FA480923Q0113 RFI Responses (2 pages) dated 8-Sep-23.pdf

PDF 153 KB Posted

Attached to
Hazardous Material (HAZMAT) Storage Units for Seymour Johnson AFB, NC
Solicitation number
FA480923Q0113
Issued by

About this file

This document contains responses to questions regarding Solicitation Number FA480923Q0113 for hazardous material storage units at Seymour Johnson Air Force Base in North Carolina. The solicitation seeks delivery and installation of multiple explosion-proof storage units for flammable liquids, aerosols, sealants, corrosives, and compressed gases. Key details include:

  • Units must meet wind load requirements of 120 mph and include a minimum of four tiers of leakproof steel shelving. Electrical components and accessories must be explosion-proof rated for Class 1 Division 1 or 2 hazards.

  • The government estimates a 45-day delivery period but requests actual lead times from offerors. Pricing should specify any considerations related to purchasing different quantities of optional units. Installation includes anchoring, electrical and fire alarm connections.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUESTS FOR INFORMATION AND RESPONSES

FA480923Q0113, HAZARDOUS MATERIAL STORAGE UNITS

Question/Topic Answer

01 Is there flexibility with this lead time?

The 45-day delivery period identified on the solicitation is estimated.

Offerors should annotate actual lead time on submitted quotations if different from the 45-day estimated delivery period estimated on the solicitation document. Reference also provision FAR 52.212-2 at page 49 of the solicitation document

Specs say sufficiently weatherproof to withstand wind load of 120 MPH. Is this only for the building only or does that include the doors? For example [if the] buildings are rated at 150 mph, but doors [that] are only rated for 90 mph.

Doors rated at 90 MPH wind load rating are sufficient, provided fire rating and door construction to include weatherproofing, are not compromised.

How much shelving is needed per unit and how many tiers on each wall?

**SOW Addition at Section III.5 A minimum of four (4) tiers of shelving along back and side walls as space allows. Shelving shall be leakproof, steel, and encompassed with a 2” lip

Only once in the specs does it call out class and division for explosion proof accessories. It calls exhaust to be class1, Division 1. Do all electrical components need to be Class1, Div1 or only the exhaust?

**SOW Additions at III. 18, 19, 21, 22, 23 Units shall meet, at minimum, the specifications of the pre-existing unit(s). All interior electrical components, air conditioner, convection heater, exhaust fan, and lighting are to be explosion proof to the ratings described below. The exterior electrical panel is to be weatherproof to the below requirements. Specifications of pre-existing unit(s) are noted below:

Interior Explosion Proof Air Conditioner:

EXPLOSION PROOF UL LISTED, CLASS I, DIVISION 2, GROUP

A,B,C,& D AIR CONDITIONER (14,500 BTU/HR, 208/230VAC,

7.4/6.9A, 1-PHASE), ONE (1) INTERIOR TEMPERATURE

CONTROLLER WITH USER ADJUSTABLE TEMPERATURE

SETTINGS. TOTALLY ENCLOSED FAN MOTOR WITH STAINLESS

STEEL SHAFT TO RESIST

CORROSION AND A HERMETICALLY SEALED OVERLOAD AND

AN EXTERIOR SWITCH TO PREVENT ARCING.

Interior Explosion Proof Convection Heater:

CONVECTION HEATER 3.6KW (12,292 BTU/HR) UL LISTED,

CLASS 1, DIVISION 1 & 2, GROUPS C & D; ZONES 1 & 2;

GROUPS IIA & IIB., 240V SINGLE PHASE 15.0A. INCLUDES

TEMPERATURE THERMOSTAT (T2A) FROM 36^F TO 82^F.

Interior XP Exhaust Fan:

EXPLOSION PROOF EXHAUST FAN CONSISTING OF ONE (1)

UL LISTED, CLASS I, DIVISION 1, GROUP C AND D TOTALLY

ENCLOSED MOTOR (115VAC, 4.5A, 60HZ, 1-PHASE) WITH NON-

STATIC TWELVE-INCH (12) DIAMETER CAST ALUMINUM FAN

BLADE. EXTERNAL HOUSING CONSTRUCTED OF 18 GA

STEEL, EPOXY-COATED OUTSIDE. EXHAUST INTAKE VENTS

LOCATED WITHIN TWELVE INCHES (12) OF THE FLOOR.

ACTIVATED BY AN EXTERIOR UL LISTED FAN SWITCH.

EXTERIOR EXHAUST FAN PORT OPENING EQUIPPED WITH

SHUTTER ASSEMBLY AND SCREEN. MECHANICAL VENT IS

SIZED TO ALLOW FOR A MINIMUM OF 6 AIR CHANGES PER

HOUR.

Explosion Proof 2 Ft. LED Strip Lights:

LED LOW PROFILE, CEILING OR WALL MOUNT, 2FT NOMINAL

LENGTH STRIP LIGHT. UL 1598A, 844, 1598, & 8750; CUL

LISTED. CLASS 1, DIV 2, GROUPS A, B, C, & D. CLASS 2, DIV 2,

GROUPS F & G. NEMA 4X. DESIGNED FOR USE IN

HAZARDOUS LOCATIONS AND WHERE MOISTURE, DIRT,

DUST, CORROSION AND VIBRATION MAY BE PRESENT.

ALUMINUM BODY W/ GRAY EPOXY FINISH; T-ONE PIECE,

NEOPRENE GASKET AND DIFFUSED

POLYCARBONATE LENS. 120-277/1, 50 OR 60HZ. 3737 LUMENS,

40 WATTS

Exterior Electrical Panel:

UL LISTED, SINGLE PHASE, 3 WIRE, 120/240V 100 AMP 8

SPACE LOAD CENTER (NEMA 3R). RAINPROOF AND SLEET-

(ICE) RESISTANT- OUTDOOR ENCLOSURES ARE INTENDED

FOR USE OUTDOORS TO PROTECT THE ENCLOSED

EQUIPMENT AGAINST RAIN AND MEET THE REQUIREMENTS

OF UNDERWRITERS' LABORATORIES, INC., PUBLICATION NO.

UL 508, APPLYING TO "RAINPROOF ENCLOSURES.

For option items 004, 005 and 006 will this be Qty 5 all or nothing?

It is the Government’s intent to have one delivery and one installation/removal period.

The quantity of options exercised shall be dependent upon funding availability.

Offerors are encouraged to specify with their submitted quote any pricing considerations that may apply with regards to the number of units purchased.

06 Shelving width **SOW Change at Section III.

Shelving should be at minimum 24”in depth.

Anchoring of units to the ground and electrical grounding.

**SOW Addition at Section IV.8 The contractor shall be responsible for anchoring units to the concrete surface and electrical grounding of unit.

08 Electric connection and existing conduit

The contractor shall be responsible for connecting the units to electrical power source. Vendors shall include electrical plan with their bids.

HVAC/Heater specifications and/or temperature requirements

**SOW Addition at Section III.

HVAC system(s) and Heating system(s) must be sufficient to maintain a maximum temperature of 68 F and a minimum temperature of 72 F respectively.

10 Fire alarm connections **SOW Addition at Section IV.9.

Provide the wiring to connect to the existing system. (Make: Monaco Enterprises Inc., Type: Radio Fire Alarm Control Panel, Model: M-1)

What type of Hazardous Material is currently being stored?

Flammable Liquids, Flammable Aerosol Cans, Flammable Sealants & Adhesives, Corrosives, Compressed Gas Cylinders.

File details come from the government source that posted it. Updated .