pipe insulation, the joints shall be sealed with a vapor retarder coating and a 4 inch wide ASJ tape which matches the jacket of the pipe insulation.
d. Anchors attached directly to the pipe shall be insulated for a sufficient distance to prevent condensation but not less than 6 inches from the insulation surface.
e. Insulation shall be marked showing the location of unions, strainers, and check valves.
3.2.1.9 Optional PVC Fitting Covers
a. At the option of the Contractor, premolded, one or two piece PVC fitting covers may be used in lieu of the vapor retarder and embedded glass tape. Factory precut or premolded insulation segments shall be used under the fitting covers for elbows. Insulation segments shall be the same insulation as the pipe insulation including same density, thickness, and thermal conductivity. The covers shall be secured by PVC vapor retarder tape, adhesive, seal welding or with tacks made for securing PVC covers. Seams in the cover, and tacks and laps to adjoining pipe insulation jacket, shall be sealed with vapor retarder tape to ensure that the assembly has a continuous vapor seal.
23 07 00-15 03/07/12
3.3 EQUIPMENT INSULATION SYSTEMS INSTALLATION
Install equipment insulation systems in accordance with the approved MICA Insulation Stds plates as supplemented by the manufacturer's published installation instructions.
3.3.1 General
3.3.1.1 Removable insulation sections shall be provided to cover parts of equipment that must be opened periodically for maintenance including vessel covers, fasteners, flanges and accessories.
Equipment insulation shall be omitted on the following:
a. Hand-holes.
b. Boiler manholes.
c. Cleanouts.
d. ASME stamps.
e. Manufacturer's nameplates.
3.3.2 Insulation for Hot Equipment
3.3.2.1 Insulation shall be furnished on equipment handling media above 60 degrees F including the following:
a. Converters.
b. Heat exchangers.
c. Hot water generators.
d. Water heaters.
e. Pumps handling media above 120 degrees F.
f. Fuel oil heaters.
g. Hot water storage tanks.
h. Air separation tanks.
i. Surge tanks.
j. Flash tanks.
k. Feed-water heaters.
l. Unjacketed boilers or parts of boilers.
m. Boiler flue gas connection from boiler to stack (if inside).
n. Induced draft fans.
o. Fly ash and soot collectors.
p. Condensate receivers.
3.3.2.2 Insulation
a. Insulation shall be suitable for the temperature encountered. Shell and tube-type heat exchangers shall be insulated for the temperature of the shell medium.
23 07 00-16 03/07/12
b. Insulation thickness for hot equipment shall be determined using Table 6:
Legend
RMF: Rigid Mineral Fiber
FMF: Flexible Mineral Fiber
CS: Calcium Silicate
PL: Perlite
CG: Cellular Glass
FC: Flexible Elastomeric Cellular
PF: Phenolic Foam
PC: Polyisocyanurate Foam
TABLE 6
Insulation Thickness for Hot Equipment (Inches and °F)
Equipment handling steam Material Thickness or media to indicated pressure or temperature limit:
15 psig RMF 2.0 inches or FMF 2.0 inches
250F CS/PL 4.0 inches
CG 3.0 inches
PF 1.5 inches
FC (<200F) 1.0 inches
__ PC 1.0 inches_____________
200 psig RMF 3.0 inches or FMF 3.0 inches
400 F CS/PL 4.0 inches
CG 4.0 inches
600 F RMF 5.0 inches
FMF 6.0 inches
CS/PL 6.0 inches
CG 6.0 inches
>600 F: Thickness necessary to limit the external temperature of the insulation to 120F. Heat transfer calculations shall be submitted to substantiate insulation and thickness selection.
3.3.2.3 Insulation of Boiler Stack and Diesel Engine Exhaust Pipe
a. Inside boiler house and mechanical room, bevel insulation neatly around openings and provide sheet metal insulation stop strips around such openings. Apply a skim coat of hydraulic setting cement directly to insulation. Apply a flooding coat of adhesive over hydraulic setting cement, and while still wet, press a layer of glass cloth or tape into adhesive and seal laps and edges with adhesive. Coat glass cloth with adhesive. When dry, apply a finish coat of adhesive at can-consistency so that when dry no glass weave shall be observed. Provide metal jackets for stacks and exhaust pipes that are located above finished floor and spaces outside boiler house or mechanical room. Apply metal jackets directly over insulation and secure with 3/4 inch wide metal bands spaced on 18 inch centers. Do not insulate name plates. Insulation type and
23 07 00-17 03/07/12 thickness shall be in accordance with the following Table 7.
