Attachment 1 - SCBA Annual Testing Statement of Work - Amended.pdf

PDF 740 KB Posted

Attached to
Self-Contained Breathing Apparatus (SCBA) Annual Testing Federal contract opportunity
Solicitation number
FA480925Q0090
Issued by
Department of the Air Force Air Combat Command

About this file

This Statement of Work (SOW) outlines annual testing requirements for Self-Contained Breathing Apparatus (SCBA) at Seymour Johnson Air Force Base in Goldsboro, NC. The contractor must perform comprehensive flow tests on MSA G1 SCBA components, including MSA G1 Packs, Masks, Escape Packs, and RIT Packs with Masks, in strict accordance with NFPA 1852 standards. Contractor personnel must be MSA Care Technician Certified and will conduct the testing during a single annual visit, with testing to be coordinated at least 14 calendar days in advance with the Fire Chief or designated representative.

The SOW specifies that the testing will occur in the Self-Contained Breathing Apparatus Maintenance Room located at 2020 Jabara Avenue, Building 4601. After completing the tests, the contractor must provide documentation of testing and compliance. The document is dated 11 August 2025 and includes Amendment 0001, indicating potential updates or modifications to the original requirements.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK (SOW)

Self-Contained Breathing Apparatus Annual Testing

Amended 11 August 2025

1. DESCRIPTION OF WORK: All Fire Fighting Self Contained Breathing Apparatus (SCBA), MSA G1 components are to be annually tested in accordance with NFPA 1852: Selection, Care & Maintenance, and repair of Open-Circuit SCBA for Emergency Services.

2. SCOPE OF WORK: The Contractor will furnish all labor, equipment, and materials required to perform annual flow tests completed on MSA G1 Self-Contained Breathing Apparatus’.

3. REQUIREMENTS: The work to be accomplished must follow the requirements listed below,

3.1 Contractor personnel to test and perform the annual flow test requirement must be MSA Care Technician Certified.

3.2 All tests will be conducted annually in accordance with NFPA 1852 para. 7.5.1 and will be performed in accordance with NFPA 1852 para. 7.5.5 and 7.5.6 requirements.

3.3 Documentation of testing and compliance will be provided after testing is complete.

3.4 All MSA G1 Self-Contained Breathing Apparatus’ will be tested during one annual visit which includes the following:

a. MSA G1 Packs

b. MSA G1 Masks

c. MSA Escape Packs

d. MSA G1 RIT Packs with Mask

4. LOCATION: The contractor will accomplish the annual testing on Seymour Johnson Air Force Base, Goldsboro, NC in the Self-Contained Breathing Apparatus Maintenance Room located at 2020 Jabara Avenue, Building 4601.

5. SCHEDULING: To schedule a date and time to perform the annual testing, prior coordination for the testing/repair shall be coordinated at minimum of 14 calendar days in advance with the Fire Chief or designated representative.

Amendment 0001