Attachment 03 - Conduit Fill Calculation.pdf
PDF 19 KB Posted
- Attached to
- B1947 Install Outlets
- Solicitation number
- FA480325SS001
About this file
This document is a conduit fill calculator results report showing specifications for an electrical conduit installation. The report details that a 1-inch EMT (Electrical Metallic Tubing) conduit will be used with 12 copper THHN wires, each with a size of 10 STR and diameter of 0.161 inches. The calculations indicate a conduit fill of 28.27% with a jam probability of 6.515528. This technical document appears to be an attachment supporting the federal contract opportunity for installing outlets at Shaw AFB, providing specifications for the electrical conduit work that would be required.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Southwire Conduit Fill Calculator
Results Computed for NEC
Conduit Fill: 28.27%
Conduit Size: 1"
Jam Probability: 6.515528
CONDUIT
Conduit Type: EMT
Conduit Size: 1
CONDUCTORS
1 Wire Type: Copper THHN
Wire Size: 10 STR
Diameter: 0.161
Number of Wires: 12
US Patent 8788221
File details come from the government source that posted it. Updated .