TABLE 7
Insulation and Thickness (Inches and °F) for
Boiler Stack and Diesel Engine Exhaust Pipe
Service & Surface Material Outside Diameter (Inches)
Temperature Range 1/4-1-1/4 1-1/2-3 3-1/2-5 6-10 11-36
(Degrees F)
Boiler Stack Mineral Fiber NA NA 3 3.5 4
(Up to 400° F) ASTM C 553
Class B-3, ASTM C 547
Class 1, or
ASTM C 612
Class 1
Calcium Silicate NA NA 3 3.5 4
ASTM C 533,
Type 1
Cellular Glass 1.5 1.5 1.5 2 2.5
ASTM C 552,
Type II
Boiler Stack Mineral Fiber NA NA 4 4 5
(401 to 600°F) ASTM C 547, Class 2, ASTM C 592
Class 1, or
ASTM C 612
Class 3
Calcium Silicate NA NA 4 4 4
ASTM C 533
Type I or II
Mineral Fiber/
Cellular Glass
Composite:
Mineral Fiber 1 1 1 1 2
ASTM C 547 Class 2
ASTM C 592
Class 1, or
ASTM C 612
Class 3
23 07 00-18 03/07/12
Cellular Glass 2 2 2 2 2
ASTM C 552,
Type II
Boiler Stack Mineral Fiber NA NA 4 4 6
(601 to 800°F) ASTM C 547
Class 3, ASTM C 592
Class 1, or ASTM C 612
Class 3
Calcium Silicate NA NA 4 4 6
ASTM C 533
Type I or II
Mineral Fiber/
Cellular Glass
Composite:
Mineral Fiber 2 2 2 3 4
ASTM C 547, Class 2, ASTM C 592
Class 1, or
ASTM C 612
Class 3
Cellular Glass 2 2 2 2 2
ASTM C 552,
Type II
Diesel Engine Calcium Silicate 3 3.5 4 4 4
Exhaust ASTM C 533
(Up to 700°F) Type I or II
Cellular Glass 2.5 3.5 4 4.5 6
ASTM C 552,
Type II
3.3.2.4 Insulation of Pumps
a. Insulate pumps by forming a box around the pump housing. The box shall be constructed by forming the bottom and sides using joints that do not leave raw ends of insulation exposed.
Bottom and sides shall be banded to form a rigid housing that does not rest on the pump. Joints between top cover and sides shall fit tightly. The top cover shall have a joint forming a female shiplap joint on the side pieces and a male joint on the top cover, making the top cover removable. Two coats of Class I adhesive shall be applied over insulation, including removable sections, with a layer of glass cloth embedded between the coats. A parting line shall be provided between the box and the removable sections allowing the removable sections to be removed without disturbing the insulation coating. The total dry thickness of the finish shall be
23 07 00-19 03/07/12
1/16 inch. Caulking shall be applied to parting line of the removable sections and penetrations.
3.3.2.5 Other Equipment
a. Insulation shall be formed or fabricated to fit the equipment. To ensure a tight fit on round equipment, edges shall be beveled and joints shall be tightly butted and staggered.
b. Insulation shall be secured in place with bands or wires at intervals as recommended by the manufacturer but not greater than 12 inch centers except flexible elastomeric cellular which shall be adhered. Insulation corners shall be protected under wires and bands with suitable corner angles.
c. On high vibration equipment, cellular glass insulation shall be set in a coating of bedding compound as recommended by the manufacturer, and joints shall be sealed with bedding compound. Mineral fiber joints shall be filled with finishing cement.
d. Insulation on heads of heat exchangers shall be removable. The removable section joint shall be fabricated using a male-female shiplap type joint. Entire surface of the removable section shall be finished as specified.
e. Exposed insulation corners shall be protected with corner angles.
f. On equipment with ribs, such as boiler flue gas connection, draft fans, and fly ash or soot collectors, insulation shall be applied over 6 by 6 inch by 12 gauge welded wire fabric which has been cinched in place, or if approved by the Contracting Officer, spot welded to the equipment over the ribs. Insulation shall be secured to the fabric with J-hooks and 2 by 2 inch washers or shall be securely banded or wired in place on 12 inch (maximum) centers.
g. On equipment handling media above 600 degrees F, insulation shall be applied in two or more layers with joints staggered.
h. Upon completion of installation of insulation, penetrations shall be caulked. Two coats of adhesive shall be applied over insulation, including removable sections, with a layer of glass cloth embedded between the coats. The total dry thickness of the finish shall be 1/16 inch.
Caulking shall be applied to parting line between equipment and removable section insulation.
3.3.3 Equipment Handling Dual Temperature Media
3.3.3.1 Below and above 60 degrees F: equipment handling dual temperature media shall be insulated as specified for cold equipment.
3.3.4 Equipment Exposed to Weather
3.3.4.1 Installation
a. Equipment exposed to weather shall be insulated and finished in accordance with the requirements for ducts exposed to weather in paragraph Duct Insulation Installation.
3.3.4.2 Optional Panels
a. At the option of the Contractor, prefabricated metal insulation panels may be used in lieu of the insulation and finish previously specified. Thermal performance shall be equal to or better than that specified for field applied insulation. Panels shall be the standard catalog product of a manufacturer of metal insulation panels. Fastenings, flashing, and support system shall conform to published recommendations of the manufacturer for weatherproof installation and shall prevent moisture from entering the insulation. Panels shall be designed to accommodate
23 07 00-20 03/07/12 thermal expansion and to support a 250 pound walking load without permanent deformation or permanent damage to the insulation. Exterior metal cover sheet shall be aluminum and exposed fastenings shall be stainless steel or aluminum.
END OF SECTION 23 07 00