Statement of Work For

AFCEC Mobile Diesel Generators

FA481919QAP02

CLIN 0001: 70kW Mobile Diesel Generator (1 each)

MINIMUM ENGINE SPECIFICATIONS:

o U.S. Tier 4 Final Emissions Rating o Diesel Engine o Electronic Based Control System

Must have Auto, Manual, Start, Stop, Fault Reset and Lamp Test/Panel Lamp Switches

Must be UL compliant.

o PC Based Service Tool Diagnostic Software (with all level access passwords provided for FULL system access) o Engine Cooling System rated at 122 degree F operation o Battery Disconnect Switch

MINIMUM ALTERNATOR SPECIFICATIONS:

o Permanently Mounted 4 position Voltage Selection Switch o Must have the following switchable 3 Phase voltages: 277/480, 139/240, 120/208 VAC o Must have the following switchable 1 Phase Voltage: 120/240 VAC

MINIMUM ELECTRICAL PACKAGE SPECIFICATIONS:

20 Amp GFCI receptacles

50 Amp 240 Twist Lock Receptacles

Cam Lock Distribution Panel o Shore Power connection for coolant heater and battery charger o Remote Start Capability o Remote Emergency Stop

MINIMUM FUEL SYSTEM SPECIFICATIONS:

o 24-hour Fuel tank o 24-hour Diesel Exhaust Fluid (DEF) Tank o Auxiliary Fuel and Diesel Exhaust Fluid Connections

MINIMUM TRAILER SPECIFICATIONS:

o Dual Axle trailer o DOT approved with Electric Brakes o 2-5/16” Ball Mount

OTHER REQUIREMENTS:

o Roof Mounted, Single Point Lift o Generator Warranty- 3 years/3000 Hours minimum

CLIN 0002: 150kW Mobile Diesel Generator (1 each) o Diesel Engine o Electronic Based Control System

Must have Auto, Manual, Start, Stop, Fault Reset and Lamp Test/Panel Lamp Switches

Must be UL compliant.

o PC Based Service Tool Diagnostic Software (with all level access passwords provided for FULL system access) o Engine Cooling System rated at 122 degree F operation o Battery Disconnect Switch

MINIMUM ALTERNATOR SPECIFICATIONS:

o Permanently Mounted 4 position Voltage Selection Switch o Must have the following switchable 3 Phase voltages: 277/480, 139/240, 120/208 VAC o Must have the following switchable 1 Phase Voltage: 120/240 VAC

MINIMUM ELECTRICAL PACKAGE SPECIFICATIONS:

20 Amp GFCI receptacles

50 Amp 240 Twist Lock Receptacles

Cam Lock Distribution Panel o Shore Power connection for coolant heater and battery charger o Remote Start Capability o Remote Emergency Stop

MINIMUM FUEL SYSTEM SPECIFICATIONS:

o 24-hour Fuel tank o 24-hour Diesel Exhaust Fluid (DEF) Tank o Auxiliary Fuel and Diesel Exhaust Fluid Connections

MINIMUM TRAILER SPECIFICATIONS:

o Dual Axle trailer o DOT approved with Electric Brakes o 2-5/16” Ball Mount

OTHER REQUIREMENTS:

o Roof Mounted, Single Point Lift o Generator Warranty- 3 years/3000 Hours minimum

CLIN 0003: 200kW Mobile Diesel Generator (1 each) o Diesel Engine o Electronic Based Control System

Must have Auto, Manual, Start, Stop, Fault Reset and Lamp Test/Panel Lamp Switches

Must be UL compliant.

o PC Based Service Tool Diagnostic Software (with all level access passwords provided for FULL system access) o Engine Cooling System rated at 122 degree F operation o Battery Disconnect Switch

MINIMUM ALTERNATOR SPECIFICATIONS:

o Permanently Mounted 4 position Voltage Selection Switch o Must have the following switchable 3 Phase voltages: 277/480, 139/240, 120/208 VAC o Must have the following switchable 1 Phase Voltage: 120/240 VAC

MINIMUM ELECTRICAL PACKAGE SPECIFICATIONS:

20 Amp GFCI receptacles

50 Amp 240 Twist Lock Receptacles

Cam Lock Distribution Panel o Shore Power connection for coolant heater and battery charger o Remote Start Capability o Remote Emergency Stop

MINIMUM FUEL SYSTEM SPECIFICATIONS:

o 24-hour Fuel tank o 24-hour Diesel Exhaust Fluid (DEF) Tank o Auxiliary Fuel and Diesel Exhaust Fluid Connections

MINIMUM TRAILER SPECIFICATIONS:

o Dual Axle trailer o DOT approved with Electric Brakes o 2-5/16” Ball Mount

OTHER REQUIREMENTS:

o Roof Mounted, Single Point Lift o Generator Warranty- 3 years/3000 Hours minimum

Delivery Location:

1001 Mississippi Rd.

Bldg. 36271 Tyndall AFB, FL 32403